| 1 | Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m in depth and getting out in soft / loose soil for laying cables, Pipes etc complete all as specified and as directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed. |
| 3 | Removal of excavated material [soil] to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed. |
| 4 | Cutting of existing road for removing / laying UG Cables/ pipe line, depth of cutting not exceeding 90cm and width 45cm and filling the trench of road i.e. excluding top 15cms with existing aggregate obtained from cutting, watered and properly rammed to satisfaction of EIC and finally provide 150 mm thick PCC 1:3:6 type C1 using 20 mm graded crushed stone aggregate to entire width of trench & finally match the top surface to road & disposal of debris to a distance not exceeding 50 Mts and depositing where directed complete all as directed. (Note: Quoted rate is deemed to be inclusive of 150 m thick PCC 1:3:6, cutting any type of road/ foot path and removal of debris). |
| 5 | Material and labour for dry river sand cushioning over and around the cable for cable protection in trenches, levelled and punned down complete all as specified and as directed. Note: The punned down thickness shall be measured for payment. |
| 6 | Taking down old existing HT PCC Cable Cover complete all as specified. |
| 7 | Supplying and laying unreinforced precast cement concrete cable covers,ISI MarkedClass HV, Flat, Type - 1, of size 300 mm X 180 mm X 40mm in trenches for cable protection, embossed with \"ELECTRIC\" on the top surface complete all as specified and as directed by the Engineer - in - Charge. |
| 8 | Laying only HTPCC cable covers for protection of UG cables in trenches, obtained from item No. 06 here in above. |
| 9 | Supplying, laying and commissioning of HT XLPE cables, insulated, screened, PVC bedded, galvanized steel strip armoured, earthed, electric power cable with Aluminium conductor, 11 kV grade, 3 Core, 95 Sqmm cross sectional area laid in trenches/ fixed on poles including taking down old cables complete all as specified and as directed. Make: Nicco/ Havells/ PolycabNote: Earth work, excavation, cable covers and sand cushioning shall be measured and paid separately. |
| 10 | Supply, laying, jointing, testing 3½ Core, cross-sectional area 300 SqmmXLPE, insulated outersheathed and innersheathed, galvanised steel armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, conforming to IS:7098 (Part-II) and laid in trenches, pipe, ducts including taking down existing damaged UG cable complete all as specified and as directed.Note: Earth Work, Excavation, Cable Cover and Sand Cusioning shall be measured and paid separately. |
| 11 | All as per item No. 10 here in above, but for 3½ Core, cross-sectional area 185 Sqmm |
| 12 | All as per item No. 10 here in above, but for 3½ Core, cross-sectional area 120 Sqmm |
| 13 | All as per item No. 10 here in above, but for 3½ Core, cross-sectional area 50 Sqmm |
| 14 | All as per item No. 10here in above, but for 4 Core, cross-sectional area 16 Sqmm |
| 15 | Taking down old existing LT PCC Cable Cover complete all as specified. |
| 16 | Supply and laying un-reinforced precast concrete cable cover, class LV type flat size 250mm x 150mm x 40mm for protection of underground cable in trenches complete all as specified. |
| 17 | Laying only oldPCC Cable Cover for protection of underground cable in trenches,obtained from item No. 15 here in above. |
| 18 | S&F 50 mm bore high density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 for protection of cable laid in trenches complete as specified. |
| 19 | S&F 100 mm bore GI tubing light grade with necessary fittings suh as bends, tees, elbows, etc in trenches, fixed on wall complete all as specified. |
| 20 | All as per item No. 19 here in above, but 80 mm bore. |
