Tender For Source Improvement And Augmentation Of Water Supply To Ward No.1 To 17 Of Jaleswar Municipality
Tender Value
4.35 Crore
Estimated cost
Bid Submission
25 Nov 2022
0 days left
EMD
Ref. Documents
Bank guarantee accepted
Document Fee
10000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
jaleswar → Odisha
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Source Improvement And Augmentation Of Water Supply To Ward No.1 To 17 Of Jaleswar Municipality
BOQ
| Sl. No. | Item Description |
| 1 | SINKING OF 6 NOS OF 200 MM DIA PRODUCTION WELL: Labour for drilling a perfectly bore hole to specified diameter for a depth below GL in alluvial soil strata by mud rotary rig drilling as required to suit the site condition as per the direction of the Engineer-in-Charge including supply of rig with all accessories T&P all consumable etc. for a finished bore suitable for lowering of 200mm dia M.S/ PVC pipe for housing fited with sockets and with or without well screen as per the necessary for soft medium hard and boulder formation (M.S./PVC casing pipe if required to be provided by the contractor to prevent collapse of over burden portion). including lowing and with drawing of casing pipe after drilling 200mm dia to 400mm dia in over burden portion. i)from 0.0 mtr to 100.0 mtr and for |
| 2 | Labour for Lowering the following size M.S./PVCcasing pipes with or without slotted pipes as per the necessary from ground level upto 250 mtr depth and fitted and fixed up in perfectly vertical position, including cutting and threading blank pipes and slotted pipes and supplying and fixing all jointing materials , extra socket and top etc.all complete and plugging the tube well to prevent entry og forign materials. (a) 200mm dia PVC pipe. from 0.0 mtr to 100.0 mtr and for |
| 3 | Cleaning and developing the tubewell withcompressorsupplied by the contractor/ continuously worked for a minimum period of 8.0 hrs or till clean and adequate discharge is obtain from the tube well including supply and use of necessary equipment and labour as per the direction of Engineer in charge. |
| 4 | supplying all labour T&P and providing sanitary ceiling by cementgrouting and annular space arround G.I/PVC/MS pipe up to 3.00 mtr below ground level to plug the bore hole including cost of cement all complete as per direction of E.I.C.sanitary ceiling |
| 5 | supplying all labour T&P and providing gravel packing of specific size (P-6) of gravel to be suplied by contractor as per the direction 0f Engineer in charge (all through ) including cost, convayance , royalty of materials as per direction of Engineer-in-charge. |
| 6 | MATERIALS USED8\" dia PVC pipe SCH-80, |
| 7 | 8\" dia PVC ( Screened and ribbed pipe ) |
| 8 | 8\" dia PVC End cap (ASTM) |
| 9 | 8\" dia PVC cone (ASTM) |
| 10 | 8\" dia PVC short piece 30 cm long (ASTM) |
| 11 | COMMISSIONING OF SIX NOS OF PUMP AND MOTORS: Supplying all, materials labour T&P such as providing fitting,fixing of medium grade G.I. pipe cutting to the required size each with threading, welding of flanges with 5/8\" dia hole in flanges. The flanges should be in a horizontal position including cutting grooves for cable with the pipe so that each flanges when joint with rubber insertion packing shall remain water tight etc.completed as per specification and direction of E.I.C. i) 80mm (3\" dia) x 3.0 mtr long G.I./M.S. pipe welded with M.S. flanges/Socket joint both side (medium grade reputed make) |
| 12 | Supplying all, materials labour T&P & fitting,fixing of following materials etc.completed as per specification and direction of E.I.C.100mm (4\" dia) x 1.0 mtr long G.I. pipe with fitting of flange both end |
| 13 | Supplying of 100mm (4\" dia) G.I. Bend |
| 14 | Supplying of 90mm (3\" dia) M.S. Clamp |
| 15 | Supplying of MS well cover plate (P/W) |
| 16 | Supplying of 100mm (4\" dia) MS flange |
| 17 | Supplying of 100mm (4\" dia) G.I. Socket |
| 18 | Supplying of Rubber insertion |
| 19 | Supplying of 3/4\" Garware rope |
| 20 | Supplying of 5/8\" x 3\" Nut bolts |
| 21 | Supplying of 75mm dia 450mm long G.I. Short piece |
| 22 | Supplying all labour, materials T&P for welding the 100mm dia socket with MS flange compt. as per specification and direction of E.I.C. |
| 23 | Supplying all labour T&P for lowering ofsubmersible motor with pump with required nos. of column pipe jointing by applying rubber insertion between the flanges with nut bolts to make it air tight perfectly, cable & garware nylon rope should be water tight perfectly including transportation charges of all materials. |
| 24 | Supplying all labour, materials, T&P for fitting fixing C.I Sluice Valve with double flanged ends for water works purposes confirming to IS: 14846-2000 for the following rating and nominal diameter as per specification complete. 100mm (4\" dia) C.I. Sluice valveRATING-PN (Normal Pressure) -1.0 ] |
| 25 | Supplying all labour, materials, T&P for fitting fixing swing check type Reflux valves (Non-Return Valves) with double flanged ends confirming to IS: 5312(Part-I)-2004 for water work purposes for the following rating and nominal diameter as per specififcation complete.100mm (4\" dia) C.I. NR valveRATING-1.0Mpa |
| 26 | Supplying all labour, materials T & P and providing laying in trenches Double Flanged Duck foot 100 mm dia C.I Duck Foot Bend confirming to IS: 1538-1993 (Part-XVIII) of the following nominal diameter as per specification complete. 100mm dia. x 90° C.I Duck foot bend |
| 27 | Supply, installation & Testing of Single Air relivevalve conforming to IS: 14845for water works purpose for the following diameter including drilling the water main (Cast iron pipe with metal straps)as per specification complete including supply ofing of all labour, materials,T & P required to perform the work (including cost of Nut bolts & washer, Rubber insertion sheet etc.)25mm dia C.I. Single Air Valve (Cost+ Labour) |
| 28 | CONSTRUCTION OF FIVE NOS OF PUMP HOUSE: Double under reamed pile foundation with RCC (1:1.5:3) using 12 mm bhg CB chipse including cost of boring and excluding cost of M.S/Tor steel and labour charges for cutting, bending and binding of steel. etc completed and as per direction of EIC .i) 250 mm dia and 3.50 mtr long double under reamed pile |
| 29 | Earth work in all kinds of soil in excavation of foundation trenches within 50 m initial lead including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding o.30 in depth and as per direction of EIC . Initial lift upto 1.50m |
| 30 | Supplying all materials, labour T&P and filling in F&P with river sandwell watered and rammed including conveyance of all materials to worksite payment of royalty, taxes etc. all complete as per direction of E.I.C. |
| 31 | Supplying all materials, labour T&Pand providing c.c (1:3:6) using 4cm h.g. metal including watering, curing, coveyance of all materials to worksite payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. |
| 32 | Supplying all materials, labour T&Pand providing c.c (1:1.5:3) using 12 mm h.g. chips including watering, curing, coveyance of all materials to worksite payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. |
| 33 | Supplying all materials, labour, T&P and providing brick work with F.A. bricks having c.s. not less than 75kg/cm2 with dimensional tolerance ± 2 % in c.m. including watering,curing conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. In F&P (1:6) |
| 34 | In S/S (1:6) |
| 35 | Supplying all materials, labour, T & P and providing 2.5 cm thick Damp proof course with (1:2:4) using 12mm size bhg CB chips including curing etc. all complete as per Specification and direction of E.I.C. |
| 36 | Supplying all materials, labour, T & P and providing 2.5 cm thick grading concrete with (1:2:2) on roof slab with 6mm size bhg CB chips including curing etc. all complete as per Specification and direction of E.I.C. |
| 37 | Supplying all materials, labour, T &P and providing C.C (1:1.5 :3) using 12mm h.g. chips for R.C.C. works including hoisting, laying, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc, all complete as per specification and direction of E.I.C. |
| 38 | Supplying all materials, labour, T&P and providing M.S. reinforcement for R.C.C. works including cutting, bending, binding and tying the grills and placing in position including cost of binding wire18 to 20 gauge, conveyance of all materials to worksite, payment of taxes etc. all complete as per specification and direction of E.I.C. |
| 39 | Supplying all materials, labour, T&P and providingrigid & smooth centering & shuttering for R.C.C.works including false work and dismantling them after casting including conveyance of all material, to worksite, paymentetc. all complete as per specification and direction of E.I.C. i) Lintel |
| 40 | G.Beam |
| 41 | Column |
| 42 | Slab |
| 43 | Supplying all materials, labour, T&P and providing cement plaster on brick/stone work including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. 12 mm thick CP (1:4) |
| 44 | 12 mm thick C.P in (1:6) |
| 45 | Supplying all materials, labour, T&P and providing cement punning including watering,curing, conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. |
| 46 | Supplying all materials, labour, T&P and providing25mm thick artificial stone flooring with c.c (1:2:4) including punning using 12mm size h.g. chips including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. |
| 47 | Supplying all materials, labour, T&P and providing and fixing M.S. pannel door single leaf with M.S. framed over all size including conveyance of all materials to worksite, payment specification and direction of E.I.C. |
| 48 | Supplying all materials, labour, T&P and providing and painting two coats with enamel paint over a coat of primer to iron works etc. complete as per direction of E.I.C. |
| 49 | Supplying all materials, labour T&Pand providing and fixing in position 50 mm thick precast cement concret jally (1:1.5:3) with hard granite chips including fitting and fixing of cement mortar (1:3) etc. all complete as per specification and direction of E.I.C. |
| 50 | Supplying all labour T&P, materials and finishing wall with cement primer one coat including cost of brushes and puttyand direction of E.I.C. |
| 51 | Finishing walls with 2 Coats of water proofing cement paint of approved shade on NEW workto give an even shade including cost of paint & labour etc. complete |
| 52 | Supplying all labour T&P, materials and finishing wall with weather paint of approve shade on new work two coats to give an even shade including cost of brushes and putty with cost of paint and direction of E.I.C. |
| 53 | PUMP AND MOTORS : Supply, Installation & Testingof pumping sets of approved make & required rating, head & discharge including supply of all labour, material, tools & plants all complete as per specification and direction of Engineer In-Charge. i) vertical submersible Pumpset |
| 54 | Horizontalsubmersible Pumpset with testing & commissioning as per required rating, head & discharge etc. complete as per direction of Engineer-in-Charge. |
| 55 | Supply, Installation & Testingof Star Delta control Pannel board with APFC arrangement for running of Horizontal & vertical submersible pump set, of approved make & required rating, head & discharge including supply of all labour, material, tools & plants all complete as per specification and direction of Engineer In-Charge. |
| 56 | 6 mm 2 x 3 core flat submersible cable ISI marked for submersible pump set. |
| 57 | Supplying fitting and fixing of 50 mm 2 x 3.50 core armoured cable solid alluminium conductor upto 10 mm 2 , PVC inner sheathed and outer sheathed 650/1100 volt grade as per IS 7098 (Part-I) 1988 |
| 58 | 63 KVA SUB-STATION [UP-GRADATION AND NEW]: Dismentalling existing Tranformer for up gradation as required as per enhancement of load factor including its supporting accessories etc. completed[ Provisional ] |
| 59 | Supplying, Fitting, Fixing, Testing & Commissioning of following items of works for 63 KVASub-Station, 11KV 3-phase line-0.120 KM 9.0 mtr PSC Pole |
| 60 | 8.0 mtr PSC pole |
| 61 | 11KV GI Pin |
| 62 | 11 Kv Pin insulator |
| 63 | T&C Hardware fittings |
| 64 | 11 Kv T & C Disc Insulator |
| 65 | 18mm G.I Stay |
| 66 | 7/10 G I Stay Wire. |
| 67 | MS Clamp for Stayset |
| 68 | 11 Kv Stay insulator |
| 69 | 3 Pole 11KV A B Switch (200Amp) |
| 70 | 3 Pole 11KV H.G Fuse |
| 71 | 40mm G I Perforted Pipe Earthing Device. |
| 72 | 100 x 50 x 6 mm M S Channel |
| 73 | 75 x 40 x 6 mm M S Channel |
| 74 | 50 x 50 x 6 mm M S Angle |
| 75 | 16 mm M S Bolt & Nuts with Washer |
| 76 | 11kv Lightning Arrestor |
| 77 | No - 6 / 8 GI Wire |
| 78 | 25x5mm GI flat for neutral earthing |
| 79 | 55mm2 AAA Conductor |
| 80 | 63 KVA 11/0.4KV Transformer (star rated) |
| 81 | Distribution Box for 63KVA Transformer |
| 82 | 50mm2 X 3.5Core PVC Cable |
| 83 | No-8 Alluminum Binding Wire /Tape |
| 84 | All cable lugs of different size |
| 85 | Red Oxide Paint |
| 86 | Alluminum Paint |
| 87 | Black Paint |
| 88 | INTERNAL ELECTRICAL WIRING TO PUMP HOUSE (Single phase) i)Internal electrical wiring to pump house (Single phase) short point |
| 89 | Medium Point |
| 90 | Long point |
| 91 | Surface wiring to fan point in 1 sqmm PVC single core multi strand copper wire run inside the casiong capping with 6amp switch including cost of all materials, labourcharges and taxes as specification (medium point) |
| 92 | Surface wiring to 3 pin 5 amp plugin 1 sqmm pvc single core multi strand copper wire in existing board with connecting of running earth |
| 93 | S/F of backlight angle holder |
| 94 | S/F of 10 Amp fuse unit |
| 95 | S/F of indicator lamp |
| 96 | S/F of 16 Amp Elemeck main switch of ISO 9002 on casing board including cost of all materials and labour including taxes as applicable. |
| 97 | Internal electrical wiring to pump house (three phase)i) Supplying of 100 Amp 415 volt TPN main switch withfuse unit and neutral bar . The Switch to be fixed on MSframe with not |
| 98 | Supplying for MS clamp set for fixing of 4 nos of 100 Amp kit-kat, inside pump house |
| 99 | Supplying of100 Amp kit-kat of good quality to be fixed inisde pump house. |
| 100 | Surface wiring to motor point, pannel board from 100 Amp kit-kat , main switch by 10mmsq PVC copper wire of ISI marked with the materials required as details below (with materials required for earth connection ) PVC single core multi Strand copper wire |
| 101 | PVC flexible pipe |
| 102 | Flexible pipe saddle |
| 103 | No. 10 earthing copper wire |
| 104 | Brass bolt 4\" |
| 105 | Nut bolt 1/4\" |
| 106 | Nut bolt 3/16\" |
| 107 | 10 mm earthing socket |
| 108 | 10 mm ring socket |
| 109 | 25 mm ring socket |
| 110 | Nail of different size |
| 111 | 4 mm thick copper bush bar plate 12\" length |
| 112 | HS 48\" Ceiling Fan (Usha/havells/Orients) |
| 113 | S & F of standard earthing conforming to IS 3043/1987 including supply and fixing of 38 mm/ 40 dia heavy duty G.I. pipe 3.0 mtr long, conforming to IS 1239 part-I/1990. The pipe shall have 12 mm dia perforated holes at 15cm interval center to center up to 2.5 mtr height from the bottom site of 0.75 x 0.75 x 3.0 mtr the earth pit shall have alternative layer of charchol and salt around the electrode upto depth of 466mm from the bottom with fitting and fixing of 8 no copper wire of soldering with earthing socket. |
| 114 | BLEACHING PUMP WIRING1.50 mm PVC wire copper make |
| 115 | PVC flexible pipe |
| 116 | PVC saddle |
| 117 | PVC grip |
| 118 | Screw 1\" & 1.5 \" |
| 119 | Earthing wire No 8 copper make |
| 120 | 8\" x 10\" casing board |
| 121 | Add labour charges of items , wiring for three phase & bleching pump wiring |
| 122 | Supply, installation, testing and commissioning of Time switch F.M Quartz 50/60 Hz 240volt A.C (Reputed make) |
| 123 | Supply, installation, testing and commissioning of 60 watt LED street light fitting including bulb & necessary connection as per specification and direction of Engineer-in- charge. |
| 124 | CONSTRUCTION OF ELEVATED STORAGE RESORVOIR : Supplying all Materials labour T&P for Soil testing, Providing of Engineering drawing design & drawing, construction ,irrection, testing & Commissioning etc. of RCC elevated storage reservoir of different capacity with stagging height of 24.0 mtr consisting of minimum 6 nos RCC Circular column and circular Dome Using Cement Concrete M-30 for the container & M-25 for other components with water proofing treatment to the interior surface of the water container by applying a coat of crystalline water proofing products like xypex or equivalent crystaline products before plastering/ finishing, piping arrangement with supply of pipes, fittings (flanged CI pipe Class-A of 100mm dia & C.I. Puddle collar) for inlet, outlet, over flow & wash out arrangement & length upto 5.0 mtr beyond fce of the structure with provision of ISI marked CI Sluice valve/ Butter fly Valve & its RCC valve Chamber.There should be RCC outer stair case with Stainless steel hand rail (both sides) and support railing at dome and landing level, stainless steel ladder inside and out side the ESR using SS tublar section of size 40mm-50mm (as horizontal and vertical members) respectively. Provision of lighting arrester using copper lightining spike rod 25mm x 3mm GI flat, standard earthing using 40mm dia and 3.0 mtr long GI earth pipe, digital water level indicator, 0.6 m dia CI manhole cover at dome , RCC vent with alluminium jally, painting of the structure with two coats of weather coat over a coat of primer as per the approved colour and opattern ofH & UD department etc. all complete as directed by the Engineer-in-charge. [Pile foundation is to be adopted]N.B.:-The structural design should be made as per the local environmental condition [Considering the design wind speed calculated based on the different risk co-efficient as Topography factor, tarrain co-efficient, cyclonic region factor etc. as per relevant IS codes. Pile foundation or raft type foundation should be proposed considering the soil bearing capacity (test report shall be witnessed by concerned field officer) and the design shall be vatted from approved state technical agency as recomended by the concerned Engineer- in- charge] Upto 1.0 lakh liter and stagging above 20.0 mtr height and for aheight of 24.0 mtr (5 nos. x 1,00,000 ltrs. capacity |
