Tender For Repair/Replacement And Maintenance Of Water Supply Distribution System, Leak Proof Valves And Allied Works At Zone 1C Under Age E/M No 1 Ge (U) Secunderabad, secunderabad-Telangana

Military Engineer Services-MES has published Tender For Repair/Replacement And Maintenance Of Water Supply Distribution System, Leak Proof Valves And Allied Works At Zone 1C Under Age E/M No 1 Ge (U) Secunderabad. Submission Date for this Tender is 19-11-2022. Water Supply Project Tenders in secunderabad Telangana. Bidders can get complete Tender details and download the document.




Tender Notice

34615700
Corrigendum : Tender For Repair/Replacement And Maintenance Of Water Supply Distribution System, Leak Proof Valves And Allied Works At Zone 1C Under Age E/M No 1 Ge (U) Secunderabad
Open Tender
Indian
Telangana
secunderabad
19-11-2022

Tender Details

Repair / Replacement And Maintenance Of Water Supply Distribution System, Leak Proof Valves And Allied Works At Zone 1C Under Age E / M No 1 Ge ( U ) Secunderabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 12-Nov-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 19-11-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 79800.0 /-
Tender Value
INR 39.90 Lakhs /-

BOQ Items

Name of Work:REPAIR/REPLACEMENT AND MAINTENANCE OF WATER SUPPLY DISTRIBUTION SYSTEM, LEAK PROOF VALVES AND ALLIED WORKS AT UMRAO LINE, NAPIER LINE, PLASSY LINE AVATAR LINE, CHARVA LINE, SARVATRA LINE, MAP OFFICERS, JCOs/ORs QTR, KOMPALLY, SIKH VILLAGE, 8 FD REGT, 2 LANCER, 61 MED REGT, TATRA UNIT, 22 MED REGT AND 54 ARTY BDE OF ZONE 1C UNDER AGE E/M NO 1 GE (U) SECUNDERABAD
Sl. No. Item Description
1M&L for attending repair/rectification ofexternal water supply complaints of GI/CI/DI/PP-R Pipe lines, sluice valves, gate valves of any type and size, Viz any type of leakages, no water supply and other water related complaints including transportation from complaint cell to complaint locations and back to complaint cell along with necessary T&P with provision of necessary excavation, returning and filling in as required at site, tightening of loose joints of union, elbow, sockets etc, cutting/threading and making joints and cleaning for any blockages, opening of float valve of service tanks, cleaning and fixing the same in its position including replacement of GI unions/sockets/nipples etc as required at site under Zone I C of AGE EM No.I areas and the following type of complaints all as specified and directed.
2All as per item No 1 here-in-before for GI tubing up to 32mm bore
3All as per item No 1 here-in-before but for GI tubing 40 mm bore to 59 mm bore
4All as per item No 1 here-in-before but for GI tubing 80 mm bore to 110 mm bore
5Notes for Sl item No 1 to 1.03:- (a)The contractor will be allotted complaints at MES complaint cell on required basis on all working days including Sundays and holidays and sufficient tradesman / resources will be deployed by him/her for completion of day to day complaints within 12 hours from the time of reporting. Any delay beyond above mentioned time limit without intimation of genuine cause, penalties will be recovered twice of the quoted rate for each un-attended complaint. (b)A detailed log book of complaints with completion/non-completion remarks from users/MES will be maintained by the contractor and the same will be updated on daily basis in consultation with JE E&M/Engr-in-Charge. (c)The contractor will make suitable arrangement for emergency complaints and will notify authorised representive/Engr-in-Charge about extraordinary circumstances for probable non-completion or delay in rectification of complaints beyond stated time limit set for disposal of complaint.In case of any dispute the decision of accepting officer will be final and binding in this regard.
6(d)The contractor will intimate MES authority well in advance if electric shutdown is required during rectification of complaints. (e)The quoted rate is deemed to be inclusive of transportation and other expenses required for the resource deployment at the complaint site around scattered Military station at Secunderabad. (f)The contractor will maintain location wise record of each spare/fittings utilized as per inventory format given by AGE E/M, Secunderabd and the same shall be submitted to E/M No Istore yard on daily basis. (g)The stationery required for the job work such as complaint slip books, gate pass book, job card and T&P shall be arranged and maintained by the contractor. (h) The cost of excavation / earth work and repairs to damaged roads, LT UG/HT cables, existing structure etc shall be deemed to be included in the quoted unit rate and no extra payment shall be allowed on this account. (j) Spares/GI fittings required to be replaced and shall be measured and paid separately under respective items.
7Taking up defective cast iron water mains (including all fittings) with spigot and socket ends and lead joints including burning out joints and recovering lead from ground, cleaning the pipes free from sedimentation/scaling etc for reusing the serviceable pipes in repairs complete all as specified and directed for the following sizes:-
880 mm bore.
9100mm bore.
10150mm bore. Note for item Nos 2.01 to 2.03:- Excavation and earth work shall be measured and paid separately.
11Re-laying only cast iron pipes obtained from item No.2 above including laying to level or to falls, in trenches or on the ground or on supports complete all as specified and directed for the following sizes:-
1280 mm bore.
13100mm bore.
14150mm bore. Note for item Nos 3.01 to 3.03 :-Lead joints shall be measured and paid separately.
15M&L CI pipes with spigot and socket ends centrifugally cast class "LA" in any length suitable for tyton / lead jointslaid in trenches including necessary cut to length to match the existing fitting/pipes, testing and making gooddisturbed surfaces of roads, path ways etc., while laying the pipe line at sitecomplete all as specified and as directed for the following sizes:-
1680mm bore.
17100mm bore.
18150mm bore. Note for item Nos 4.01 to 4.03 :-Lead joints shall be measured and paid separately.
19Taking up or down GI/PVC/PP-R water tubing and connections including cleaning the pipes free from scaling for reusing the same in repairs / alteration or removable to store etc to water pipes and connections complete all as specified and directed for the following sizes:-
2020 mm bore.
2125 mm bore.
2240 mm bore.
2350 mm bore.
2475/80 mm bore.
25100/110 mm bore
26Re-laying /refixing or reroutingof GI/PVC/PP-R old water tubing and connection in new or old position including fittings with old/new bends, elbows, socket nipples, tapers, and reducers etc as per site requirement (on floors, walls and ceilings) complete all as specified and directed.
2720 mm bore.
2825 mm bore.
2940 mm bore.
3050 mm bore.
3175/80 mm bore.
32100/110 mm bore
33Supply, lay and fixing steel water tubes,medium grade, ISI marked, galvanized with all fitting laid in trenches complete all as specified and directed forfollowing bore of pipes :-
3420 mm bore.
3525 mm bore.
3640 mm bore.
3750 mm bore.
3880 mm bore. Note :- Excavation and Earth work shall be measured separately.
39Supply, laying and testing of Polypropylene random copolymer (PP-R) (PN-16/SDR 7.4)-3 Layerspipes, UV stabilized and antimicrobial welded having thermal stability with and including all PP-R plain & brass threaded polypropylene random fittings fixedsuch as bends, Elbow, Tee, Short Length, Socket, Union, Check Nuts, Nipples etc. (Females/Males as required), suitable for hot cold water supply line including making good disturbed surfaces/cutting chassis in CM 1:3, laid in trenches and including testing complete allas per manufacture’s instruction and all as specified and directed for the following outer dia of pipes:- Make:- SFMC/SUPREME/FINOLEX/KPT
4020 mm bore (OD)
4125 mm bore(OD)
4240 mm bore(OD)
4350 mm bore(OD)
4475 mm bore(OD)
45110 mm bore(OD) Note :- Excavation and Earth work shall be measured separately.
46Supply only GI fittings 20 mm bore, medium grade, ISI marked, smooth finished and make embossed on fittings complete all as specified and directed for the following fittings:-
47Union
48All equal Tee
49Socket
50Nipple 75mm Long
51Nipple 100mm Long
52Plug
53Elbow
54All as per item No 09 here-in-before but for 25 mm bore.
55Union
56All equal Tee
57Socket
58Nipple 75mm Long
59Nipple 100mm Long
60Elbow
61Plug
62Reducer elbow 25mm x 20mm
63All as per item No 09 here-in-before but for 40 mm bore.
64Union
65All equal Tee
66Socket
67Nipple 75mm Long
68Elbow
69Reducer elbow 40mm x 25mm
70All as per item No 09 here-in-before but for 50 mm bore.
71Union
72All equal Tee
73Socket
74Elbow
75All as per item No 09 here-in-before but for 80 mm bore.
