Tender For Repair/Maintenance Of Dg Set, Amf Panels And Connected Works At Domestic Area And Outside Locations Under Ge (Af) Jamnagar No 1, jamnagar-Gujarat

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Dg Set, Amf Panels And Connected Works At Domestic Area And Outside Locations Under Ge (Af) Jamnagar No 1. Submission Date for this Tender is 25-11-2022. Diesel Generators Tenders in jamnagar Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

34566248
Corrigendum : Tender For Repair/Maintenance Of Dg Set, Amf Panels And Connected Works At Domestic Area And Outside Locations Under Ge (Af) Jamnagar No 1
Open Tender
Indian
Gujarat
jamnagar
25-11-2022

Tender Details

Repair / Maintenance Of Dg Set, Amf Panels And Connected Works At Domestic Area And Outside Locations Under Ge ( Af ) Jamnagar No 1

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Nov-2022 Corrigendum No. 1 BOQ 18-11-2022
2 05-Nov-2022 Corrigendum No. 1. BOQ 18-11-2022
3 18-Nov-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 25-11-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 92000.0 /-
Tender Value
INR 46 Lakhs /-

BOQ Items

Name of Work: REPAIR/MAINTENANCE OF DG SET, AMF PANELS AND CONNECTED WORKS AT DOMESTIC AREA AND OUTSIDE LOCATIONS UNDER GE (AF) JAMNAGAR NO 1
Sl. No. Item Description
1Maintenance and servicing of 400 KVA DG set of any make Diesel Generator Sets including connected Alternator, Panel Board (AMF/ Non AMF) and carrying out routine "A" check of the engine complete for smooth functioning all as per manufacturer"s instructions and as directed-02 Nos NOTES: (i) Control switches such as MCCB, Main switch, contactors, multi display meter and engine control unit shall be out of scope of the item of work and the rate quoted shall exclusive of servicing/ maintenance of the above said fittings.
2(ii) Servicing of DG Set along with connected Alternator and Panel Board including "A" Check of the Engine shall be carried out once in every month (Except during the month when "B" check is carried out) as directed by the Engineer-in-charge and the Contractor shall carry out periodical inspections during the maintenance period and he shall be responsible for the smooth functioning of the DG set for a period of 30 days from the date of service and shall also attend all the maintenance works as and when required in that period except in case of Major repairs. (iii) Spare parts required for replacement during the maintenance period shall be measured and paid separately at supply only rates and cost of labour for fixing these spares shall be deemed to be included in the rate quoted for this item.
3(iv) Cost of all consumables required during the maintenance period shall be deemed to be included in the rate quoted for this item. (v) List of checks to be carried out under "A" check is attached as Appendix "A" to the Particular specifications.
4All as per Item No .1 here in before but for 320 KVA DG set -05 Nos
5All as per Item No .1 here in before but for 250 KVA DG set -01 Nos
6All as per Item No .1 here in before but for 200 KVA DG set -07 Nos
7All as per Item No .1 here in before but for 160 KVA DG set -07 Nos
8All as per Item No .1 here in before but for 100 to 125 KVA DG set -06 Nos
9All as per Item No .1 here in before but for 70 to 83KVADG set -06 Nos
10All as per Item No .1 here in before but for 62.5/63KVADG set -04 Nos
11All as per Item No .1 here in before but for 50KVADG set - 01 Nos
12All as per Item No .1 here in before but for 25 to 30KVADG set -04 Nos
13All as per Item No .1 here in before but for 20 KVADG Set - 02
14All as per Item No .1 here in before but for 10 to 15 KVADGset -04 Nos
15Maintenance and servicing of 400 KVA DG set of any makeDiesel Generator Sets including connected Alternator, Panel Board (AMF/ Non AMF) and carrying out routine "B" check of the engine including items covered in "A" check complete for smooth functioning all as per manufacturer"s instructions and as directed - 02 Nos NOTES:(i) Control switches such as MCCB, Main switch, contactors, multi display meter and engine control unit shall be out of scope of the item of work and the rate quoted shall exclusive of servicing/ maintenance of the above said fittings
16(ii) "B" check shall be carried out once in every six months or 250 hours of running of DG Set whichever is earlier. Servicing of DG Set along with connected Alternator and Panel Board including items covered in "A" Check of the Engine shall also be carried out in that month as directed by the Engineer-in-charge and the Contractor shall carry out periodical inspections during the maintenance period and he shall be responsible for the smooth functioning of the DG set for a period of 30 days from the date of service and shall also attend all the maintenance works as and when required in that period except in case of Major repairs (iii) Spare parts, engine oil and radiator coolant oil required for replacement during the maintenance period shall be measured and paid separately at supply only rates and cost of labour for fixing these spares/ filling of oils shall be deemed to be included in the rate quoted for this item.
17(iv) Cost of all consumables required during the maintenance period shall be deemed to be included in the rate quoted for this item,contractor to be provided fuel filter, oil filter, water filter,top head gaskets,fuel pipes, battery terminal, battery lead and distilled water. (v) List of checks to be carried out under "B" check is attached as Appendix "B" to the Particular specifications.
18All as per Item No .13 here in before but for 320 KVA DG set -05 Nos
19All as per Item No .13 here in before but for 250 KVA DG set -02 Nos
20All as per Item No .13 here in before but for 200 KVA DG set -07 Nos
21All as per Item No .13 here in before but for 160 KVA DG set -07 Nos
22All as per Item No .13 here in before but for 100 to 125 KVA DG set -06 Nos
23All as per Item No .13 here in before but for 70 to 83KVADG set -06 Nos
24All as per Item No .13 here in before but for 62.5/63KVADG set -04 Nos
25All as per Item No .13 here in before but for 50KVADG set - 01 Nos
26All as per Item No .13 here in before but for 25 to 30KVADG set -04 Nos
27All as per Item No .13 here in before but for 20 KVADG Set - 02
28All as per Item No .13 here in before but for 10 to 15 KVADGset -04 Nos
29Repair / overhauling of following mentioned Self Starter assembly of DG Set by disconnecting and removing from the engine, cleaning of all accessories, replacing of worn out parts such as brushes, bushes, contact plates, jumping leads and seals, revarnishing the field coil, armature and re-assembling the same and re-fixing into the engine including testing all as per manufacturer"s instructions and as directed.(a) Self starter assembly, 24 Volt DC 250/320/400
30All as per item No 25 above but Self starter assembly, 24Volt DC 160/180/200
31All as per item No 25 above but Self starter assembly, 12Volt DCup to 100 kva
32Repair / overhauling of following mentioned radiator assembly of DG set by disconnecting and removing from the engine, dismantling the top and bottom chambers, descaling the sediments, scales, corrosion etc. by means of acid, cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets including arresting leakages, if any and fixing to the engine with new hoses, clips etc. all as required and as directed. Note: The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges. (a) Radiator assembly320/ 400 KVAcapacity
33All as per item No 28 above but Radiator assembly 250 KVA/ 200 KVA/180 KVA capacity
34All as per item No 28 above but Radiator assembly 160KVA capacity
35All as per item No 28 above but Radiator assembly 100KVA/75 KVA/70 KVA/82.5 KVA/ 62.5 KVA/ 40 KVA capacity.
36All as per item No 28 above but Radiator assembly 100KVA/75 KVA/70 KVA/82.5 KVA/ 62.5 KVA/ 50 KVA capacity.
37All as per item No 28 above but Radiator assembly 10 TO 30KVA capacity.
38Supply and Fix in repairsLead acid battery, 12 volt, 180 AH
39Supply and Fix in repair Lead acid battery, 12 volt, 150 AH
40Supply and Fix in repairLead acid battery, 12 volt, 130 AH
41Supply and Fix in repair Lead acid battery, 12 volt, 120 AH
42Supply and Fix in repairLead acid battery, 12 volt, 92 AH
43Supply and filling Engine oil SAE 20W-40W. Make :- VOLVOLINE/ IOC/HP
44Supply and filling radiator coolant Make : VOLVOLINE/ IOC/HP.
45M&L for distilled water (electrolyte ) to be filled in lead acid batteries all as directed.
46Supply and Fix in repairs solenoid switch, 240volts, suitable for 400/250/200/180/160 KVA DG set.
47Supply and Fix in repairs solenoid switch, 240volts, suitable for 83.5/75/70/62.2 KVA DG set.
48Supply and Fix in repair solenoid switch, 240volts, suitable for 10 to 50 KVA DG set
49S&F in repairs Automatic voltage regulator (AVR) Suitable for DG Set 400/250/200/180/160/100 KVA
50S&F in repairs Automatic voltage regulator (AVR) Suitable for DG Set 10 to 83KVA
51Supply and fixing in repairs Battery charger panel mounted 24 volt 15 Amps suitable for AMF Panels of DG Set 100/125/160/200/250/400 KAV capacity
52Supply and fixing in repairs Battery charger panel mounted 12 volt 15 Amps suitable for AMF Panels of DG Set 10 to 83KVA KAV capacity
53Supply and fix in repairs fan belt as per existing make for the following capacities of DG sets. (a)250 to 400KVA
54All as per item No 49 above but 200/180/ 160 KVA
55All as per item No 49 above but 125/100 KVA
56All as per item No 49 above but 70/ 75/82.5KVA
57All as per item No 49 above but 10 to 63 KVA
58Supply & fix in repairs Air filter element as per existing make for the following capacities of DG sets. (a) 400 KVA
59All as per item No 54 above but 320 KVA
60All as per item No 54 above but 250 KVA
61All as per item No 54 above but 200 KVA
62All as per item No 54 above but 160 KVA
63All as per item No 54 above but 100 t0 125 KVA
64All as per item No 54 above but 70 KVA to 83KVA
65All as per item No 54 above but 50 KVA
66All as per item No 54 above but 25 to 30 KVA
67All as per item No 54 above but 10 to 20KVA
68Overhauling the fuel injection pump assembly and injectors, disconnecting the fuel supply lines, and takingout Fuel Injection Pump (FIP) to workshop for servicing/repair, replacement the worn out/un serviceable parts like service kit, D-Valve, Elements, nozzles etc., as required and calibrating the same, assembling at site and testing on load all as directed for the following capacity of Gen sets:-(a) 400 KVA
69All as per item No 64 above but 320 KVA
70All as per item No 64 above but 250 KVA
71All as per item No 64 above but 200 KVA
72All as per item No 64 above but 160 KVA
73All as per item No 64 above but for 100 to 125 KVA
74All as per item No 64 above but 70 to83 KVA
75All as per item No 64 above but 64.5 /63 KVA
76All as per item No 64 above but 50 KVA
77All as per item No 64 above but 25 to 30KVA
78All as per item No 64 above but 20 KVA
79All as per item No 64 above but 10 to 15KVA
80Disconnecting the inlet and outlet supply of the fuel tank cleaning thetank internally by draining out the fuel into clean container , taking out the corroded sludge and foreign impurities ,cleaning with pressure water and air, drying the tank, preparing the external old paintedsurface of tank including steel platform /stand of fuel tank and paintingthe prepared surface with one coat of synthetic enamel paint of existing shade, including writingSM /MESNo& date of cleaning of fuel tank complete all asdirected for the following capacity of Gen sets :-400 KVA DG set Diesel Generator Sets including connected Alternator, Panel Board (AMF/ Non AMF)
81All as per item No 65 above but 320 KVA .
82All as per item No 65 above but 250 KVA .
83All as per item No 65 above but 200 KVA .
84All as per item No 65 above but 160 KVA .
85All as per item No 65 above but for 100 to 125 KVA .
86All as per item No 65 above but 70 to83 KVA .
87All as per item No 65 above but 62.5 /63 KVA .
88All as per item No 65 above but 50 KVA .
89All as per item No 65 above but 25 to 30KVA.
90All as per item No 65 above but 20 KVA .
91All as per item No 65 above but 10 to 15KVA .
92Supply & fix in repairs solenoid coil of self starter of24V capacity of any capacityDG sets taking out of self starter and transportation to workshop is deemed to be included in quoted rate all as directed.
93Supply & fix in repairs solenoid coil of self starter of 12Vcapacity of any capacityDG sets taking out of self and transportation to workshop is deemed to be included quoted rate all as directed .
94M&L for repairs in Right / Left hand lock with catcher for acoustic enclosure (canopy) of any capacityDG setsallas specified & directed.
95M&L in repairs for Dial type mechanical fuel level indicator for any capacity DG set complete all as specified & directed.
96S&F in repairs 4 Pole, 32 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 03 and cat no.CS97011) or equivalent of make siemens/ABB
97S&F in repairs 4 Pole, 63 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 12 and cat no.CS97014) or equivalent of make siemens/ABB
98S&F in repairs 4 Pole, 95/100 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 22 and cat no.CS97017) or equivalent of make siemens/ABB
99S&F in repairs 4 Pole, 125/130 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 23 and cat no.CS970118) or equivalent of make siemens/ABB
100S&F in repairs 4 Pole, 160 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 32 and cat no.CS97020) or equivalent of make siemens/ABB
101S&F in repairs 4 Pole, 200 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 33 and cat no.CS97021) or equivalent of make siemens/ABB
102S&F in repairs 4 Pole, 225/255 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 34 and cat no.CS97022) or equivalent of make siemens/ABB
103S&F in repairs 4 Pole, 325 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 41 and cat no.CS97023) or equivalent of make siemens/ABB
104S&F in repairs 4 Pole, 400 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 43 and cat no.CS97025) or equivalent of make siemens/ABB
105S&F in repairs 4 Pole, 600/630 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 45 and cat no.CS97027) or equivalent of make siemens/ABB
106S&F in repairs MCCB 400 Amps, 4 pole, breaking capacity 35/36 kA with thermal Magnetic release range 320 Amps to 400 Amps, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
107S&F in repairs MCCB 250 Amps, 4 pole, breaking capacity 35/36 kA with thermal Magnetic release range 200 Amps to 250 Amps, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
108S&F in repairs MCCB 160 Amps, 4 pole, breaking capacity 25 kA, fixed typefixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
109S&F in repairs MCCB 100 Amps, 4 pole, breaking capacity 25 kA, fixed typefixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
110S&F in repairs 2pole DC supply ON / OFF selector switch,rated voltage 12 V DC rated current 16 A fixing in existing AMF panel & connecting complete all as specified & directed Make:- BCH / C&S / Havells / Simens / L&T
111S&F in repairs 2 pole 3 way selector switch for auto / manual / test, rated voltage 240 V AC, rated current 16 Amps fixing in existing AMF panel& connecting complete all as specified & directed . Make:- BCH / C&S / Havells / Simens / L&T
112S&F in repairs indicating lamp LED type, size 22.5 mm voltage 240 V AC. fixing in existing AMF panel& connecting complete all as specified & directed by Engr-in-Charge. Make:- BCH / C&S / Havells / Simens / L&T
113S&F in repairs push button with element for PB1 - Engine start / PB2 - Engine stop / PB3 - DG contactor ON / PB4 - DG contactor OFF / PB5 - Mains contactor ON / PB6 - Mains contactor OFF, fixing in existing AMF panel& connecting complete all as specified & directed by Engr-in-Charge. Make:- BCH / C&S / Havells / Simens / L&T
114S&F in repairs Aux control relay with socket 3 C/O 12 V DC, 5 A fixing in existing AMF panel& connecting complete all as specified & directed . Make:- BCH / C&S / Havells / Simens / L&T
115S&F in repairs amps meter digital type 0-400 Amps of size 96 mm x 96 mm, fixing in existing AMF panel & connecting complete all as specified & directed .
116S&F in repair C T ratio 100 A Class of accuracy 1, VA 15, ring type fixing in existing AMF panel& connecting complete all as specified & directed by Engr-in-Charge.
117S&F in repairs Digital type DC Voltmeter, 0 to 30 V DC, size 96 mm x 96 mmfixing in existing AMF panel & connecting complete all as specified & directed by Engr -in-Charge
118S&F in repairs Digitaltype DC Ammeter, 0 to 20 ADC, size 96 mm x 96 mmfixing in existing AMF panel & connecting complete all as specified & directed by Engr -in-Charge
119S&F in repairs Electronic type Hooter, supply voltage 12 V, DC flush mounted, suitable for DG set, fixing in existing AMF panel & connecting complete all as specified & directed .
120Supply and fix in repairs MCB’s single pole 6-32 Amps, 415 volts with ‘C’ curve,fixing in existing AMF panel & connecting complete all as specified & directed .
121Supply and fix in repairs Aux supply 12 V DC, voltage sensing relay 415 V AC fixing in existing AMF panel & connecting complete all as specified & directed . Make:- BCH / C&S / Havells / Simens / L&T
122Supply and fix in repairs electronic type auto battery charger for AMF of any capacity DG sets 440 / 12 V output voltage complete all as directed.
123S & F in repair electronic controller for AMF panel of capacity 63to 100 KVA DG sets showing the complete details to run the DG sets and to stop the DG sets complete with logical programming as per existing AMF panel all as directed.
124S & F in repair electronic controller for AMF panel of capacity 125 to 160 KVA DG sets showing the complete details to run the DG sets and to stop the DG sets complete with logical programming as per existing AMF panel all as directed.
125S & F in repair electronic controller for AMF panel of capacity 200 to 400 KVA DG sets showing the complete details to run the DG sets and to stop the DG sets complete with logical programming as per existing AMF panel all as directed.
126Dismantling of alternator assembly complete from DG set of capacity from 10KVAto 400 KVA andremoving the burnt out copper winding cleaning of limb thoroughly and rewinding the same with supper enameled copper winding wire of the same gauge and turn with proper class of insulation impregnated & baking, assembling and testing complete all as specified & directed by Engineer-in-Charge.
127Supply & fix in repairs silencer assembly complete suitable for DG set cap 10 to 35 KVA
128Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 160 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour.......
129.......coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete including taking down old AMF panel , Controller with battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts including taking down existing unserviceable chamber of any description all as specified and as directed.
130(a) 4 Pole 250 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos
131(b) MCCB,250 Amps 4 pole 25KA 50 Hz - 02 Nos
132(c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job
133(d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No
134(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos
135(f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos
136(g) push button with element PB1 - Engine start PB2 - Engine stop PB3 - DG contactor ON PB4 - DG contactor OFF PB5 - Mains contactor ON PB6 - Mains contactor OFF
137(h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos
138(j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos
139(k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No
140(l) Miniature circuit breaker, 1 pole 6 Amps with over load & short circuit protection , short circuit strength 10 kA - 06 Nos .
141(m) Miniature circuit breaker, 1 pole 10 /16 Amps with over load & short circuit protection , short circuit strength 10 KA. - 02 Nos
142(n)Neutral link rated current 15 A-01 No
143(o)Auxsupply 24 V DC , voltage sensing relay415 VAC.- 02 Nos
144Note :- (a) Quoted rate includes excavation, earth work and PCC work and connection & testing complete.(b) PCC 1:3:6 platform with angle iron frame for mounting AMF panel 1.2m above ground level, all as directed by Engineer in Charge. (c)AMF Panel should be mounted on platform of PCC (1:3:6) and supported by Angle sections complete all as directed by Engg-in- Charge.
145Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 83/100 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour.......
146........coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete including taking down old AMF panel , Controller with battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts including taking down existing unserviceable chamber of any description all as specified and as directed.
147(a) 4 Pole 160 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos
148(b) MCCB,160 Amps 4 pole 25KA 50 Hz - 02 Nos
149(c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job
150(d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No
151(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos
152(g) push button with element PB1 - Engine start PB2 - Engine stop PB3 - DG contactor ON PB4 - DG contactor OFF PB5 - Mains contactor ON PB6 - Mains contactor OFF
153(h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos
154(j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos
155(k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No
156(l) Miniature circuit breaker, 1 pole 6 Amps with over load & short circuit protection , short circuit strength 10 kA - 06 Nos .
157(m) Miniature circuit breaker, 1 pole 10 /16 Amps with over load & short circuit protection , short circuit strength 10 KA. - 02 Nos
158(n)Neutral link rated current 15 A-01 No
159(o)Auxsupply 24 V DC , voltage sensing relay415 VAC.- 02 Nos
160Note :- (a) Quoted rate includes excavation, earth work and PCC work and connection & testing complete.(b) PCC 1:3:6 platform with angle iron frame for mounting AMF panel 1.2m above ground level, all as directed by Engineer in Charge. (c)AMF Panel should be mounted on platform of PCC (1:3:6) and supported by Angle sections complete all as directed by Engg-in- Charge.
161Material and Labour for cleaning of dust particles from inside the AMF Panel by air blowers, tightening of loose connections, filling of gaps with sealants, removing of vegetation, surface dressing surrounding the panel, welding of damaged panel doors, fixing of hinges, providing locking arrangements, applying one coat of primer, painting of panel with two coats synthetic enamel paint of existing colour complete including providing lock all as specified and directed by Engr-in-charge.
162M&L for taking out fuel tankfrom 200 KVA DG Set, welding / brazing at all leakage joint to make leak proof & reinstalled as specified & directed .
163Supply & fix in repairs AMF controller of 400 KVA DG Set of existingmake complete (officer Mess)all as specified and directed .
164Supply & fix in repair AMF controller of 250/320 KVA DG Set of existingmake completeall as specified and directed .
165Supply & fix in repairs AMF controller of 160/200 KVA DG Set of existingmake complete all as specified and directed .
166Supply & fix in repair AMF controller of 63/100 KVA DG Set of existingmake complete all as specified and directed by Engr-in-charge.
167Supply & fix in repair AMF controller of 10/50 KVA DG Set of existingmake complete all as specified and directed by Engr-in-charge.
168NOTE:-(i) Item No. 1 to 111 if any DG set and connected items becomes breakdown ,the contractor shall locate the problem/Fault at site within 12 hours on intimation by JE/Engineer-in-charge and ensure that the fault and rectified within 48 hours ,failing which an amount of Rs.200/- per hour will be recovered as penal recovery from any payment due to contractor after expiry of 48 hours.