| 125 | CONSTRUCTION OF UGR AND COMMISSIONING:Design, drawing, construction, testing, commissioning of following capacity of RCC UGR/GSR etc. all complete as per specification & direction of Engineer-in-Charge. A) 02 nos. 300000 ltrs. Capacity. |
| 126 | 01 no. 1,00,000 ltr. Capacity |
| 127 | COMMISSIONING OF 3.0 LAKH LITER UGR-2 Nos AND 1.0 LAKH LITER -1 No RCC OF UGR AND COMMISSIONING: Commissioning of UGR including Installation of pump set with cutting and threading and welding of 4\" dia G.I. pipe (medium), fitting and fixing of valve 4\" dia G.I. bend, and specials including transportation of materials to site etc. including laying of cable line fromUGR to pump house etc. all complete, Supplying all labour T & P with transportation for 10 HP Submersible pump set with motor and fitting and fixing of flat cable tagingfixing M.S. clamp and M.S. plate and necessary materials |
| 128 | Labour for 4\" dia flange joint to socket and bend |
| 129 | Labour for welding of 4\" dia flange with 4\" G.I.socket to column pipe etc. completed |
| 130 | Labour for Flame Cutting and facing of MS Plate or pipes upto 8mm thick etc. completed |
| 131 | Earthwork in all kind of soil |
| 132 | Metal road cutting |
| 133 | Labour for cable joint |
| 134 | Labour for laying of cable pipe up to pump house |
| 135 | Supplying all, materials labour T&P such as providing fitting,fixing of medium grade G.I. pipe cutting to the required size each with threading, welding of flanges with 5/8\" dia hole in flanges. The flanges should be in a horizontal position including cutting grooves for cable with the pipe so that each flanges when joint with rubber insertion packing shall remain water tight etc.completed as per specification and direction of E.I.C 80mm (3\" dia) x 3.0 mtr long G.I.pipe welded with M.S. flanges/Socket joint both side (medium grade |
| 136 | 100mm (4\" dia) x 1.0 mtr long G.I.pipe welded with M.S. flanges joint both side (medium grade) |
| 137 | Fitting and fixing of following materials i) 100mm x 100mm x 100mm x MS Tee |
| 138 | 100mm dia MS flange |
| 139 | 100mm dia 90 0 MS Bend |
| 140 | 100mm C.I. NR Valve |
| 141 | 100mm C.I. Sluice Valve Valve |
| 142 | Fitting and fixing of 25mm dia C.I Airvalve |
| 143 | 100mm C.I. Duck foot Bend |
| 144 | 100mm dia G.I. Socket |
| 145 | 100mm x 75mm dia G.I. R/S |
| 146 | 75 mm dia G.I. Nipple 450 mm long |
| 147 | Supplying all materials, labour T & P and installation of automatic water level controller (Sensor) for three phase pump set including round cable, electronic flot & sensor unit etc. all complete including testing & commissioning etc. all complete as per direction of Engineer-in- charge) |
| 148 | DISTRIBUTION NET WORK : Earth work in excavation in pipe line trenches within 50.0 mtriniial lead and 1.50 mtr initial lift in all kind of soilinclding rough dressing and breaking the clods maximum 5cm to 7cm and laying in layers not exceeding 0.30 mtr in depth and as per direction of Engineer-in-charge. |
| 149 | Laying in trenches centrifungally cast (Spun) Ductile iron socket and spigot pipeof the following nominal diameter as per specification and direction of Engineer -in- charge including supplying of all labour, materials,tools & plants required to perform the work (Earth work work in trenches, jointing of pipes, specials & fittings to be measured and paid seperately, including carriage ), 100 mm dia Class K-7 D.I. Socket & Spigot pipe |
| 150 | 150 mm dia Class K-7 D.I. Socket & Spigot pipe |
| 151 | 200 mm dia Class K-7 D.I. Socket & Spigot pipe |
| 152 | Supplying all labour , materials T&P and making Push-on joints using rubber rings or push on joints to centrifungally (Spun) C.I/D.I. pipes using rubber gasketsof SBR (Styrevebutadine-Rubber) quality of the following nominal dia including testing of the joints but including the cost of rubber rings as per specification complete.i) 100 mm dia Class K-7 D.I. pipe |
| 153 | 150 mm dia Class K-7 D.I. pipe |
| 154 | 200 mm dia Class K-7 D.I. pipe |
| 155 | Supplying all labour , materials T&P and providing flanged jointsto flanged D.I. pipes and fittings of the following nominal dia including testing of the joints, cost of bolts & nuts & rubber insertion as per specification complete.i) 100 mm dia |
| 156 | 150 mm dia |
| 157 | 200 mm dia |