76Union
77All equal Tee
78Socket
79Elbow
80Supply and fixing in replacement of DIrising Spindle Resilient seated Gate Valve PN 16 (Soft Sealed) soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or equivalent grade as per IS 3896- Part - 2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quiality and Seals of NBR and the valve should be vacum tight and 100 % leak proof with face to face dimention as per BS 5163-89/IS 14846-2000/DIN 3202 F4 and Valves should be electrostatic powder coating both inside and outside pocket less body passage.including all jointing materials (Gasket, Nutbolts ets) connecting , testing and taking down old unservicable sluice valve complete all as specified and directed
8180 mm bore.
82100 mm bore.
83150 mm bore.
84200 mm bore.
85S&FMJ collar double ended flanged ISI embossed pressure 1.6 including jointing such as rubber gasket, nuts and bolts, washers materials etc complete including replacement of unserviceable sluice valves of any typecomplete all as specified and directed for the following sizes:-
8680 mm bore.
87100 mm bore.
88150 mm bore.
89200 mm bore.
90300 mm bore.
91S&F DI socket ISI embossed pressure 1.6 including jointing such as rubber gasket, etc complete including replacement of unserviceable socket of any typecomplete all as specified and directed for the following sizes:-
92100 mm bore.
93150 mm bore.
94200 mm bore.
95300 mm Bore
96Supply and fix gun metal gate valve, ISI embossed, conforming to is 781-1984, connected with iron wheel head, screwedat both ends for iron pipes and fixed including taking down of unserviceable gate valve complete all as specified and directed for the following sizes:-
9720 mm bore.
9825 mm bore.
9940 mm bore.
10050 mm bore.
101S &FPP-R Gate valves (brass insert), with iron wheel head, screwed both ends for PP-R Pipesand fixedin repair forfollowing bore of pipes :- Make:- SFMC/SUPREME/FINOLEX/KPT
10220 mm bore.
10325 mm bore.
10440 mm bore.
10550 mm bore.
106Supply only PP-R Pipe fittings 20mm bore, ISI marked, smooth finished and make embossed on fittings in repairs complete all as specified and directed for the following fittings:- Make:- SFMC/SUPREME/FINOLEX/KPT
107All equal Tee
108Socket
109Elbow
110All as per item No 19 here-in-before but for 25 mm bore.
111All equal Tee
112Socket
113Elbow
114All as per item No19 here-in-before but for 40 mm bore.
115All equal Tee
116Socket
117Elbow
118All as per item No19 here-in-before but for 63 mm bore.
119All equal Tee
120Socket
121Elbow
122All as per item No19 here-in-before but for 110 mm bore.
123All equal Tee
124Socket
125Elbow
126Supply and fix Cast Iron Air Valves with two air Outlets, conforming to IS 14845 of size 100 mm dia bore double acting (DS2) heavy duty including providing jointing material such as rubber fiber board gasket, suitable size bolts and nuts and washers, necessary supports, rasing DI pipe 100 mm dia double side and not less than 1.20 Mtr lengthIncluding taking down old unserviceable Air release valve complete all as specified and as directed by Engr-in-charge. Note :- CI/DI specials required at site are measured and paid separately.
127Supply and fix Cast Iron Air Valves with two air Outlets, conforming to IS 14845 of size 150 mm dia bore double acting (DS2) heavy duty including providing jointing material such as rubber fiber board gasket, suitable size bolts and nuts and washers, necessary supports, rasing DI pipe 150 mm dia double side and not less than 1.20 Mtr lengthIncluding taking down old unserviceable Air release valve complete all as specified and as directed by Engr-in-charge. Note :- CI/DI specials required at site are measured and paid separately.
128Excavation in trenches not exc 1.5m wide and not exc 1.5m depth for laying of pipe lines, valve chambers, man holes etc including forming bottom surface to required level and gradient and getting out in hard /dense soil complete all as specified and directed.
129Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc. 25 cms thick in soils complete all as specified and directed.
130Removing excavated soil to a distance not exceeding 59m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
131M&L cutting of road up to a sizenot exc 1.5m wide and not exc 1.5m depth for laying of water pipe lines making good the disturbed surfaces so as to match with existing finishing with PCC 1:2:4 type B1 , cement motor in CM 1:2 complete all as specified and directed
132Burning out lead joints of the existing CI mains in position including removing old lead carefully without damaging the pipes etc complete all as specified and as directed for the following sizes:-
13380 mm bore.
134100 mm bore.
135150 mm bore.
136200 mm bore. Note:- Excavation and earth work shall be measured and paid separatelyunder the relevant Sch "A" item.
137M&L for lead joint for CI pipes includingspun yarn etc for spigot & socket pipes and fittings complete all as specified and as directed for the following sizes:-
13880 mm bore.
139100 mm bore.
140150 mm bore.
141200 mm bore.
142M&L Rubber Gasket joints (Tyton joints) including rubber ring suitable for spigot and socket DI pipe and fittings complete all as specified and as directed for the following sizes:-
143150 mm bore.
144200mm bore. Note:- Excavation and earth work shall be measured and paid separately.
145S&F ductile iron pressure pipes 200 mm bore, class K9, centrifugally cast with spigot and socket ends conforming to IS 8329/2000 with cement mortar lining inside the pipes and outside zinc coating suitable for push-on-joint including (rubber gasket D jointing) inany length as required at site confirming to IS 8329/2000 and all jointing materials and making good for disturbed surfaces of roads, path ways etc while laying the pipe line at site, site clearance for the route of pipe line, welding, cutting the existing CI/DI/MS pipe line of any size up to 400 mm bore for inserting branch connections etc including taking down old existing one completeall as specified and directed :- Notes:- (a)DI pipe shall be laid in trenches at a depth of 1.0 to 1.5 m below the existing GL (b)DI specials will be measured and paid separately. (c) The contractor is responsible for obtaining the approval from Police Department for Traffic Diversion and related works if required in consultation with the MES department. (d) Contractor is responsible for repair/replacement of any damages to the existing structures, Under Ground HT/LT/OFC Cables etc during the course of execution.
146All as per Item No. 33 here-in-before but 150 mm ductile iron pressure pipe
147All as per Item No. 33 here-in-before but 100 mm ductile iron pressure pipe Notes for item No 33 to 35 :- (a)DI pipe shall be laid in trenches at a depth of 1.0 to 1.5 m below the existing GL (b)DI specials will be measured and paid separately. (c) The contractor is responsible for obtaining the approval from Police Department for Traffic Diversion and related works if required in consultation with the MES department. (d) Contractor is responsible for repair/replacement of any damages to the existing structures, Under Ground HT/LT/OFC Cables etc during the course of execution.
148M&L for Construction of brick masonry valve chamber of size 1000 x 1000 x 1000 mm (Internal dimensions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 159 mm thick, 159 mm wide off sets all-round over 100 mm thick hard core, brick masonry walls built in CM 1:6, 59 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally and 159mm below GL externally and top of floor including excavation, earth work in hard/dense soil, 5 mm thick MS sheet cover fixed on 59 mm x 59 mm x 6 mm thick angle iron frame with hold fasts embedded in PCC coping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of red oxide primer including disposal of surplus soil to a distance not exceeding 59 m etc complete all as specified and directed.
149Disconnecting the delivery pipe line and electric connections of submersible pump set of 7.5 HP / 5 HP and removing it from its original position along with pipes and fittings carefully including chain pulley with tripod and transporting the same to the work shop situated within thecity limits for repair and lowering including all pipes and fittings by means of chain pulley and tripodincluding connecting up of water and electric connections, testing andcommissioning complete all as specified and directed. Notes:- (i)Expendable stores like cotton waste / cleaning materials, lubricants, gland packing, metal filling, machining and transportation from site to work shop and back are deemed to be included in unit rate quoted. (ii) Labour element is deemed to be included in unit rate quoted. (iii)Replacement of worn out parts and rewinding will be measured and paid separately.
150M&L for rewinding ofthesubmersible motor with PVC insulated conductor with super enameled copper conductor,‘F’ class heavy grade insulation, weight and turns to achieve its full efficiency including tying the winding and connecting the coils and brining the connections as that of existing one including applying insulating varnish, heating and backing the windings thoroughly for submersible motor of 7.5 HP capacity including taking down old unserviceable existing copper winding complete all as specified and directed.
151All as per item No 38 here-in-before butfor thesubmersible motor 5 HP capacity.
152Supply only the following spares for repairs of submersible pump set of 7.5 HP capacity complete all as specified and directed.
153Gun metal impeller
154Stage casing
155Stage casing bush (LB)
156SS sleeves
157Pump shaft
158Pump coupling
159Discharge outlet bush LB
160Discharge outlet SS sleeves
161Supply only the following spares for repairs of submersible pump set of 5 HP capacity complete all as specified and directed.
162Motor bearing bush (LB) 04 Nos set
163Thrust bearing set
164NRV body
165Section bush
166Middle bush LB
167Middle SS sleeve
168Rotor (RE) work
169Opening Mono block pump set 5 HP capacity for inspection, repairs and reassembling the pump and motor as per the original assembly after repairs / replacing the worn out unserviceable parts with new parts as ordered including cleaning, replacing the minor items like packing bolts, nuts washers and MS clamps etc and applying one coat of approved hammertene spray paint on exposed steel surfaces, making the pump and motor fully serviceable including machining etc and testing the both after refixing and commissioning for satisfactory operation on its full load complete all as specified and directed.
170M&L for rewinding ofthemono block pump set 5 HP capacity with PVC insulated conductor with super enameled copper conductor‘F’ class heavy grade insulation, weight and turns to achieve its full efficiency including tying the winding and connecting the coils and brining the connections as that of existing one including applying insulating varnish, heating and backing the windings thoroughlyincluding taking down old unserviceable existing copper winding complete all as specified and directed.
171Supply only the following spares for repairs of Mono block pump set of 5 HP capacity:-
172Ball bearing
173Blind bush Gun metal
174Gland rope nut
175Terminal
176Opening Mono block pump set 7.5/10 HP capacity for inspection, repairs and reassembling the pump and motor as per the original assembly after repairs / replacing the worn out unserviceable parts with new parts as ordered including cleaning, replacing the minor items like packing bolts, nuts washers and MS clamps etc and applying one coat of approved hammertene spray paint on exposed steel surfaces, making the pump and motor fully serviceable including machining etc and testing the both after refixing and commissioning for satisfactory operation on its full load complete all as specified and directed.
177M&L for rewinding ofthemono block pump set 7.5/10 HP capacity with PVC insulated conductor with super enameled copper conductor‘F’ class heavy grade insulation, weight and turns to achieve its full efficiency including tying the winding and connecting the coils and brining the connections as that of existing one including applying insulating varnish, heating and backing the windings thoroughlyincluding taking down old unserviceable existing copper winding complete all as specified and directed.
178Supply only the following spares for repairs of Mono block pump set of 7.5/10 HP capacity:-
179Ball bearing
180Impellers
181PCV fan
182Gland rope
183Gland rope flang set
184S&F DOL starter 3 phase 415 Volts, 7.5 HP capacity rating 14 Amps, relay range 9 to 14 Amps, MK-1, including connecting up of incoming and outgoing connections and testing commissioning, including removingthe existing unserviceable one complete all as specified and directed.
185S&F submergible pump controller stator in sheet metal enclosure 3 phase 415 Volts, 5 HP capacity rating 32 Amps, relay range 20-32 Amps, Type MF -G3 $including connecting up of incoming and outgoing connections and testing commissioning, including removingthe existing unserviceable one complete all as specified and directed.
186S&F in repairs CI foot valve leather sheet type / flange type suitable for 80 mm dia GI suction heavy duty including replacement of nuts, bolts washers, gaskets and flanges etc. complete all as directed and specified by Engr-in-charge.
187S&F in repairs CI foot valve leather sheet type / flange type suitable for 100 mm dia GI suction heavy duty including replacement of nuts, bolts washers, gaskets and flanges etc. complete all as directed and specified by Engr-in-charge.
188S&F connecting and testing in repairs of non return valve of size 80 mm dia ISI marked , as per IS 5312 both ends flanged CI body with check nuts including jointing material complete all as specified and directed by Engr-in-charge.
189S&F connecting and testing in repairs of non return valve of size 100 mm dia ISI marked , as per IS 5312 both ends flanged CI body with check nuts including jointing material complete all as specified and directed by Engr-in-charge.
190Supply and lay submersible copper conductor cable 1100 volts grade PVC insulated, flexible, PVC sheathed with multistranded copper conductor of size 3 core 6 Sq mm cutting to required length connecting with necessary end ferrules / water proof joints including removing the existing unserviceable cable complete all as specified and directed
191M&L Flushingof existing bore wells of size 150 mm dia, 150 Mtrs depth with drilling compressorincluding surgingand flushing the bore at a pressure of 7 Kg / Sq cm complete with compressed air andflushing the sand, mud etc from the bore well till discharge of the fresh water, including testing of watersamples for chemical and bacteriological tests and yield testing for 8 hours complete all as specified and directed .
192S&F single phase preventer, SPPR type 360/380/415 volts suitable up to 7.5 HP pump including connecting up of wire / cable testing complete including removing the existing unserviceable one all as specified and directed. Make:-L&T Cat Part No CS81809OOOO orequivalent make in Indio Asian/Leagrand/ HPL as approved by GE.
193Supply only free chlorine testing kit paper strips (Colome metirc TMG) for detection levels (0.05, 0.1, 0.2, 0.4, 0.6, 0.8, 1.2, 1.5, 2.0, 4.0, 6.0 ppm (Mgle) test time 40 seconds having each bottle of 50 test strips complete all as specified and directed.
194Design Fabricating supply and erectingconnecting and testing totally enclosed LT cubicle panel board3 Phase 4 wire system outdoortype front openabletype, separate compartment for each control gear, cable alley,provision ofknock out type plates for various sizes of cablein and out, incoming and out going feeders duly marked on revited plates etc complete CPRI approved factory madefabricated out of3.15 mm thick CRCA sheet duly treatedthrough 7 tank pre treatment process andpaintedwith epoxy powder coated mat finish ofSIEMENS GREY structural RAL 7032 shade colour built in industrial type locking arrangement on front and back, and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs ,Panel mounted on Angle iron frame of 50x50x6mm thick duly painted and embeded in PCC 1:3:6, typeC2 using 40 mm graded stone aggregate, 45 CM below ground level and 15 Cm above ground level including taking down old existing one and consisting the following provisions:- (a) MCCB 63 Amp 25 KA 4 pole -1 No (b) DOL starter Heavy duty 7.5 HP with relay 9-14 Amp - 1No (c) Single phase preventer -1No (d) Pump ON and Supply ON indicator- 1 Set (e) Phase reversal protection for protecting motor from reverse running.
195Supply only TCCA 90% Chlorine (Trichloroisocyanuric Acid), effective content of chlorine % : = 90, Content of water % : = 0.5, PH Value of 1% Solution: 2.7 to 3.3, Granular Chlorine/Tablet in packing of 50 kg complete all as specified and directed.
196M&L for painting of water distribution header including all control valves and all exposed pipe of any sizeby using synthetic enameledspraypainting after scrapping /cleaning complete all as directed at Napiers line
197Supply only Water treatment chemical calcium hypo Chloride 65%-70% chlorine content (calcium based granular disinfectant for water treatment, packedin 45 kg drum complete all as specified and directed.
198Taking down old unserviceable HDPE Pipe and High density polyethylene pipes (HDPE) of pressure rating 20 kgf/cm2 including socket for fixing with pump in borewell of size of size 50 mm complete all as specified and directed by Engr-in-Charge
199Taking down old unserviceable HDPE Pipe and High density polyethylene pipes (HDPE) of pressure rating 20 kgf/cm2 including socket for fixing with pump in borewell of size 40 mm complete all as specified and directed by Engr-in-Charge
200Supply and laying pipes ERW steel including specials, nominal dia 200mm as per IS 3589 (1981) 6.00mm thick and including cutting work, welding work and taking down of unserviceable ERW/CI pipe complete all as specified and directedby Engr-in-charge.
201M & L for GI pipe heavy grade 50mm dia, cut into 3.0 Mtr length including providing of threading on both sides and lowering into the existing bore well along with existing GI pipe for increasing the length of the borewell pipe as in repairs complete all as specified and directed.
202Reboreing/re-Drillingof existing borewell up to 350 mm dia, from the existing depth, at any type of strataby mud flash rotating equipment,from the Existingdepth to 100 Meters . Notes:- (i) Water injection charges if required (ii) Transport Charges , (iii) , Vehicle settlings & Flashing charges (iv)Expendable stores like cotton waste / cleaning materials, (v)Labour element. should beincluded in unit rate quoted.
203All as per item No 66 here-in-before but 100 Mtr to 200 Meters
204M&L for measuring exact depth of borewell by lowering 1/4" dia wire rope with its rolling stand all as specified and directed by Engr-in-charge.
205M&L for cleaning of existing column pipes (3 Mtr length ) duly scraping, cleaning and painting complete through anti corrosive black bituminous paint all as per directed by engr-in-charge
206Supply fix Steel wire rope anti corrosion (SS) of cage 6 mm thickness for fixing submersible pumps includingnecessary nut , bolt & clamps all as specified and directed by Engineer-in-Charge
207M&L for emptying and cleaning/removal of hold up sewage from and sludge from drains including cleaning of Bar Screen chamber of STP of capacity of capacity 100 Cum/Day all as specified and directed by Engr-in-Charge
208M&L for removal of sewage and garbage from oil grease chamber of STP capacity of 100 Cum/Day with the help of sewage pump mounted on portable bowser complete all as specified and directed by Engr-in-charge
209M&L for removal of sewage and garbage from collection tank with the help of sewage pump mountedon portablebowser and replacementof air diffusers with unserviceable distribution pipe network of STP of capacity 100 Cum/Day all as specified and directed by Engr-in-Charge
210M&L for removal of sewage and garbade from Aeration tank ofSTP of capacity 100 CUM /day with the help of pump mounted on portable bowser/manual includingcleaning of distributionpiping networkcomplete all as specified and directed
211Dismantling the unserviceablepart of sewage treatment compressor blower and replace with new spare part including testing after completion all as specified and directed by Engr-in-Charge
212Supply OnlyWater treatment chemicalBio Clean Septic Powder available complete all as specified and directed
213Supply only Water treatment chemical sodium hypo Chloride consisting 14% chlorine content diluted ClNao, complete all as specified and directed.
214Supply only Water treatment chemical enzyme-2 (DAP consisting 18:46:0, 18% Nitrogen and water soluble phosphates 46% by minimum weight, packedin 50 Kg Polythene bagcomplete all as specified and directed. Makes: Akron India Pvt Ltd/Andhra Sugar Pvt Ltd/Aquafit India Pvt Ltd/IIFCO India Ltd or equivalent make as approved approved by GE.
215Material and labour for MBBR fludised bio-media of vergin PPUV stablized material,cylindrical with external fins structure,black colour,22mm dia x 16mm height ,specific gravity 0.9 to 0.95 gms/sqcm all as specififed and as directed . Make: TP Aqua/Cool tech/Hydrotech as approved
216Material and labour Bactria culture for STP for developing MLSS and control odor complete all as directed by Engr-in-Charge. Make: Organic plus or its techno commercial equivalent make aproved by GE.
217Repairs/replacent of wornout spares ofAir blower 3-ph,415volts,50hz of capacity 125cum/hr @0.45 Kg/Sq.cm Head - 4 Mtr,including suction filter,motor pully & replacement of unservceable spares such as"V" belt,bearings, shaft,suction filter,motor pulley & blower motor oilwith new oneincluding all nessary misc items for satisafactory completion of job complete all as Specififed & directed by Engr-in-Charge
218M&L cleaningthe all type of tanks pertains to sewage treatment plant 100 KLD with suiatble chemeicals, drying the tanks and disposal of Dry sludge minmum distance of 1km raduis from STP location & maintain high level hygiene in STP permises, including cleaning of Filter Feed water Tank, Teated water tankcomplete all as specified and directed by Engr-in-Charge. Note: (i) For disposal of dry sludge contactor shall make arrange transport sysytem quoted rate shall be inclusive in unit rate.
219M&L for painting of MBBR reactor PACKAGE TYPE of 100 KLD with two coats of FRB anti corrosive coating inside and outside, including MBBR Media of Bio Pac type including clarifier/areation system and CI retention tank including all control valves and all exposed pipe of any sizeby using synthetic enameledspraypainting after scrapping /cleaning complete all as directed.
220Taking out water sample from collection/recieving sump of STP in cleancontainer and getting the same tested from the “any NABI (National Accreditation Board for testing and Calibration Lboratories) approved labs ” of (STP inlet and treated water) forPh/TSS, TS and TDS, COD, BOD, Oil/ Greases& other parameters as per NABI standard proforma complete all asdirected by Engr-in-Charge. Note: Contractor shall make arrangments for taking out the sample & deemed to be inclusive in quoted rate.
221M&L for cleaning of sewage well including chocking of all incoming sewage line entering to sewage well for dewatering and desuldging of slurry of sewage pump
222M&L for De- watering sewager cleaning machine of cap 3000 ltrs and depositing in MCD main hole at distance of 1 Km
223Cutting anxious green growth/vegetation growth for cleaning out the area around STP AND E/M installations by JCB or Men Power at ground level by cutting out roots, un wanted plants bushes and removal of the same by surface excavation not exceeding 30 cm deep average 15 cm