Drinking Water Supply and Sanitation Government Departments Closing in 0 days TDR #34396009

Tender For Construction Testing And Commissioning Of Rcc Oht Pump House Di K9 Rising Main Hdpe Pipe Distribution System And Fhtc Etc Of Bhogpur Jaspur Gov Solar Pumping Water Supply Scheme In Block Jaspur Distt Us Nagar

Issued by Government Departments · jaspur, Uttarakhand
Tender Value
1.98 Crore
Estimated cost
Bid Submission
29 Oct 2022
0 days left
EMD
3.98 Lakhs
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
jaspur → Uttarakhand
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Construction Testing And Commissioning Of Rcc Oht Pump House Di K9 Rising Main Hdpe Pipe Distribution System And Fhtc Etc Of Bhogpur Jaspur Gov Solar Pumping Water Supply Scheme In Block Jaspur Distt Us Nagar

BOQ

Name of Work : Construction, Testing & Commissioningof RCC OHT, Pump House, D.I. K-9 Rising main, HDPE Pipe distribution System & F.H.T.C. etc. of Bhogpur Jaspur GOV Solar Pumping Water Supply Scheme in Block Jaspur Distt. U.S. Nagar
Sl. No. Item Description
1Soil testing of proposed O.H.T. site by some reputed institute like I.I.T. Roorkee or equivalent & accordingly design and construction of 100 KL capacity, 21 m staging RCC Over Head Tank with foundation considering seismic forces, including supply of all materials, labour, T&P etc. as required for proper completion of work and submission of detailed design/drawings before starting of the work.The earthquake resistant design must be in conformity with IS:456, IS:3370,IS:1893, IS:13932 & IS:13920 (latest versions) etc. Water retaining portion i.e. container of O.H.T. will be constructed in M-30 design mix concrete as per latest guidelines of BIS. The work also includes the following item
2One meter wide balcony around the tank at the middle ring beam (Junction of conical wall and containers vertical wall).
3One meter wide RCC Spiral stair case as an access to the top dome of the tank from ground level.
4Supplying & fixing M.S. gate with locking arrangement on first landing to avoid access to the O.H.T. as per direction of Engineer-in-charge.
5Supplying & fixing of 60cm, wide M.S. ladder from tope dome to the inside of the tank upto bottom dome of 50×50×6mm angle iron and 20mm dia plain M.S. bars @ 25 cm. C/C welded or riveted with suitable hand rail etc.
6Supplying & fixing of 1200mm dia ventilator of 50×50×6mm angle iron fitted at the crown of top dome with mosquito proof wire mesh over expanded metal jali.
7Supplying & fixing of 600×600mm M.S. Manhole cover of 5mm thick M.S. plate duly hinged with 50×50×6mm angle iron frame embedded in the top dome at appropriate place with locking arrangement shall be provided with overlap.
8Supplying & fixing of Three rows of G.I. (medium) 20mm dia pipe railing with 50×50×6mm angle iron post of clear height 1.00m at a distance of 1.25m centre to centre around the balcony, top dome and along the stair case from ground level to top dome.
9Supplying & fixing of water level indicator confirming to latest specifications & as per direction of engineer I/C
10Supplying & fixing of lighting conductor arrangements including earthing as per latest I.S. code.
11Supplying & fixing of 1 Nos. inlet of 100mmdia , 1 no.outlet of 150mm dia,washout of dia 100mm and over flow of150mm dia of D.I.D/F (Class K-9) pipes and their sluice valves, (confirming to I.S.-780) duck foot bends on sutaible R.C.C. column based on raft foundation as per direction of Engineer- in- charge,other special etc. including supply of all materials, necessarily required for jointing and erecting. The limits of pipe fixing shall be from dome of the tank to one meter outside the apron of the tank. Overflow pipe shall be vertical type at required position or otherwise specified. Also, construction of 1 Nos. inlet, 1 No. outlet & 1 No. washout/over flow chambers and their R.C.C. covers as per departmental type design. Complete in all respect as per the satisfaction of Engineer-in-charge.
12Supplying & Clamping the vertical pipe with M.S. clamps of size 50×6mm.
13Filling the tank as many times as required with water and testing for water tightness and making it water tight, water for testing the tank shall be arranged by the contractor.
14Supplying & Painting the outlet inlet, washout and over flow pipe with one coat of oxide primer (Asian, Berger, Nerolac etc.) and two coats of paint of approved quality (Asian, Berger, Nerolac etc.) and shade.
15Supplying & Painting the entire tank with three coats of (including base coat) exterior weather coat Apex or equivalent of Asian, Berger, Nerolac etc. of approved quality and shade as per direction of the Engineer-In-charges.
16Supplying & Painting the balcony and staircase railing and M.S. Manhole cover, ventilator angle iron posts with one coat of oxide primer (Asian, Berger, Nerolac etc.) and two coats of paint of approved quality (Asian, Berger, Nerolac etc.) and shade.
17Supplying & Filling of earth, ramming and watering the earth upto the plinth level (Made Up G.L.) which will be about 1.00 M above from natural ground level for construction floor & projecting one meter form the tank columns and 1 M wideapron with suitable drain. Floor shall be 40mm thick P.C.C. 1:2:4 over80 mm thick P.C.C. 1:4:8 at floor of the tank withsuitable glass strips.230 mm thick masonary walls in 1:6 cement sand mortar requires to raise ground level to plinth level including all materials etc.
18Providing and Laying Double Flanged (Screwed/Welded) Centrifugally Cast (Spun) Ductile Iron Pipes of class K-9 with true to alignment & Jointing of full lenght including supply ofpacking confirming to IS: 5382-1985 with testing of pipe line complete.D.I. Double Flanged Pipe K-9 -100mm dia
19Providing and Laying of D.I. Specials of class K-12 suitable for mechanical jointing as per IS: 9523- 2000
20Making Flanged joints between D.I D/F pipes and D.I D/F specials,including of jointing materials like nut bolt ,paking of standar quality and make with testing of joints
21Instalation of Product Pipe by Auger Boring method including making of entry and exit pits, all related civil works like excavation, horing/ strutting, etc., shielded excavation through auger boring process, lowering of pipe segments in the jacking pit, laying and jointing of product pipeline through jacking process from the jacking pit and after project completion as per the instructions of the Engineer-in-charge all complete except the cost of the pipe.(upto 80 meter installation length) Upto 300 mm dia (In all type of Soil)
22Providing, Lowering into trenches with true to alignment, Laying & Jointing of full lenghts of HDPE Pipes of specified grade as per IS:4984-1995 and specifications, with testing of pipe line including supply of jointing materials and specials.HDPE PN-6.0 PE-100 (Make- Apollo, Jain Irrigation, Aashirwad, Supreme, Vectus, Astral,Relience etc.)
2390 mm
24125 mm
25Excavation in ordinary soil (loam, clay, sand) for pipe line trenches including lift up to 1.5M and lead up to 30M with back filling, watering, ramming of excavated earth in the trenches.
26Supplying and fixing of following sizes of valves including carting the same upto site of work and fixing the same in water supply lines including cost of valves, specials, labour and T&P complete in all respect but excluding the cost of earth work and construction of chamber. C.I. D/F Sluice Valves/ Scour valves Confirming to IS: 14846-2000Pressure PN 1.0 (Make- Kirloskar, Zoloto, Kartar etc.)
2780 mm dia
28100 mm dia
29125 mm dia
30Constructing masonry Chamber 90x90x100 cm inside for Sluice Valve , in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/necessary excavation, foundation concrete 1:5:10 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
31Dismantling manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge :
32Water bound macadam road
33Bituminous road
34Supplying and fixing of following sizes of valves including carting the same upto site of work and fixing the same in water supply lines including cost of valves, specials, labour and T&P complete in all respect but excluding the cost of earth work and construction of chamber. C.I. Air Valve Double Acting50 mm dia (Make- Kirloskar, Zoloto, Kartar etc.)
35Supplying and fixing of following sizes of valves including carting the same upto site of work and fixing the same in water supply lines including cost of valves, specials, labour and T&P complete in all respect but excluding the cost of earth work and construction of chamber. C.I. D/F Non Return Valves PN 1.0- 125 mm dia (Make- Kirloskar, Zoloto, Kartar etc.)
36Constructing masonry Chamber ofsize45x45x60cm inside for Air valve with a floating coat of neat cement complete as per standard design :With F.P.S. bricks
37Providing and fixing Ultrasonic Water Flow Meter for Bulk Pipe lines inline type, flange end with Integral mounted, Flow rate & Totaliser display, Battery operated { with five year battery life) communication : UART/RS485, suitable against antifraud attempts etc. including all necessary fittings complete.
3880 mm dia nominal bore
39150mm dia nominal bore
40Providing and fixing C.I dirt box strainer for bulk type water meter with nuts, bolts, rubber insertions etc. complete conforming to IS : 2373
4180 mm dia
42150 mm dia
43Providing and fixing 80mm dia.FireHydrant Valve Confirming to IS: 5290 (Flanged) in position including all materials, labours, T&P etc complete.
44Disposal of Road rubbish/ malba/ earth/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
45Dismantling of Structures - Dismantling of existing structures like culverts, bridges, retaining walls and other structure comprising of masonry, cement concrete, wood work, steel work, including T&P and scaffolding wherever necessary, sorting the dismantled material, disposal of unserviceable material and stacking the serviceable material with all lifts and lead of 1000 m as per Technical Specification Clause 202- Cement Concrete
46Concrete with cement, coarse sand and 40 mm gauge stone ballast in proportion 1:4:8 in foundations and floors including supply of all material, labour and T&P etc. required for proper completion of the work. as per drawings and technical specifications Clause 802, 803, 1202 & 1203
47Cement Concrete (PCC M-30) Pavement:- Construction of Un-reinforced, Cement concrete pavement, thickness as per design, over a prepeared sub base with 43 grade cement or any other type PCC Grade M-30, coarse and fine aggregates conforming to IS: 383, maximum size of coarse aggregate not exceeding 25 mm, mixed in a concrete mixer of not less then 0.2 cum capacity and appropriate weigh batcher using approved mix design, laid in approved fixed side formwork (Steel channel, laying and fixing of wedges, steel plates including levelling the formwork and laying and fixing of 125 micron thick polythene film, as per drawing), spreading the concrete with shovels, rakes, compacted using needle, and plate vibrators, finished in continuous operation and curing o fconcrete slabs for 14 days, using curing compound where specified and water finishing to lines and grade as per drawings and technical specifications.
48Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge.
49Laying old cement cocrete interlocking paver blocks of any design/ shape laid in required line, level, curvature, colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineerin-charge. (Old 50% old tiles to be used
50Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in requiredcolour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.50% new tiles to be required
51Dismantling of Flexible Pavements Dismantling of flexible pavements and disposal of dismantled materials upto a lead of 100 m, stacking serviceable and unserviceable materials separately as per Technical Specification Clause 202 By Manual Means Bituminous Courses
52WBM Grading 1 Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing, rolling with three wheel 80-100 kN static roller in stages to proper grade and camber, applying and brooming, crushable screening to fill-up the interstices of coarse aggregate, watering and compacting to the required density Grading 1 as per Technical Specification Clause 405. By Manual Means
53WBM Grading 2 Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing, rolling with three wheel 80-100 kN static roller in stages to proper grade and camber, applying and brooming, crushable screening to fill-up the interstices of coarse aggregate, watering and compacting to the required density Grading 2 as per Technical Specification Clause 405. By Manual Means
54WBM Grading 3 Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing, rolling with three wheel 80-100 kNstatic roller in stages to proper grade and camber, applying and brooming, crushable screening to fill-up the interstices of coarse aggregate, watering and compacting to the required density Grading 3 as per Technical Specification Clause 405. By Manual Means
55Providing and applying primer coat with bitumen emulsion (SS-1) on prepared surface of granular base including cleaning of road surface and spraying primer at the rate of 0.70-1.0 kg/sqm using mechanical means as per Technical Specification Clause 502
56Dense graded bituminous macadam for grading I 37.5mm nominal size (bitumen @ 4.25% by weight of total mix
57Bituminous Concrete for Grading - II-13.2 mm (Nominal Size) : Bitumen @ 5.4 % of the weight of total mix
58Fog Spray - Providing and applying low viscosity bitumen emulsion for ealing cracks less than 3 mm wide or incipient fretting or disintegration in an existing bituminous surfacing By Mechinacal Means
59Demolishing dry brick pitching in floors, drains etc. including stacking serviceable material and disposal of unserviceable material within 50 metres lead :
60Brick on edge pavement with straight overburnt bricks laid on edge including preparation of subgrade to prescribed camberand including supply of briks, fillingj oints with local sand and spreading blinding coat 1cm (3/8\")depth of local sand over the entire surface and including supply of all materials, labour and T&P etc. required for proper completion of the work.
61Laying of old cement cocrete interlocking paver blocks (Tiles) for Ist stage reinstatementof pipe line trencheslaid in required line and level as per existing surface etc. all complete as per the direction of Engineer-in-charge. (Existing C.C. Interlocking tiles to be used).
62Laying of brick on edge pavement by old Bricks for Ist stage reinstatement (old brick obtained from the site shall be used) and preparing the surface complete as per direction of engineer in charge.
63PUMP HOUSE AND BOUNDARY WALL
64Earth work in excavation by mechanical means(hydraulic excavator) /manual meansin foundation trenches or drains (not exceeding 1.5 mtr in width or 10 sqm on plan) including dressing of sides and ramming of bottom, lift up to 1.5 mtr including gettingout the excavated soil and disposal of surplus excavated soil as directed, within a lead of50 m in all kinds of soil.
65Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - all work up to plinth level in 1:4:8(1Cement:4coarsesand:8gradedstone aggregate 40 mm nominal size).
66Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering and shutteringfinishing and reinforcement -all work up to plinth level in 1:1.5:3(1cement:1.5coarse sand: 3grad aggregate 20 mm nominal size)
67Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15 degree landing, balconies, shelves, chajjas, lintels, bands, plain window sills, stair cases and spiral stair casesup to floor five level excluding the cost of centering and shutteringfinishing and reinforcement -all work up to plinth level in 1:1.5:3(1cement:1.5coarse sand: 3grade aggregate 20 mm nominal size)
68Reinforcement in RCC work including straightening, cutting, bending, placing in position and binding, using Thermo-Mechanically Treated bars all complete.
69Centering and shuttering including strutting, roping etc. and removal of form for
70Foundation raft & tie beams
71Slab
72Lintels, beams, plinth beams, girders, bressmers and cantilevers
73Columns, pillars, piers, abutments, posts and struts
74Edges of slabs and breaks in floors and walls under 20cm wide
75Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand)
76Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand)
77Honey-comb brick work 10 / 11.4 cm thick with common burnt clay bricks of class designation 7.5 in super structure above plinth level upto floor V level with cement mortar 1:4 (1 cement : 4 coarse sand).
78Steel work welded built of section /framed works including cutting fixing in position applying a priming code of approved steel primer using steel its as requiredingratings,frames,guardbar,ladder,railing gates and similar works.
79Cement concrete flooring 1:2:4 (1 cement: 2 coarse sand : 4graded stone aggregate) finished with a floating coat of neat cement including cementslurry, but excluding the cost of nosing of steps etc. complete. 40mm thick with 20mm nominal size stone aggregate.
80Provide 5mm thick glass strips on flooring 20mm deep.
81Provide 12mm thick plaster in 1:6 (1 cement : 6 fine sand)
8215 mm cement plaster on the rough side of single or half brick wall of mix :1:6 (1 cement: 6 fine sand)
83provide15 mm thick cement plaster finished with a floating coat of neat cementof mix 1:3 (1 cement : 3 fine sand)
84Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade (Make Asian, Berger, Nerolac etc.) : New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) (Make Asian, Berger, Nerolac etc.)
85Supply of all labour, material and T & P etc. andConstruct brick-on-edge pavement inside proposed water works compound.
86Paintingwood / Steel workwithDeluxeMultiSurfacePaintof required shade.Twoor more coat applied @0.90ltr/10sqm [email protected]/10sqm (Make Asian, Berger, Nerolac etc.)
87Supply and fixing of 4mm thick plane glass panes on window\"s including supply of nails and putty etc all complete.
88Providingandlayingintegral cement based waterproofing treatment includingpreparationofsurfaceasrequiredfortreatmentofroofs, balconies,terracesetc consisting of following operations: (a) Applying aslurrycoatof neat cementusing2.75kg/sqm. ofcement admixed with water proofing compoundconformingto IS. 2645 andapproved byEngineer-in-chargeovertheRCCslabincludingadjoiningwalls upto 300mm heightincludingcleaning the surfacebefore treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115mm sizewith50% of cementmortar 1:5(1cement: 5coarse sand) admixed with water proofing compound conforming to IS : 2645 andapprovedbyEngineer-in-chargeover20mmthicklayerofcementmortarofmix1:5(1cement:5 coarsesand)admixedwith waterproofingcompoundconformingtoIS : 2645 andapprovedby Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs (c) Aftertwo daysof proper curing applying asecond coatof cementslurryusing2.75kg/sqmofcementadmixedwith waterproofingcompoundconformingtoIS:2645 andapprovedby Engineer-in-charge.(d)Finishingthesurfacewith20mmthick jointlesscementmortarofmix1:4(1cement:4coarsesand) admixed with waterproofing compoundconformingto IS:2645 and approvedbyEngineer-in-chargeincludinglayingglassfibreclothof approved quality in top layer of plaster and finally finishing the surface withtrowelwithneatcementslurryandmakingpatternof300x300 mmsquare3mmdeep.(e)Thewholeterracesofinishedshallbe for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120mm and minimumthickness at khurra as 65 mm mmsquare3mmdeep.(e)Thewholeterracesofinishedshallbe flooded with water for a minimum period oftwoweeks forcuring and forfinal test.
89Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
90Supply and fixing of PVC pipes for waste water and sewer pipes.
9175 mm diameter
92110 mm diameter
93Providing and fixing 15 mm dia. Nominal bore G.I. pipes complete with G.I. fittings and clamps/c cutting and making good the walls etc. Internal work
94Filling available excavatedearth (excluding rock)in trenches,plinth,sidesoffoundationsetc.inlayersnotexceeding20cmin depth,consolidatingeachdepositedlayerbyramming andwatering, leadup to 50 m and lift up to 1.5 m.
95Supplying and filling in plinth with Local sand including watering, ramming, consolidating and drassing complete in proposed water works.
96Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 liter low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required White Vitreous china Orissa pattern W.C. pan of size 580x440 mm.
97Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required. White Vitreous China Flat back wash basin size 450x 300 mm with single 15 mm C.P. brass pillar tap
98Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : 15 mm nominal bore
99S/Filling brick ballast90 mm to 40 mm size
100Earth work in rough excavation, banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up in embankments for roads, flood banks, marginal banks and guide banks or filling up ground depressions, lead upto 50 m and lift upto 1.5 m
101House Service Connection
102Providing and supplying blue MDPE pipes confriming to ISO 4427:1996 manufactured from vergin PE 80 foot grade compoundedraw material having blue colour only with qualityagencies like WRC/CIPET (india) /DVGM/KIWA/SPGN for usage in drinking water with quality system alll comlete including cost all taxes, inspection comlete job as per secification and direction of E/I. 20 mm dia pipe. PN 16 (Make:- Duraline, EPC, Ashirwad, Astral, Oriplast, Jain Irrigation etc.)
103Providing and fixing SS Flow Control Non Return Valve for Avg. Flow 5 lpm. Material of construction to be SS 304. Connection threading IS:554 BSPT, ISO: 7-1. Valve consiste of proprietary design which regulates the designed flow. All machined parts shall be manufactured on CNC lathe machine. Casting is not allowed. The valve is designed to prevent illegal tapping of water by using electric suction motor. Flow control Valve (SS) 5 lpm (Ave. Flow at 0.5 - 1.0 kg/ cm2)(Make:- Kimplas, Georg Fischer, Bentlay etc.)
104Providing and fixing brass bib cock of approved quality : 15 mm nominal bore
105Providing and fixing PP clamp Saddles shall comply with AS/ NZS 4129 or relevant International Standards - Mechanical tapping saddles for waterworks purposes and designed for use with PVC/PE pipe as per IS 4985/ IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be blue with mouldedSS304 metal female threaded outlets. Seal shall be Thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer withSS304 with trivalent blue. Pressure rating will be PN 16 / PN 10 (Make:- Kimplas, Georg Fischer, Bentlay etc) Size:- 80mm & above
106Suppl & fixing PP Compression Metal Insert Female Thread Adaptor with SS304 material with BSP Threads as per ISO 14236 standard. Body, Nut / Cap –Polypropylene, Clip Ring-POM (Acetylic resin ),Packing bush- Polypropylene, “O” ring – NBR. Pressure rating will be PN 16.The Compression fittings for intended for conveyance of Potable water for Human consumption to be tested to comply with BS 6920 specifications in any of the laboratories like DVGM / KIWA / SPGN / WRc –NSF and certificate of compliance to be produced for the following parameters. (Make:- Kimplas, Georg Fischer, Bentlay etc.)
107Supply & fixing Double Compression Elbow with Body, Nut / Cap –Polypropylene, Clip Ring-POM (Acetylic resin ),Packing bush- Polypropylene, “O” ring – NBR. Pressure rating will be PN 16.The Compression fittings for intended for conveyance of Potable water for Human consumption to be tested to comply with BS 6920 specifications in any of the laboratories like DVGM / KIWA / SPGN / WRc –NSF and certificate of compliance to be produced for the following parameters. (Make:- Kimplas, Georg Fischer, Bentlay etc.)
108Supply & fixing UPVC Ball Valves, with compression- female threaded 20mm withBody, Nut / Cap –Polypropylene, Clip Ring-POM (Acetylic resin),Packing bush- Polypropylene, “O” ring – NBR. Pressure rating will be PN 16.The Compression fittings for intended for conveyance of Potable water for Human consumption to be tested to comply with BS 6920 specifications in any of the laboratories like DVGM / KIWA / SPGN / WRc –NSF and certificate of compliance to be produced for the following parameters. (Make:- Kimplas, Georg Fischer, Bentlay etc.)
109Making ferrule connection in the existing main of D.I., G.I, A.C, PVC or any type of pressure mains with saddle piece, service connections, fittings and fixing of G.M. ferrule including tapping the main, but excluding the cost of earth work and cost of all materials. Ferrule Connection (Labour cost only)

AI Tender Summary

OUR REF NO 34396009
AUTHORITY Government Departments
TENDER VALUE 1.98 Crore
LAST DATE 29-10-2022
Authority
Authority Name Drinking Water And Sanitation Department
Work Description Construction Testing And Commissioning Of Rcc Oht Pump House Di K9 Rising Main Hdpe Pipe Distribution System And Fhtc Etc Of Bhogpur Jaspur Gov Solar Pumping Water Supply Scheme In Block Jaspur Distt Us Nagar
Basic Detail
Tender No 5537/613/746 Dated 13.10.2022
Bidding Type Tender
Location
City jaspur
State Uttarakhand
Key Dates
Publish Date 15 Oct 2022
Submission Date 29 Oct 2022
Open Date 01 Nov 2022
Finance
Tender Value 1.98 Crore
Tender Fee 5900
EMD 3.98 Lakhs
Exemption Not Available
Document List
150411b8-282e-40ee-93fe-56b1c79711ee.html
bhogpurjaspur.pdf
BOQ_60690.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 15, 2022
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 29, 2022
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Nov 01, 2022

Bid Opening Date

Technical bids will be opened and evaluated.