Repairing Of Round Body Single Phase 10 Kva And 16 Kva Damaged T / F At Akbarpur Workshop.- 1 Handling And Dragging Of Damaged Transformer From Stacking Yard To Repairing Hall With Accessories 2 10 Kva 3 16 Kva 4 Cutting / Opening Of Top Cover , akbarpur-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Repairing Of Round Body Single Phase 10 Kva And 16 Kva Damaged T / F At Akbarpur Workshop.- 1 Handling And Dragging Of Damaged Transformer From Stacking Yard To Repairing Hall With Accessories 2 10 Kva 3 16 Kva 4 Cutting / Opening Of Top Cover . Submission Date for this Tender is 21-10-2022. Coats and Jackets Tenders in akbarpur Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

34272383
Repairing Of Round Body Single Phase 10 Kva And 16 Kva Damaged T / F At Akbarpur Workshop.- 1 Handling And Dragging Of Damaged Transformer From Stacking Yard To Repairing Hall With Accessories 2 10 Kva 3 16 Kva 4 Cutting / Opening Of Top Cover
Open Tender
Indian
Uttar Pradesh
akbarpur
21-10-2022

Tender Details

Repairing Of Round Body Single Phase 10 Kva And 16 Kva Damaged T / F At Akbarpur Workshop.- 1 Handling And Dragging Of Damaged Transformer From Stacking Yard To Repairing Hall With Accessories 2 10 Kva 3 16 Kva 4 Cutting / Opening Of Top Cover Plates & Fittings Of The Transformers, Draining Of Its Oil & Detanking Of Core & Coil Assembly. 5 10 Kva 6 16 Kva 7 Dismantling Of Core & Coil Assembly And Its Cleaning. 8 10 Kva 9 16 Kva 10 Dismantling Of Shell Core And Coil Assembly. Removing Of Hv And Lv Leg Coils For Assessing Its Reuse, Reuse Of Major Insulating Material If Possible, Checking And Recording Of Physical Dimensions Of Coil. 11 10 Kva 12 16 Kva 13 Making Of Complete Hv & Lv Leg Alu. Leg Coils Identical To Original One With Same Number Of Turns, Weight Etc Providing Super Enameled / Dpc Conductor / Strip Confirming To Is 1971 153 In Place Of Old And Damage Coil. Alu.Coil, Wire Strip Will Be Provided By The Department. All Coil Assembly Of Identical Voltage Shallbe Interchangeable Without Requiring Any Special Equipment. Shell Coil Shall Be Supported Betweenadjacent Sections By Insulations ( Flick Paper ) Paper, Spacers, Beamers And Other Insulations. Rewinding Shall Be Arranged To Ensure Free Circulation Of Oil To Reduced Hot Spots In Winding. The Insulation Of Coil Shall Be Treated With Suitable Insulating, Varnish Or Equivalent Compound To Develop The Full Electrical Strength Of 14 10 Kva 15 16 Kva 16 Assembly Of Shell Core ( Three Limbs ) Coils And Fitting Of Top And Other Parts. Replacement Of Insulation Such As Press Board, Craft Paper, Making Support Between Adjacent Section By Insulating Spacers And Wrapping Etc. Shifting Of Repaired Core Coil Assembly And Placementinside The Oven For Proper Dry Out. 17 10 Kva 18 16 Kva 19 Shifting And Keeping The Assembled Core& Coil Etc. In Oven From The Repairing Hall 20 10 Kva 21 16 Kva 22 Dragging Of Transformers Tank From The Repairing Hall To Washing Area And Its Complete Washing, Cleaning, Removing Of Rust And Carbon Etc. 23 10 Kva 24 16 Kva 25 Repairing Of Damaged T / F Body / Radiator By Electric / Gas Welding Complete In All Respect For Arresting Oil Leakage. 26 10 Kva 27 16 Kva 28 Painting Of Inner Side Of T / F Tank With Heatproof Zinc Chromatic Paints In Two Coats After Providing Primer Of Red Oxide Paint. 29 10 Kva 30 16 Kva 31 Dragging / Shifting Out Completely Dried Empty Tank After Painting To Repairing Hall. 32 10 Kva 33 16 Kva 34 Taking Out Core And Coils Assembly From The Oven And Shifting To Repairing Hall. 35 10 Kva 36 16 Kva 37 Welding / Tightening The Top Cover After Tanking Of Core And Coil Assembly Into Painted Tank And Tightening Of Assembly Into The Tank And Fitting All Accessories Of Transformer And Filling Of Oil. 38 10 Kva 39 16 Kva 40 Spray Painting Of Transformer Tank From Outside With Supper Enamel Synthetic Grey Paint In Two Coats After Providing Primer Of Red Oxide Paint 41 10 Kva 42 16 Kva 43 Dragging / Shifting Of Repaired T / F Near To The Test Cabin / Testing Place And Dragging / Shifting T / F To Yard After Testing And Its Stacking At Identified Place. 44 10 Kva 45 16 Kva 46 Punching And Welding Of M.S. Plate Of 100X50x3mm Size On The Outside Of T / F Containing Following Information. ( I ) Job Number, ( Ii ) Capacity ( Iii ) Name Of Workshop ( Iv ) Date Of Repair 47 10 Kva 48 16 Kva 49 Package Rate Per Transformer Of Supply Item To Be Provided By The Contractor For Repairing Of Transformer. Details Of Supply Items Are Annexed Hereto. 50 10 Kva 51 16 Kva

Key Value

Document Fees
INR 1180 /-
EMD
INR 10000.0 /-
Tender Value
INR 10 Lakhs /-

BOQ Items

Name of Work: FOR REPAIRING OF ROUND BODY SINGLE PHASE 10 KVA & 16 KVA DAMAGED T/F AT AKBARPUR WORKSHOP
Sl. No. Item Description
1Handling and Dragging of damaged Transformer from stacking yard to repairing hall with accessories
210 KVA
316 KVA
4Cutting/Opening of top cover plates & fittings of the transformers, draining of its oil & Detanking of core & coil Assembly.
510 KVA
616 KVA
7Dismantling of core & coil Assembly and its cleaning.
810 KVA
916 KVA
10Dismantling of Shell Core and coil assembly. Removing of HV and LV Leg coils for assessing its reuse, reuse of major insulating material if possible, checking and recording of physical dimensions of coil.
1110 KVA
1216 KVA
13Making of complete HV & LV leg Alu. Leg coils identical to original one with same number of turns, weight etc providing super enameled/DPC conductor/Strip confirming to IS 1971 153 in place of old and damage coil. Alu.coil, wire strip will be provided by the department. All coil assembly of identical voltage shallbe interchangeable without requiring any special equipment. Shell Coil shall be supported betweenadjacent sections by insulations (flick Paper) Paper,spacers, beamers and other insulations. Rewinding shall be arranged to ensure free circulation of oil to reduced hot spots in winding. The insulation of coil shall be treated with suitable insulating, varnish or equivalent compound to develop the full electrical strength of
1410 KVA
1516 KVA
16Assembly of Shell core (Three Limbs) coils and fitting of top and other parts. Replacement of insulation such as press board, craft paper, making support between adjacent section by insulating spacers and wrapping etc. shifting of repaired core coil assembly and placementinside the oven for proper dry out.
1710 KVA
1816 KVA
19Shifting and keeping the assembled core& coil etc. in OVEN from the repairing hall
2010 KVA
2116 KVA
22Dragging of transformers tank from the repairing hall to washing area and its complete washing, cleaning, removing of rust and carbon etc.
2310 KVA
2416 KVA
25Repairing of damaged T/F body/radiator by electric/gas welding complete in all respect for arresting oil leakage.
2610 KVA
2716 KVA
28Painting of inner side of T/F tank with heatproof zinc chromatic paints in two coats after providing primer of red oxide paint.
2910 KVA
3016 KVA
31Dragging/shifting out completely dried empty tank after painting to repairing hall.
3210 KVA
3316 KVA
34Taking out core and coils assembly from the OVEN and shifting to repairing hall.
3510 KVA
3616 KVA
37Welding/Tightening the top cover after tanking of core and coil assembly into painted tank and tightening of assembly into the tank and fitting all accessories of transformer and filling of oil.
3810 KVA
3916 KVA
40Spray painting of transformer tank from outside with supper enamel synthetic Grey paint in two coats after providing primer of red oxide paint
4110 KVA
4216 KVA
43Dragging/shifting of repaired T/F near to the test cabin/testing place and dragging /shifting T/F to yard after testing and its stacking at identified place.
4410 KVA
4516 KVA
46Punching and welding of M.S. plate of 100x50x3mm size on the outside of T/F containing following information.(I) Job number, (II) Capacity (III) Name of workshop (IV) Date of repair
4710 KVA
4816 KVA
49Package rate per transformer of supply item to be provided by the Contractor for repairing of transformer. Details of supply items are annexed hereto.
5010 KVA
5116 KVA