| 21 | Material and Labour for heat shrinkable HT, 11 kV, outdoor type, cable straight through joint suitable for 11 kV, 3 Phase, AC, 50 Hz, 3 Core,50 to 95 Sqmm XLPE Cable including jointing materials etc complete all as specified and as directed. |
| 22 | Material and labour for heat shrinkable HT, 11 kV, indoor type, cable end joint suitable for 11 kV, 3 Phase, AC, 50 Hz, 3 Core, 50 to 95 Sqmm XLPE Cable including jointing materials complete and taking down old end joints all as specified and as directed. |
| 23 | Material and labour for heat shrinkable HT, 11 kV, outdoor type, cable end joint suitable for 11 kV, 3 Phase, AC, 50 Hz, 3 Core, 50 to 95 Sqmm XLPE Cable including jointing materials and taking down old end joints all as specified and as directed. |
| 24 | M &L Straight through heat shrink joints PVC/ XLPE insulated armoured heavy duty LT UG Cables with aluminium conductor cross sectional area 16 Sqmm 4 Core including aluminum lugs/ thimbles complete all as specified. |
| 25 | All as per item No. 24 here in above but cross sectional area 25 Sqmm to 50 Sqmm, 3.5 Core |
| 26 | All as per item No. 24 here in above but cross sectional area 70 Sqmm to 95 Sqmm, 3.5 Core |
| 27 | All as per item No. 24 here in above but cross sectional area 120 Sqmm to 185 Sqmm, 3.5 Core |
| 28 | All as per item No 24 here in above but cross sectional 240 Sqmm to 300 Sqmm, 3.5 Core |
| 29 | All as per item No. 24 here in above but cross sectional area400 Sqmm to 500 Sqmm, 3.5 Core |
| 30 | M&L for Danger Notice Plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT of size 25X20 cm complete all as specified and as directed by Engineer-in-Charge. |
| 31 | M&L for PCC 1:3:6 type C1 20 mm graded aggregate in coping of pole complete |
| 32 | S&F in repairs earth continuity conductor or main earthing lead of Galvanised iron strip of size 32x6mm, fixed on pole / wall from existing earth test point complete all as specified and as directed. |
| 33 | M&L for servicing and repair to HT RMU/ VCB of size up to 630 Amp complete by taking the shut down with prior intimation and cleaning the contacts put the trolly in position and testing complete all as specified and as directed. |
| 34 | S&F in repairs Shunt trip coil for HT VCB of C&S make |
| 35 | S&F in repairs closing coil for HT VCB of C&S make |
| 36 | S&F in repairs spring charging motor for HT VCB of C&S make |
| 37 | S&F in repairs Limit switch oftype LSMS11, AC 15, 3A/400 V for HT VCB of C&S make |
| 38 | S&F in repairs Limit switch oftype MU25-I/l 2, 16 A/250 V AC for HT VCB of C&S make |
| 39 | S&F in repairs Breaker control switch 10A, spring return to neutral 3 position & label trip-neutral-close for HT VCB of C&S make |
| 40 | S&F in repairs Hand reset master trip relay, aux-110V DC(CLR-H-3). Make: C&S |
| 41 | S&F in repairs IDMT non directional O/C & E/F relay aux.-110V DC (IRI-PRO-3I-EI-5-5) complete all as directed. |
| 42 | S&F in repairs HT HRC fuse of 10 to 63 Amp as per sample. Make: L&T/ Bussmann |
| 43 | S&F in repairs CT\"s 200-100/5-5A dual core, resin cast ,core 1:- metering-15VA CL-1, core2:- protection-15VA CL-5P10, STC-18. 4kA for 3s |
| 44 | S&F in repairs CT\"s 100-50/5-5A dual core, resin cast, core1:- metering-15VA CL-1, core2:- protection-15VA CL-5P10, STC-18.4kA for 3s |
| 45 | S&F in repairs VT 11kv/ v3/110 vac/v3, 200VA, CL-1, 1 phase resin cast |
| 46 | S&F in repairs Digital load manager/ Multifunction LED meter3ph. 4 wire (a, v, kwh, kVA, pf, kVAR) CTR-200-100/5A, PTR-11kv/ v3/ 110vac/ v3, CL-1 Aux.-110V, DC, size - 96x96mm (Make:- L &T of 6000 series) |
| 47 | S&F in repairs Analog ammeter 0-100-200A CTR-200-100/5A CL-1 size 144x144mm |
| 48 | S&F in repairs Analog ammeter 0-50-100A CTR-100-50/5A CL-1 size 144x144mm |
| 49 | S&F in repairs 0-15kV analog voltmeter PTR-11kv/110 vac. Size - 144x144mm |
