Border Security Force-BSF has published Tender For Repair And Maintenance Of Amf Distribution Panels Mfp And Sfp Of Bfl Panels Installed At Various Bops In Aor Of 96 Bn Bsf Including Batteries Under Shq Bsf Udaipur. Submission Date for this Tender is 16-11-2022. Dry Cell Batteries Tenders in udaipur Tripura. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Providing and fixing 160 amps MCCBs, 4 pole with breaking capacity 36 KA, 415 volts with suitable operating mechanism extended rotary handle and spreader terminal in existing cubical panel board including drilling holes in cubical panel, making connections (including deducting the cost of old , scrapped material) etc as required Make- L&T Cat no- CM98065OONO or its equivalent make of Havells/Standard/Legrand/ABB/C&S. |
2 | Providing and fixing 32 amps, 415 volt, TPN Disconnector fuse switch unit open execution with suitable HRC fuse link,for fixing in existing SS enclosure with door interlock facility including dismantling of defective one, drilling holes complete with connections, testing ,commissioningetc. as reqd. L&t make Cat no SK95703 or its compatible to Havells/or its equivalent make of Standard/Legrand/ABB/C&S. |
3 | Providing and fixing 63 amps, 415 volt, TPN Disconnector fuse switch unit open execution with suitable HRC fuse link,for fixing in existing SS enclosure with door interlock facility including dismantling of defective one, drilling holes complete with connections, testing ,commissioningetc. as reqd. L&t make Cat no SK95704 or its compatible to Havells/or its equivalent make of Standard/Legrand/ABB/C&S. |
4 | Providing and fixing 125 amps, 415 volt, TPN Disconnector fuse switch unit open execution with suitable HRC fuse link,for fixing in existing SS enclosure with door interlock facility including dismantling of defective one, drilling holes complete with connections, testing ,commissioningetc. as reqd. L&t make Cat no SK95001 or its compatible to Havells/or its equivalent make of Standard/Legrand/ABB/C&S. |
5 | Providing and fixing 250 amps, 415 volt, TPN Disconnector fuse switch unit open execution with suitable HRC fuse link,for fixing in existing SS enclosure with door interlock facility including dismantling of defective one, drilling holes complete with connections, testing ,commissioningetc. as reqd. L&t make Cat no SK95001 or its compatible to Havells/or its equivalent make of Standard/Legrand/ABB/C&S. |
6 | Providing and fixing of combined type digital display meter suitable for measuring AC voltage, current , KWH,KW,PF Frequency etc having three line display 3 phase multifunction meter in existing cubical panel board including , making connections (including deducting the cost of old scrapped material) etc. as reqd. Make- L&T code-WL441010OOOO or its equivalent make of Havells/ Standard/Legrand/ABB/C&S. |
7 | Supplying and making interconnections with following size of single core PVC insulated 1.1 KV grade copper conductor cable between switch gears, bus bars etc of existing panel including providing suitable size cable lugs/thimbles (including deducting the cost of old scrapped material) etc complete as required (Finolex/Polycab/KEI/Havells/L&T)(i)-16 SQMM single core HeavyDuty copper cable. |
8 | 35 SQMM single core HeavyDuty copper cable. |
9 | Providing & fixing of capsule type metal panel hinges (plain electric panels) size 16 mm X 80 mm for main/sub feeder pillar door/cover installed at BFLs pole, includingfixing by gas/ arc welding on existing looping box/bus bar chamber etc. as required. |
10 | Providing & fixing of capsule type metal panel hinges (plain electric panels) size 12 mm X 50 mm for main/sub feeder pillar door/cover installed at BFLs pole, includingfixing by gas/ arc welding on existing looping box/bus bar chamber etc. as required. |
11 | Providing & fixing of tool box/suitcase box metal spring loaded toggle latche (size 90 mm x 35 mm x 15 mm ) sutable for control gear box cover installed at BFLs pole,including fixing by welding on existing control gear box etc. as reqd. |
12 | Providing and fixing of 125 amps , 415 volt, Bolted fuse link suitable for 125 amps disconnector fuse unit, size A4 conf. IS/IEC 60947-3 and testing , commissioning and dismantling of existing fuse etc. as required Make-L&T cat no ST30769 or its compatible to Havells/Standard/Legrand/Schneider . |
13 | Providing and fixing of 63 amps , 415 volt, Bolted fuse link suitable for 63 amps disconnector fuse unit, size A1L, conf. IS/IEC 60947-3 and testing , commissioning and dismantling of existing fuse etc. as required Make-L&T cat no ST35828 or its compatible to Havells/Standard/Legrand/Schneider . |
14 | Providing and fixing of 32 amps , 415 volt, Bolted fuse link suitable for 32 amps disconnector fuse unit, size A1L, conf. IS/IEC 60947-3 and testing , commissioning and dismantling of existing fuse etc. as required Make-L&T cat no ST34529 or its compatible to Havells/Standard/Legrand/Schneider . |
15 | Providing and fixing of spreader terminals 4P,suitable for 160 amps MCCB, 4 pole, breaking capacity 36 KA , making connections etc. as required. Compatible to L&T make cat.no- CM92007OOOO (set of 8) make Havells/Standard/Legrand/Schneider/ABB/Seimen. |
16 | Supplying & fixing of 3 nos LED indicator 16 mm surface mounted low power consumption, surge & low voltage glow protection cat no SIL, in the yellow and Blue colours, L&T make, including connections with 0.75 sqmm FRLS single copper conductor cable etc. as reqd. |