| 158 | Providing and fixing ofCI Mechanical joint socket to flanged ends of CI/DI pipes including supply of all materials, labour, tools & plantsand testing of joints etc. all complete as per specification and direction of E.I.C. including supplying of all labour,materials,tools & Plants required to perform the work, i) 100 mm dia |
| 159 | 150 mm dia |
| 160 | 200 mm dia |
| 161 | Supplying all labour , materials T&P and Providing laying of MS pipe of all classesconforming to IS :3589 & IS: 3601 of the following outer diameter withpainting two coats over coat of primeretc. all complete as per specification & direction of E.I.C. including supply of all labour, materials T & P requiredto perform the work (Earth work will be measured separately).100.0mm outside dia & 4.0 mm thick MS pipe |
| 162 | 100 mm dia x 90 0 MS bend |
| 163 | 100 mm dia MS Flange |
| 164 | 168.30 mm outside dia & 4.50 mm thick MS pipe |
| 165 | 150 mm dia x 90 0 MS bend |
| 166 | 150 mm dia MS Flange |
| 167 | Flame cutting and facing the MS plate or pipe up to 8mm thick including supply of all labour materials T & P for following plate thickness all complete as per specification and direction of Engineer-in- Charge |
| 168 | Providing joint by welding with two welding beads/Pass conforming to IS; 816-1998 (Fillet weld) to MS pipe and fittings at site by using welding generator including testing of joints, as per specification complete including supplying of all labour, materials, tools & plants required to perform the work |
| 169 | Supplying all labouur , T&P for filling in foundation and plinth and pipe trench with excaveted materials including watering and ramming as directed by the Engineer-in-charge. |
| 170 | Dismentalling cement concrete pavement by mechanical means using pnemutic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismentalled materials up to a lead of 1000 mtr , stacking the serviciable and un-serviciable materials separately. |
| 171 | Supplying all materials, labour T&Pand filling in F & P with river sand well watered and rammed including conveyence of all materials etc.all complete as per approved specification and direction of the E.I.C. |
| 172 | Supplying all materials, labour T&P and providing C.C. (1:3:6) using 40mm hg metal including curing including conveyence of all materials to work site payment of royalty taxes etc.all complete as per approved specification and direction of the E.I.C. |
| 173 | Supplying all materials, labour T&P and providing C.C. (1:2:4) using 12mm hg chipse including curing including conveyence of all materials to work site payment of royalty taxes etc.all complete as per approved specification and direction of the E.I.C. |
| 174 | Supply, installation & Testing of Cast Iron Sluice valve of RATING PN -1.0 (IS 14846) with double flanged ends for water works purpose conforming to IS: 2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, materials, T & P required to perform the work (including cost of Nut bolts & washer, Rubber insertion sheet etc.)100 mmdia C.I. S. Valve (PN-1.0) with wheel |
| 175 | 200 mmdia C.I. S. Valve (PN-1.0) with wheel |
| 176 | Supply, installation & Testing of Single Air relivevalve conforming to IS: 14845for water works purpose for the following diameter including drilling the water main (Cast iron pipe with metal straps)as per specification complete including supply ofing of all labour, materials,T & P required to perform the work (including cost of Nut bolts & washer, Rubber insertion sheet etc.)i) 25mm dia C.I. Single Air Valve |
| 177 | Suppying all labour materials T&P for cutting C.I./ D.I. pipes and inserting specials for jointing, Cutting and welding pipe lines fixing of valves etc. all complete as per direction of Engineer-in- charge: 150mm/100 mm dia pipe |
| 178 | Construction of sluice valve chamber of the following nominal size and Specification withprovision for earthwork in excavation in all kinds of Soil, filling sand 0.10 m thick, 0.15 m thick PCC (1:3:6) over wall top, B/W in F & P in CM (1:4), 0.15 m thick RCC (1:1.5:3) in cover slab, 12 mm thick CP in CM (1:4) on outside and top of the wall portion etc. all complete.as per specification for different size of sluice valve ( Details estimate attached) Size 0.91m x 0.91m x 1.20 mtr inside |
| 179 | Transportation of surplus earth and dedris by mechanical means & disposing it within a distance of 5 KM all labour, T & P complete as per direction of Engineer -in-charge |
| 180 | Providing laying, fixing & testing of D.I. specials, bends, etc. in trenchesall complete as per specification and direction of Engineer-in- charge in cluding supplying of all labour,materials, t & P required to perform the work (Excluding E/W) |
| 181 | Supplying all labouur , T & P for repair of consumer house connection during excavation of trench for laying of D.I. pipe line including earth work in all kinds of soil, fitting and fixing of necessary pipe and fittings, dewatering & refilling the pit with excavated materials etc. all complete to resume the water supply to consumer as per specification & direction of E.I.C. |
| 182 | Supplying all labouur , T&P for shifting of consumer house connection (after commissioning of newly laid pipe line) including earth work in all kinds of soil, fitting and fixing of 15 mm dia ferrulel with necessary 25 mm dia HDPEpipe of 4.0 mtr length & fittings, dewatering, refilling the pit with excavated materials including cutting C.C. road & mending the same providing sand filling, C.C. (1:3:6) with 4 cm metal & C.C. (1:2:4) with 12 mm chips etc. all complete as directed by the Engineer-in-charge. |
| 183 | Single under reamed pile foundation with RCC (1:1.5:3) using 12 mm bhg CB chipse including cost of boring and excluding cost of M.S/Tor steel and labour charges for cutting, bending and binding of steel. etc completed and as per direction of EIC . 250 mm dia and 3.0 mtr long single under reamed pile |
| 184 | Supplying all materials, labour, T &P and providing C.C (1:1.5:3) using 12mm h.g. chips for R.C.C. works including hoisting, laying, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc, all complete as per specification and direction of E.I.C. |
| 185 | Supplying all materials, labour, T&P and providing M.S. reinforcement for R.C.C. works including cutting, bending, binding and tying the grills and placing in position including cost of binding wire18 to 20 gauge, conveyance of all materials to worksite, payment oftaxes etc. all complete as per specification and direction of E.I.C. |
| 186 | Supplying all materials, labour, T&P and providingrigid & smooth centering & shuttering for R.C.C.works including false work and dismantling them after casting including conveyance of all material, to worksite, payment of etc. all complete as per specification and direction of E.I.C. i) Column |
| 187 | CONSTRUCTION OF COMPOUND WALL : Single under reamed pile foundation with RCC (1:1.5:3) using 12 mm bhg CB chipse including cost of boring and excluding cost of M.S/Tor steel and labour charges for cutting, bending and binding of steel. etc completed and as per direction of EIC .i) 250 mm dia and 2.50 mtr long single under reamed pile |
| 188 | Earth work in all kinds of soil in excavation of foundation trenches within 50 m initial lead including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding o.30 in depth and as per direction of EIC . i) Initial lift upto 1.50m |
| 189 | Supplying all materials, labour T&P and filling in F&P with river sandwell watered and rammed including conveyance of all materials to worksite payment of royalty, taxes etc. all complete as per direction of E.I.C. |
| 190 | Supplying all materials, labour, T&P and providing brick work with F.A. bricks having c.s. not less than 75kg/cm2 with dimensional tolerance ± 2% including watering, curing conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. i) In F&P (1:6) |
| 191 | In Super Structure (1:6) |
| 192 | Supplying all materials, labour, T & P and providing 2.5 cm thick Damp proof course with (1:2:4) using 12mm size bhg CB chipse including curing etc. all complete as per Specification and direction of E.I.C. |
| 193 | Supplying all materials, labour, T &P and providing C.C (1:1.5 :3) using 12mm h.g. chips for R.C.C. works including hoisting, laying, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc, all complete as per specification and direction of E.I.C. |
| 194 | Supplying all materials, labour, T&P and providing M.S. reinforcement for R.C.C. works including cutting, bending, binding and tying the grills and placing in position including cost of binding wire18 to 20 gauge, conveyance of all materials to worksite, payment of taxes etc. all complete as per specification and direction of E.I.C. |
| 195 | Supplying all materials, labour, T&P and providingrigid & smooth centering & shuttering for R.C.C.works including false work and dismantling them after casting including conveyance of all material, to worksite, payment ofetc. all complete as per specification and direction of E.I.C.i) Foundation & Plinth |
| 196 | Column |
| 197 | G. Beam |
| 198 | Slab |
| 199 | 1Supplying all materials, labour, T&P and providing cement plaster on brick/stone work including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. i) 2 mm thick C.P in (1:6) |
| 200 | Supplying all materials, labour, T&P and providing cement punning including watering,curing, conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as per specification and direction of E.I.C. |
| 201 | Supplying all materials, labour, T&P and providing and fixing M.S. Grill gate with M.S. framedincluding conveyance of all materials to worksite, as per specification and direction of E.I.C. |
| 202 | Supplying all materials, labour, T&P and providing and painting two coats with enamel paint over a coat of primer to iron works etc. complete as per direction of E.I.C. |
| 203 | Supplying all labour T&P, materials and finishing wall with cement primer one coat including cost of brushes and putty with cost of paint and direction of E.I.C. |
| 204 | Supplying all labour T&P, materials and finishing wall with weather paint of approve shade on new work two coats to give an even shade including cost of brushes and putty with cost of paint and direction of E.I.C. |
| 205 | BLEACHING DOZING ARRANGEMENT: Chlorination, Supplying,Installation , Testing & Commissioning of Chemical dozing system Chlorinator consisting of Mechanically actuated diapharam type metering pump having capacity to discharge 30 LPH of chemical solution (Bleaching/ Sodium hypochlorite solution) with injection pressure of 10 kg/cm 2 all complete to run the system as per direction of Engineer-in- charge. including supply of in/out suction discharge, NR valve & flexible dozing pipe 5.0 mtr |
| 206 | Supplying all materials labout T & P for fitting and fixing of CPVC flow guard pipes, grade conforming to IS 15778/2007 (SDR-11) with 100 % lead free with NSF & CBRI approved with good quality fittings on walls, floors and mending good the damages after laying as per site requirement etc. complete including testing as per specification and ditection of Engineer-in-charge. 25 mm dia CPVC Pipe |
| 207 | Supplying all materials labout T & P for fitting and fixing of GM/Brass Ball Valve including cost of materials & taxes etc. all complete and testing at site as per site requirement etc. complete including testing as per specification and ditection of Engineer-in-charge. 25 mm dia GM/Brass ball valve |
| 208 | Supplying all materials labout T & P for construction of RCC tank foundation & Padestal for installation of RCC tank in RCC (1:1.5:3) of size 1.0m x 1.0m x 0.60 mtr over PCC (1:3:6) including certering and shuttering, cost of street, curing & supply of required materials in proper alignment and level etc. all complete as per specification and ditection of Engineer-in-charge. |
| 209 | Supplying all materials labout T & P for construction of RCC Pump foundation &installation of Pump set in RCC (1:1.5:3) of size 1.0m x 1.0m x 0.60 mtr over PCC (1:3:6) including certering and shuttering, cost of street, curing & supply of required nos of S/S foundation bolt & nuts, fixing the pump base plate in proper alignment and level and level etc. all complete as per specification and ditection of Engineer-in-charge. |
| 210 | Supplying all materials labout T & P for fitting and fixing of S/S or special quality PVC check Valve or Non-return valve, Class-2 suitable for pipes etc. complete as per specification and ditection of Engineer-in-charge. |
| 211 | Supplying all materials labout T & P for construction of RCC storage tank in RCC (1:1.5:3) of following size including centering and shuttering, plastering, punning, cost of steel, Curing in proper alignment and level etc. all complete as per specification & direction of Engineer-in- charge-500 ltr capacity RCC storage tanki) 500 ltr capacity RCC storage tank each |
| 212 | Accessories for pump sets like coupling, coupling guard, Y type strainer and Pressure release valve (Safty type) complete with installation & testing as per direction of Engineer-in- Charge |
| 213 | Supplying, fitting and fixing of electrical wiring for 3-phase power including supply of necessary electrical cable, plugs etc. from nearest 3-phase power point to work site etc. as per direction of Engineer-in- charge |
AI Tender Summary
Tender Timeline
Nov 10, 2022
11:30 IST
Tender Published
Tender notice published.
CompletedNov 25, 2022
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedNov 28, 2022
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender