| 1 | Taking down carefully copper / aluminium point wiring (light, fan, socket or power) complete including fittings such asswitches, ceiling roses, pendants, regulators, sockets etc., removing materials out side MD land in case of Credit and making good disturbed surfaces of walls, floors, etc., all as specified and as directed. |
| 2 | Material and labour for Point wiring for complete with PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor conforming to IS-694, 1.5sqmm (nominal area) drawn through and including non metallic PVC casing / capping (not less than 20mm wide) (ISI marked) andaccessories on surface of wall/roof with sunken type pressed steel/welded terminal boxes made out of 1.6mm mild steel sheet, 3mm thick laminated sheet cover for mounting of switches, socket outlets, regulators etc., including provision of PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor 1.5sqmm as earth continuity conductor and connecting to common earth dolly complete all as specified and as directed by Engineer-in-Charge. |
| 3 | One light / Fan / Exhaust fan / bell point controlled by one, one way switch |
| 4 | One 3 pin 5/6 Amps switch socket combination point on independent board |
| 5 | One 3 pin 5/6 Amps switch socket combination point on the same board with other switches controlled by one switch. |
| 6 | All as per item No. 2 described here - in - before but for 3 pin 15/16 Amps switch socket combination on independent board with 2.5sqmm copper cable and provision of 2.5sqmm PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor connected to common earth dolly connecting up to fittings complete. |
| 7 | Material and labour for Point wiring for complete with PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor conforming to IS-694, 1.5sqmm (nominal area) drawn through and including non metallic PVC conduit 20mm dia (ISI marked) andaccessories laid on surface of wall/roof with sunken type pressed steel/welded terminal boxes made out of 1.6mm mild steel sheet, 3mm thick laminated sheet cover for mounting of switches, socket outlets, regulators etc., including provision of PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor 1.5sqmm as earth continuity conductor and connecting to common earth dolly complete all as specified and as directed by Engineer-in-Charge. |
| 8 | One light / Fan / Exhaust fan / bell point controlled by one, one way switch |
| 9 | One 3 pin 5/6 Amps switch socket combination point on independent board |
| 10 | One 3 pin 5/6 Amps switch socket combination point on the same board with other switches controlled by one switch. |
| 11 | All as per item No. 4 described here - in - before but for 3 pin 15/16 Amps switch socket combination on independent board with 2.5sqmm copper cable and provision of 2.5sqmm PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor connected to common earth dolly connecting up to fittings complete. |
| 12 | Supply and fix in repairs batten type LED tube light fitting, 1x20 watts, 230 volt, 4 feet with long lasting PVC body with slim & sleek looks all pre-wired fixed on walls with all fixing accessories such as 2 Nos of PVC square/round boxes, screws, etc and connecting up with three core flexible copper conductor cable of size 24/0.20sqmm complete all as specified and directed by Engineer-in-Charge-in-Charge, Make : Havells Cat Part No LHEXBLP7PN1W020 or equivalent in Bajaj / CG / Phillips |
| 13 | Supply and fix in repairs batten type LED tube light fitting, 1x10 watts, 230 volt, 2 feet with long lasting PVC body with slim & sleek looks all pre-wired fixed on walls with all fixing accessories such as 2 Nos of PVC square/round boxes, screws, etc and connecting up with three core flexible copper conductor cable of size 24/0.20sqmm complete all as specified and directed by Engineer-in-Charge-in-Charge, Make : Havells Cat Part No LHEXBLP7IN1W009 or equivalent in Bajaj / CG / Phillips |
| 14 | Supply and fix in repairs surface/recess mounted LED ceiling light fitting, 600mmx600mm, 36w, 230v, 50Hz complete with all accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable fixed on the false ceiling with necessary cutting of false ceiling wherever necessary screw/fasteners etc completeall as specified and directed by Engineer-in-Charge-in-Charge, Make : Havells Cat Part No BOCR2X2R34WLED857SPCMSSL or equivalent in Bajaj / CG / Phillips |
| 15 | Supply and fixSwitch Piano, flush type, single pole, one way, 5/6 Amps, 240 volts, ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T / Havells |
| 16 | Supply and fix switch single pole one way 6Amps,flush type,ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T / Honeywell |
| 17 | Supply and fix switch single pole one way 16Amps,flush type,ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T / Honeywell |
| 18 | Supply and fixSwitch bell push, flush type, single pole, one way, 5/6 Amps, 230 volts, ISI marked complete all as specified and as directed.Make: Anchor / Legrand / L&T |
| 19 | Supply and fix Call bell electric (Ding Dong type) suitable for working on 230 volts AC supply multi music type complete all as specified and as directed.Make: Anchor / Legrand / L&T |
| 20 | Supply and fix Ceiling rose,surface type Bakelite, three terminal 65x32mm, ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T |
| 21 | Supply and fix angle holder, PVC/Polycarbonate type with back plate suitable for batten / angular fittingscomplete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T |
| 22 | Supply and fixswitch socket outlet, combination 5 Pin 5Amps / 3 Pin 6Amps,flush type, ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T |
| 23 | Supply and fixsocket outlet, combination 5 in 1, 3 Pin, 5/15Amps,flush type 240 volts, universal ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T |
| 24 | Supply and fix socket , 2/3 Pin combined, 6 Amps, 2 module, 230 V,ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T / Honeywell |
| 25 | Supply and fix socket 2/3 Pin combined, 6/16Amps, 2 module, 230 V,ISI marked complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T / Honeywell |
| 26 | Supply and fixstepped type electronic fan regulator on existing phenolic laminated sheet etc complete all as specified and as directed by Engineer-in-Charge.Make: Anchor / Legrand / L&T |
| 27 | Supply and fix in repairs double door, sheet metal enclosure powder coated MCB DB SPN 6 way with 200 Amps rated bus bar, 240 volt, horizontal type, IP 43 protection, flush in walls including making good of disturbed surface to match with existing surface complete all as specified and as directed by Engineer-in-Charge. Make: Schneider / Havells / L&T / ABB / Legrand / Siemens/ Benlo/Larsen & Toubro. |
| 28 | Supply and fixin repairs MCB SP, 5 to 32 Amps, 240 volts,10 KA complete all as specified and as directed by Engineer-in-Charge.Make :Legrand / L&T / Havells / ABB / Siemens / Schneider |
| 29 | Supply and fixin repairs MCB SPN, 32 Amps, 240 volts,10 KA complete all as specified and as directed by Engineer-in-Charge.Make :Legrand / L&T / Havells / ABB / Siemens / Schneider |
| 30 | Supply and fixin repairs meter box in replacement with new meter box for housing meter and MCB DB\"s, MCCB, made out of 2mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide primer of size 0.60m x 0.60m x 0.20m grouted in wall and refixing of existing meters and MCB\"s including front door with hinges and locking arrangements and slot for meter reading duly covered with 3 mm thick sheet glass of size 100x 100 mm and mounting on wall with proper fixing arrangement with wooden planks for mounting meter and MCBs complete including taking down of old rusted meter box and making good the surface as required all as specified and as directed by Engineer-in-Charge |
| 31 | Material and labour for earthing complete with Galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of earth the plate not less than 1.5 metres below normal ground level, connected to plate with GI earth wire 4mm dia, 7.5 m long from earth point to test point and other end connected to control board / panel / equipment, laid under floors/plinths or fixed on walls or concealed in wall etc by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel with provision of charcoal & common salt packed upto minimum 150 mm all around the earth plate and protected by 40 mm bore light grade galvanised iron pipe complete allas shown in electrical plate No.3 of MES schedule Part I, 2009 withPCC pit in PCC 1:2:4 type B1 using 20 mm graded stone aggregate,MS angle iron frame of size 50mm x 50mm x 5mm, cast iron cover with locking arrangements, GI 20 mm bore medium grade pipe and GI funnel with wire mesh for watering arrangement including necessary excavation and earth work in any type of soil/strata & testing complete all as specified and as directed by Engineer-in-Charge. |
| 32 | Supply and fix in repairs, LED building Security light fittings and commissioning 1 x 35 watts, pressure die cast aluminium housing, heat resistance toughened glass with frame, IP 66 protection, better optics for uniform distribution complete including necessary copper wire connection of suitable size, GI bracket made out of 40mm GI pipe light grade, not less than 1.5m long, ISI marked duly fixed with MS clamps of 3mm thick 02 Nos with nuts bolts etc complete all as specified and as directed by Engineer-in-Charge. Make : Havells / Bajaj / CG / Phillips / Wipro/ Halonix |
| 33 | Supply and fix in repairs, decorative gate light LED fittings and commissioning 1x20 watts,made up with high grade unbreakable polycarbonatematerial suitable for retrofit LED lamp with pressure die cast aluminiumhousing, heat resistance toughened glass with frame, IP 66 protection, better optics for uniform distribution complete with necessary copper wire connection of suitable size including GI bracket made out of 40mm pipe light grade ISI marked duly fixed with 02 nuts bolt complete all as specified and directed by Engineer-in-Charge-in-Charge, Make : Havells Cat Part No LHFXAMN1TN6F035 or equivalent in Bajaj / CG / Phillips |
| 34 | Material and labour for sub main wiring completewith and including2 runs of 6.0sqmm,single core FRLS, PVC insulated and unsheathed, multistranded, copper conductor cable, single core, 1100 Volts grade drawn through and including PVC conduit, medium grade of size 25mm diaincluding accessories such as Tees, Elbows, junction box, reducers etc as required and fixed on walls and 6.0sqmm PVC multistranded copper conductor cable for earthing and connected to common earth dolly including taking down the existing sub main wiring complete all as specified and as directed by Engineer-in-Charge.Note :Two runs of 6.0sqmm PVC insulated cable and one run of 6.0sqmm cable and one run of PVC conduit shall be measured as one unit length. |
| 35 | Material and labour for taking down ceiling fan by disconnecting electric connection, dismantling blades, down rod andopening stator of ceiling fans of sweep 1200mm, 230 volts, AC, single phase, cleaning of parts, replacement of unserviceable parts as ordered, greasing movable parts, taking out burnt out coil, cleaning the segments complete and including rewinding with super enamelled copper winding wire of same gauge & weight with insulating material, heating, varnishing, re-assembling the same after repaired, testing and refixing with suitable size copper connecting wire etc complete all as specified and as directed by Engineer-in-Charge.Note:(i) Spare parts viz Capacitor, ball bearing, bushes, split pin, \"U\" clamp with rubber reel, shaft, PVC canopy, down rod and fan blade will be measured and paid separately as\"Supply only\".(ii) Serviceable spares shall be reused. |
| 36 | All as per item No. 29 described here-in-before butceiling fan 1400mm sweep |
| 37 | Supply only ball bearing No. 6210/6202 as approved suitable for ceiling fan of any sweep and make etc complete all as specified and as directed by Engineer-in-Charge.Make: NBC, SKF, TATA |
| 38 | Supply only capacitor 2.5 MFD, 440V, AC, 50Hz suitable for ceiling fan of any sweep and make etc complete all as specified and as directed by Engineer-in-Charge.Make: Universal, Usha, Aristo, Epcos |
| 39 | Supply only split pin suitable for ceiling fan of any sweep and make etc complete all as specified and as directed by Engineer-in-Charge. |
| 40 | Supply only Gun metal bushes suitable for ceiling fans of different sizes complete all as specified and as directed by Engineer-in-Charge. |
| 41 | Supply only down rod, MS, 15mm dia, heavy duty, 300mm long down rod, clamps with rubber reel of suitable sizes including necessary mild steel nuts, bolt & washers etc complete all as specified and as directed by Engineer-in-Charge. |
| 42 | Supply only down rod, MS, 15mm dia, heavy duty, 450mm long down rod, clamps with rubber reel of suitable sizes including necessary mild steel nuts, bolt & washers etc complete all as specified and as directed by Engineer-in-Charge. |
| 43 | Supply only PVC canopy for 1200/1400mm sweep as per existing size and make complete all as specified and as directed by Engineer-in-Charge. |
| 44 | Supply only new metal fan blades suitable for ceiling fan of 1200mm sweep complete all as specified and as directed by Engineer-in-Charge. |
| 45 | Supply only new metal fan blades suitable for ceiling fan of 1400mm sweep complete all as specified and as directed by Engineer-in-Charge. |
| 46 | Material and labour for preparing old surfaces ofceiling fan of any capacity or sweep, by scrapping and removing dust etc and filling cavities with one coat of filler and applying synthetic enamel paint by spraying and writing MES Nos in block letters as per existing complete all as specified and as directed by Engineer-in-Charge. |
| 47 | Material and labour for taking down exhaust fan / wall fan by disconnecting electric connection, dismantling blades, down rod andopening stator of exhaust fan / wall fan of sweep, 230 volts, AC, single phase, cleaning of parts, replacement of unserviceable parts as ordered, greasing movable parts, taking out burnt out coil, cleaning the segments complete and including rewinding with super enamelled copper winding wire of same gauge & weight with insulating material, heating, varnishing, re-assembling the same after repaired, testing and refixing with suitable size copper connecting wire etc complete all as specified and as directed by Engineer-in-Charge.Note:(i) Spare parts viz Capacitor, ball bearing, fan blade etc will be measured and paid separately as\"Supply only\".(ii) Serviceable spares shall be reused. |
| 48 | Supply only ball bearing suitable for exhaust fan of any size 300/400/450mm sweep etc complete all as specified and as directed by Engineer-in-Charge.Make: NBC, SKF, TATA |
| 49 | Supply only new metal blades suitable for exhaust fan of size 300mm sweep complete all as specified and as directed by Engineer-in-Charge. |
| 50 | Supply only new metal blades suitable for exhaust fan of size 400/450mm sweep complete all as specified and as directed by Engineer-in-Charge. |
| 51 | Supply only capacitor 4 MFD, 440V, AC, 50Hz suitable for exhaust fan of any sweep and make etc complete all as specified and as directed by Engineer-in-Charge.Make: Universal, Usha, Aristo, Epcos |
| 52 | Supply and fix in repairs ceiling fan regulator AC, 230 volts, 100 watts, electronic type, mini (step type) complete all as specified and as directed by Engineer-in-Charge.Make: Usha, Anchor( Penta), Cona |
| 53 | Supply and fix in repairs modular ceiling fan regulator AC, 230 volts , 100 watts, 2 module, electronic type, deluxe (step type) complete all as specified and as directed by Engineer-in-Charge.Make: Usha, Anchor( Penta), Cona |
| 54 | Taking down carefully storage type electric water heater (Geyser) of any capacity. carrying out servicing includingreplacement of various size screws and clamps, base assembly, washers, glands of all types/ valves / heating elements / Thermostat pipes / drain plug / thermal cut-out / safety valve and to ensure water tightness and worn out minor parts including re-fixing in the position after testing complete all as specified and as directed by Engineer-in-Charge.Note :Base plate assembly, Heating elements, thermostat pipes, thermal cut out and safety valve will be measured and paid separately as \"Supply only.\" |
| 55 | Supply only base plate assembly of 25/50 ltrs capacity geyser complete with inlet, outlet and thermostat pipes complete all as specified and as directed by Engineer-in-Charge. |
| 56 | Supply onlyheating elements of capacity 1.5/2 KW, AC, 230 Volt complete all as specified and as directed by Engineer-in-Charge. |
| 57 | Supply only thermal cut out, suitable for 25/50 ltrs capacity geysers complete all as specified and as directed by Engineer-in-Charge. |
| 58 | Supply only 15mm bore safety valve/high pressure release valve, ISI marked complete all as specified and as directed by Engineer-in-Charge. |
| 59 | Material and labour for preparing old surfaces ofgeyser of any capacity , by scrapping and removing dust etc and filling cavities with one coat of filler and applying synthetic enamel paint by spraying and writing MES Nos in block letters as per existing complete all as specified and as directed by Engineer-in-Charge. |
| 60 | Material and labour for geyser inner tank bracing and arresting leakage of any type complete all as specified and as directed by Engineer-in-Charge. |
| 61 | Supply and fix in repairs PVC heavy duty connecting pipe of 15 mm dia and 600 mm long with adaptor complete all as specified and as directed by Engineer-in-Charge. |
| 62 | Supply and fix ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 volt, 1200 mm sweep, min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC), complete all as specified and as directed by Engineer-in-Charge.Note: Old fan will be deposited in MES Store yard.Make: Usha, Crompton Greaves, Khaitan |
| 63 | Supply and fix exhaust fan, made of sturdy Engineering plastic complete with louvers shutter, voltage 230 v, 50 Hz, RPM 1200, copper winding of sweep 300 mm including taking down existing exhaust fan etc complete all as specified and as directed by Engineer-in-Charge.Note: Old fan will be deposited in MES Store yard.Make: Usha, Crompton Greaves, Khaitan |
| 64 | Note:Deduct Credit for demolished / dismantled material of Rs. (-) 38,195.00 (Minus) as listed in Schedule of Credit.Tenderers will not quote against this item being a tentative amount to be considered to arrive at the \"Contract Sum\" |