| 50 | S&F in repairs HT fuse 11kV/3.15A,length - 195mm, diameter - 25.4mm |
| 51 | S&F in repairs LED type indication lamp red, yellow, blue color 63.5v ac, dia - 22.5mm |
| 52 | S&F in repairs LED type indication lamp red, green, blue, white color 110v ac, dia - 22.5mm |
| 53 | S&F in repairs Space heater 80W 230V AC for 11kV HT electric VCB |
| 54 | S&F in repairs Thermostat 0-110°C 15A 230V AC for 11kV HT electric VCB |
| 55 | S&F in repairs VCB breaker mechanism for 11 kV HT electric VCB |
| 56 | S&F in repairs Spout of VCB/RMU of 11kV |
| 57 | S&F in repairs PT Spout of VCB/ RMU of 11kV |
| 58 | M&L for Power pack suitable for VCB with Input Voltage 230V, AC, O/P -110 V DC, with LED indication showing Main ON, Battery Mode, Battery Low, Out Put O/Load etc complete all as per existing type. |
| 59 | Taking out the existing transformer from site and transporting to workshop for servicing and repairing including loading unloading and handling to carry out the following repairs and refixing the same after repairing, installation, testing and commissioning at its original/ new location all as directed. |
| 60 | Decanting the transformer oil and checking of all parts for repair/ replacement of parts of cap from 63 to 400 kVA capacity of distribution transformer 11/0.440 kV . |
| 61 | Rewinding of coils all as per its original specifications by copper conductor and with HT/ LT necessary insulation materials. |
| 62 | Replacement of HT 11 KV bushing with brass terminal, neoprene rubber gasket and washers etc complete. |
| 63 | Replacement of LT bushing with brass terminal, neoprene rubber gasket and washers etc complete. |
| 64 | Supply and fill new Transformer oil up to conservator level marking as per IS 335 having dielectric strength not less than 40 KV at 2.5mm gap.Make: Electrol, Power Oil, Indian Oil, Savita |
| 65 | Replacement of silica Jel in existing transformer breathers. |
| 66 | Replacement of HT 11 KV off-load tap changing assembly complete |
| 67 | Painting of Transformer body complete with one coat of Simense gray paint with spray paint all as directed by the Engineer-in-charge. |
| 68 | De-moisturising/ Filtration of transformer oil of the transformer at site by providing filtration machine at site |
| 69 | Supply, installing, testing and commissioning of Surge Wave receiver SLE-90 with Ground Micro Phone and Streo Head Phone DJ-9200 (OKAY-II) suitable for High Voltage Surge Tester SWP 16D-5, 0-4, 8, 16kV-1500JOULES mdr complete all as directed by Engineer-in-Chage. Make:- TELE Metrics |
| 70 | Dismantling the existing HT 11mtr four pole structure with transformer complete alongwith any size & type of cross arm sections, insulators, ACSR busbar of any size, GOD any size of HT and LT cable (upto 20 Rm) approx etc and relaying the same at new route as required at site as ordered and including PCC foundation suitable for existing Transformer and necessary HT & LT connections complete all as directed by Engineer-in-Charge.Note: (i) Excavation & Earth Work for relaying cable shall be measured & paid under relevant items of BOQ. (ii) Care should be taken so that damage the existing LT/ HT cable network should not be disturbed/ damaged. |
| 71 | M&L for Earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead 32x6mm GI stripmeans of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected or indicated including testing on completion including necessary excavation, earth work, PCC pit, RCC cover, funnel with watering pipe 20mm bore light grade, GI protection pipe 40mm bore light grade complete all as specified and as directed. |
| 72 | M&L for write SM/ MES No. by synthetic enamel paint on E/M equipments i.e. Transformer/ VCB/ ACB/ Pump/ AC Plant/ APFC Panel/ AC\"s etc by qualified person/ painter all as per site requirement and as directed. |