Tender For Repair/ Maintenance / Servicing Of Dg Sets, Lifts, Solar Water Equipments, Fire-Fighting Equipments, Lightning Conductors Installed At Various Locations At Ins Mandovi Under Ge (P) Navy Mandovi, North Goa-Goa

Military Engineer Services-MES has published Tender For Repair/ Maintenance / Servicing Of Dg Sets, Lifts, Solar Water Equipments, Fire-Fighting Equipments, Lightning Conductors Installed At Various Locations At Ins Mandovi Under Ge (P) Navy Mandovi. Submission Date for this Tender is 28-11-2022. Passenger Lift Tenders in North Goa Goa. Bidders can get complete Tender details and download the document.




Tender Notice

34583383
Corrigendum : Tender For Repair/ Maintenance / Servicing Of Dg Sets, Lifts, Solar Water Equipments, Fire-Fighting Equipments, Lightning Conductors Installed At Various Locations At Ins Mandovi Under Ge (P) Navy Mandovi
Open Tender
Indian
Goa
North Goa
28-11-2022

Tender Details

Repair / Maintenance / Servicing Of Dg Sets, Lifts, Solar Water Equipments, Fire-Fighting Equipments, Lightning Conductors Installed At Various Locations At Ins Mandovi Under Ge ( P ) Navy Mandovi As Per Tender Documents

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-Nov-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 28-11-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 40000.0 /-
Tender Value
INR 20 Lakhs /-

BOQ Items

Name of Work:
Sl. No. Item Description
1Maintenance and overhauling of DG sets of following capacities installed at various locations in INS Mandovi, once in six months including checking, cleaning, adjusting/ tightening, oiling, greasing and re-seting of existing parts, decarbonising of battery terminals etc, for smooth operation of generator sets and ensuring proper functioning of valves, "V" belts, pulleys, fan hub, idler, water pump, filters, engine cylinder head, bolts, nuts and washers, vibration dampers, coupling, alternator terminals, carbons brushes, vibration dampers, coupling, alternator terminals, carbon brushes, springs, AVR"s, exhaust pipes etc complete all as specified and directed. Note:- Spares shall be measured and paid separately under relevant items of this Schedule
2250 KVA Capacity
3125 KVA Capacity
463 KVA Capacity
540 KVA Capacity
662.5 KVA Capacity
735 KVA Capacity
8Supply only following spare parts, as per existing sample, suitable for DG sets of 125 KVA capacity and make Kirloskar (KCL) complete all as specified and directed.
9Lub oil filter element with "O" Ring
10Fuel filter element with "O" Ring
11Fuel hose pipe, steel
12Radiator hose pipe kit
13Air filter i.e. Inner and outer element
14Engine gasket set
15V belt for radiator and charging alternator
16Supply only following spare parts, as per existing sample, suitable for DG sets of 250 KVA capacity and make Kirloskar (KCL) complete all as specified and directed.
17Lub oil filter element with "O" Ring
18Fuel filter element with "O" Ring
19Fuel hose pipe, steel
20Radiator hose pipe kit
21Air filter i.e. Inner and outer element
22Engine gasket set
23V belt for radiator and charging alternator
24Supply only following spare parts, as per existing sample, suitable for DG sets (04 nos) of 35 to 63 KVA capacity and make Kirloskar (KCL) / Greeves Power complete all as specified and directed.
25Lub oil filter element with "O" Ring
26Fuel filter element with "O" Ring
27Piston with pin
28Radiator hose pipe kit
29Air filter i.e. Inner and outer element
30Oil pressure gauge
31Engine upper gasket kit
32Water pump assy
33Turbo charger repair kit
34Piston Ring Set
35Liner with "O" ring
36V belt for radiator fan
37Dismantling oil sump from DG Sets of following capacities, draining out oil, cleaning, removing sediments/ foregin particles from the oil circulation system, refilling/ replacing the oil and refixing oil sump including replacing oil sump gasket and testing complete all as specified and directed.
38250 KVA Capacity
39125 KVA Capacity
4063 KVA Capacity
4140 KVA Capacity
4262.5 KVA Capacity
4335 KVA Capacity
44Dismantling fuel injection pump assembly from DG Sets of following capacities, overhauling/ servicing, replacing valves, washers etc, assembling, calibratiing, setting for proper functioning, refixing and testing complete all as specified and directed.
45250 KVA Capacity
46125 KVA Capacity
4763 KVA Capacity
4840 KVA Capacity
4962.5 KVA Capacity
5035 KVA Capacity
51Dismantling, removing self starter motor from DG Sets of following capacities, opening up, overhauling/ servicing, replacing carbon brushes with holders, assembling back, refixing and testing for proper functioning complete all as specified and directed.
52250 KVA Capacity
5363 KVA Capacity
5440 KVA Capacity
5562.5 KVA Capacity
5635 KVA Capacity
57Dismantling, removing alternator/ dynamo from DG Sets of following capacities, opening up, overhauling/ servicing, replacing carbon brushes with holders, assembling back, refixing and testing for proper functioning complete all as specified and directed.
58250 KVA Capacity
59125 KVA Capacity
6063 KVA Capacity
6140 KVA Capacity
6262.5 KVA Capacity
6335 KVA Capacity
64Dismantling radiator assembly from DG Sets of following capacities by disconnecting inlet and outlet connections, overhauling/ servicing the radiator, clearing/ removing blockages, arresting leakages, assembling back including necessary welding/ brazing as required, refixing, reconnecting and testing for proper functioning complete all as specified and directed.
65250 KVA Capacity
66125 KVA Capacity
6763 KVA Capacity
6840 KVA Capacity
6962.5 KVA Capacity
7035 KVA Capacity
71S & F in repairs 400 Amps capacity off load changeover switch complete all as specified and directed.
72S & F in repirs power contactor including single core copper cable of 10 to 25 sqmm with suitable lugs for connecting to starter panel complete all as specified and directed. Make: L & T model No: MNX 45 or equivalent
73S & F in repairs wiring to AMF panel for DG set of any capacity including interlock system of AMF panel with existing size of copper wiring including proper connection and testing complete all as specified and directed.
74S & F in repairs radiator assy with tank, complete set made up of copper/aluminium fins and tube suitable for 35KVA to 250 KVA capacity DG set of any make complete all as specified and directed.
75S & F in repairs heavy duty contactor suitable for AMF panel as per existing on site including testing and comissioningcomplete all as specified and directed. Make: L&T model No. ML4 or equivalent
76S & F in repairs heavy duty contactor suitable for AMF panel as per existing on site including testing and comissioningcomplete all as specified and directed. Make: L&T model No. ML6 or equivalent
77S & F in repairs heavy duty contactor suitable for AMF panel as per existing on site including testing and comissioningcomplete all as specified and directed. Make: L&T model No. ML3 or equivalent
78S & F in repairs lead acid type 12 V / 180 AH battery with initial charging and comissioning as required at site to the concerned DG set complete all as specified and directed.
79Supply and top up diesel engine oil 15W 40 (as per site requirement) in DG sets installed at various locations in INS Mandovi complete all as specified and directed.
80Supply & filling coolant concentrate as required in the DG oil sump complete all as specified and directed.
81Dismantling defective alternator of any capacity from the existing foundation and DG set after removing all electrical connections, transporting to an approved / authorised / directed workshop, opening and taking out burnt winding, cleaning the stator assy rewinding with super enameled copper wire as per existing gauge and original manufacturer, applying insulating varnishing of ‘F’ class, baking in oven, re-assembling the alternator, transporting back to site, re-installing in the same locaton, carrying out alignment of complete DG set, connecting up all electrical connections, testing and commissioning complete all as specified and directed. Notes :- (a) Rate quoted shall be deemed to be inclusive of making good the disturbed surfaces. (b) DG set shall be tested on load as per rated capacity for the satisfaction of Engineer- in- Charge to achieve designed parameters.
82S & F in repairs battery terminals, brass, suitable for 95 AH to 180 AH battery complete all as specified and directed.
83Dismantling defective self starter assy of 12/24 volts, repairing, replacing of defective spares such as, carbon brushes, carbon spring, bearing, bushes, defective wiring, etc, soldering after repairs, re-assembling, refixing at site and testing on completion complete all as specified and directed.
84S & F in repairs AVR unit suitable for 35 KVA to 250 KVA DG Set complete all as specified and directed.
85S & F in repairs PVC insulated battery lead made from multistranded copper conductor cable of 1.5 mtr length and suitable size (minimum 35 sqmm) including suitable copper/ brass clamps and lugs for fixing on battery terminals and self starter complete all as specified and directed.
86S & F in repairs asbestos rope of 12 mm dia and superior quality for wrapping with the exhaust pipe of the DG set complete all as specified and directed.
87M & L for preparation of old surfaces of DG set of capacity upto 250 KVA, applying one coat of synthetic enamel paint as per existing colour and writing of SM/MES No at easily visible location complete all as specified and directed.
88S & F in repairs electronic DG set controller control unit suitable for 250 KVA Capacity DG set including battery charger, relay board, oil pressure sensor, water temperature sensor, complete control wiring, neccessary connections and testing complete all as specified and directed.
89S & F in repairs complete wring harness system including necessary electric connections for 35 to 125 KVA capacity DG set of Kirloskar make complete all as specified and directed.
90Supplying and adding distilled water in the DG batteries complete all as specified and directed.
91S & F in repairs DG set Exhaust Bellow including any cutting and welding works with new nut & bolts of suitable size and testing after completion
92S & F in repairs key arrangement for DG set of 63 KVA to 125 KVA capacity and make Kirloskar including suitable engine safety unit, solenoid switch, sensors, gauges complete all as specified and directed.
93S & F digital LCD display multifunction meter having facility to measure parameters like voltage, current, kW, kWh, KVA, KVAR, KVARH, PF, frequency, power factor, on and run hours, neutral current etc including suitable CT"s depending on load requirement, complete wiring with suitable size copper cable with cable protection conduits, testing and commisioning including taking down old pattern meters such as volt meter, ammeter etc complete all as specified and directed. Make: L&T MFM 4410 LCD meter Cl 1 model Cat no: WC441010OOOO or equivalent as approved in List of manufacturers.
94S & F in repairs lightening conductor assembly upto 2 RM made out of 50 mm dia bore heavy grade galvanised iron pipe alongwith welded flange at one end and galvanised iron reducer socket 50 x 40mm at another end connected with 40 mm bore heavy grade galvanised iron pipe with one end having galvanised iron reducer socket to connect air termination and connector for earth strip duly fixed with necessary nuts, bolts and washers in PCC 1:2:4 type B-0 using 12.5 mm graded stone aggregate of size 30cm x 30cm x30cm complete all as specified and as directed. Notes :- 1. Quoted rate shall be deemed to be inclusive of cost of 40mm and 50mm dia bore GI pipe and PCC. 2. Air temination shall be measured and paid separately under relevant item of this Schedule.
95S & F in repairs copper air termination rod, 12 mm dia, single pointed, 300mm long, withbase plate welded at bottom of termination rod of size 10 cm lenhgth, fabricated out of 25 x 3 mm thick copper strip alongwith making 9mm dia for fixing in fastners complete all as specified and directed.
96S & F in repairs aluminium strip 25x3 mm with saddle and fixing screws etc for roof conductors and down conductors above ground level complete all as specified and directed.
97S & F in repairs GI Strip 32x6 mm with saddle and fixing screws etc from test terminal block to earth pit complete all as specified and directed.
98S & F in repairs porcelain insulator of existing size for isolation of conductor from the building wall upto a height of G+8 floors by providing 15cm long fastners at every 16 cm distance in the wall complete all as specified and directed.
99M & L for repairing/ overhauling of centrifugal pump sets of 7.5 to 10 HP capacity, 3 phase, after disconnecting water/ electric connections including cleaning, repairing, machining, greasing, replacing of washers for lock nuts complete all as specified and directed. Note:- Spares required shall be measured and paid separately under relevant items of this schedule.
100Supply only ball bearing driving end complete all as specified and directed.
101Supply only ball bearing non-driving end complete all as specified and directed.
102Supply only Gun metal bush complete all as specified and directed.
103Supply only Cast Iron Impeller complete all as specified and directed.
104Supply only terminal block complete all as specified and directed.
105Supply only PVC blade complete all as specified and directed.
106Supply only gland with cover complete all as specified and directed.
107Supply only main shaft MS complete all as specified and directed.
108M & L for rewinding electric motor of 3 phase 415 volts 50 Hz AC mono block/ centrifugal pump sets of 10 to 7.5 HP capacity after disconnecting (electric/water connections). taking down electric motor from the existing position, inspecting the same, transporting to a reputed workshop for repairs, transporting it back, cutting and removing burnt out winding conductors, rewinding with insulated super enameled copper conductor of same gauge and weight, providing cotton insulated sleeves, varnishing, drying, refixing in position checking the alignment, connecting up all the electrical and water line connections, testing and commissioning complete all as specified & directed.
109Annual Maintenance contract for fully automatic electrically operated passenger lifts (04 Nos) of make "Kone Elevators"; carrying capacity of 08 Passengers (544 kg) to serve (G+ 03 - 01 No) & (G + 7 - 02 Nos) and carrying capacity of 130 Passengers (884 kg) to serve (G+ 05 - 01 No); with AC variable voltage & variable frequency drive (VVVF drive) complete with all standard accessories, simplex collective automatic & manual dual controlled operation with/ without attendant, automatic center opening doors with VVVF door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infrared sensor in full height of door & built-in announcing system without handset (04 Nos, one each in car, machine room & near Ground floor landing door) comprising of all devices and accessories, including repairs/ replacement of all defective and unserviceable parts as per manufacturer"s recommendation, attending of breakdown as and when intimatedthroughout the year for all days including sundays/holidays complete all as specified and directed. Notes: (i). Maintenance/repair work shall be carried out through trained service engineer from OEM. (ii). The contractor shall sign a MoU with OEM for a period of 1 year from the date directed by Engineer-in-Charge for carrying out the maintenance and repair work of lifts and shall produce original MoU to Accepting officer . (iii). Contractor shall ensure that routine maintenance is carried out and lifts are maintained in serviceable condition 24 hrs x 365 days.
110Inspection and testing of lift by lift inspector authorised by Goa State Govt, for serviceability and safety aspects of lifts and submission of necessary report as per proforma complete all as specified and directed.
111M & L for servicing of solar water heater upto 300 ltrs capacity including checking serviceability of individual components and replacing worn out fasteners, gaskets, washers accessories, inspection of the entire system, cleaning of sacrificial anode, rectification of any leaks, tightening of loose electric connections etc. and making system operational complete all as specified and directed by Engineer-in-Charge. Note:- Spares shall be measured and paid separately under relevant item of this Schedule.
112Supply and fix in repairs of solar water tube 58x1500mm for the solar water heaters complete all as specified and directed.
113Supply and fix in repairs of solar water tube 58x1800mm for the solar water heaters complete all as specified and directed.
114S & F in repairs heating element of 3 kW, 230 volts, ISI marked, suitable for storage type water heater complete all as specified and directed.
115M & L for complete servicing of firefighting system consisting of 100mm dia fire pipe, fire cabinet box, fire hose reel drum, fire hydrant valve, manual call point, fire addressible panel, siren/sounder etc including repair/replacement of defective items complete all as specified and directed. Note: Material cost for spares required shall be measured and paid separately under relevant items of this schedule.
116Supply only manual call point, glass, complete all as specified and directed.
117Supply only sounder/siren complete all as specified and directed.
118Supply onlyfire hydrant valve complete all as specified and directed.
119Supply only 12 Volts 7ah battery complete all as specified and directed.
120S & F in repairs float valve for solar water heater upto 300 LPD capacity complete all as specified and directed.
121M & L for preparation of old surfaces of fire fighting pipe line fitted upto G+7, applying one coat of synthetic enamel paint over a coat of red oxide primer, as per existing colour, complete all as specified and directed.
122M & L for earthing complete with steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground vertically (earth pit not less than 2.25 mtr below ground level) with top edge of plate not less than 1.5 mtr below ground level, connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers etc including 20 mm dia protection pipe, connecting the earth lead to earth connection in the main distribution box with lugs and GI nuts, bolts etc as shown onelectrical plate No 3 of SSR Part I including neccessary excavation and earthwork in any strata, PCC earth chamber inPCC 1:3:6, precast RCC chamber cover and testing including taking out old earthing complete all as specified and directed. Note: On testing after completion if the desired earth resistance is not obtained, the entire earthing shall be redone at no extra cost.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail