| 1 | M&L Point Wiring with 2.5 Sqmm (nominal area) FRLSH 1100 Volt grade PVC insulated, Unsheathed, Multi-stranded, Single Core Copper Conductor Cable with 2.5 Sqmm (nominal area) FRLSH 1100 Volt grade PVC insulated, Unsheathed, Multi-stranded, Single Core Copper Conductor Cable (Green Colour) as Earth Continuity Wire, drawn in and including PVC Casing Capping (ISI Marked) of suitable Size (25/32mm in Width) along with all Fitting/ Fixtures as Tee, Bend, Elbow, Socket, Saddles, etc. complete with PVC Board of suitable Size for accommodating Switches, Sockets, Regulators, etc. Earth Continuity Wire connected to Common Earth dolly for ONE 3/5 PIN SOCKET OUTLET 6/16 AMP POINT on INDEPENDENT BOARD, complete all as specified and as directed. |
| 2 | M&L Sub-main Wiring with 2-Run of 6.0 Sqmm (nominal area) FRLSH 1100 Volt grade PVC insulated, Unsheathed, Multi-stranded, Single Core Copper Conductor Cable and 1-Run of 6.0 Sqmm (nominal area) FRLSH 1100 Volt grade PVC insulated, Unsheathed, Multi-stranded, Single Core Copper Conductor Cable (Green Colour) as Earth Continuty Conductor drawn in and including Surface or Recess PVC Conduit (ISI Marked) of suitable Size (25/32mm width) along with all Fitting/ Fixtures as Tee, Bend, Elbow, Socket, Saddles, etc., complete all as specified and as directed.NOTE :-(a)Cost of 3-Run of Cable & 1-Run of PVC Conduit will deemed to be included in the Quoted Unit Rate and the same will be Mesured as ONE UNIT.(b)Sub-main Wiring will be measured PVC Conduit only. Wires required/ as ordered for looping, etc. will deemed to be included in the Quoted Unit Rate. |
| 3 | S&F Rigid Non-metallic PVC Conduit of Size 20mm (External Dia) Exclusive of Boxes (Junction/ Terminal) but inclusive of all Tees, Bends, Elbows, Reducers, Bell Mouth Tube Ends and Fixing Accessories such as Couplers, Lock Nuts, Saddles, Pipe Hooks, etc., complete all as specified and as directed. |
| 4 | S&F Switch Socket Combination 6/16 Amp, 2-in-1, (3 Pin & 3 Pin), multi-purpose, Flush type, 230 Volt AC and Connecting up, complete all as specified and as directed. |
| 5 | S&F MCB Single Pole & Neutral 10 Amp to 32 Amp, \"C\" Series, 50 Hz, 10 kA, 240 Volt and Connecting up, complete all as specified and as directed. |
| 6 | S&F MCB 6.0 Amp to 32 Amp, Double Pole, \"C\" Series, 50 Hz, 10 kA, 240 Volt and Connecting up, complete all as specified and as directed. |
| 7 | S&F MCB 40 Amp, Double Pole, \"C\" Series, 50 Hz, 10 kA, 240 Volt and Connecting up, complete all as specified and as directed. |
| 8 | S&F Sheet Metal Enclosure for DB\"s when MCBs to be used SPN 2-way, 240 Volt AC, Single Door, Epoxy Based Powder coated and Connecting up, complete all as specified and as directed. |
| 9 | S&F Sheet Metal Enclosure, Single Pole & Neutral, 2 Pin & Earth Plug Top and Socket 20 Amp rating with and including 1 No. MCB 20 Amp, Single Pole and Connecting up, complete all as specified and as directed. |
| 10 | Supply, Installation & Commissioning Hi Wall Split Air Conditioner 1.5 TR Capacity with Indoor/ Outdoor Units including Cordless Remote Control Unit and in-bulit Air Ioniser and Plasma Filtter for better Indoor Air quality, having Minimum 5 Star rated and EER 3.2, Providing Electric Connection, complete all as specified and as directed. |
| 11 | M&L Copper Pipe 5/8\" and 3/8\" Dia, Nitril Insulation Tubler type Electric Wire from Indoor Unit to Outdoor Unit of suitable Size, Providing necessary Connections, complete all as specified and as directed. |
| 12 | M&L PVC Drain Pipe 20mm bore (dia) for draining out Water from Split ACs and Providing necessary Connections, complete all as specified and as directed. |
| 13 | Supply & Installation Refrigerator 320 LITRE Capacity, Electric Driven, Single Phase, BEE 5 Star rated and as approved, complete all as specified and as directed. |
| 14 | Supply, Installation & Commissioning of Water Cooler, Fully Stainless Steel Body, Electric Driven, Single Phase, BEE 5 Star rated and as approved, having approx Storage and Nominal Cooling Capacity 40/80 LITRE, complete all as specified and as directed. |
| 15 | M&L PVC Drain Pipe 20mm bore (dia) for draining out Water from Watter Coolers and Providing necessary Connections, complete all as specified and as directed. |
| 16 | Supply & Installation Voltage Stabilizer 3.0 KVA Capacity, suitable for Automatic Operation, Single Phase, Naturally Air Cooled, Indoor type and Designed for Input Variation between 170 Volt to 250 Volt with Output Voltage stabilized at 230 Volt with accuracy of +2.5%, complete all as specified and as directed. |
| 17 | Supply & Installation Voltage Stabilizer 5.0 KVA Capacity, suitable for Automatic Operation, Single Phase, Naturally Air Cooled, Indoor type and Designed for Input Variation between 170 Volt to 250 Volt with Output Voltage stabilized at 230 Volt with accuracy of +2.5%, complete all as specified and as directed. |
| 18 | Excavating in Trenches, not exc. 1.50 Metre Wide and not exc. 1.50 Metre in Depth for Laying of Water Pipe Line, Cable Line, etc., Forming surfaces to required Foundation/ Gradient and getting out in Soft/Loose Soil, complete all as specified and as directed. |
| 19 | Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in layers not exc. 25 Cm, Providing Heaps with surplus Soil along the Route of the Water Pipe Line, Cable Line, etc., in Soft/Loose Soil, complete all as specified and as directed. |
| 20 | Removing Excavated Materials (Soils) not exc. 50.00 Metre and Depositing where directed at a level not exc. 1.50 Metre above the Starting Point in Soil, complete all as specified and as directed. |
| 21 | M&L Cement Concrete 1:3:6 (20mm graded stone aggregate) in Copping of Poles, etc., Weathering slightly Rounded or Chamfered Angle and Throating, Fair Finishing to all Exposed Faces of Concrete including necessary Earthwork and Formwork, complete all as specified and as directed.NOTE : Cost of Formwork will deemed to be included in the Quoted Unit Rate. |
| 22 | S&F LED Bollard Light Fitting 8/9/10 Watt (as approved), New Generation, Environ-mental Friendly, Energy Saving, Long Life, Aesthetically Designed, Aluminium Land-scape Luminaire for Diffused Lighting with High Power LED as Light Source, IP-65 Protected, Electrically connecting up with and including suitable Size and Length PVC Flexible Twisted Copper Wire, 3 Core, complete all as specified and as directed. |
| 23 | Supply & Laying or Fixing or Passing through Pipe, 1100 Volt grade Heavy duty Cable with PVC insulated Aluminium Stranded Conductor served with an Inner sheathing of PVC Tape armoured with Galvanised Steel Wire or Tape and Overall PVC sheathed Weather Proof Flat Twin Core 10 Sqmm, complete all as specified and as directed. |
| 24 | Supply, Laying & Testing LT Under Ground Cable 1100 Volt grade, XLPE insulated, PVC Sheathed, Heavy duty, Armoured with Mmulti-stranded Aluminium Conductor all as per IS:7098 (Part-I)-1998 having Cross-sectional Area 10 Sqmm, 2 Core, laid in Trenches, Ducts or through Pipes, etc., complete all as specified and as directed. NOTE : Earth Works, Protection Pipes/ Bricks or Pre-cast Concrete Cable Covers, etc. will be Measured and Paid separately under relevent Items. |
| 25 | Supply, Laying & Testing XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross-sectional Area 35 Sqmm, 3½ Core, laid in Trenches/ Ducts or Passing through Pipe or Fixing on Poles, etc., complete all as specified and as directed. NOTE : Necessary Earthworks, Sand Cushioning, Bricks Protection, GIPipe, etc. will be Measured and Paid separately under relevent Items. |
| 26 | Supply, Laying & Testing XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross-sectional Area 150 Sqmm, 3½ Core, laid in Trenches/ Ducts or Passing through Pipe or Fixing on Poles, etc., complete all as specified and as directed. NOTE : Necessary Earthworks, Sand Cushioning, Bricks Protection, GIPipe, etc. will be Measured and Paid separately under relevent Items. |
| 27 | Supply, Laying & Testing XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross-sectional Area 185 Sqmm, 3½ Core, laid in Trenches/ Ducts or Passing through Pipe or Fixing on Poles, etc., complete all as specified and as directed. NOTE : Necessary Earthworks, Sand Cushioning, Bricks Protection, GIPipe, etc. will be Measured and Paid separately under relevent Items. |
| 28 | M&L Sand Cushioning (dry) in Trenches/Ducts for Protection of UG Cables (below, above and around the UG Cable laid) of 230mm Spread thickness (8.0mm in Depth before laying the Cable and 150mm in depth after laying the Cable) and Consolidated (Ppunned) upto 180mm thickness, complete all as specified and as directed.NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only will be Measured. |
| 29 | Supply & Laying Sub-class ‘B’ Bricks of Size 230x115x75mm, Kiln burnt, for Covering to UG Cable as Protection, laid Flat, Transversally Width Equal to the Length of the Cable, complete all as specified and as directed. |
| 30 | S&F HDPE Double Wall Corrugated (DWC) High density Polythene Pipes of Outer dia 40mm and Inner dia 32mm, cut to length/Size as per Site requirement having Corrugation on the Outer Wall and Plain Surface on the Inner Wall, confirming to IS:14930 (Part I & II) for Protection of Under Ground Cable/ in PCC with and including all Fittings as required at Site including Cutting Floor and Making Good the same to match the Existing/ Adjoining Surfaces, etc., complete all as specified and as directed.MAKE : REX POLY EXTRUSIONS (ELDREX) or equivalent (ISI marked).NOTE : The Cost of All Accessories for fixing of DWC Pipe along the Wall/ Roof/ Cable Trays will deemed to be included in the Quoted UNIT RATE. |
| 31 | S&F Air Termination Single Pointed Aluminium Rod 12mm dia and 300mm long mounted on GI Pipe, complete all as specified and as directed. |
| 32 | S&F Aluminium Strip 25x3.15mm with PVC Saddle and fixing Screws for Roof/ Earth Conductors and Down Conductors above Ground, complete all as specified and as directed.NOTE : All Joints should be joined by Exothermic Welding or Brazing. |
| 33 | S&F Galvanised Iron Strip 32x6mm with Saddle and fixing Screws from Test Point Terminal Block to Earth Pit, complete all as specified and as directedNOTE : All Joints should be joined by Exothermic Welding or Brazing. |
| 34 | S&F Epoxy/ DMC Electrical Insulator T-type with Bolts, Nuts, Screws, etc. for fixing of Aluminium/ Copper Strip on Walls, Roof or any specified Surface, complete all as specified and as directed. |
| 35 | S&F Steel Water Tubing 40mm bore (dia), Galvanised, ‘light grade’ with all Fittings, laid on Floor or fixing to Walls or any other Situation, complete as all specified and as directed. |
| 36 | S&F Test Point Terminal Block made of Gun Metal or Phosphorus Bronze Size 75x75x25mm, drilled and screwed including 3 No. 8mm dia, 25mm long Hexagonal Head Screws, complete all as per specified and as directed. |
| 37 | M&L Earth Pit of Cement Concrete 1:3:6 (20mm grade stone aggregate) and Pre-cast Reinforced Cement Concrete 1:2:4 (20mm grade stone aggregate) Earth Pit Cover Slab of Size 350x350x50mm, reinforced with TMT Bars 10mm dia @ 100mm Centre-to-Centre in Bothways including GI Wire Mesh, PGI Funnel, complete all as specified and as directed. |
| 38 | M&L LPIEarly Streamer Emission (ESE) Stormaster type Lighting Protection complete with Lightening Air Terminal configured as a Spheroid which is comprised fo seperate Elecrically isolated 4 Panels surrounding an Earth Central Finial. The Insulation Materials used to Electrically isolate the Panels comprised of Base Polymer which Provides High Ozone & UV Resistance with a Di-electric Strength of 24-38 KV/mm Tested as per IEC 60-1:1989 including Installation, Commissioning & Testing, complete all as specified and as directed.Constructional Details :- Central Pic up Rods, Upper & Lower Series of Electrodes and Triggering Device Housed in a Stainless Steel Water Proof and Non-corroding Housing. This System Comprising the following :- (a)GI Mast : GI Tubular Mast of 5.0 Metre High with Mild Steel Base Plate and Adaptor to mount Air Terminal with Coupler/ Reducer, multi-strand Stay Wires, Joints, Clamps and Accessories including Cement Concrete Work.(b)Down Conductor : PVC insulated Copper Flexible Cable of Size 70 Sqmm for Down Conductor with suitable Clamps and Other Accessories from Air Terminal to Earth Pit.(c)CPRI Tested Lightening Transient Event Counter Resettable 7 Digit LCD Display with-in Built Lithium Battery in IP-67 rating Enclosure with Transparent Lid, Mounting Arrangement, etc. as required.(d)Chemical Earthing (Each Set of 3 Earthing) with Solid Rod of Length 3.00 Metre having 17.2mm dia, Copper coating of 250 Micron along with Poly Plastic Pit Cover and Ground Enhancement Materials of 100 Kilogram with Exothermic Brazing for Joints as per IS:3034, complete all as specified and as directed. |
| 39 | Supply, Installation & Commissioning LT Feeder Pillar Box, Factory Made (CPRI Approved/ Tested Manufacturer), made out of 3.15mm thick CRCA Sheet with Angle Iron Frame 50x50x6.0mm, Outdoor type, Double Doors, Front & Rear Opening with Locking Arrangements, suitable for 415 Volt, 3 Phase, 4-Wire System, 50 Hz Supply having 4 No. Copper Bus-bars 200 Amp rated, installed on Porcelain/ Epoxy Insulator, Dust Proof and Vermin Proof (IP-54), Feeder Pillar Box Painted with Two Coats of Synethetic Enamel Paint over a Coat of Red Oxide Zinc Chrome Primer and Fixing with Mild Steel Bolts, Nuts, Washers, etc. on Cement Concrete 1:2:4 (20mm graded Stone aggregate) Platform (minimum 600mm in Height from Natural Ground Level) and grouting Mild Steel Angle Iron Legs in Floor, Providing all Electric Connections and Testing, Comprising with and including following Accessories, complete all as specified and as directed :-(a) MCCB 100 Amp, 4 Pole, 36 kA, 415 Volt -01 No.(b) Digital Ammeter 0-200 Amp, Square Flush Pattern -01 No.(c) Digital Volt Meter 0-500 Volt, Square Flush Pattern -01 No.(d)Indicating Lamp LED type in Incomming Phase -01 Set(e) Internal Wiring with PVC insulated Copper Conductor Multi-stranded Cable 1100 Volt grade IS-694 marked of appropriate gauge including Copper Lugs(f) Connection from MCCB to Bus-bars with Solid Copper Conductor.(g) MCCB shall be provided with suitable Spreader of Aluminium Conductor for fixing of Incoming Cable |
| 40 | Supply, Installation & Commissioning LT Feeder Pillar Box, Factory Made (CPRI Approved/ Tested Manufacturer), made out of 3.15mm thick CRCA Sheet with Angle Iron Frame 50x50x6.0mm, Outdoor type, Double Doors, Front & Rear Opening with Locking Arrangements, suitable for 415 Volt, 3 Phase, 4-Wire System, 50 Hz Supply having 4 No. Copper Bus-bars 200 Amp rated, installed on Porcelain/ Epoxy Insulator, Dust Proof and Vermin Proof (IP-54), Feeder Pillar Box Painted with Two Coats of Synethetic Enamel Paint over a Coat of Red Oxide Zinc Chrome Primer and Fixing with Mild Steel Bolts, Nuts, Washers, etc. on Cement Concrete 1:2:4 (20mm graded Stone aggregate) Platform (minimum 600mm in Height from Natural Ground Level) and grouting Mild Steel Angle Iron Legs in Floor, Providing all Electric Connections and Testing, Comprising with and including following Accessories, complete all as specified and as directed :-(a) On Load Change Over 160 Amp, 4 Pole-01 No.(b) MCCB 160 Amp, 4 Pole, 36 kA, 415 Volt -01 No.(c) MCCB 125 Amp, 4 Pole, 16 kA, 415 Volt -01 No.(d) Digital Ammeter 0-200 Amp, Square Flush Pattern -01 No.(e) Digital Volt Meter 0-500 Volt, Square Flush Pattern -01 No.(f)Indicating Lamp LED type in Incomming Phase -01 Set(g) Internal Wiring with PVC insulated Copper Conductor Multi-stranded Cable 1100 Volt grade IS-694 marked of appropriate gauge including Copper Lugs(h) Connection from MCCB to Bus-bars with Solid Copper Conductor.(j) MCCB shall be provided with suitable Spreader of Aluminium Conductor for fixing of Incoming Cable |
| 41 | M&L Earthing with Galvanised Earth Plate Electrode 600x600x6.0mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with and including Galvanised Earth Strip of size 32x6.0mm by means of Bolts, Nuts, Check nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar with GI 40mm bore (dia) Light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke dust mixed with Common Salt in alternate layers of not exc. 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab 350x350x50mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, PGI Funnel with GI Watering Pipe 20mm bore (dia) Medium grade including necessary Excavation in Soft/Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion, complete all as per specified and as directed. NOTE : All Joints should be joined by Exothermic Welding or Brazing. |