| 1 | EI Works Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.(a) Group C |
| 2 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 3 | (b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 4 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(a) 25 mm |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing6 pin 15/16 & 5/6 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 7 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required.(a) 100 mm X 100 mm X 60 mm deep |
| 8 | (b) 180 mm X 100 mm X 60 mm deep |
| 9 | (c) 200 mm X 250 mm X 60 mm deep |
| 10 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.(a) 1 or 2 Module (75 mmX75 mm) |
| 11 | (b) 3 Module (100 mmX75 mm |
| 12 | (c) 6 Module (200 mmX75 mm) |
| 13 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(a) 8 way (4 + 24), Double door |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) Single pole |
| 15 | Supplying, installation, testing & commissioning of stains steel panel pedestal type with G.I. cabinet storage type Water Cooler 150/150 Ltr. Capacity, fully Stainless Steel suitable for operation on 230V + 10% 50 Hz single phase AC supply includingmaking water line & electrical connection etc. as reqd. |
| 16 | Supplying, installation, testing & commissioning of Reverse Osmosis Purifier 50LPH basic on line complete i/c plumbing work etc. as reqd. as per following specification:-(a) Dimension (WXDXH) : 460X250X790(b) Input Power rating : 230V AC,50Hz(c) Production Capacity : 50LPH(d) RO Membrane : 80GPD X 4Nos(e) Power Consumption : 120W(f) Weight in KG : 45(g) % of Rejection in TDS : 90% (Approx) |
| 17 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 18 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 19 | Supplying and laying of following size \"B\" class heavy duty G.I. pipe conforming to IS : 1239 including associate fittings such as bend, socket/coupler complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.(a) 150 mm dia |
| 20 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.(a) Above 95 sq. mm and upto 185 sq. mm |
| 21 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.(a) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/ 40x3mm MS flat clamp) |
| 22 | Providing and fixing of 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 23 | AC Works Supplying, installation, testing & commissioning of 1.5 TR capacity Window Type Air-Conditioner unit of 5 star rating, certified by BEE complete with condenser coil, evaporating coil (copper coil), filtering and dehumidifying, suitable for operation on 220V, 50Hz, single phase AC supply i/c accessories, wooden work, repairing of wall/window with minor civil work etc. complete as required. |
| 24 | Supplying, installation, testing & commissioning of High Wall Split Air Conditioner of Invertor Type of capacity not less than 1.5TR complete with outdoor condensing unit & wall mounted evaporating unit having cordless remote control and Copper refrigerant pipe (upto 4 Meters length), capable of filtering, cooling, dehumidifying and suitable for operation on Eco-friendly gas (R407/R410/R32), single phase, 230Volts, AC supply (5 star rating model, as certified by BEE) including mounting/ fitting of Indoor/ outdoor units, insulation the suction & discharge pipe with EPF tubing, charging of refrigerant, providing of electrical connections, interconnections with suitable size cable and providing of drain pipe etc. complete as required at site. |
| 25 | Supplying, installation, testing & commissioning of 2.0TR High Wall Split Air Conditioner of 3 Star, Non-Invertor Type complete with outdoor condensing unit & wall mounted evaporating unit having cordless remote control and Copper refrigerant pipe (upto 4 Meters length), capable of filtering, cooling, dehumidifying and suitable for operation on Eco-friendly gas (R407/R410/R32), single phase, 230Volts, AC supply including mounting/ fitting of Indoor/ outdoor units, insulation the suction & discharge pipe with EPF tubing, charging of refrigerant, providing of electrical connections, interconnections with suitable size cable and providing of drain pipe etc. complete as required at site. |
| 26 | Supplying, installation, testing and commissioning of 5 KVA, copper wounded, wall mounted voltage stabilizer with LED display, surge indicator, automatic reset suitable for 1.5/2.0 TR AC unit complete etc. as required. |
| 27 | Providing and fixing of M.S. outdoor, floor/ wall mounting powder coated stand suitable for 1.5/2.0 Ton capacity split type A.C. outdoor unit complete as reqd. |
| 28 | Providing & laying of refrigerant copper piping of size (5/8” & 1/4” dia) with nylon/foam type insullation, clamp and accessories from indoor unit to outdoor unit of split type AC dully complete as required. |
| 29 | Providing & fixing of PVC drain pipe of size 25 mm dia medium gauge drain pipe with necessary fitting such as nipple, reducer, clamp on surface / recess i/c cutting the wall and making good the same complete as required. |
| 30 | Supplying and fixing of 3 core, 2.5 sq.mm PVC round sheathed multicore flexible copper cable on surface connecting indoor unit to outdoor unit i/c connection, testing & commissioning etc. as required. |
| 31 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 32 | Boom Barrier WorksSupplying, installation, testing & commissioning of electromechanical swing type Barrier Gate of Length 3 Mtr. to 6 Mtr. with following important features:(a) Opening and closing time - 3 Sec. to 5 Sec. adjustable at site as per requirement(b) DC Brushless Motor for smooth and reliable operation(c) 100% DUTY cycle (d) Amperomatic Device to Auto-Reverse Barrier in case of coming in contact with any Vehicle/ Person/ Obstruction(e) Manual Operation in case of power failure(f) Dual Channel Loop Detector provision(g) Barrier Arm of Extruded Aluminum with red reflecting tapes in length(h) 1 Year Defect Liability Period(i) Freight delivery at actual site of execution |
| 33 | Supplying, installation, testing & commissioning of safety IR Photo sensors to prevent boom/arm to fall on anybody (vehicle or human) under it etc. complete as required. |
| 34 | Supplying, installation, testing & commissioning of 3 way opening switch controller complete as required. |
| 35 | Providing and laying high grade concrete cement in foundation construction of minimum size of 400mm x 400mm x 400mm including trench work for mains cable and control cable ducting etc. complete as required. |
| 36 | Supplying and laying of 3 x 2.5 sq.mm XLPE insulated & PVC sheathed copper conductor unarmored power cable of 1.1 KV grade on surface etc. as required. |
| 37 | Less for credit of following old dismantle items etc. complete as required.(a) 1.5/2.0 TR Window AC |
| 38 | (b) 1.5/2.0 TR Split AC |
| 39 | (c) 1.5/2.0 TR Indoor Unit |