Tender For Addition And Alteration In The Govt. Sr. Sec. School, Sitanagar, Diglipur
Tender Overview
Project Description
Addition And Alteration In The Govt. Sr. Sec. School, Sitanagar, Diglipur. Sw:-Minor Renovation Of Iei And Providing Extra 15 / 16A Plug Points At Newly Altered Integrated Lab And Replacement Of Conventional Light Fittings And Ceiling Fans With Led Fittings And Bldc Ceiling Fans In Gmsss Sitanagar Under Cd, Apwd, Diglipur.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor singlecorecableinsurface /recessedmediumclassPVC conduit,withpianotypeswitch,phenoliclaminatedsheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Wiringforlight/powerplugwith 2X4sq.mmFRLSPVC insulatedcopperconductorsinglecorecableinsurface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 7 | 32 mm |
| 8 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 9 | Supplying and fixing 3pin, 5A ceiling rose on the existing junctionbox/woodenblockincludingconnectionsetc.as required. |
| 10 | Installation ,Testing,Commissioningofwallbracket/ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lampsperfitting,completewithallaccessoriesincluding connections etc. as required. |
| 11 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 12 | 4 way (4 + 12), Double door |
| 13 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of followingpolesintheexistingMCBDBcompletewith connections, testing and commissioning etc. as required. |
| 14 | Single pole |
| 15 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 16 | 40 A |
| 17 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 18 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 19 | Supply of following LED Retrofit Tube light Battensuitable for 230 Volts,50 Hz AC supply similar toLUKER Retrofit Battens Model no. LLTBetc. or its equivalent to IS specification. |
| 20 | 18W |
| 21 | Supply of following 4 Feet Retrofit LED Retrofit Tube light suitable for 230 Volts,50 Hz AC supply similar toLUKER Retrofit Tubes Model no. LLTI1818Tetc. or its equivalent to IS specification. |
| 22 | 18W LED 6500K |
| 23 | Supplying of following size ISI marked PVC insulated and PVC sheathed/ XLPE unarmoured aluminum conductor cable of 1.1 KV grade conforming to IS:7089 (part-I) as applicable make: Havells/ Gloster/ Polycab etc. as required. |
| 24 | 4x10 sq.mm |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender