Tender For Computational Biology Centre And Cross-Talk Lab On Turnkey Basis At Actrec, kharghar-Maharashtra

Tata Memorial Centre has published Tender For Computational Biology Centre And Cross-Talk Lab On Turnkey Basis At Actrec. Submission Date for this Tender is 17-01-2023. Coats and Jackets Tenders in kharghar Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

34260320
Corrigendum : Tender For Computational Biology Centre And Cross-Talk Lab On Turnkey Basis At Actrec
Open Tender
Indian
Maharashtra
kharghar
17-01-2023

Tender Details

Computational Biology Centre And Cross-Talk Lab On Turnkey Basis At Actrec Engineering, Procurement Supply, Installation, Testing And Commissioning Of Computational Biology Centre And Cross Talk Lab On Turnkey Basis At Actrec , Part – A: Core Infrastructure , Civil , Demolishing Existing Brick Masonry With Cement Mortar And Plaster At All Floors And Levels Including Scaffolding Stacking Of Serviceable Materials Without Damaging The Adjacent Masonry / Rcc Structure Sanitary Fittings & Fixtures And Disposal Of Unserviceable Material Carting Away The Debris Out Of Hospital Premises And Scope Also Include Dismantling And Careful Removal Of Doors, Distribution Panel And Storing And Stacking Complete All As Directed By The Engineer-In-Charge. ( Existing Toilets, Guard Room & Record Room & Ground Floor & All Areas Wherever Required For Hpc Facility ) , Dismantling Of Wash Basin And Removing Of Wall Tiles And All The Allied Stonework And Pipes & Fittings Wherever Necessary And Disposal Of Unserviceable Material Carting Away The Debris Out Of Hospital Premises Or Handing Over The Same To Engineer-In Charge , Flooring Breaking: Dismantling Carefully The Existing Damaged Cracked Serviceable Tiles / Slabs / Clay Tiles / Marble Slab / Granite Slab / Kota Stone / Tandoor Stone / Shahabad Stone And All Types Of Flooring In Flooring Etc. Including Removing The 20Mm Thick Bedding Of Cement Mortar Stone Grit Or Brick Bat Coba Etc. At All Floors & Levels Including Stacking Of Serviceable Material And Disposing Unserviceable Material Out Of Hospital Premises As Directed By The Engineer-In-Charge. , Dismantling And Removal Of Complete Fire Fighting System And Handing Over All The Material ( Without Any Damage ) Anywhere Within The Campus As Per The Instructions Of Engineer In Charge. This Includes Plant, Machinery, Equipment For Cutting, Welding And Dismantling Complete Material Safely. , Demolishing Cement Concrete And Bitumen Road / Kerb Stone Manually / By Mechanical Means Including Disposal Of Material Within 50 Metres Lead As Per Direction Of Engineer - In - Charge. , Providing And Fixing 12 Mm Thick Frameless Toughened Glass Door Shutter Of Approved Brand And Manufacture, Including Providing And Fixing Top & Bottom Pivot & Floor Spring Type Fixing Arrangement And Making Necessary Holes Etc. For Fixing Required Door Fittings, All Complete As Per Direction Of Engineer-In-Charge ( Door Handle Size 600Mm Center To Center, Lock And Stopper Etc. Included In The Item Rate ) . Anyquality Approved By Engineer Incharge Based On Sample. , Providing And Fixing Of Hollow Metal Un-Insulated Fire Rated Doorsas Per Is 3614 Part-1, For Stability And Integrity. Pressed Galvanized Steel Confirming To Is 277 With The Following Specification. Recommended Fire Door Shall Be Tested To Is 3614 Part 2 / Iso 834-1 Part 1 / Bs476 Part 20 & 22, Cbri / Certifire Or Third Party Certified Or Equivavelent Lab, For Maximum Rating Of 120Mins, .Labeled Doors With Certification Shall Be With Vision Glass As A Part Of Complete Assembly. Deviation In Specification And Sheet Thickness Other Than What Is Mentioned In The Test Certificates Are Not Allowed. Proper Label Confirming The Type Of Door And The Hourly Rating Is Mandatory. Door Frame Shall Be Single Rebate Grooved Profile Of Size125 X 60Mm Made Out Of 1.60Mm ( 16Gauge ) Minimum Thick Galvanized Steel Sheet. Frames Shall Be Mitered And Field Assembled With Self Tabs.Door Frames Should Be Prepared For Suitable Hardware And Should Have Necessary Reinforcement To Withstand Regular Wear And Tear.Frames To Have Inbuild Grooved Sealing System And Shall Be Site Fitted With Fire Rated Epdm Gasket As Standard. All Provision Should Be Mortised, Drilled And Tapped For Receiving Appropriate Hardware. Door Leaf Shall Be 46Mm Thick Fully Flush Double Skin Door, Un-Insulated With Vision Lite. Door Leaf Shall Be Manufactured From 1.2Mm ( 18Guage ) Minimum Thick Galvanised Steel Sheet. The Internal Construction Of The Door Should Be Rigid Reinforcement Pads For Receiving Appropriate Hardware. The Edges Should Be Interlocked With A Bending Radius Of 1.4Mm. For Pair Of Doors Integrated Astragals Has To Be Provided On The Meeting Stile For Both Active And Inactive Leaf. Vision Lite Wherever Applicable Should Be Provided As Per Manufacturers Recommendation With A Clipon Arrangement. The Glass Should Be 6Mm Clear Borosilicate Fire Rated Glass Of Relavant Rating Of The Door.All Doors And Frames Shall Be Finished Powder Coated And Shall Have Passed Minimum 500 Hours Of Salt Sprey Test. Rate Shall Include Supply And Installation Of Door And Hardware As A Complete Assembly Including Door Closure, Hinges Etc..All Doors Shall Be Provided With Stainless Steel Hinges With Concealed Door Closures Of Required Capacity And Rating. Provision Of Access Control Interlock And Wiring Shall Be Made In All Door Shutters And Frames With Requisite Hardware. Rate Excludes Installation Of Panic Bar. , Supply And Fixing Of Slim Glass Partition Of 12Mm Toughened Glass Using System-45 Frames To A Height Of Maximum 3M Or As Per Drawing.The Fixed Glass To Be Fixed Usingbp45 Profiles At Top & Bottom &Sp45 At Sides ( The Profile Is For Reference ) . The Profile Size To Be 45X25mm To Be Fixed On To The Floor / Wall / Ceiling As Per The Architect Design.H Junction Profile To Be Used At All Glass To Glass Vertical Joints, 90 Deg L Junction Profiles And T Junction Profiles Necessary As Per Design.In Case Of Glass Overall Panel Mp45 & Bp45 Overpanel Profile To Be Used.In Case Of Open Glass Edges Ep45 End Profile To Be Used. The Alexa Profiles Shall Be Suitable For Glass Thickness Of 10 / 12 / 13.52Mm.The Profile Shall Be 20 Micron Matt Natural Anodized, The Profile Manufacturer To Supply All The Necessary Clips, Seals And Fixing Accessories For The System. All Profiles To Be With 2 Mm Gauge Thickness Including 20 Micron Of Anodizing. , Supply & Installation Of 2 Hrs Fire Resistance Rated - Fm Approved - Sandwiched Wall Panels With 0.80 Mm Skin Thickness With Overall Thickness Of 150Mm And With 98 +-2Kg / Cu.M Density Of Rockwool Insulation. Both Sides Gi Powder Coated Sheet As Per Clients Approved Shade Along With Flashing And With Water Resistant Silicon Sealant At Required Area And Providing Necessary Accessories For Fixing Of Metal Partitions As Per Drawings With Gi Profile For Reinforcement. ( Inclusive Of Bottom Track / Interlock Sections / Silicon ) ( Certificate For Fire Rating To Be Provided ) . Vision Glass On All Sides For Direct Observation Of Hpc From Outside Should Be Compatible With Partition And In Fire Rating And With Maximum Dimension Of 1M*1M. With Porcelain Finish Having Rewritable Capabilites And Printing Work To Be Done Wherever Required As Per The Instruction Of Engineer In Charge. One Side Measurement Will Be Taken. Anyquality Approved By Engineer Incharge Based On Sample. , Supply & Installation Of 2 Hrs Fire Resistance Rated - Fm Approved - Sandwiched Wall Panels With 0.80 Mm Skin Thickness With Overall Thickness Of 50Mm And With 98 +-2Kg / Cu.M Density Of Rockwool Insulation Or 40+-2Kg / Cum Puf Insulation . Both Sides Gi Powder Coated Sheet As Per Clients Approved Shade Along With Flashing And With Water Resistant Silicon Sealant At Required Area And Providing Necessary Accessories For Fixing Of Metal Partitions As Per Drawings With Gi Profile For Reinforcement. ( Certificate For Fire Rating To Be Provided ) As Per The Instruction Of Engineer In Charge. One Side Measurement Will Be Taken. , Supply & Installation Of 80Mm Thick Sliding Folding Partition With Aluminium Frame, Track And Trolley And 1Mm Thick Hard Pressed Laminate Finish Of Approved Shade On Both Sides In The Middle Of Conference Room Including All The Hardware, Accessories And Rotating And Retracting Mechanism Required As Per The Instruction Of Engineer In Charge Complete. One Side Measurement Will Be Taken. , Toughened Lacquered Glass Panelling: Providing And Fixing Of 6Mm Thick Toughened Glass ( Premium Griha Rated Lacquered Glass From Glass Manufacturer ) Of Approved Colour By Doit&C, Mounted On Clip ( J / J1 / I Type ) Or Equivalent On A Perfectly Levelled Surface ( 12Mm Thick Water Proof Marine Plywood / Acc Blockwork / Aluminium Channel / Bare Rcc Wall Surface ) . Lacquered Strong Glass Must Be Made Industrially ( Via Curtain Coating Process ) ; Opaque ( If Viewed Against A Support Wall ) , Coated With Pu Lacquer ( 100 Micron Thick ) ; Colour Consistency ( Measured By Spectrophotometer Cm5081 ) ; Highly Durable ( Passes Persoz Hardness Test For Minimum 220 Oscillations ) ; Humid Resistant ( Conforms To Bs En 1036 1999 ) ; Environmentally Friendly ( No Lead, No Arsenic, No Copper, No Formaldehyde ) ; Appropriate Recycled Content ( 12% Post Industrial / 6% Post Consumer ) ; Compressive Strength ( 1000 Mpa ) & Tensile Strength ( 40 Mpa ) , Same As Float Glass. Tempering Should Be Done As The En 12150. Glasses Are To Be Fixed With Polymer Clips ( Single Sided J1 & J2 Type, Double Sided I Type ) , White Backing Foam And Grey Impact Absorbing Foam; To Accommodate Upto ± 10Mm Substrate Undulation, And With A Horizontal Load Capacity Of 30Kg / 100Mm And Vertical Pullout Load > 200Kg / 100Mm, Glass Should Be Supported With 1Mm Thick Lip Covering Upto 3Mm Of Glass Surface; Clips Should Be Fixed Using Durable, Non Corrosive, Strong S.S.Screw 45Mm Long. All Wooden Material To Be Used Shall Be Anti-Termite Treated. The Measurement Only For The Portion Covered By Glass To Be Considered. , Providing And Fixing Fabric Backing Commercial Grade Wall Paper Of Approved Shade With Recommended Adhesive Of Approved Quality Which Have 100% Washable, Scratch Resistance, Peel Proof, And Fire Retardant Properties. The Wall Paper Should Give A Seamless Finish. Including Cost Of Preparation On The Base Surface For Fixing The Wall Paper As Per The Manufacturer Specification, Complete In All Respect As Per Direction Of Eic. , Supply & Installation Of 80Mm Thick Insulated Metal Partition Cladded With Fabric And Insulated With Glasswool / Rockwool For Sound Insulation. The Partition Should Have Provision For Modular Electrical And Plumbing Fittings As Per The Site Conditions. Skin Thickness - 0.6 To 0.8Mm. Finish : Powder Coated. Face Of Partition : Interior Face: G-90 Galvanized Or Az-50 Aluminum-Zinc Coated Steel In 26, 24 And 22 Ga. , Supply & Installation Of 80Mm Thick Insulated Metal Partition Cladded With Fabric ( Towards Conference Room ) , On The Other Side Clad With Marine Mdf. Insulated With Glasswool / Rockwool For Sound Insulation. The Partition Should Have Provision For Modular Electrical And Plumbing Fittings As Per The Site Conditions. Skin Thickness - 0.6 To 0.8Mm. Finish : Powder Coated. Face Of Partition : Interior Face: G-90 Galvanized Or Az-50 Aluminum-Zinc Coated Steel In 26, 24 And 22 Ga. , Providing And Fixing Flush Doors 35Mm Thick With 1.0 Mm Laminates On Both Sides. The Item Includes Teakwood Chaukhat ( Frame ) Made From 75X50 Teakwood. The Door To Have 12Mm Teak Wood Lipping On Edges. The Door Is To Be Complete With Cylindrical Door Lock , 200Mm Ss / Brass Handles, Tower Bolts, 119Mm Brass / Ss Hinges, Ss Door Stopper With Double Rubber Stopper And Necessary Screws Etc. All Teakwood Surfaces To Be Malamine Polished Complete To The Satisfaction Of Architect / Employer. Cost To Include All Edgings And Vision Panel Of Size 250Mm*150Mm. , Providing&Fixing 50Mm Thick Bwpgradesingle Leaf Flushdoorofsize ( 1200 X2400 ) Includingteakwood Lippingpatti12x55mmtoachieveexposedperiphery Section Of Flush Door Finished With4mmthick Veneer Outside & Inside 1 Mm Thick Laminate With Suitable Mounting Door Frame As Required. Allwood& Veneer Surfaces Shall Be Finished With Melamine Polish As Per Approvedtint Includingmoulding, Nails, Screws, Fevicol Including Necessary Scaffolding & Cleaning As Per Architects Detailed Drawing & Design Etc. Complete. The Door Is To Be Complete With Cylindrical Door Lock, 200Mm Ss / Brass Handles, Tower Bolts, 119Mm Brass / Ss Hinges, Ss Door Stopper With Double Rubber Stopper And Necessary Screws Etc. All Teakwood Surfaces To Be Malamine Polished Complete To The Satisfaction Of Architect / Employer. Cost To Include All Edgings And Vision Panel Of Size 250Mm*150Mm. ( D1 ) , Providing And Fixing Panic Bar / Latch ( Double Point ) Fitted With A Single Body, Trim Latch & Lock On Back Side Of The Panic Latch Of Reputed Brand And Manufacture To Be Approved By The Engineer- In- Charge, All Complete. , Providing And Constructingaac Light Weight Block Masonry With 75Mm / 100Mm / 150Mm / 200Mm / 300Mm Thick At All Levels In By Using Approved Block Laying Polymer Modified Adhesive Mortar, Including 75Mm Thick Patli / Stiffeners Of M-15 Gradeat Every 1000Mm With 2 Nos 8Mm Steel Bars All To Be Considered In The Cost And No Separate Measurement Will Be Done For Steel And Patli, Also Including Scaffolding, Racking Out Joints, Curing With Curing Compound Etc. In Line, Level And Plumb, All Complete As Per Specification For All Height Of Floor Or As Directed Etc. ( Rate Includes The Cost Of Stiffeners Hoop ) . ( No Holes For Scaffolding Will Be Permitted Into The Blockwork ) , Grproc Plaster : Providing Andapplying 1Stqualitygyprocplaster ( Gyproc Elite -90 ) Including Bonding Coat Of Gyproc Bondwith Minimum 10-12Mm Thickness To Internal Brick / Block / Concrete Walls At All Position In Proper Line, Level And Plumb Including Scaffolding, Cleaning, Hackingofconcretesurface, Removing Debris Out Of Site Etc. Complete. As Directed To Achieve Perfect Line Level And Plumb. , Providing And Applying Plaster Of Paris Putty Of 2 Mm Thickness Over Plastered Surface To Prepare The Surface Even And Smooth Complete. , Providing And Applyingacrylic ( Premium ) Emulsion Paint Of Approved Qualityandshadeonwallswithsand Papering& Cleaning The Surface, Applying One Coat Of Primer And Lambi / Puttytofullsurface3times, Thereafterpaintingthe Surfaceintwo Coatsoverbaseprimercoattoachieveeven Finish. Rate Is Inclusive Of All Double Scaffolding, All Material And Cleaning As Per Manufactures Standard Application Method & Specification Etc. Complete. , Providing And Fixing Artificial Grass With Recommended Adhesive Of Approved Quality Which Have 100% Washable, Peel Proof, And Fire Retardant Properties. The Grass Should Give A Seamless Finish. Including Cost Of Preparation On The Base Surface For Fixing The Grassas Per The Manufacturer Specification, Complete In All Respect As Per Direction Of Eic. , Providing And Installing Of 8Mm Thk Brick Claddingas Per The Manufacturer Specification In Approved Pattern With Backing Coat Of 1:4 Cement Plaster And Neatcementfloatusingpolymerbasedtileadhesivesof Approved Quality Including Filling Joints, Complete In All Respect As Per Direction Of Eic. , Providing And Laying 600 X 600 Vitrified Tiles As Specifiedbelowconformingtoi.S.15622-2006Withwater Absorptionlessthan0.08%Forflooring And Skirting Ofanapproved, Quality, And Pattern / Design For Flooring Including Cementmortarbeddingof25mmthickin1:4Proportion, Cutting, Levelling, Jointing, Fillingthejointsby App Colour , Curing, Finishing Etc. Complete As Directed By Engineer In Charge.As Per Manufacturers Specifications. , Providing And Laying 800 X 800 Vitrified Tiles As Specifiedbelowconformingtoi.S.15622-2006Withwater Absorptionlessthan0.08%Forflooring And Skirting Ofanapproved, Quality, And Pattern / Design For Flooring Including Cementmortarbeddingof25mmthickin1:4Proportion, Cutting, Levelling, Jointing, Fillingthejointsby App Colour , Curing, Finishing Etc. Complete As Directed By Engineer In Charge.As Per Manufacturers Specifications. , Providing And Layingoutdoorvitrifiedtiles600mmx600mmas Specifiedbelowconformingtoi.S.15622-2006Withwater Absorptionlessthan0.08%Forflooring And Skirtingofanapproved, Quality, And Pattern / Design For Flooring And Skirtingincluding Cementmortarbeddingof25mmthickin1:4Proportion, Cutting, Levelling, Jointing, Fillingthejointsby App Colour , Curing, Finishing Etc. Complete As Directed By Engineer In Charge. , Providing And Layinglapato Finish Vitrified Tiles 600Mm X 600Mmas Specifiedbelowconformingtoi.S.15622-2006Withwater Absorptionlessthan0.08%Forflooringand Skirting Ofanapproved, ` And Pattern / Design For Flooring And Skirting Including Cementmortarbeddingof25mmthickin1:4Proportion, Cutting, Levelling, Jointing, Fillingthejointsby App Colour , Curing, Finishing Etc. Complete As Directed By Engineer In Charge. , Providing And Fixing 1St Quality Antiskidceramic Floortile Size 300X300 Mm Or More ( Thickness To Be Specified By The Manufacturer ) For Flooring And Skirting Confirming To Is : 13755 And Is : 15622 Colour Such As White, Grey, Ivory, Fume Red Brown, Light Green, Light Blue And Other Light Shades In Floors, Steps, Pillars Etc. Laid On A Bed Of Neat Cement Slurry Finished With Flush Pointing In The White Cement Mixed With Pigment To Match The Shade Of The Tile Complete ( Including The Cost Of Cement Mortar Bed 1:4 ) . , Providing And Laying Machine Cut, Mirror Polished Approved Coloured Granite Slab Of Any Approved Size 20 + / -2Mm Thick For Flooring In Required Pattern With Approved Coloured Granite Inlay Work On A Bed Of 1:4 Cement Mortar Including Neat Cement Float, Filling Joints With Neat Coloured Cement Slurry, To Match The Colour Of Granite, Curing, Polishing And Cleaning Complete. , Providing And Laying Machine Cut, Mirror Polished Marble Stone Flooring And Skirting, In Required Design ( Simple Geometrical, Abstract Etc. ) And In Patterns In Combination With Italian Marble Stones Of Different Colours, Shades And Finished Surface Texture Etc., In Linear Portions Of The Building, All Complete As Per The Architectural Drawings, With 18 Mm Thick Stone Slab Laid Over 20 Mm ( Average ) Thick Base Of Cement Mortar 1:4 ( 1 Cement : 4 Coarse Sand ) Laid And Jointed With White Cement Slurry @ 4.4 Kg / Sqm Including Pointing With White Cement Slurry Admixed With Pigment To Match The Marble Shade Including Rubbing, Curing And Polishing Etc. All Complete As Specified And As Directed By The Engineer-In-Charge. In Combination With 18 Mm Thick Italian Marble Stone Slab, Perlato, Rosso Verona, Fire Red Or Dark Emperadore Etc Is To Be Included. , Providing And Fixing Machine Made Synthetic Carpet Having Total Carpet Weight More Than 550 Gm / Sqm. And More Than 5Mm Thickness Superior Quality Complete In All Respect As Per Direction Of Engineer-In-Charge. ( Euronics Or Equivalent Quality Preapproved By Engineer Incharge ) , Providing And Laying Machine Cut, River Finish Graniteof Anyapprovedsize20+ / -2Mm Thick For Flooringin Required Patternwithapprovedcolouredgraniteona 20Mm Thick Bedof1:4 Cement Mortar Including Neat Cement Float, Filling Joints With Neatcolouredcementslurry, Tomatchthe Colourof Granite, Curing, Polishingandcleaningcomplete. , Providing & Laying Ofimported Engineered Wooden Flooringofsize 215 Mm Width Xlength 2200 Mm X 20 - 25 Mm Thick ( As Per Manufacturers Specifications ) , Asperiso24346 ( En428 ) Texture&Design, Top Wear Layer Thickness 3.5 Mm, With 3 Mm Under Lay Of Foam With A Direct Laminated Surface Treated With Aluminium Oxide On Top Ofa High-Density Fibre Board With A Density Of 850 Kg. / Per Mtr. Having A Click System Tongue And Groove Joint To Secure A Long Lasting Joint. The Planks Are To Be Termite Resistant And Water Protected With Both Side Lamination, Withpremiumfinish Plank, Glue Freelocking System;2Lock, With Maximum Floor Surfacetemperature 27 C, With Self –Regulating Under Float Heat System, With Formaldehyde Emission E1 As Per En 13986, Reaction To Fire Dfl As Per En 13501 And100% Recyclable With Mini-Or Maxi Bevel Lengthwise Etc. Complete. ( Offices & Conference Room ) , Kota Stone Slab Flooring 25 Mm Thick Over 20 Mm ( Average ) Thickbase Laid Over And Jointed With Grey Cement Slurry Mixed With Pigment To Match The Shade Of The Slab Including Rubbing And Polishing Completewith Base Of Cement Mortar 1 : 4 ( 1 Cement : 4 Coarse Sand ) , Providing & Fixing 12Mm Thick X 100 Mm Highfirst Quality Solid Teakwoodskirtingwherever Necessary Including Melamine Polish Shade To Be Match With The Same Matching Shadeofwoodenflooring &Withveneershadetoallwood Surfaceswith 6Mm Groove Between Skirting & Gyp / Veneer To T.W.Frameworkort.W.Panellingasperarchitectsdetail Drawing & Design Etc. Complete. , Providingandfixingmachinecutmirrorpolishedblue Pearlgranitestoneslabofrequiredsizeand20mm Thick Of Approved Quality , Vein And Colour For Dado Fixed On Base Plaster On 20Mm Thick Cement Mortar 1:4 Including Filling Joint With Neatcolouredcementslurry, Curing, Handpolishing, Moulding, Edgefinishing, Andcleaningetc.Complete. , Providing&Fixingvitrifiedtilesfortoiletdado Of Size 600X600 As Per Manufacturers Specificationanyothersuitablesize Approvedby Architect Andofapprovedcolourandshade Finished, In Approved Pattern With 12Mm Thick Backing Coat Of 1:4 Cement Plaster / Mortar And Neatcementfloatusingpolymerbasedtileadhesivesof Approved Quality Including Filling Jointsto Match The Colour Of Dado Curing, Acid Cleaning Etc. Complete. For Toilet , Italian Marble Cladding Providing And Fixing Machine Cut And Mirror Polished Approved Coloured Italian Marbleslabwithinlaysofapprovedsize, 20Mm+2Mm Thk. Of Approved Quality For Required Pattern On A Bed Of 1:4 Cm25mmaveragethicknessincludingneatcement Float, Filling Joints With Neat Coloured Pigment , Curing, Polishingandcleaning, Highglosstinoxidepolishwith Italianpolishmachineetc. Complete. , Providingand Constructinggranite Kitchen Platformwith Fixing Of Quartz Sink 600 Mm X 450 Mm Size As Per Detailed Drawing Includingverticalbothsidepolishedgranite Stone 19 To 22 Mm Thick Double Supports With Kadappah Base 35 To 40 Mm Thick And Polished Granite19 To 22Mm Ontop With Side Strips Of Granite At Front And Both Sides Of Platform Raised With Two Vertical Granite Supportsincluding Cutting, Opening Asperarchitectsdetailsdrawing Anddesign Asdirectedby Engineer In Charge. For Sink Of Required Size In Graniteetc. Complete. ( Rateexcludesquartzsink But Includes Rate For Kadappah ) .Only Total Surface ( Plan ) Area Of Platform To Be Measured , Supply Of Quartz Sink 600Mm X 450 Mm Size Including Fixing The Sink In Position With Waste Coupling, Bottle Trap And Any Other Fixtures All Complete As Per The Specifications And Directed By Engineer-In Charge. , Providing & Fixing Single Piece Rimless Bowl For Coupled Wc With Uf Soft Close Slim Seat Cover, Hinges, Fixing Accessories And Accessories Set, Size : 380X660x850 Mm, S Trap - 250 Mm. As Per Approved Sample. , Providing & Fixing Soap Dispenser Metallic Bottle. As Per Approved Sample. , P&F Soap Dish Holder.As Per Approved Sample. , Providing & Fixing Toilet Paper Holder With Flap Recessed Type ( Stainless Steel ) . , P&F Stainless Steel Surface Mounted Sanitary Napkin Disposal ( With Flap ) Of Approved Quality / Quality. Cabinet - 18-8, Type-304, Stainless Steel Size 270Mm ( L ) X 105Mm ( W ) X 385Mm ( D ) Capacity:- 4.6 Litres Equipped With Full-Length Stainless Steel Piano Flap. As Per Approved Sample. , Paper Towel Dispenser. Cabinet - 18-8, Type-304, Size 265X90x365 Stainless Steel Finish: Stainless Steel Satin Capacity: 450 C-Fold, 600 Multifold. As Per Approved Sample. , P & F Stainless Steel Hand Dryer Of Approved Quality / Quality. Casing:Stainless Steel # 304 Non Magnetic, Matt Finish Mounting :Wall Mounted Operation :Touch-Free Infra-Red Activation Sensor Range : 12 Cm - 15 Cm Hand Dry Time :Less Than 20 Secs Auto Cutoff: 30 Seconds Motor:Brush Type, Dual Ball Bearings Speed:25, 000 Rpm Rated Power :550 W ( No Heating Element ) Current:2.5 A Protection Class :Ip X 1 Blowing Volume : > 270 M3 / H Air Speed:95 M / S ( With Speed Controller ) As Per Approved Sample. , Modular Cubicle Based Restrooms Of Stainless Steel Make With Stainless Steel Hardware With Locking Arrangement And 1 Spare Lock Each.Handles And Hinges To Be Included In The Rate. Measurement Per Cubicle. , P & F 1St Quality Wvc Urinal ( Is:2556 Mark ) With 25Mm Dia G.I. Waste Pipe, Dome Waste Couplings, Concealed Iron Brackets Or Screws Etc. Complete. As Per Approved Sample. , P & F 12Mm Thick Toughened Glass Urinal Partition With All Type Fitting. ( Partition Size 300Mm X 1050 ) . As Per Approved Sample. , P&F Bevelled Edge Mirror / Mirror With 25Mm Width Teak Wood Lipping Including Melamine Polish Around Of Special Glass Of Approved Quality As Per Direction Of Engineer-In-Charge Complete With 6Mm Thick Commercial Ply Basefixed To Wooden Screws & Washers. ( Size 600 X 450Mm X 4 Mm Thick ) , False Flooring-Providing And Fixing Cementitious Access Floor Systems Of Preferred / Standard Quality Confirming To En12825 Or Equivalent Standards. The Access Floor System To Be Installed Shall Be Of Finished Floor Height Of 450 Mm From The Existing Floor Level Comprising Of 600Mm X 600Mm Cementitious Square Panels. The System Will Provide For Suitable Pedestal And Under-Structure Designed To Withstand Various Static Loads And Rolling Loads Subjected To It In Server / Rack Area. The Entire Access Floor System Will Provide For Adequate Fire Resistance, Acoustic Barrier And Air Leakage Resistance. At Least 4 Nos. Of Lifting Suction Devices To Be Provided. The Raised Floor Must Be Capable Of Withstanding A Uniform Distribution Load Of 1500Kg / Sq. Mtr As Per Specification.-It Room ( A4 Server ) , It Room ( A2 & A3 Server ) & Power Room , Structural Steel Work In Single Section, Fixed With Or Without Connecting Plate, Including Cutting, Hoisting, Fixing In Position And Applying A Priming Coat And Two Coats Of Acrylic Paint Of Approved Quality For Primer And Paint All Complete. , Plain Cement Concrete M15 Grade Using Graced Stone Aggregate Of 20Mm / 40Mm Max. Size Including Consolidation Using Vibrator & Needle If Required Finishing, Curing, Form Work Shuttering, Centering Etc. Complete All As Per Specification And In Quantity As & When Required By The Engineer-In-Charge, , Hexagon Shape Ceiling Made Out Of Folded Aluminium. The Hexagon Shapeunits Shall Be In 6 Sides Customise Size Of Each Side 750Mm And 1Mm ( Thick ) , Non-Perforated Aluminium. The Ceiling Hexagon Units Shall Be Installed At Distance Of 300Mm One Hexagon To Second Hexagon. The Hexagon Units Are Then Attached To Baffle Ceiling ( Included In Scope Of This Item ) By Slotted Cleats And Screwing Arrangement Alongwith Bolted Brackets Attached To Ceiling By Baffle Splice And Carrier Splice Combination With Hangers And Screw Bolting To Ceiling Which Is Included In The Scope. , Providing And Fixing Tiled False Ceiling Of Approved Materials Of Size 595X595 Mm In True Horizontal Level, Suspended On Inter Locking Metal Grid Of Hot Dipped Galvanized Steel Sections ( Galvanized @ 120 Grams / Sqm, Both Side Inclusive ) Consisting Of Main “T” Runner With Suitably Spaced Joints To Get Required Length And Of Size 24X38 Mm Made From 0.30 Mm Thick ( Minimum ) Sheet, Spaced At 1200 Mm Center To Center And Cross “T” Of Size 24X25 Mm Made Of 0.30 Mm Thick ( Minimum ) Sheet, 1200 Mm Long Spaced Between Main “T” At 600 Mm Center To Center To Form A Grid Of 1200X600 Mm And Secondary Cross “T” Of Length 600 Mm And Size 24X25 Mm Made Of 0.30 Mm Thick ( Minimum ) Sheet To Be Interlocked At Middle Of The 1200X600 Mm Panel To Form Grids Of 600X600 Mm And Wall Angle Of Size 24X24x0.3 Mm And Laying False Ceiling Tiles Of Approved Texture In The Grid Including, Required Cutting / Making, Opening For Services Like Diffusers, Grills, Light Fittings, Fixtures, Smoke Detectors Etc. Main “T” Runners To Be Suspended From Ceiling Using Gi Slotted Cleats Of Size 27 X 37 X 25 X1.6 Mm Fixed To Ceiling With 12.5 Mm Dia And 50 Mm Long Dash Fasteners, 4 Mm Gi Adjustable Rods With Galvanised Butterfly Level Clips Of Size 85 X 30 X 0.8 Mm Spaced At 1200 Mm Center To Center Along Main T, Bottom Exposed Width Of 24 Mm Of All T-Sections Shall Be Pre-Painted With Polyester Paint, All Complete For All Heights As Per Specifications, Drawings And As Directed By Engineer-In-Charge.Gi Metal Ceiling Lay In Plain Tegular Edge Global White Colour Tiles Of Size 595X595 Mm, And 0.5 Mm Thick With 8 Mm Drop; Made Of Aluminium Sheet Having Electro Statically Polyester Powder Coated Of Thickness 60 Microns ( Minimum ) , Including Factory Painted After Bending. , Providing & Supplying Stainless Steelss 202And Aboveperforated Type Cylindricaldustbinof230mmdia&400Mmheightas Approved By Consultant. . , Providingandapplyingthreecoatsofmelaminepolishof Requiredfinishtowoodworkbyspraymachineincluding Knottingandpreparingthesurfacebyscrapping, Applying Wood Filler, Scaffolding If Required Etc. .Complete , Providing And Applying First Quality Metallic Transparent Pu Coating Of Approved Quality And Shadeon Plywoodor Veneer Wherever Required With Sand Papering & Cleaning The Surface, Applying One Coat Of Primer And Lambi / Putty Including Wood Filler To Full Surface 3 Times, Thereafter Polishing The Surface In Twofinishingcoatsoverbaseprimercoattoachieveeven Finish. All Complete As Per Instructions Of Engineer In Charge. Etc. Complete , Supplying&Installingsunscreenperforatedrollerblind Optima Series - Basket 125 Tex With Fabric Specification Of - ( Fabric Composition Polyester 22 % And Pvc 78 % , Openness Factor - 5%, Thickness - 0.68Mm + / - 5%, Weight Perm2-480.00Gsm, Yarnscountinwrap / Weft / Cm19 / 18+ / - 5%, Fireresistance-Fr ( Usa ) Kfi ( Korea ) , Tearresistance- Wrap11.9 Dan+ / -5%, Weft 150 Dan+ / -5%, Colour Fastness-6- 7 / 8 ( Whitecolourbase ) , Artificiallightxenonlamp, Uv Resistance Min 3 ( White Colour Base ) , Width 2.5M & 3 M The Roller Mechanism Shall Be A Moulded Unit Made From Engineering Gradeplastic Polymerwith Pvcspring Support. Thefabricshallbeattachedtotherollertubewithhigh Quality Self Adhesive Tape With Manual Operation . The Total Area Of Opening Covered Will Be Measured. , Blackout-Providing, Supplying&Installingroller Blindsinseclusionserieswithspecificationof Basic Material-1005Polyester, Fabricwidth200 / 250Cm, Fabric Weight- 20 / 295G / Sq.M. Thickness-0.50Mm Finishing-Blackout Fabric, Reverse&Frontsidepigmentcolourcoatedcolour Fastness>5 / 6, Rubbing Fastness-Depending On Colour, Shrinkage-Wrap:<0.5%Withapprovedshadefabric, ( Forexternalwindows ) Comprisingofpolymercoatedfibre Fabric.Therollermechanismshallbeamouldedunitmade Fromengineeringgradeplasticpolymerwithpvcspring Support . The Fabric Shall Be Attached To The Roller Tube With High Quality Selfadhesive Strip.The Total Area Of Opening Covered Will Be Measured. , Supply & Fixing Rigid Autoglow Photo Luminescent Signages, On Glowinthedarkrigidsheetwithhighintensityluminous Propertiesenclosedintransparentweatherproofuv Stabilized Coated Sheet With Uv Screen Printing By Imported Ink Thickness Of Photo Luminescent Sheet 1Mm, Glow Should Be Visible For 24 Hours In Total Darkness. These Signs Adheres To Pspaclassadin67510part2, Bs5499-1, Nfpa101etc. Complete. Any And All Sizes Below 2Ft*2Ft. , Providing And Fixing Gypsum Cove As Per Architects Drawing Between Ceiling & Wall / Column With Gi Frame Support, Finished From The Top & Sides By 12Mm Thick Gypboard Including Making Necessaryhousing For Concealed Lightfittings, Speakers, Etc.Completeasperarchitectsdetailed Drawing And Design And As Directed With Necessary Scaffolding Etc. Complete. , Officetable ( Maincabintable ) -Providingandfixing Table & Pedestal With 3 Drawers ( Size -400 X450x725 ) To Be Made Out Of 19Mm Thk Bwp ( Is710 ) Marine Ply Cladded With 4Mmthkveneer&Finishedwiththreecoatsofmelamine Fromoutside&0.8Mmthklaminatefinishedfrominside. Onlytabletopedgefinishedwithpostform&Otheredges Finishedinpvcedgebinding.Tabletop46mmthickness Inside Finished With 0.8Mm Thk Laminate.Pedestal Drawerto Be Operate With Telescopic Drawer Channel As Per Detail Drawing ) . Complete With All Necessary Hardware & Fixture. Note : All Furniture To Be Made Out Ofcalibrated Plywood ( Is : 710 ) Bwpall Internal & External Surfaces Of Plywood Finishedwithlaminateandveneerrespectively.All Hardware Complete As Perdetaileddrawing & Instructions Directedbyengineerincharge.Includingloading, Unloading, Transportation, Installation. With1yearwarranty. Rate To Include Wire Manager System Of Approved Quality Size: 1800 X 900 X 750 Mm , Thrive + With Head Rest Chair. Thrive Plus High Back With Headrest And Coat Hanger .Thrive Plus High Back With Headrest And Coat Hanger Generally Size In 75 Cm * 75 Cm Height 115-130. , Bravo Visitor Chairs Width 61.4Cm * Depth 64.5Cm*Height 89.5Cm * Seat Height 46.5Cm , Sidestorage ( Dgmcabin ) -Providingandfixingside Storageunittobemadeoutof19 / 12Mmthkbwp ( Is710 ) Marineplycladdedwith4mmthkveneer&Finishedwith Melamine From Outside & 0.8Mm Thk Laminate Finished From Inside. Only Side Storage Top Edge Finished With Post Form & Otheredgesfinishedinpvcedgebinding.Tabletopinside Finishedwith0.8Mmthklaminate. Complete With All Necessary Hardware & Fixture. Note : All Furniture To Be Made Out Ofcalibrated Plywood ( Is : 710 ) Bwp All Internal & External Surfaces Of Plywood Finished With Laminate And Veneer . All Hardwarecomplete As Per Detailed Drawing & Instructions Directed By Engineer Incharge.Includingloading, Unloading, Transportation, Installation. With 1 Year Warranty.Size: 1050 X 400 X 750Mm , Workstation - Providing&Supplyingat Site , Workstation Comprising Of Modular 1200Mm Height, 60Mmthickness Partitionsystemwithpowder Coatedaluminiumframingwithpowdercoated Aluminiumcaping..Ratetoincludetable, 25Mm Thick Postformed Top Made Out Ofcalibrated Plywood ( Is : 710 ) Bwp Finishedwith P / F 0.6Mm Laminate With Edge Binding, Wire Management, Raceway- Double Raceway Soft Board+White Board Combination.In Workstation Table One Side Of Table Understructure 50 X 50Full Frame Metal Structure Considerwithonesidemetalmodesty ( 600X450ht ) . Provisionfornecessarywiremanagementasdirected. Complete With All Necessary Hardware & Fixture. Note:Allfurnituretobemadeoutof Calibrated Plywood ( Is:710 ) Bwp, Allinternal&External Surfaces Of Plywood Finished With Laminatecomplete, Asperdetaileddrawing&Instructionsengineerin Charge.With1 Yearwarranty. Ratetoincludewire Managersystemofapprovedquality. Size : 1350 / 1350 X 600 X 750 / 1200Mm , Sharing Workstation - Providing & Supplying At Site , Workstation Comprising Of Modular 1200Mm Height, 60Mmthickness Partitionsystemwithpowder Coatedaluminiumframingwithpowdercoated Aluminiumcaping..Ratetoincludetable, 25Mm Thick Postformed Top Made Out Ofcalibrated Plywood ( Is : 710 ) Bwp Finishedwith P / F 0.6Mm Laminate With Edge Binding, Wire Management, Raceway- Double Raceway Soft Board+White Board Combination.In Workstation Table One Side Of Table Understructure 50 X 50Full Frame Metal Structure Considerwithonesidemetalmodesty ( 600X450ht ) . Provisionfornecessarywiremanagementasdirected. Complete With All Necessary Hardware & Fixture.. Note:Allfurnituretobemadeoutof Calibrated Plywood ( Is:710 ) Bwp, Allinternal&External Surfaces Of Plywood Finished With Laminatecomplete, Asperdetaileddrawing&Instructionsengineerin Charge With 1 Year Warranty. Rate To Include Wire Managersystemofapprovedquality. Size: 1200 X 600 X 750 / 1200. , Nonsharingworkstation-Providing& Supplyingatsite, Workstationcomprisingofmodular 1200Mmheight, 60Mmthickness Partitionsystemwith Powder Coated Aluminium Framing With Powder Coated Aluminiumcaping..Ratetoincludetable, 25Mm Thick Postformed Top Made Out Ofcalibrated Plywood ( Is : 710 ) Bwp Finishedwith P / F 0.6Mm Laminate With Edge Binding, Wire Management, Raceway- Double Raceway Soft Board+White Board Combination.In Workstation Table One Side Of Table Understructure 50 X 50Full Frame Metal Structure Considerwithonesidemetalmodesty ( 600X450ht ) . Provisionfornecessarywiremanagementasdirected. Complete With All Necessary Hardware & Fixture. Note:Allfurnituretobemadeoutof Calibrated Plywood ( Is:710 ) Bwp, Allinternal&External Surfaces Of Plywood Finished With Laminate Complete, Asperdetaileddrawing&Instructionsengineerin Charge With 1 Year Warranty. Rate To Include Wire Manager System Of Approved Quality.Size: 1200 X 600 X 750 / 1200. , Cubicletable -Cubicletableproviding& Supplyingatsite, Comprisingofmodular1200mm Height, 60Mmthickness Partitionsystemwithpowder Coatedaluminiumframingwithpowdercoated Aluminiumcaping..Ratetoincludetable, 25Mm Thick Postformed Top Made Out Ofcalibrated Plywood ( Is : 710 ) Bwp Finishedwith P / F 0.6Mm Laminate With Edge Binding, Wire Management, Raceway- Double Raceway Soft Board+White Board Combination.In Workstation Table One Side Of Table Understructure 50 X 50Full Frame Metal Structure Considerwithonesidemetalmodesty ( 600X450ht ) . Provisionfornecessarywiremanagementasdirected. Complete With All Necessary Hardware & Fixture. Note:Allfurnituretobemadeoutof Calibrated Plywood ( Is : 710 ) Bwp, Allinternal & External Surfaces Of Plywood Finished With Laminatecomplete, Asperdetaileddrawing&Instructionsengineerin Charge.With 1 Year Warranty. Rate To Include Wire Managersystemofapprovedquality. Size: 1800 / 1800 X 600 X 750 / 1200 / 700 X 1800 , Conferencetable- Providing And Fixing Conference Table To Be Made Out Of 19Mm X 2 = 38Mm Top / / 12Mm Thk Boxing Supports Of Bwp ( Is710 ) Marine Plycladded With 4Mmthk Veneer&Finishedwith Melamine From Outside & 0.8Mm Thk Laminate Finished From Inside. All Expose Surfaces To Be 4Mm Veneer With 48X48mmedgelipping Fortabletop&100X 25Mm Teakwoodedgelippingforsupportingboxingfinish. Completewithallnecessaryhardware& Fixture. Provision For Necessary Wire Management And 6 Nosofdeskportof8 Moduleas Directed ( Without Electrical ) .Complete With All Necessary Hardware & Fixture. Etched Glass To Be Installed If Required. Note:Allfurnituretobemadeoutof Calibrated Plywood ( Is:710 ) Bwp, Allinternal&External Surfacesofplywoodfinishedwith4mmveneerand3 Coatsofp.U.Coating, Allhardware Complete, Asper Detailed Drawing & Instructions Directed By Engineer In Charge.Includingloading, Unloading, Transportation, Installation. With1yearwarranty.Ratetoincludeall Provisionofinstallationconcealedspeakersystemand 12Mmthickbwpmarine Plyapronwith4mmthick Veneerfinishonbothsideand20x12mmteakwood Edgelipping.Ratetoincludewiremanagersystemof Approved Quality. Size: 5500 X 1200 X 750. , Meeting Table - Providing And Fixing Meeting Table Tobemadeoutof19mmplus12mmtabletopand 12Mmthickboxingsupportsbwp ( Is710 ) Marineply Cladded With 4Mm Thk Veneer & Finished With Melamine From Outside & 0.8Mm Thk Laminate Finished From Rear Side.All Expose Surfacesto Be 4Mmveneer With37 X 37Mmedgelippingfortabletop.Completewithall Necessaryhardware&Fixture. Provisionfornecessary Wire Management And Deskport Of 8 Module As Directed ( Withoutelectrical ) .Completewithallnecessary Hardware & Fixture. Note:.Allfurnituretobemadeoutof Calibrated Plywood ( Is:710 ) Bwp, Allinternal&External Surfaces Of Plywood Finished With Laminate And Veneer Of . All Hardware , Complete As Per Detailed Drawing & Instructionsdirectedbyengineerincharge.Including Loading, Unloading, Transportation, Installation. With 1 Yearwarranty.Rate To Includewiremanagersystemof Approved Quality. Size:2700 X1050 X 750.Mm / 600Mm Dia , Cafeteriatable-Cafeteriatable-Providing& Supplyingatsite31mmthick Cafeteriatable Comprisingof 25Mmthickbwpgrademarineply Tabletopwith12mmthk Corianfinish &37X 12Mmcorianedgebindingthetabletopissupported With S.S.304Gradebaseunderstructurecomprising Of 75Mm Diapipe&4Pronged Withpvcleveller. Complete With All Necessary Hardware & Fixture. Size: 900 X 900 X 750.Mm / 900 X 2970Mm , Receptiontable-Providing&Supplyingatsite Custom Made Reception Table & Apron In 19Mm Marine Ply Construction Inclusive Of Support Framing, Table, Counter Top & Drawer Box With Key Board Tray Asper Architect Drawing &Design. Rate To Include 19Mm Thick Italian Marblecounter Top & Edging62 X 19Mminclusiveofedgepolishing&Finishing.Basic Rate Of Italian Marble Rs.800 / -Sqft. Facia To Be Finish With 12Mm Thick Corian With Polishing & Buffing, Edge Bindingwith12mmcorian.Concealedledlighting Strips With Drivers To Be Installed In Pelmet ( Led Strip Is19mmx 12Mmwithpolycarbonatecover.All Other Surfacesinternal&Externaltobefinishwithveneer Inclusiveofteakwoodedgelippingof10mm Thickness. Provisionfornecessarywiremanagementas Directed ( Withoutelectrical ) .Completewithall Necessary Hardware & Fixture. Note:Allfurnituretobemadeoutof Calibrated Plywood ( Is:710 ) Bwp, Allinternal&External Surfaces Of Plywood Finished With Laminate . All Hardware Complete, As Perdetaileddrawing & Instructionsdirectedbyengineerincharge.Including Loading, Unloading, Transportation, Etc. Complete. Size: 1800 X 750 X 1050Mm Ht , Medium Ht Storage - Providing & Supplying At Site, Med Ht Storage Unit 18 Mmthick Top, All Sides, Shelf, Bottom Made Out Of Calibrated Plywood ( Is : 710 ) Bwp With P / F 0.6Mm Laminate, Other Edges Finished With 2.0 Mm Thick Pvc Edgeband For Exposed Edges & 0.8 Mm Thick For Non Exposed Edges T.Complete As Per Architects Detailed Note :All Furniture To Be Made Out Ofcalibrated Plywood ( Is : 710 ) Bwp, All Internal & External Surfaces Of Plywood Finished With Laminate . All Hardwarecomplete, As Per Detailed Drawing & Instructions Directed By Engineer In Charge. Including Loading, Unloading, Transportation, Installation., With 1 Year Warranty. Size : 900 X 450 X1200mm , Lockers -Providing & Supplying At Site, Locker Storage Unitof8compartments18mm Thicktop, Allsides, Shelf, Bottom& Shutters Made Out Of Calibrated Plywood ( Is:710 ) Bwpwithp / F0.6Mmlaminate, Other Edges Finished With 2.0Mm Thick Pvc Edgeband Forexposededges&0.8Mmthickfornonexposed Edges Complete, As Per Architects Detailed Note:Allfurnituretobemadeoutof Calibrated Plywood ( Is:710 ) Bwp, Allinternal&External Surfaces Of Plywood Finished With Laminate . All Hardware Complete, As Perdetaileddrawing & Instructionsdirectedbyengineerincharge.Including Loading, Unloading, Transportation, Installation, With 1 Year Warranty. Rate To Include Locking Arrangement With Hinges, Handles&Hardware.Size :1050X450x 2400Mm. , Revolving Type Chair With Wheels : Seat Assembly :- The Cushioned Seat Is Made Of Injection Moulded Plastic Outer & Inner. Plastic Inner Is Upholsteredwithleatherette Andmouldedhighresilience ( Hr ) Polyurethane Foam Ofdensity45±2 Kg / M³ And Hardness Load 16 ± 2 Kgf As Per Is:7888 For 25% Compression * Seat Size : 47.0 Cm ( W ) X 48.0 Cm ( D ) Backassembly:-Thecushionedbackismadeofpu Foam With Insitu Moulded Ms Moulded E.R.W.Round Tube Of Size1.9±0.03Cm X0.16±0.0128Cm.Itupholsteredwith Leatherette.*Mid Back Size :- 47.7 Cm ( W ) X 60.1Cm ( D ) Armrests:-Thearmresttopismouldedfrom Polyurethane ( Pu ) And Mounted On To A Drop Lift Adjustable Type Tubular Armrest Support Made Ofø 3.81 ± 0.03 Cmx 0.2 ± 0.01Cm Thk M.S.E.R.Wtube Having Chrome Plated Finish . Thearmrestheightadjustableupto6.5±0.5Cm In5 Steps. Seatdepthadjustment:-Seatdepthadjustmentis Integrated In The Seat Through A Sliding Mechanism. Seat Depth Adjustmentrangeisof6.0±0.5Cm.Adjustable Back Support :- Back Frame Is Connected To The Up / Dn Mechanismhousedinplastictspine.Itcanbeadjustedin The Range Of 7.42 ± 0.5 Cm For The Comfortable Back Support To Suit Individual Need .Active Bio -Synchro Mechanism:- The Adjustable Tilting Mechanism Is Designedwiththefollowing Features:- • 360°Revolving Type . Djustment :- The Pneumatic Height. Adjustment Has Anadjustment Stroke Of 10.0 ± 0.3 Cm . , Revolving Type Chair With Wheels: Seat / Back Assembly :- The Seat & Backis Made Up Of 1.2±0.1Cmthk. Hotpressedplywoodmeasuredasperqa Method Describedin Qcp-Olta-Pl14-18:Upholstered With Synthetic Leather Over Moduled High Resilience Polyurethane Foam. • High Back Size : 51.8 Cm ( W ) X 75.2Cm ( H ) • Seat Size : 49.0 Cm ( W ) X 48.8 Cm ( D ) High Resilience ( Hr ) Polyurethane Foam :- The Hr Polyurethanefoam Ismoduledwithdensity=55+ / -2 Kg / M³andhardnessload16±2 Kgfasis:7888For25% Compression. Armrests :- The Adjustable Armrest Is Designedwiththefollowing Features • Up- Down Adjustment- 8 Steps ( 8.0 ± 0.5Cm Range ) • Height Adjustable Armreststructurewhichischromeplatedandfittedwithan Armrest Top • Fixed Armrests Topispu Moulded Over Metal Insert. Backheightadjustibality:-Backcanbe Adjusted In 5 Positions By Manually .Stroke Of Height Adjustable Spine Is 7Cm.Back Height Adjustability Is Applicable For High Back & Mid Back Chairs .Pneumatic Height Adjustment :- The Pneumatic Height. Adjustment Has Anadjustment Stroke Of 10.0 ± 0.3 Cm . , Bean Bagchairs Xxl Size Of Approved Colour, Shade And Material As Per The Direction Of Engineer In Charge , Providing, Fixing, Installing & Putting In Place& In Proper Condition, As Per Layout & As Per Direction Of The Engineer In Charge.Seating Asperfollowingdetails. Basicratefor Fabric Upholstery Rs 450 / -.Per Mtr: 1Seater Sofa Size:- ( 860W X 905D X 855H ) Seatfoam:Theseatismadeupofpufoamindensity 28±2 Kg / Cu. Mtr With An Additional Top Layer Of Supersoft Pu Foam In Density 32±2 Kg / Cu, Upholstered With Fabric Or Leatherette. Backfoam:Thebackismadeupofpufoamdensity 28±2Kg / Cu, Mtrwithtwoadditionaltoplayerofsupersoft Foam Ofdensity 32±2Kg / Cu, Mtr, Upholstered Withfabric Or Leatherette. Undersructure:Understructureismade Upof 1.2±0.1 Cm. Thick Hot Pressed Plywood ( Moisture Resistance & Termite Proof As Per Is:303 ) & Pinewood Of Cross Sections Devoid Of Majorknots&Surfacedefects.6Nosperseat&3.8Mm Dia Zigzagspringassemblyismountedoverunderstructurefor Cushioning Purpose. Leg Assembly: It Is A Welded Assembly Made In Stainless Steel ( Grade Ss 202 ) Tube & Plate With Plastic Endcap The Product To Be Tested And Passed The Quality Standards As Laid Down Under Iso 9001, 1S014001, Iso18001, Ohsas Andbifmacertificationsforqualityassurance.Ithasa Green Assurance Card Validated By Tuv India. Location - Staff & Wherever Required, , Electrical , Dg Set , Supply , Installation, Testing & Commisioning Of Diesel Generating ( D.G. ) Set With Class G3 Governing ( 40% Step Load ) , Alternator Of 325 Kva Output At 0.8 Pf Continuous Rating With 10% Overload Capacity For 1 Hour In 12 Hours, 3 Phase, 415 V, 50C / S, Radiator Cooled, Multi-Cylinder Diesel Engine At 1500 Rpm , Seperately Excited Amg Having Class H, Spdp Alternator ( With Battery Charging Generator ) , With Static Avr + / - 1% & Thd<3%, Running At 1500 Rpm. Both The Engine And Alternator Shall Be Direct Coupled On A Common Fabricated Steel Base Frame Anti Vibrating Pad Mounted With Controller Suitable For Full Parallel Operation Of Multiple Generators Having Engine & Generator Protection ( Including Ref & Rpr ) / Parameter Display / Operator Interface / Power Command 3.3 Control System / Amf Panel / Synchronization / Dedicated Earthing System / Rs 485 Modbus Connectivity, Etc. The Complete Set Shall Be Enclosed In Composite Acoustic Enclosure As Fully Assembled Integral Unit In Silenced Accoustic Canopy, Giving 75 Db At 1 Meter, Made Of 16 / 14 Swg Crca Sheet, Complete With First Filling Of Lube Oil / Diesel / Coolant & Fuel Hoses, Battery, 990 Liter External Fuel Tank, Residential Silencers, Mounted On Plinth & Obtaining Necessary Approval From Electrical Inspector. A. Amf Panel Comprising Of Suitable Rating Fp Edo Acb For Mains And D.G., Auto / Manual Selector Switch, Engine Start / Stop Push Button, Indication Lamps, Voltmeter / Ammeter / Kwh Meter / Rpm Meter / Hour Meter / Announciator / Relays / Battery Charger / Dc Ammeter / Voltmeter, Etc. B ) Exhaust Piping To Be Raised Upto Terace Level Of Nearest Building. C ) Power / Control Cabling, Terminations, Etc. D ) 990 Ltr. Capacity External Diesel Tanke ) . Height Of Stack To Be Maintained As= Height Of Building + 0.2 * Vkva . F ) Factory Testing To Be Carried Out In Present Of Actrec Engineering Before Despatch Of Equipments. , Supply, Installation, Testing And Commissioning Of Following All Indoor Panels Comprising Below Points. 1 ) -Panels Shall Be Fabricated Out Of 16 / 14 Swg Crca Sheet Steel, With Necessory Structural Supports In Form Of Structural Steel Sections. 2 ) -Floor Mounted, Ip-52 Degree Protection, Top Bus Duct Or Cable Entry As Per The Case & Top Cable Exitsteel, 2Mmframe, 1.6 Mm Compartments & Tank Process Treated & 2- Times Epoxy Painted. 3 ) -The Panel Shall Be Compartmental, Form 3B Type, With Suitable Size Of Bus Bar And Separate Cable And Busbar Chambers. 4 ) -Proper Gland Size Holes To Be Provided Bythe Manufacturer With Proper Sticker And Danger Sign On All Sides Of Panel. 5 ) -The Cable Chambers Shall Be Free From Any Live Open Connections And Minimum Cleareance To Be Provided For Termination. 6 ) -Current Density- 1.2 Ampere / 1 Sq.Mm For Copper And 0.8 Ampere / 1 Sqmm For Aluminium ( Is-8623 For Factory Built Assembly ) . Specification Of Copper For Copper Bush Bar C11000 - Electrolytic-Tough-Pitch ( Etp ) . 7 ) Earthing Terminal.8 ) Fault Level 50Ka / Sec.9 ) Panel Inside Illumination To Be Provided10 ) Receptacles , Space Heater Provided As Per Standard. 11 ) Epoxy Paint Colour Type Ral 7032 To Be Use. , L.T. Panel 1 & 2 ( As Per Sld Attached ) , Office Panel ( As Per Sld Attached ) , Utility Panel 1 & 2 ( As Per Sld Attached ) , 30Kva Ups O / P Panel ( As Per Sld Attached ) , Pdu 1 & 2 ( As Per Sld Attached ) , 5Kva Ups O / P Db For Emergrncy Lighting And Ibms Load. ( As Per Sld Attached ) , Automatic Changeover Switch ( Ats ) , 32A 4P Automatic Changeover Switch ( Ats ) , Ups System , Supply , Installation, Testing & Commisioning Of 80Kva Online, Pure Sine Wave Modular Ups System, 3 Phase Input And 3 Phase Output With Upf, 0.96% Efficiency, Igbt Based Rectifier Technology, Isolation Transformer, Suitable Capacity Smf Batteries For Minimum 20 Minutes Backup, Battery Rack, Cables For Interconnections. Ups Should Have Provision Of Auto & Manual Bypass In Case Of Any Internal Fault In Ups System.80% Dod Is Accepted For Li Battery , Acceptable Inputthd 5% , Supply , Installation, Testing & Commisioning Of 30Kva Online, Pure Sine Wave Modular Ups System, 3 Phase Input And 3 Phase Output With Upf, 0.96% Efficiency, Igbt Based Rectifier Technology, Isolation Transformer, Suitable Capacity Smf Batteries For Minimum 20 Minutes Backup, Battery Rack, Cables For Interconnections. Ups Should Have Provision Of Auto & Manual Bypass In Case Of Any Internal Fault In Ups System.80% Dod Is Accepted For Li Battery , Acceptable Inputthd 5% , Supply , Installation, Testing & Commisioning Of 5Kva Online, Pure Sine Wave Modular Ups System, 1 Phase Input And 1 Phase Output With Upf, 0.96% Efficiency, Igbt Based Rectifier Technology, Suitable Capacity Smf Batteries For Minimum 20 Minutes Backup, Battery Rack, Cables For Interconnections. Ups Should Have Provision Of Auto & Manual Bypass In Case Of Any Internal Fault In Ups System.80% Dod Is Accepted For Li Battery , Acceptable Inputthd 5% , Distribution Boards , Supply And Fixing Of Tpn, Double Door Power Distribution Board Having 63 Amps Tpn Mcb--1 No. / / / 40 Amps , 10Ka , Dp Elcb ( 30 Ma ) --3 Nos / / / 20 / 32 Amps Sp Mcb ( 8Ways ) --24 Nos. Ip 55, Ik 08, , Supply And Fixing Of Tpn, Double Door Lighting Distribution Board Having 63 Amps Tpn Mcb--1 No. / / / 40 Amps, 10Ka , Dp Elcb ( 30 Ma ) --3 Nos / / / 10 Amps Sp Mcb ( 12Ways ) --36 Nos.Ip 55 , Ik 08 , Supply And Fixing Of Spn, Double Door Power Distribution Board Having 32Amps , 10Ka Dp Elmcb--1 No. / / / 16 Amps , 10Ka Dp Mcb--6 Nos. , Ip 55 , Ik 08 , Supply And Fixing Of Spn, Double Door Lighting Distribution Board Having 16Amps 10Ka , Dp Elmcb--1 No. / / / 10 Amps , 10Ka Sp Mcb--6 Nos., Ip 55 , Ik 08 , Mains Wiring , Wiring For Circuit / Sub Main Wiring Along With Earth Wire With The Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required. , 2 X 2.5 Sq. Mm + 1 X 2.5 Sq. Mm Earth Wire , 2 X 4 Sq. Mm + 1 X 4 Sq. Mm Earth Wire , Point Wiring , Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Medium Class Pvc Conduit, With Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable Etc. As Required. , Wiring For Group Controlled ( Looped ) Light Point / Fan Point / Exhaust Fan Point / Call Bell Point ( Without Independent Switch Etc. ) With 1.5 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Pvc Conduit, And Earthing The Point With 1.5 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable Etc. As Required. , Wiring For Plug On Board, Switch With Multi-Socket Concealed Type And Copper Wiring, Earthing And With Modular Accessories. , Providing Fan Regulator On Board With Modular Switch And Regulator. , Switches, Sockets & Accessorie , Supplying And Fixing Of 3 / 4 Module Switch Box With Modular Plate Including Connections But Excluding Modular Plate Etc. As Required. , 15 Amps Switch , 5Pin 5 / 15 Amp Socket Outlet , 32A 3P+N+E Socket With Plug Ac Powerenclosure And Mcb , 16A 1P+N+E Mobile Socket With Plug Ac Power , Lighting Fixtures / Exhaust Fans / Ceiling Fans , Supplying And Erecting Of Recessed Type Square Shaped Crca / Die-Cast Aluminum Powder Coated Housing Led Panel Light 600X600mm Of Premium Range Suitable For Upto 36 W With Provision For Plane Front Frame With Translucent Cover Fixed To The Housing Complete.Lumens Output >3200 , Cri More Than 80 , Cct 6500K, Thd <10% , Supplying And Erecting Led Square / Circular 13 To 18 W Premium Range Down Lighter Having Pressure Die-Cast Aluminum Housing With White Front Frame With Opal Translucent Cover With Provision For Spring Loaded Mounting Clips Complete. Lumens Output 900 / 935 / 980 , Cri More Than 85 , Cct 3000K To 6000K, Thd <10% , Supply And Erecting Of Box Type Led Light Fitting With 1 X22w Led Tube Light Complete With All Accessories. , Standerd 230V Ceiling Mounted Day Light Cum Occupancy Sensor. , Supply And Fixing Of Call Bell With All Accessories. , Supply And Fixing Of 225Mm Sweep Exhaust Fans. , Supply And Fixing Of 1200Mm Sweep Ceiling Fans. , Cable Tray , Supply , Installation, Testing & Commisioning Of Hot Deeped Galvanised Perforated Type Cable Tray Manufactured From 16 Swg ( 1.6 Mm Thick ) Gi Sheet Of 300 Mm Width & 50 Mm Height Complete With Necessary Coupler Plates, Support & Hardware In Approved Manner.Coating Thickness Of Hot Dip Galvanized Cable Trays Will Be 80 To 100 Microns Or 610 Grams Per Square Meter ( Depends On Thickness ) And Follows Is: 2629, 1985&Is 4759. , Supply , Installation, Testing & Commisioning Of Hot Deeped Galvanised Perforated Type Cable Tray Manufactured From 16 Swg ( 1.6 Mm Thick ) Gi Sheet Of 500 Mm Width & 75 Mm Height Complete With Necessary Coupler Plates, Support & Hardware In Approved Manner. Coating Thickness Of Hot Dip Galvanized Cable Trays Will Be 80 To 100 Microns Or 610 Grams Per Square Meter ( Depends On Thickness ) And Follows Is: 2629, 1985&Is 4759. , Supply , Installation, Testing & Commisioning Of Hot Deeped Galvanised Perforated Type Cable Tray Manufactured From 16 Swg ( 1.6 Mm Thick ) Gi Sheet Of 750Mm Width & 75 Mm Height Complete With Necessary Coupler Plates, Support & Hardware In Approved Manner.Coating Thickness Of Hot Dip Galvanized Cable Trays Will Be 80 To 100 Microns Or 610 Grams Per Square Meter ( Depends On Thickness ) And Follows Is: 2629, 1985&Is 4759. , Lt Cables , Supply And Laying Of 1.1Kv, Frls, Xlpe Armoured Cable 3.5Cx300 Sqmm Aluminium Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls, Xlpe Armoured Cable 3.5Cx185sqmm Aluminium Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls, Xlpe Armoured Cable 3.5Cx150sqmm Aluminium Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls, Xlpe Armoured Cable 3.5Cx70 Sqmm Aluminium Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls, Xlpe Armoured Cable 3.5Cx50 Sqmm Aluminium Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls, Xlpe Armoured Cable 3.5Cx35 Sqmm Aluminium Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls, Xlpe Armoured Cable 3.5Cx25 Sqmm Aluminium Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls Multicore Flexible Cable 1Cx70sqmm Copper Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls Multicore Flexible Cable 1Cx35 Sqmm Copper Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls Multicore Flexible Cable 1Cx10 Sqmm Copper Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Laying Of 1.1Kv, Frls Multicore Flexible Cable 3Cx6 Sqmm Copper Conductoron Wall / In Provided Tray As Per Instructions. , Supply And Fixing Of End Termination With Brass Double Compression Gland Andlugs Of Copperor Aluminiumor Bi Metallic Lugswhich Are Suitable At Sitefor Following Size Of Frls Insulated And Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. , 3.5C X 300 Sq.Mm. , 3.5C X 185 Sq.Mm. , 3.5C X 150Sq.Mm. , 3.5C X 70Sq.Mm. , 3.5C X 50Sq.Mm. , 3.5C X 35 Sq.Mm. , 3.5C X 25 Sq.Mm. , 1C X 70 Sq.Mm. , 1C X 35 Sq.Mm. , 1C X 10 Sq.Mm. , 3C X 6 Sq.Mm. , Earthing , Supply And Fixing Of 50 Mm X 6 Mm Copper Strip On Surface Or In Cable Tray For Connections Etc As Required. , Supply And Fixing Of 40 Mm X 5 Mm Copper Strip On Surface Or In Cable Tray For Connections Etc As Required. , Supply And Fixing Of 25 Mm X 3 Mm Copper Strip On Surface Or In Cable Tray For Connections Etc As Required. , Supply And Fixing Of 8 Swg Copper Wire On Surface Or In Cable Tray For Connections Etc As Required. , Tinned Copper Earth Plate Electrode 600 X 600 X 3.15 Mm Earth Station, 2.5 Mtr Below Ground Level As Per Drawing Complete With All Required Materials Like Cole, Charcoal, Salt, Brass Nut Bolts & Washers, Watering Arrangements, Gi Pipe ( B Class ) , Concrete Chamber, Heavy Duty Cast Iron Cover Plate & Excavation In All Types Of Soil In Ground Refilling & Removal Excess Earth Within A Radius Of 500 Mtr. The Chamber Cover & Plate Shall Be Of Heavy-Duty Hinged Type & It Shall Weigh Approx. 65 To 75 Kgs. Plastering Shall Be Done Both Inside & Out Side.The Measurement Of Resistance Of Earth Station & Resistance Of Complete Scheme Of Earthing Layout Shall Be Measured, Recorded & Got Approved By Engg-In-Charge. , Chemical Earthing / Maintenance Free Earthpits Having Better Earth Resistance Value. , Addressable Fire Alarm Systems & Detection Systems : , Supply , Installation , Testing And Commissioning Of Addressable -Automatic Dual Led Smoke Detector With Two Integrated Light-Scattering Smoke Sensors Using Leds With Different Colors / Wavelengths ( Blue / Infrared ) To Avoid False Alarm & Should Comply To Test Fire 1, Including Mounting Base With Led, Drift Compensation Feature & Automatic Addressing.High Resistance To Electromagnetic Effects In Accordance With Efsg Agreement Efsg / F / 97 / 005 Shall Be En54 / Vds / Ul Certification.2Isolators ( One For Incoming & One For Outgoing Line ) Integrated In Detector For Maintaining Operational Availability Of All Elements In The Loop , Even In The Evennt Of A Short Circuit, Bosch Model Fap 0 420 Or Equivalent. , Sitc Of Addressable Thermal Detector Including Mounting Base With Led..Etc Complete As Required With Inbuilt Isolator.Temprature Sessor Triggers@ 54Deg C Or 69 Deg C & Drift Compensation Feature.Shall Have Ul / Vds Certification Bosch Model Fah T 420. , Supply, Installation, Testing & Commissioning Of Addressable, Ul Listed, Duct Smoke Detector Comprisingsplash & Hose Proof, Uv Resistant, Housing Assembly With Sampling Tubes & Photoelectric Detector With Heat Element ( 57Deg C ) , Suitable For Air Speeds Of 100 -4000 Fpm, Loop Powered, Class A Wired, Low Profile, Temper Resistant, Low Quiescent Current, Rotary / Dip Decimal Address Setting Switch, 24V Dc ( 15-32V ) , Wiring Box, In / Out Cable Glands. , Supply, Installation, Testing & Commissioning Of Addressable, Ul Listed, Control Module For Switching Power Supply To Hooter & Strobe, Loop Powered, Class A Wired, Low Quiescent Current, Rotary / Dip Decimal Address Setting Switch, 24V Dc ( 15-32V ) , Suitable For Surface / Recess Installation, Wiring Box, In / Out Cable Glands. , Supply, Installation, Testing & Commissioning Of Addressable, Ul Listed, Control Module With Relay For Ahu / Damper / Switchgear Operation, Loop Powered, Class A Wired, Low Quiescent Current, Rotary / Dip Decimal Address Setting Switch, 24V Dc ( 15-32V ) , Suitable For Surface / Recess Installation, Wiring Box, In / Out Cable Glands. , Supply At Site, Installing In Proper Position Testing And Commissioning Of 2 Core X 1.5 Sqmm Frls Armouredcopper Conductor Cable Of Approved Quality All Complete As Required And As Per Final Direction. , Removing And Refixing Of Detectors, Isolators, Monitor Moduls, Control Moduls, Etc. , Supply And Fixing Of Junction Boxes With Cable Glands, Lugs, Etc. , Fire Suppression System Comprising Of Following , Novec 1230 Based Fire Suppression System Comprising Of The Following Items: , Sitc Of Ccoe Approved Ul Listed Seamless Novec 1230 Cylinder And Valve Assembly, 120 Ltrs. Capacity, Oem Factory Filled With Novec 1230 Suppression Liquid ( Item No. 2 ) , Pressurised To 25 / 42 Bar. Along With Hydraulic Flow Calculations For The Suppression Areas, And Vetting Of The Software Results From The Oem Factory Engineer. , Sitc Of Ccoe Approved Ul Listed Seamless Novec 1230 Cylinder And Valve Assembly, 80 Ltrs. Capacity, Oem Factory Filled With Novec 1230 Suppression Liquid ( Item No. 2 ) , Pressurised To 25 / 42 Bar. Along With Hydraulic Flow Calculations For The Suppression Areas, And Vetting Of The Software Results From The Oem Factory Engineer. , Sitc Of Novec 1230 Fire Protection Fluid, Oem Factory Filled Per Kgs. , Sitc Of Tank Bracket Assembly Complete With C- Channel Stand And Supports For Above Cylinder. The Price Shall Include Ms Fabricated Floor Supported Cylinder Support Stand, Wherever Required. Complete With 1 Coat Of Primer And 2 Coat Of Black Enamel Paint. ( Refer Drawing For Cylinder Locations ) . , Sitc Of Ul Listed Discharge Hose Withmanifold Check Valve ( Check Valve If More Than One Cylinder In Bank ) For Above Cyilnders, Complete With Listed Adapters & Accesories As Required. , Sitc Of Ul Listed Electrical Actuator For Master Cylinder. , Sitc Oful Listed Local Manual Actuator , Sitc Oful Listed Pneumatic Actuator Shipping Assembly With Actuation Hose & Elbow. , Sitc Oful Listednozzles, 360 Deg / 180 Deg Throw, Selection As Per Approved Hydraulic Flow Calculations. , Sitc Of Warning Sign Board With Marking Gas Discharge. Do Not Enter. Shall Operate On 24 V Dc, Driven Through Gas Release Panel. ( For Use Outside Room ) , Sitc Of Warning Sign Board With Marking Gas Discharge. Evacuate Immediately. Shall Operate On 24 V Dc, Driven Through Gas Release Panel. ( For Use Inside Room ) , Sitc Of Ul Listed Cylinder Low Pressure Switch , Sitc Of Ul Listed Cylinder Discharge Pressure Switch, Shall Be Install On The Novec Piping After Discharge Hose. , Sitc Of Novec Piping & Manifold As Required, Sch 40; Astm A106 Gr B, As Per Flow Calculations For The Specific Hazard Volume And Stand To Hold, Position & Support The Manifold And Piping Properly. Pressure Testing For Piping With Nitrogen As Per Nfpa 2001. , Supply Installation Testing & Commissioning Oful Listed Single Zone Gas Release Panel Facility To Connect Manual Abort / Release Switches. The Panel Shall Provide Potential Free Contacts For First Knock, Second Knock, Trouble / Fault Status. The Panel Shall Be Complete With Red Colour Housing, Monitored Power Supply Unit, Battery Charger & Batteries. , Supply Installation Testing & Commissioning Ofmanual Abort Stations, Shall Be Fitted With Transparent Hinged Covers To Avoid The Possibility Of Accidental Operation. The Abort Will Be Monitored Simultaneously By Fire Alarm Or Bms System. , Supply Installation Testing & Commissioning Of Manual Release Stations, Shall Be Fitted With Transparent Hinged Covers To Avoid The Possibility Of Accidental Operation. The Release Switch Will Be Monitored Simultaneously By Fire Alarm Or Bms System. , Towards Conducting Room Integrity Test : Door Fan Test To Meet The Requirements Of The Nfpa 2001, And Predicting The Efficacy Of The Protected Area Enclosure From The Perspective Of Fire Suppression. , Supply Installation Of 2 Core X 1.5 Mm2, Multistranded At Copper, Frls Armoured Cable, Red In Colour. The Cable Shall Belaid On Surface With Gi Saddle-Spacers Every 0.3 Meters. Complete With Gi Junction Box, Lugs, Cable Compression Glands, Cable Tags And Ferruling. , Public Address System , Supply, Installation, Testing And Commssioining Offollowing Items , Ul Listed, 6 Watt Ceiling Mount Speaker With Junction Box For Ceiling Mount , Goosneck Micro Phone , Cd / Mp3 Player , 6 Zone Selection Panel For Pa Announcement , Rack To Mount Amplifier, Cd Player And Console , 2 Core 1 Sq.Mm Copper Conducter Cable With 20 Mm Dia Pvc Conduits , Lannetwork , Supplying And Drawing Of Utp 4 Pair Cat 6 Lan Cable In The Existing Surface / Recessed Pvc Conduit As Required. , Supplying, Installing & Testing Utp Connector ( Rj-45 ) As Per Specification No. Wg-Nas / Utpc. , Supplying And Fixing Following 3 Module, Gi Box Along With Modular Base & Cover Plate As Required. , Supplying And Fixing 1 Meter Length, Utp Patch Cord Of Cat 6 Type In Position As Per Requirement. , Supplying And Fixing 24 Port Patch Panel With Tool-Less Keystone Jacks In Provided U Rack Complete As Per Requirement. , Supply & Fixing Of 25Mm Pvc Conduit With Accessaries. , Sitc Of It Rack -19 Wall Mounted President Quality Rack 15U ( Double Section ) With Acrylic Glass Door With The Accessories - [ Two Fan Position Tray With Two 90 Cfm Fans ( Ac 230V ) , 3 Horizontal Cable Manager- 3Nos, Ac Power Panel Strip With 5 X 5 Amp Sockets , Fuse And On / Off Switch, 1 Packet Mounting Hardware , Supplying And Fixing 7 Ft Length, Utp Patch Cord Of Cat 6 Type In Position As Per Requirement For End Point Device ( Pc / Laptop Etc ) , Sitc Of Lazr Speed 300 Fiber, 6 Core- Indoor Application, Multimode, To Be Laid Through Conduit And Flexible With All The Connectors, Couplers, Pigtels, Lius At Both End , Telephonenetwork , Supplying & Erecting Jelly Filled Armoured Telephone Cable 20 Pair With 0.5 Mm Dia. , Supplying, Erecting & Commissioning Of Telephone Tag Block With Crone Module Suitable For 20 Pairs As Required. , Supplying And Fixing Of Rj-11 / Rj-45 Modular Telephone Socket With G.I. Switch Box, Modular Plate Including Connections As Required. , Supplying, Installing, Testing & Commissioning Approved Type Push Button Telephone Instrument Desk Top / Wall Mount Unit As Per Specification In Approved Manner. ( Panasonic Model No Kx-Ts 580 ) , Supplying And Drawing Of Utp 4 Pair Cat 6 Lan Cable In The Existing Surface / Recessed Pvc Conduit As Required For Ip Phone. , Ip Telephone Instrument. , 24 Port Poe Network Switch’S, Gigabit Ethernet Web Smart Chassis In A 1U Form Factor With 24X10 / 100 / 1000Poebase-Tports, 2Fixedsfp ( 1G ) Withinternalpowersupply ( 192Wpoe Budget ) . , 8 Port Poe Network Switch’S, Gigabit Ethernet Web Smart Chassis In A 1U Form Factor With 24X10 / 100 / 1000Poebase-Tports, 2Fixedsfp ( 1G ) Withinternalpowersupply ( 192Wpoe Budget ) . , 12U Wall Mounted Double Section Rack With Acrylic Glass Door Having 2 Nos. 90 Cfm Fans, Cable Managers, 5A Sockets, Fuse, On / Off Switch, 1 Packet Mounting Hardware, Etc. , Supply & Fixing Of Cat 6 , 24 Port Patch Panel Loaded. , Supply & Fixing Of 2 Mtr. Patch Cord. , Supply & Fixing Of 25Mm Pvc Conduit With Accessaries. , Cctv System , Supply, Installation, Testing And Comissioningof The Following Equipment For Cctv System , Indoorip Base Day & Night, 2Mp Hd Resolution With Ir Illumination, Varifocal Lens Cmos, Resolution 1920X1080p @ 25 Fps, Widedynamicrange @ 90 Db, Wdr Ccd Dome Cameras, 2.8Mm To 12Mm Ir Lense, Min. 15Mtr Coverage, Sd / Sdhc Memory Card Slot., Camera Should Be Poe Enabled. The Camera Should Be Onvif Compliant. , Indoorip Base Day & Night, Fixed Dome Cameras, 2.8 Mm Ir Lens, Minimum 110 Degree Of Horizontal Field Of View, Resolution 1920 X 1080P @ 25 Fps, 10 Mtr Coverage, Camera Should Be Poe Enabled. The Camera Should Be Onvif Compliant. , Supply, Installation, Testing And Commissioning Of 16 Port 10 / 100T Managed Poe Access Switch With 2 Sfp Uplinks ( Layer 2 ) . Configuration To Be Decided By Vendor Base On Real Time Image Transmission From Camera / Encoder To Server. All The Switches Should Be In Racks. , Supply, Installation, Testing And Commissioning Of 16 Ports 10 / 100 / 1000T Managed Poe Switch ( Layer 3 ) Along With Sfp Module. Configuration To Be Decided By Vendor Base On Real Time Image Transmission From Camera / Encoder To Server. All The Switches Should Be In Racks. , Nvr / Nas & Vms , Supply, Installation, Connfiguration, Testing & Commissioning Of Video Networked Recorder ( Nvr ) Of Suitable Channel With 30 Days Motion Based Storage At 20 Fps, Along With Vedio Management Software ( Vms ) Along With Required Camera License. , Supply , Installation , Testing And Commisioing Ofcat-6 Cable For Power / Data Cabling From Camera To Switchwith 25 Mm Pvc Conduit. , Supply, Installation, Testing And Commissioning Of Color High Resolution Led Tv Comprising Of 42 Display, Full Hd, Hdmi Input Provision; Complete With All Supports And Accessories. , Sitc Of 6Pair Multimode Fiber Optical Cable With Termination All Necessary Accessories And Termination As Required. , Cat-6 Iowith Back Box & Surface Plate , Cat-6 Patch Cords , Access Control System Comprising Of Following , Supplying, Installing, Testing & Commissioning Of The Access Control System Consisting Of The Following: , Supply , Installation, Testing And Commissioning Of 4 Reader Ip Based Door Controller For Controlling The Above Card Readers As Per Specification Mentioned Including All Accessories.Max. 4 Reader Combition ( Tenderer To Mention Quantity Of Controllers Based On Their System. ) System Should Have Capability To Expand Up Toadditional 100 Doors In Future. , Supply , Installation, Testing And Commissioning Of 2 Reader Ip Based Door Controller For Controlling The Above Card Readers As Per Specification Mentioned Including All Accessories.Max. 4 Reader Combition ( Tenderer To Mention Quantity Of Controllers Based On Their System. ) System Should Have Capability To Expand Up Toadditional 100 Doors In Future. , Sitc Of Biometric Fingerprint + Pinpadreader , Supply , Installation, Testing & Commissioning Of Proximity Card Readers As Per Specification Suitable For Mounting On Metal Surface / Metal Frames Or Wooden Frames Wall Or As Required Based On Site Conditions Including All Accessories , Sitc Of Panic Bar With Egress Switch , Supply , Installation, Testing And Commissioning Of Smart Cards As Per Specification. , Sitc Of Break Glass Unit For Access Doors , Sitc Of Single Leaf Electromagnet Door Holder ( Fail Safe Type ) Of 600 Lb Holding Force , Sitc Of Double Leaf Electromagnet Door Holder ( Fail Safe Type ) Of 600 Lb Holding Force , Sitc Of Door Contact Sensor , Sitc Oftime, Attendance And Visitor Management Software For Access Control With Seamless Integration With Bms Module, Visitor Management Module And Time And Attendance Module As Per The Specifications. Software Shall Be Capable Of Handelling Additional 10 Nos. Of Access Readers. , Supply , Installation , Testing And Commisioing Ofclient Workstation Processor -Intel Core I-7 Os -Genuine Windows Xp / 7Prof Colour Monitor -21 Flat Panel Lcd / Led Monitor Ram -16 Gb Ddr3 Sdram Memory -1 Tb Hdd A4 Laser Jet Printer Network: 100 / 1000 Mb Ethernet Network Card Resolution Support: 1024 By 768; 1280 By 1024; 2048 By 768; 2560 By 1024 , Cables & Accessories For Acs System , Supply , Laying , Testing And Commissioning Of The Following Cables Signal & Communication Cablesfor Security Access Control, Alarm Monitoring System With All Accessories Including Glanding And Termination. , 6 Cx 1Sqmmshielded Armouredsheilded Cable , 4Cx 1Sqmmshielded Armouredsheilded Cable , 2Cx 1Sqmmshielded Armouredsheilded Cable , Cat 6 Cable For Network Controllers With 25 Mm Pvc Conduit , Building Management System Comprising Of Following: , The Rate Of Each Item Of Work For Bas Shall Also Include The Following : 1. All Materials, Fixing Materials, Accessories, Appliances, Tools And Equipment. 2. Approvedcoverplates For Inspection, Junctionandoutlet Boxes. 3. 2 Mm Thick Outlet Boxes And Junction Boxes. 4. All Fixing Accessories Such As Clips, Nails, Screws Etc. 5. Providing And Fixing Approved Saddles, Hooks And Grouting The Same As Required, In The Case Of All Exposed Cable Work. 6. Embeddingcablesand Accessories Inwall, Floorsetc.Duringconstruction And / Or Cutting Chases And Makinggood As In The Case Of All Concealed Cables Work. 7. Testing And Commissioning Of Each Device As Per Approveddesign Concept , Sitc Ofduel Core2 Quad, 80Gb Hdd, 2Ghz Processor, 8Gb Ram, 52X Cd Rom Drive 1.44 Fdd, 17 Colour Monitor, Microsoft Bus Mouse, 2 Serial, 1 Parallel Port & Windows Xp Operating System , Sitc Of Colour Inkjet Printer , Supply Of Necessary Software Packages Containing Building Management & Control Software Programmes With Dynamic Graphics Interfaces , Software And Hardware Required For Integration Of Following Third Party System With Bms , Energy Meters - 5 Nos. , Ups - 4 Nos. , Dg ( 2 Nos ) & Transformer ( 1 No. ) , Cooling Unit8 Nos. , Pdu - 2 Nos. , Supply, Installation, Testing & Commissioning Of Stand Alone, Intelligent, Ul Listed, Interoperable Ddc . , Ddc Controller For Monitoring As Per Io Summary , Room Temperature Cum Rh Sensor , Room Temperature Sensor , Outside Temperature And Rh Sensor , Hydrogen Sensor , Wi-Fi Modem For Tap Off Box Meters Data Connectivity. , Signal Cable 2 Core 1.5 Sq.Mm Pvc Insulated Cu Armoured Cable , Communication Cabling ( Cat-6 ) For Bms In Pvc Conduit , Supply , Installation , Testing And Comissioning Of 16 Port Unmanaged Network Poe Switch With Accessories. , Rodent Repellent System Comprising Of Following: , Digital Master Console Catering Lp 12 Satellites For Rodent Repellent System , Satellites ( Streem ) , Wall Mount Bracket , 2 Core 1 Sq.Mm Cu. Flexible Shielded Cable Bundle ( 300 Yards ) With 20Mm Pvc Conduit , Rrp Software , Water Leak Detection ( Wld ) System: , Sitc Of Water Leak Detection Panel With Modbus Connectivity ( For All Data Center Server Area , Ups Locations And Electrical Control Rooms ) , Sitc Of Water Leak Detection Module , Water Leak Detection Cable Sensor , Electronic Hooter , 2 Core X 1.5 Sqmm Frls Armoured Copper Cableas Per Technical Specification , Miscellaneous Items , 150X150x3mm Danger Notice Board & 415 Enameled Danger Board , 150X150x3mm Danger Notice Board & 11Kv Enameled Danger Board , Shock Treatment Chart With Frame In Local & English Language , First Aid Medical Box , Supplyandinstallationof9 Kgcapacityco2 Typefire Extinguishers Conforming To Is : 2171 , Abc Type – Manual Fire Extinguishers With 6Kgs. , Providing Of Set Of 4 Nos.9.5 Litre Capacity G.I. Buckets Painted In Post Office Red Colour With Prior Coat Of Red-Oxide Paint And Written With White Paint Fire And , Mounted On Ms Angle Iron Frame With Bracket Of Appropriate Size And Capacity Including , 1000 X1000 Mm Wide 2.5Mm Thick Rubber Matting Suitable For 1100 Grade , Providing Pair Of Duly Tested Rubber Hand Gloves As Per Is:340715 Suitable For Working On 11Kv And 415V Supply. , 50Mm Size Pvc Flexible Conduit , 25Mm Size Pvc Flexible Conduit , 50Mm Size Pvc Rigid Conduit With Accessories , 1 Year Warranty Is Included In The Above Items. Cmc Rate ( Electrical Components ) Post 1-Year Warranty Period Will Be Fixed At 5% Of The Of The Cost Of The Equipment For Each Year For Up To Six Years Without Any Escalation Clause , Hvac , Variable Refrigerant Volume ( Vrv ) , Sitc Of Variable Refrigerant Volume Modular Type Air-Conditioning Equipment Complete With Indoor And Out Door Units With Central Control System Unit Shall Have Central Controller For Controlling All The Indoor And Outdoor Units And Should Be Capable Of Integration With The Computer System Based Building Management System Of Hvac , Outdoor Unit , Supply Installation, Testing & Commissioning Of Modular Type Variable Refrigerant Flow / Variable Refrigerant Volume Air-Cooled Outdoor Units Suitable For Cooling And Heating, Having All Hermetically Sealed Inverter Type Scroll Compressor ( S ) , Minimum Two Compressors For Above 14Hp Modules, Microprocessor Based Controller , Top Discharge Type Condensing Unit ( S ) , With R410a Refrigerant, Vibration Isolators, With Suitable Foundation Etc. Complete As Required. The Unit Shall Deliver The Rated Capacity At Ahri Condition Sand Work Even At 50°C Ambient Temperature Without Tripping. The Unit Shall Be Suitable To Work On 400V+ / -10%, 3Phase, 50Hz Ac Power Supply. The Unit Shall Be Filled With First Charge Of The Refrigerant And Ready For Use As Required. The Cop At Ahri Conditions Shall Not Be Less Than 3.1 And Ieer Not Less Than 6.5 , System 1 : 18 Hp ( Cold Type ) , System-2 : 10 Hp ( Cold Type ) ( 2W+1S ) , Indoor Units ( Vrv / Vrf Compitable ) , Supply, Installation, Testing And Commissioning Of Following Minimum Capacity 4- Way Flow Vrv / Vrf Cassette Type Indoor Ceiling Mounted Unit Equipped With Synthetic Washable Media Pre-Filter, Fan Section With Low Noise Fan / Dynamically Balanced Blower, Multi Speed Motor, Coil Section With Dx Copper Coil, Electronic Expansion Valve, Outer Cabinet, Drain Pump, Grill, Necessary Supports, Vibration Isolation, Cordless Remote Control Etc., Suitable For Operation On Single Phase 230V±10%, 50Hz Ac Supply, Complete, Asr Equired. The Unit Shall Have Automatic Force Shut Down Provision In Case Of Fire On Receiving Signal From Bms System.The Cooling Capacity Of Indoor Unit Wil Be At Air Inlet Conditions Of 27 Degreec Db And 19 Degree C Wb Temperature. , Cassette Unit With Inbuilt Drain Pump , 2.8 Tr , 2.4 Tr , 1.6 Tr , Supply, Installation, Testing And Commissioning Of Following Minimum Capacity Vrv / Vrf High Wall Type Indoor Unit Equipped With Synthetic Washable Media Pre-Filter, Fan Section With Low Noise Fan / Dynamically Balanced Blower, Multi Speed Motor, Coil Section With Dx Copper Coil, Electronic Expansion Valve, Outer Cabinet, Cordless Remote Control, Drain Pan, Necessary Accessories Etc., Suitable For Operation On 230V±10%, 50Hz, Single Phase Ac Supply, Complete As Required. The Unit Shall Have Automatic Force Shut Down Provision Incase Of Fire On Receiving Signal From Bms System. The Cooling Capacity Of Indoor Unit Will Beat Air Inlet Conditions Of 27 Degree C Db And 19 Degree C Wb Temperature. , 2 Tr , 1.65 Tr , 0.8 Tr , Floor Mounted Ahu Vertical / Horizotal , Supply, Installation, Testing & Commissioning Of Double Skin Floor Mounted Horizontal / Vertical Ahu Having 50 Mm Sandwiched Puf Insulation ( 0.80 Mm Thk Inner Skin & 0.80 Mm Thk Outer Plasticized Gi ) . It Shall Have Pre-Filter ( 90% Down To 10 Micron ) Of Washable Type > 6Row Vrv / Vrf Dx Cooling Coil Having 12-13 Fpi And Anti Corrosion Coatingfins With Face Velocity Of 500 Fpm > Didw Kruger Quality Backward Curved Fan With Tefc Squirrel Cage Induction Motor With Drive Set. Other Accessories Like Inspection Door, Vibration Isolator, Limit Switch, Marine Light, Outlet Mouth Damper For Supply To Be Provided. Insulated Ss 18G Drain Pan With 19Mm Thich Class O Nitrile Rubber Insulation. The Outlet Velocity Not More Than 7.5 M / Sec. Motor Shall Be Ie3, Class F Insulation, Ip55 Rating, & Suitable For 415 ± 10 % Volts, 3 Phase, 50 Cycles Ac Supply. The Noise Level Should Be Less Than 65 Dba At 1.5 M Distance. Unit To Be Tripped On Receipt Signal From Fire Damper Installed In The Room And Interconnection With Fire Damper Shall Be Provided. Note:- Ahu Should Supply With Inbuit Control Panel Which Is Bms Compititble. , 14 Tr / 5600 Cfm / 50 Mm Esp ( External Static Pressure ) ( Vendor To Verify The Esp As Per Drawing For Supply And Calculate The Total Including Internal Pressure Drops -Filter / Coil / Etc. ) Ahu Should Have 1Working +1 Standby Motor. , Ahu Connecting Kit , Refnet Joints And Other Fittings , Supply And Installation Of Hard Drawn 16G Copper Tubing Insulated With 19 Mm Thick Class O Nitrile Rubber Insulation With Gc Cloth Insulation Shall Be Provided With Weather Proof Additional Cover For Exposed Areas. For Indoor Units Tubing Of Appropriate Diameter To Be Provided. All Piping Inside The Room Shall Be Properly Supported With Hanger And All External Piping Shall Run In Covered Cable Tray. Piping Quantity Is Mentioned Is For Pair Of Suction And Discharge Pipes. , Gas Charging And Testing & Commissioning Of The System , Supply & Installation Of Transmission & Control Wiring With Gi Conduit Between Indoor And Out Door Unit. , ( 2 Core X 1.5 Sq Mm Cu.Cable ) , 4 Core X 4 Sqmm Cu Cable , Supply & Installation Of Support Arrangement For Out Door Units, Ahu With Necessary Vibration Isolation Arrangement, Ms Frame For Mounting The Units To Be Provided With Rubber Pads, The Frame Should Be Painted With Two Coats Black Colour Synthetic Enamel Paint. , Supply & Installation Of Gi Class C Drain Pipe With 13 Mm Thk Nitrile Rubber Insulation , 32 Mm Dia , 25 Mm Dia , Supply & Installation Of Perforated Type Powder Coated M.S. Cable Trays Of 50 Mm In Height & 2.5Mmthick With Two Coats Of Red-Oxide And With Necessarysupporting Frame Etc , 200 Mm Wide , 300 Mm Wide , Supply & Installation Of Bms Integration Charges For The Vrv Outdoor Unit / Indoor Units From Central Controller To Bms. All The Outdoor / Indoor Unit Parameters Will Be Integrated Through Bms & Required Hardware / Software To Be Included Via Modbus / Bacnet. , Supply , Installation , Testing & Commissioning Of Split Type Airconditioners With Scroll Compressor Comprising Indoor Air , Outdoor Condensing Unit, With Stand And All Other Necessary Hardware For Proper Hanging Of Units. , Hiwall Split 2.0Tr Ac ( 3 Star Rating ) , Hiwall Split 1.5Tr Ac ( 3 Star Rating ) , All Refrigerant Piping Shall Be Of Copper, Complete With Supports Between Indoor & Outdoor Units Duly Insulated With 13Mm Nitrile Rubber Insulationwith Gc Cloth.Rmt Indicated Is For Set Of Piping Between Indoor And Outdoor Machine, Individual Piping Will Not Be Measured. , 1 / 4, 5 / 8 Or Equivalent To The Unit , 1 / 4, 1 / 2 Or Equivalent To The Unit , Air Distribution System , Design, Supply, Fabrication And Installation Of G.S.S. Ductingon Every Branch If There Is, With Required Hardware’S, Supports, Wooden Frame And Painting On Ducts, Ms Parts Etc As Per The Smacna Standard, Approved Drawings And Instructions Of Engineer-In-Charge With The Following Gauges. The Ducts Shall Be Fabricated From Galvanized Steel Sheets Class Viii - Light Coating Of Zinc Conforming To Iss: 277-1962 ( Revised ) With Accompanying Mill Test Certificates.Galvanizing Shall Be Of 120Gms / Sq.M. ( Total Coating On Both Sides ) .Exposed Duct Should Provide With 26G Aluminium Cladding. , 24 G ( 0-750 ) , 22 G ( 751-1500 ) , 20 G ( 1501-2250 ) , 18 G ( 2250 Above & Plenums ) , Supply, Installation, Testing And Commissioning Of Gi Volume Control Duct Damper With Bronze Bush Bearing Complete With Neoprene Rubber Gaskets, Nuts, Bolts, Screws Linkages, Flanges Etc, As Per Specifications. , 18G Gi Constructed Vcd , Supply, Installation, Testing & Commissioning Of Back Draft Damper , 18G Gi Constructed Bdd , Supplying, Fixing Testing Commissioning Of Supply Air Diffusers Of Powder Coated Aluminium With Aluminium Volume Control Dampers With Anti Smudge Ring & Removable Core. , Supply, Installation, Testing And Balancing Of Powder Coated Extruded Aluminium Return Air Diffusers With Removable Core In Accordance With The As Directed And As Instructed By Oic-Es , Supply, Installation Of Extruded Al. Powder Coated Louvers For Fresh Air Intake & Exhaust Complete Withss Bird Screen Mesh. , Supply, Installation, Testing And Balancing Of Extruded Al. Powder Coated Supply / Return / Exhaust Air Grilles With Bronze Bush Bearing Sleeve Of Different Sizes , Without Collar Damper , 150 X 150 With Collar Damper For Toilet Exhaust , Supply Installation Testing And Commissioning Of Motorised Fire & Smoke Damper , Casing Made Of 16G Gi With Factory Fitted Gi Sleeve Of 18G, 120 Min Fire Rating Complete With Standard Accessories As Per Ul-555S. , Total Area - Fire Damper With Pvc Gear ( Only Damper Price ) , Smoke / Fire Sensors With All Controls, Accessories, Actuators, Extended Sleeve For Wall Mounted ( Actuator Outside Wall ) And Other Accessories - Torque 5 Nm , Supply, Fabrication, Installation And Testing Of The Flexible Connections Constructed Out Of Fire Resistant Double Canvas Sleeve As Per Instructed And As Directed By Oic-Es , Supply, Installation, Testing And Balancing Of Extruded Al. Profile Powder Coated Supply & Return Slot Diffuser Of Diiferent Sizes. , 4 Slot Of 25 Mm Slot Opening , Hit & Miss Damper , Inline Fan , Supply, Installation, Testing & Commissioning Of Cabinet Type / In Line Fan Complete With Forward Curved / Didw Centrifugal Fans, Motor And Drive. It Shall Be Suitable For 230 ± 10% V, 1 Phase, 50Hz Ac Supply.. Other Accessories Like Inspection Door, Vibration Isolator Outlet Mouth Damper To Be Provided. , Cap:500 Cfm / 12 Mm Wc , Insulation , Supply And Installation Of External Thermal Insulation Class O Closed Cell Elastomeric Nitrile Rubber Insulation With Adhesives On Ducts, Tapes As Per Instuction And As Directed By Oic-Es , 13 Mm Thick For Supply Air Duct In Return Air Path , 19 Mm Thick For Supply Air Duct , Supply, Installation And Testing Of Acoustic Lining For Supply And Return Air Ducts Of Following Thickness Of Rigid Fiber Glass Of 50Kg / Cum Density Covered With Factory Laminated Rp Tissue And Finished With 26G Perforated Aluminium Sheet As Per The Specifications. , 25 Mm , 1 Year Warranty Is Included In The Above Items. Cmc Rate ( Hvac Components ) Post 1-Year Warranty Period Will Be Fixed At 5% Of The Of The Cost Of The Equipment For Each Year For Up To Six Years Without Any Escalation Clause , Part – B: Hpc, Cdc And Other Related Work , Research Cluster - Head Node-1 ( 1+1 Redundency ) : Dual Intel Xeon Gold 5320 26 Core, 2.2 Ghz; 128 Gb Ecc Ddr4 Ram; Shared Storage – Raid-5 / 6 Usable 10 Tib Read Intensive Ssds Or Sas 10K Rpm Hdd With Hot-Spare, Ha Configuration , Research Cluster - Login -1 ( 1+1 Redundency ) : Dual Intel Xeon Gold 5320 26Core, 2.2 Ghz; 512 Gb Ecc Ddr4 Ram; Shared Storage – Raid-5 / 6 Usable 1.9 Tib Read Intensive Ssds Or Sas 10K Rpm Hdd With Hot-Spare, Load Sharing With Dns Server , Research Cluster - General Nodes-1: Dual Intel Xeon Gold 6348 28 Core, 2.6 Ghz; 256 Gb Ecc Ddr4-3200 Ram In 100% Balanced Memory Configuration; 2 X 960Gb Mixed Use Ssds , Research Cluster - High Memory Nodes-1: Dual Epyc 7763 64 Core, 2.45 Ghz; 2048 Gb Ecc Ddr4-3200 Ram In 100% Balanced Memory Configuration; 2 X 1.9Tb Mixed Use Ssds , Research Cluster - Gpu Nodes-1: Dual Intel Xeon Gold 6348 28 Core, 2.6 Ghz; ( Or Equivalent / Better Amd Cpu ) ; 256 Gb Ecc Ddr4-3200 Ram In 100% Balanced Memory Configuration; 2 X 960Gb Mixed Use Ssds; 2 X Tesla A100 ( 80 Gb ) Nvlink / Bridge , Research Cluster - Gpu Nodes-2: Dual Intel Xeon Gold 6348 28 Core, 2.6 Ghz; 256 Gb Ecc Ddr4-3200 Ram In 100% Balanced Memory Configuration; 2 X 960Gb Mixed Use Ssds; 2 X Rtx A6000 / A40 Nvlink Or Pcie , Research Cluster - Interconnect / Network-1: A ) Gigabit Switch With All The Compatible Cables For Managing All The Cluster Components With Sufficient Ports. Managed Switches With Rps And Redundant Fans Need To Be Offered In The Solution. B ) Gigabit Switch With 10G Sfp+ Uplink Ports , All The Structured Cabling And Other Required Components For Connecting All The Client Devices ( Approximately 40 Clients ) In The Office Area; 100G Hdr Infiniband Off-Loading Fat Tree Internally Managed Network On Hdr-200 Switches, Secondary Cluster Management 1G Network Switches, Remote Management 1G Network Switch. Managed Switches With Rps And Redundant Fans Need To Be Offered In The Solution. Kvm Switch With Display, Keyboard / Mouse And Adequate Ports Is Required At Each Site For Easy Monitoring And Troubleshooting Of Installed Servers. , Research Cluster - Storage - Scratch-1 Lustre: 1 Pib Usable On Raid-6 ( 8+2 ) As Per Below :-200Tib ( 50 Gib / S Write / Read Each Individually ) Must Be Offered Using Flash Drives And 800 Tib ( 10 Gib / S Write / Read Each Individually ) Must Be Offered Using Ssd / Nl-Sas Drives; Scalable; All Ssd / Nl-Sas Components Should Be High-Endurance Enterprise Grade; The Metadata-Based File-Type Wise Policy For Data-Backup / Movement Should Be Provided. 1 Disk Hot-Spare Every 30 Disks. The Metadata / Object Storage Array Should Be Separate For Both Storage. Metadata / Object Storage Should Be Redundant And With Ssds Only Of Suitable Capacity As Per Solution Requirement With Minimum 90000 Files / Sec. , Research Cluster - Linux Licence ( Rhel Or Equivalent ) For Proposed Cluster , Research Cluster - Pcm Professional Cluster Manager Solution For Proposed Cluster - Perpetual Licence With Oem’S Support For 5Yrs , Research Cluster - Compiler : Latest Version Of Intel One Api Hpc Toolkit ( 2 Concurrent Users ) - With 5 Yrs Support From Oem Professional Workload / Scheduler Solution - Perpetual Licence With Support , Research Cluster - Pbs Pro Schedular Professional Workload / Scheduler Solution For Proposed Cluster + 2 Nodes - Perpetual Licence With Support For 5 Yrs , Research Cluster - Linux Mn ( Rhel Or Equivalent ) For Proposed Cluster , Virtual Servers ( 1+1 Redundancy ) : Dual Intel Xeon Gold 6326 16 Core, 2.9 Ghz; 512 Gb Ecc Ddr4 Ram In 100% Balanced Memory Configuration ; Latest Windows Data Centre Edition - Virtual Environment With Windows Hyperv Service; Expandable Shared 50 Tb Usable Raid-5 / 6 ( 8+2 ) San Storage ( 1 Disk Hot-Spare Every 30 Disks ) ; Scalable With All The Cables And Interface Cards To Establish The Connectivity With Redundant Host Server. , Display:At-Least 42 1080P / 4K Led Wall-Mount Smart Tv With Hdmi & Usb, 20 Watts Sound, X-Protection Pro Outside The Data Centre For Monitoring & Management. , Wifi And Lan : Dedicated 1Gige Lan Connectivity To Each Office Seating Space ( ~ 60 Ports / Users ) And Other Room. Managed Wifi Connectivity For Entire Area ( ~ 100 Concurrent Users ) Is To Be Installed In Compliance With Actrec It Infrastructure. Briefly, Two Dgs-1010P-E Switches And Five Ac1750 Aps Could Be Installed For This Requirement. , Software Solution For Comprehensive Building, Cluster, Interconnect, Network & Data Centre Resource Management , Man Power & Support ( 1 System Administrator For Day To Day Administration Of I.T. Infra, Container / Tool Installation / Maintenance, Web / Ftp-Servers, Back-Up Scheduling Etc. + 1 Data Centre Management Engineer ) , All In 3 Shifts For 24 X 7 X 365 Days Support Covered By Oem / Vendor For 5 Years. Actrec Will Advertise And Select Support Staff On Behalf Of The Vendor For Hpc And Cdc Management And Administration. Experienced Employees Of The Vendors Could Also Be Qualified For The Interview Based Upon The Experience. , Computational Data Centre ( Cdc ) Turn-Key: Any Other Work Required For Complete And All Inclusive Functioning Of Project Considering Turn-Key Project Should Be Described By The Vendor. Additional Items Included Here Should Be Justified And Detailed At The Time Of Submission. , Amenities: Projector, Interactive Display, Wall-Art, Plants, Recreation Room Accessories Etc As Per The Details In Tender Document , 5 Years Warranty Is Included In The Above Items. Cmc Rate ( Hpc, Cdc And Other Related Work ) Post 1-Year Warranty Period Will Be Fixed At 5% Of The Of The Cost Of The Equipment For Each Year For Up To Two Years Without Any Escalation Clause , Total Equipment And Works Cost :Part – A: Core Infrastructure ( Civil+Electrical+Hvac ) +Part – B: Hpc, Cdc And Other Related Work Including Cmc As Applicable

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Nov-2022 EXTENSION OF DUE DATES Date 29-11-2022
2 29-Nov-2022 CORRIGENDUM 2 FOR EXTENSION OF DUE DATES Date 06-12-2022
3 06-Dec-2022 THIRD EXTENSTION OF DUE DATES Date 19-12-2022
4 07-Dec-2022 Corrigendum post Pre-bid Technical Bid 19-12-2022
5 19-Dec-2022 Due date extension Date 02-01-2023
6 31-Dec-2022 Due date extension 5 Date 09-01-2023
7 09-Jan-2023 CORRIGENDUM NO.6 FOR EXTENSION OF CRITICAL DUE DATES Date 17-01-2023

Key Value

Document Fees
Refer document
EMD
INR 500000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:
Sl. No. Item Description
1PART – A: CORE INFRASTRUCTURE
2CIVIL
3Demolishing existing brick masonry with cement mortar and plaster at all floors and levels including scaffolding stacking of serviceable materials without damaging the adjacent masonry/RCC structure sanitary fittings & fixtures and disposal of unserviceable material carting away the debris out of hospital premises and scope also include dismantling and careful removal of doors, Distribution panel and storing and stacking complete all as directed by the Engineer-in-Charge.(existing toilets, guard room & record room & Ground Floor & all areas wherever required for HPC facility)
4Dismantling of wash basin and removing of wall tiles and all the allied stonework and pipes & fittings wherever necessary and disposal of unserviceable material carting away the debris out of hospital premises or handing over the same to Engineer-in charge
5FLOORING BREAKING: Dismantling carefully the existing damaged cracked serviceable tiles/slabs/clay tiles/Marble slab/granite slab/Kota stone/tandoor stone/Shahabad stone and all types of flooring in flooring etc. including removing the 20mm thick bedding of cement mortar stone grit or brick bat coba etc. at all floors & levels including stacking of serviceable material and disposing unserviceable material out of hospital premises as directed by the Engineer-in-Charge.
6Dismantling and removal of complete fire fighting system and handing over all the material (without any damage) anywhere within the campus as per the instructions of Engineer in charge. This includes Plant, machinery, equipment for cutting, welding and dismantling complete material safely.
7Demolishing cement concrete and bitumen road/kerb stone manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.
8Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle size 600mm Center to Center, lock and stopper etc. included in the item rate). anyquality approved by Engineer incharge based on sample.
9Providing and fixing of Hollow metal Un-Insulated fire rated doorsas per IS 3614 part-1, for stability and integrity. Pressed galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall be tested to IS 3614 part 2 / ISO 834-1 Part 1 / BS476 Part 20 & 22, CBRI / Certifire or third party certified or equivavelent lab, for maximum rating of 120mins, .Labeled doors with certification shall be with vision glass as a part of complete assembly. Deviation in specification and sheet thickness other than what is mentioned in the test certificates are not allowed. Proper label confirming the type of door and the hourly rating is mandatory. Door frame shall be single rebate grooved profile of size125 x 60mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs.door frames should be prepared for suitable hardware and should have necessary reinforcement to withstand regular wear and tear.Frames to have inbuild grooved sealing system and shall be site fitted with fire rated EPDM gasket as standard. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Door leaf shall be 46mm thick fully flush double skin door, Un-insulated with vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement. The glass should be 6mm clear borosilicate fire rated glass of relavant rating of the door.All doors and frames shall be finished Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of door and hardware as a complete assembly including door closure, hinges etc..All doors shall be provided with stainless steel hinges with concealed door closures of required capacity and rating. Provision of access control interlock and wiring shall be made in all door shutters and frames with requisite hardware. Rate excludes installation of Panic bar.
10Supply and Fixing of Slim Glass partition of 12mm Toughened Glass using System-45 Frames to a height of maximum 3m or as per drawing.The Fixed glass to be fixed usingBP45 Profiles at Top & Bottom &SP45 at sides (the profile is for reference). The profile size to be 45x25MM to be fixed on to the floor/wall/ ceiling as per the architect design.H Junction profile to be used at all Glass to Glass vertical joints, 90 Deg L Junction Profiles and T Junction profiles necessary as per design.In case of Glass overall panel MP45 & BP45 Overpanel Profile to be used.In case of Open glass edges EP45 End Profile to be used. The Alexa profiles shall be suitable for Glass thickness of 10/12/13.52mm.The Profile shall be 20 micron matt natural anodized, the Profile Manufacturer to supply all the necessary clips, seals and fixing accessories for the system. All Profiles to be with 2 mm Gauge thickness including 20 Micron of Anodizing.
11Supply & Installation of 2 Hrs Fire Resistance Rated - FM Approved - sandwiched Wall panels with 0.80 mm skin thickness with overall thickness of 150mm and with 98 +-2kg/Cu.m density of Rockwool insulation. Both sides GI powder coated sheet as per clients approved shade along with Flashing and with water resistant silicon sealant at required area and Providing necessary accessories for fixing of Metal Partitions as per drawings with GI profile for reinforcement. (inclusive of bottom track / interlock sections / silicon ) (Certificate for fire rating to be provided). Vision glass on all sides for direct observation of HPC from outside should be compatible with partition and in fire rating and with maximum dimension of 1m*1m. With Porcelain finish having rewritable capabilites and printing work to be done wherever required as per the instruction of engineer in charge. One side measurement will be taken. Anyquality approved by Engineer incharge based on sample.
12Supply & Installation of 2 Hrs Fire Resistance Rated - FM Approved - sandwiched Wall panels with 0.80 mm skin thickness with overall thickness of 50mm and with 98 +-2kg/Cu.m density of Rockwool insulation or 40+-2Kg/Cum PUF insulation . Both sides GI powder coated sheet as per clients approved shade along with Flashing and with water resistant silicon sealant at required area and Providing necessary accessories for fixing of Metal Partitions as per drawings with GI profile for reinforcement. (Certificate for fire rating to be provided) as per the instruction of engineer in charge. One side measurement will be taken.
13Supply & Installation of 80mm thick Sliding Folding partition with aluminium frame, track and trolley and 1mm thick hard pressed laminate finish of approved shade on both sides in the middle of conference room including all the hardware, accessories and rotating and retracting mechanism required as per the instruction of Engineer in charge complete. One side measurement will be taken.
14TOUGHENED LACQUERED GLASS PANELLING: Providing and fixing of 6mm thick Toughened Glass(premium GRIHA rated lacquered glass from glass manufacturer) of approved colour by DoIT&C, mounted on CLIP (J/J1/I type) or equivalent on a perfectly levelled surface (12mm thick water proof marine plywood / ACC Blockwork / Aluminium channel / Bare RCC wall surface). Lacquered strong glass must be made industrially (via curtain coating process); opaque (if viewed against a support wall), coated with PU lacquer (100 micron thick); colour consistency (measured by spectrophotometer CM5081); highly durable (passes PERSOZ hardness test for minimum 220 oscillations); humid resistant (conforms to BS EN 1036 1999); environmentally friendly (no lead, no arsenic, no copper, no formaldehyde); appropriate recycled content (12% post industrial / 6% post consumer); compressive strength (1000 MPa) & tensile strength (40 MPa),same as float glass. Tempering should be done as the EN 12150. Glasses are to be fixed with polymer clips ( Single Sided J1 & J2 Type, Double sided I Type ),white backing foam and grey impact absorbing foam; to accommodate upto ± 10mm substrate undulation,and with a horizontal load capacity of 30Kg/100mm and vertical pullout load > 200kg/100mm, Glass should be supported with 1mm thick lip covering upto 3mm of glass surface; clips should be fixed using durable, non corrosive, strong S.S.screw 45mm long. All wooden material to be used shall be Anti-termite treated. The measurement only for the portion covered by glass to be considered.
15Providing and fixing fabric backing commercial grade wall paper of approved shade with recommended adhesive of approved quality which have 100% washable, scratch resistance, peel proof, and fire retardant properties. The wall paper should give a seamless finish. Including Cost of preparation on the base surface for fixing the wall paper as per the manufacturer specification, complete in all respect as per direction of EIC.
16Supply & Installation of 80mm thick insulated metal partition cladded with Fabric and insulated with Glasswool/Rockwool for sound insulation. The partition should have provision for modular electrical and plumbing fittings as per the site conditions. Skin Thickness - 0.6 to 0.8mm. Finish : Powder coated. Face of partition : Interior Face: G-90 galvanized or AZ-50 aluminum-zinc coated steel in 26, 24 and 22 Ga.
17Supply & Installation of 80mm thick insulated metal partition cladded with Fabric (towards conference room), on the other side clad with Marine MDF. Insulated with Glasswool/Rockwool for sound insulation. The partition should have provision for modular electrical and plumbing fittings as per the site conditions. Skin Thickness - 0.6 to 0.8mm. Finish : Powder coated. Face of partition : Interior Face: G-90 galvanized or AZ-50 aluminum-zinc coated steel in 26, 24 and 22 Ga.
18Providing and fixing Flush doors 35mm thick with 1.0 mm laminates on both sides. The item includes Teakwood chaukhat (Frame) made from 75x50 teakwood. The door to have 12mm teak wood lipping on edges. The door is to be complete with Cylindrical door Lock , 200mm SS/Brass handles, Tower bolts, 119mm Brass /SS hinges, SS Door stopper with double rubber stopper and necessary screws etc. all Teakwood surfaces to be malamine polished complete to the satisfaction of Architect/Employer. Cost to include all edgings and vision panel of size 250mm*150mm.
19Providing&Fixing 50mm thick BWPGradeSingle leaf FlushDoorofsize(1200 x2400) IncludingTeakwood Lippingpatti12x55mmtoachieveexposedperiphery section of flush door finished with4mmthick Veneer outside & inside 1 mm thick laminate with suitable mounting door frame as required. Allwood& Veneer surfaces shall be finished with melamine polish as per approvedtint includingmoulding, nails,screws,Fevicol including necessary scaffolding & cleaning as per Architects detailed drawing & design etc. complete. The door is to be complete with Cylindrical door Lock, 200mm SS/Brass handles, Tower bolts, 119mm Brass /SS hinges, SS Door stopper with double rubber stopper and necessary screws etc. all Teakwood surfaces to be malamine polished complete to the satisfaction of Architect/Employer. Cost to include all edgings and vision panel of size 250mm*150mm. ( D1)
20Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete.
21Providing and constructingAAC Light weight Block Masonry with 75mm/100mm/150mm/200mm/300mm thick at all levels in by using approved block laying polymer modified adhesive mortar, including 75mm thick Patli / Stiffeners of M-15 Gradeat every 1000mm with 2 nos 8mm steel bars all to be considered in the cost and no separate measurement will be done for steel and patli, also including scaffolding, racking out joints, curing with curing compound etc. in line, level and plumb, All complete as per specification for all height of floor or as directed etc. ( Rate includes the cost of stiffeners hoop ). (No holes for scaffolding will be permitted into the blockwork)
22Grproc Plaster : Providing andapplying 1stqualityGyprocplaster(Gyproc Elite -90 ) including bonding coat of GYPROC BONDwith minimum 10-12mm thickness to internal brick/block/concrete walls at all position in proper line,level and plumb including scaffolding,cleaning,hackingofconcretesurface, removing debris out of site etc. complete. as directed to achieve perfect line level and plumb.
23Providing and applying plaster of Paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
24Providing and applyingAcrylic (Premium) Emulsion Paint of approved qualityandshadeonwallswithsand papering& cleaning the surface, applying one coat of primer and lambi/puttytofullsurface3times,thereafterpaintingthe surfaceintwo coatsoverbaseprimercoattoachieveeven finish. Rate is inclusive of all double scaffolding, all material and cleaning as per Manufactures standard application method & specification etc. complete.
25Providing and fixing artificial grass with recommended adhesive of approved quality which have 100% washable, peel proof, and fire retardant properties. The grass should give a seamless finish. Including Cost of preparation on the base surface for fixing the grassas per the manufacturer specification, complete in all respect as per direction of EIC.
26Providing and installing of 8mm thk brick claddingas per the manufacturer specification in approved pattern with backing coat of 1:4 cement plaster and neatcementfloatusingpolymerbasedtileadhesivesof approved quality including filling joints, complete in all respect as per direction of EIC.
27Providing and laying 600 x 600 vitrified tiles as specifiedbelowconformingtoI.S.15622-2006withwater absorptionlessthan0.08%forflooring and skirting ofanapproved, quality,and pattern /design for flooring including cementmortarbeddingof25mmthickin1:4proportion, cutting,levelling,jointing,fillingthejointsby app colour , curing, finishing etc. complete as directed by Engineer In Charge.As per manufacturer"s specifications.
28Providing and laying 800 x 800 vitrified tiles as specifiedbelowconformingtoI.S.15622-2006withwater absorptionlessthan0.08%forflooring and skirting ofanapproved, quality,and pattern /design for flooring including cementmortarbeddingof25mmthickin1:4proportion, cutting,levelling,jointing,fillingthejointsby app colour , curing, finishing etc. complete as directed by Engineer In Charge.As per manufacturer"s specifications.
29Providing and layingOutdoorVitrifiedtiles600mmx600mmas specifiedbelowconformingtoI.S.15622-2006withwater absorptionlessthan0.08%forflooring and skirtingofanapproved, quality,and pattern /design for flooring and skirtingincluding cementmortarbeddingof25mmthickin1:4proportion, cutting,levelling,jointing,fillingthejointsby app colour , curing, finishing etc. complete as directed by Engineer In Charge.
30Providing and layingLapato Finish Vitrified tiles 600mm x 600mmas specifiedbelowconformingtoI.S.15622-2006withwater absorptionlessthan0.08%forflooringand skirting ofanapproved, ` and pattern /design for flooring and skirting including cementmortarbeddingof25mmthickin1:4proportion, cutting,levelling,jointing,fillingthejointsby app colour , curing, finishing etc. complete as directed by Engineer In Charge.
31Providing and fixing 1st quality antiskidceramic floortile size 300x300 mm or more (thickness to be specified by the manufacturer) for flooring and skirting confirming to IS : 13755 and IS : 15622 colour such as white, grey, ivory, fume red brown, light green, light blue and other light shades in floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (including the cost of cement mortar bed 1:4).
32Providing and laying machine cut, mirror polished approved coloured granite slab of any approved size 20 +/-2mm thick for flooring in required pattern with approved coloured granite inlay work on a bed of 1:4 cement mortar including neat cement float, filling joints with neat coloured cement slurry, to match the colour of granite, curing, polishing and cleaning complete.
33Providing and laying machine cut, mirror polished Marble stone flooring and skirting, in required design (Simple geometrical, abstract etc.) and in patterns in combination with Italian marble stones of different colours, shades and finished surface texture etc., in linear portions of the building, all complete as per the architectural drawings, with 18 mm thick stone slab laid over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with white cement slurry @ 4.4 kg/sqm including pointing with white cement slurry admixed with pigment to match the marble shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. In combination with 18 mm thick Italian Marble stone slab,Perlato, Rosso verona, Fire Red or Dark Emperadore etc is to be included.
34Providing and Fixing machine made Synthetic Carpet having total Carpet weight more than 550 gm /sqm. And more than 5mm thickness superior quality complete in all respect as per direction of Engineer-in-charge. (Euronics or equivalent quality preapproved by Engineer incharge)
35Providing and laying machine cut, River Finish Graniteof anyapprovedsize20+/-2mm thick for flooringin required patternwithapprovedcolouredgraniteona 20mm thick bedof1:4 cement mortar including neat cement float, filling joints with neatcolouredcementslurry,tomatchthe colourof granite, curing,polishingandcleaningcomplete.
36Providing & Laying ofImported Engineered Wooden Flooringofsize 215 mm width xlength 2200 mm x 20 - 25 mm thick (As per manufacturer"s specifications),asperISO24346(EN428)texture&design,Top wear layer thickness 3.5 mm, with 3 MM Under lay of Foam with a direct laminated surface treated with aluminium oxide on top ofa high-density fibre board with a density of 850 Kg./per Mtr. having a click system tongue and groove joint to secure a long lasting joint. The planks are to be termite resistant and water protected with both side lamination,withPremiumfinish plank,glue freelocking system;2lock,with maximum floor surfacetemperature 27 C, with self –regulating under float heat system, With formaldehyde emission E1 as per EN 13986, Reaction to fire Dfl as per EN 13501 and100% recyclable with Mini-or maxi bevel lengthwise etc. complete. (Offices & Conference room)
37Kota stone slab flooring 25 mm thick over 20 mm (average) thickbase laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing completewith base of cement mortar 1 : 4 (1 cement : 4 coarse sand)
38Providing & fixing 12mm thick x 100 mm highfirst quality Solid TeakwoodSkirtingwherever necessary including Melamine polish shade to be match with the same matching shadeofwoodenflooring &withveneershadetoallwood surfaceswith 6mm groove between skirting & gyp/veneer to T.W.frameworkorT.W.panellingasperarchitect"sdetail drawing & design etc. complete.
39ProvidingandfixingmachinecutmirrorpolishedBLUE PEARLGRANITEstoneslabofrequiredsizeand20mm thick of approved quality ,vein and colour for dado fixed on base plaster on 20mm thick cement mortar 1:4 including filling joint with neatcolouredcementslurry,curing,handpolishing, Moulding, Edgefinishing,andcleaningetc.complete.
40Providing&fixingVitrifiedTilesfortoiletDado of size 600x600 as per manufacturer"s specificationanyothersuitablesize approvedby architect andofapprovedcolourandshade finished,in approved pattern with 12mm thick backing coat of 1:4 cement plaster/mortar and neatcementfloatusingpolymerbasedtileadhesivesof approved quality including filling jointsto match the colour of dado curing, acid cleaning etc. complete. FOR TOILET
41ITALIAN MARBLE CLADDING Providing and fixing machine cut and mirror polished approved coloured ITALIAN MARBLESLABwithinlaysofapprovedsize,20mm+2mm thk. Of approved quality for required pattern on a bed of 1:4 CM25mmaveragethicknessincludingneatcement float, filling joints with neat coloured pigment ,curing, polishingandcleaning,highglosstinoxidepolishwith ItalianPolishMachineetc. Complete.
42Providingand constructinggranite kitchen platformwith fixing of Quartz sink 600 mm x 450 mm size as per detailed drawing includingverticalbothsidepolishedGranite stone 19 to 22 mm thick Double supports with kadappah base 35 to 40 mm thick and polished granite19 to 22mm ontop with side strips of granite at front and both sides of platform raised with two vertical granite supportsincluding cutting, opening asperArchitectsdetailsdrawing anddesign asdirectedby Engineer In Charge. for sink of required size in Graniteetc. complete.(RateExcludesQuartzSink but includes rate for kadappah).Only total surface (Plan) area of platform to be measured
43Supply of quartz sink 600mm x 450 mm size including fixing the sink in position with waste coupling, bottle trap and any other fixtures all complete as per the specifications and directed by engineer-in charge.
44Providing & fixing Single piece Rimless Bowl for Coupled WC with UF soft close slim seat cover, Hinges, Fixing Accessories and Accessories Set, Size : 380x660x850 mm, S Trap - 250 mm. As per approved sample.
45Providing & fixing Soap dispenser Metallic Bottle. As per approved sample.
46P&F Soap Dish Holder.As per approved sample.
47Providing & fixing Toilet paper holder with flap Recessed Type (Stainless Steel).
48P&F Stainless Steel surface mounted sanitary Napkin Disposal(with Flap) of approved quality/ quality. Cabinet - 18-8, type-304, stainless steel size 270mm(L) X 105mm(W) X 385mm(D) Capacity:- 4.6 Litres Equipped with full-length stainless steel piano flap. As per approved sample.
49PAPER TOWEL DISPENSER. Cabinet - 18-8, type-304, size 265x90x365 Stainless steel Finish: Stainless Steel Satin Capacity: 450 C-fold, 600 multifold. As per approved sample.
50P & F Stainless steel Hand Dryer of approved quality/quality. Casing:Stainless Steel # 304 Non Magnetic, Matt Finish Mounting :Wall Mounted Operation :Touch-Free Infra-Red activation Sensor Range : 12 cm - 15 cm Hand Dry Time :Less than 20 secs Auto Cutoff: 30 seconds Motor:Brush Type, Dual Ball Bearings Speed:25,000 RPM Rated Power :550 W ( No Heating Element ) Current:2.5 A Protection Class :IP x 1 Blowing Volume : > 270 m3/H Air Speed:95 m/s (with speed controller) As per approved sample.
51Modular Cubicle based restrooms of Stainless Steel make with Stainless steel hardware with locking arrangement and 1 spare lock each.Handles and hinges to be included in the rate. Measurement per cubicle.
52P & F 1st quality WVC Urinal (IS:2556 MARK) with 25mm dia G.I. waste pipe, dome waste couplings, concealed iron brackets or screws etc. complete. As per Approved sample.
53P & F 12mm thick toughened glass urinal partition with all type fitting. (partition Size 300mm X 1050). As per approved sample.
54P&F Bevelled edge Mirror / mirror with 25mm width teak wood lipping including melamine polish around of special glass of approved quality as per direction of Engineer-in-charge complete with 6mm thick commercial ply basefixed to wooden screws & washers. (Size 600 x 450mm x 4 mm thick)
55False Flooring-Providing and fixing cementitious Access floor systems of Preferred/ standard quality confirming to EN12825 or equivalent standards. The Access floor system to be installed shall be of finished floor height of 450 mm from the existing floor level comprising of 600mm x 600mm cementitious square panels. The system will provide for suitable pedestal and under-structure designed to withstand various static loads and rolling loads subjected to it in server / rack area. The entire Access floor system will provide for adequate fire resistance, acoustic barrier and air leakage resistance. At least 4 nos. of lifting suction devices to be provided. The raised floor must be capable of withstanding a uniform distribution load of 1500Kg/Sq. mtr as per Specification.-IT Room(A4 server),IT Room(A2 & A3 server) & Power room
56Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat and two coats of acrylic paint of approved quality for primer and paint all complete.
57Plain cement concrete M15 grade using graced stone aggregate of 20mm / 40mm max. size including consolidation using vibrator & needle if required finishing, curing, form work shuttering, centering etc. complete all as per specification and in quantity as & when required by the Engineer-in-Charge,
58HEXAGON SHAPE CEILING made out of Folded Aluminium. The HEXAGON SHAPEunits shall be in 6 sides customise size of each side 750mm and 1mm (thick), non-perforated Aluminium. The ceiling Hexagon units shall be installed at distance of 300mm one Hexagon to second Hexagon. The Hexagon units are then attached to BAFFLE CEILING (included in scope of this item) by slotted cleats and screwing arrangement alongwith bolted brackets attached to ceiling by baffle splice and carrier splice combination with hangers and screw bolting to ceiling which is included in the scope.
59Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main “T” runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross “T” of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main “T” at 600 mm center to center to form a grid of 1200x600 mm and secondary cross “T” of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main “T” runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.GI Metal Ceiling Lay in plain Tegular edge Global white colour tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of Aluminium sheet having electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending.
60Providing & Supplying Stainless steelSS 202and abovePerforated type cylindricalDustBinof230mmdia&400mmheightas approved by Consultant. .
61ProvidingandapplyingthreecoatsofMelaminepolishof requiredfinishtowoodworkbyspraymachineincluding knottingandpreparingthesurfacebyscrapping,applying wood filler, scaffolding if required etc. .complete
62Providing and applying First Quality Metallic Transparent PU Coating of approved quality and shadeon plywoodor veneer wherever required with sand papering & cleaning the surface, applying one coat of primer and lambi/putty including wood filler to full surface 3 times, thereafter Polishing the surface in twofinishingcoatsoverbaseprimercoattoachieveeven finish. All complete as per instructions of Engineer In Charge. etc. complete
63Supplying&InstallingSunscreenperforatedRollerblind optima series - Basket 125 Tex with fabric specification of - ( Fabric composition polyester 22 % and PVC 78 % , Openness Factor - 5%, Thickness - 0.68MM +/- 5%, weight perm2-480.00gsm,yarnscountinwrap/weft/cm19/18+/- 5%,FireResistance-FR(USA)KFI(Korea),TearResistance- wrap11.9 daN+/-5%,WEFT 150 daN+/-5%,colour fastness-6- 7/8(whitecolourbase),artificiallightxenonlamp,UV resistance Min 3(White colour base),width 2.5M & 3 M The Roller mechanism shall be a moulded unit made from engineering gradeplastic polymerwith PVCspring support. TheFabricshallbeattachedtotherollertubewithhigh quality self adhesive tape with manual operation . The total area of opening covered will be measured.
64BLACKOUT-Providing,supplying&InstallingRoller BlindsinSECLUSIONserieswithspecificationof Basic material-1005Polyester,fabricwidth200/250cm,Fabric weight- 20/295g/sq.m. Thickness-0.50mm Finishing-Blackout Fabric,reverse&frontsidepigmentcolourcoatedcolour fastness>5/6,Rubbing Fastness-Depending on colour, shrinkage-wrap:<0.5%withapprovedshadefabric,( Forexternalwindows)comprisingofpolymercoatedfibre fabric.Therollermechanismshallbeamouldedunitmade fromengineeringgradeplasticpolymerwithPVCspring support . The fabric shall be attached to the roller tube with high quality selfadhesive strip.The total area of opening covered will be measured.
65Supply & fixing Rigid autoglow photo luminescent signages, on glowinthedarkrigidsheetwithhighintensityluminous propertiesenclosedintransparentweatherproofUV stabilized coated sheet with UV screen printing by imported ink thickness of photo luminescent sheet 1mm, glow should be visible for 24 hours in total darkness. These signs adheres to PSPAclassADIN67510Part2,BS5499-1,NFPA101etc. complete. Any and all sizes below 2ft*2ft.
66Providing and fixing Gypsum Cove as per Architects Drawing between ceiling & wall/column with GI frame support, finished from the top & sides by 12mm thick gypboard including making necessaryhousing for concealed lightfittings,speakers,etc.completeasperArchitectsdetailed drawing and design and as directed with necessary scaffolding etc. Complete.
67OfficeTable(MainCabinTable)-Providingandfixing Table & pedestal with 3 drawers (Size -400 X450X725) to be made out of 19mm thk BWP (IS710) marine ply cladded with 4mmthkveneer&finishedwiththreecoatsofmelamine fromoutside&0.8mmthkLaminatefinishedfrominside. Onlytabletopedgefinishedwithpostform&otheredges finishedinPVCedgebinding.Tabletop46mmthickness inside finished with 0.8mm thk laminate.Pedestal drawerto be operate with telescopic drawer channel as per detail drawing). Complete with All necessary hardware & Fixture. Note : All Furniture to Be Made Out ofCalibrated plywood (IS : 710) BWPAll Internal & External Surfaces of Plywood FinishedwithLaminateandveneerrespectively.All Hardware Complete as perdetailedDrawing & Instructions directedbyEngineerincharge.Includingloading, unloading, transportation,installation. With1yearwarranty. Rate to include wire manager system of approved quality SIZE: 1800 x 900 x 750 mm
68Thrive + with Head Rest Chair. Thrive Plus High Back with Headrest and Coat Hanger .Thrive Plus High Back with Headrest and Coat Hanger Generally Size in 75 cm * 75 cm Height 115-130.
69Bravo Visitor chairs width 61.4cm * depth 64.5cm*height 89.5cm * Seat Height 46.5cm
70SideStorage (DGMCABIN)-Providingandfixingside storageunittobemadeoutof19/12mmthkBWP(IS710) marineplycladdedwith4mmthkveneer&finishedwith melamine from outside & 0.8mm thk Laminate finished from inside. Only side storage top edge finished with post form & otheredgesfinishedinPVCedgebinding.Tabletopinside finishedwith0.8mmthklaminate. Complete with All necessary hardware & Fixture. Note : All Furniture to Be Made Out ofCalibrated plywood (IS : 710) BWP All Internal & External Surfaces of Plywood Finished with Laminate and veneer . All HardwareComplete as per detailed Drawing & Instructions directed by Engineer incharge.Includingloading,unloading, transportation, installation. With 1 year warranty.SIZE: 1050 x 400 x 750mm
71Workstation - Providing&Supplyingat site ,Workstation comprising of modular 1200mm height,60mmthickness partitionsystemwithpowder coatedAluminiumframingwithpowdercoated aluminiumcaping..RatetoincludeTable,25mm thick Postformed Top made out ofCalibrated plywood (IS : 710) BWP finishedwith P/F 0.6mm laminate with edge binding, wire management, Raceway- Double raceway Soft board+White board combination.In workstation table One side of table understructure 50 X 50full frame metal structure considerwithonesidemetalmodesty(600x450ht). Provisionfornecessarywiremanagementasdirected. Complete with All necessary hardware & Fixture. Note:AllFurnituretoBeMadeOutof Calibrated plywood(IS:710)BWP,AllInternal&External Surfaces of Plywood Finished with LaminateComplete, asperdetailedDrawing&InstructionsEngineerin charge.with1 yearwarranty. Ratetoincludewire managersystemofapprovedquality. SIZE : 1350/1350 x 600 x 750/1200mm
72Sharing Workstation - Providing & Supplying at site ,Workstation comprising of modular 1200mm height,60mmthickness partitionsystemwithpowder coatedAluminiumframingwithpowdercoated aluminiumcaping..RatetoincludeTable,25mm thick Postformed Top made out ofCalibrated plywood (IS : 710) BWP finishedwith P/F 0.6mm laminate with edge binding, wire management, Raceway- Double raceway Soft board+White board combination.In workstation table One side of table understructure 50 X 50full frame metal structure considerwithonesidemetalmodesty(600x450ht). Provisionfornecessarywiremanagementasdirected. Complete with All necessary hardware & Fixture.. Note:AllFurnituretoBeMadeOutof Calibrated plywood(IS:710)BWP,AllInternal&External Surfaces of Plywood Finished with LaminateComplete, asperdetailedDrawing&InstructionsEngineerin charge with 1 year warranty. Rate to include wire managersystemofapprovedquality. SIZE: 1200 x 600 x 750/1200.
73NonSharingWorkstation-Providing& Supplyingatsite,Workstationcomprisingofmodular 1200mmheight,60mmthickness partitionsystemwith powder coated Aluminium framing with powder coated aluminiumcaping..RatetoincludeTable,25mm thick Postformed Top made out ofCalibrated plywood (IS : 710) BWP finishedwith P/F 0.6mm laminate with edge binding, wire management, Raceway- Double raceway Soft board+White board combination.In workstation table One side of table understructure 50 X 50full frame metal structure considerwithonesidemetalmodesty(600x450ht). Provisionfornecessarywiremanagementasdirected. Complete with All necessary hardware & Fixture. Note:AllFurnituretoBeMadeOutof Calibrated plywood(IS:710)BWP,AllInternal&External Surfaces of Plywood Finished with Laminate Complete, asperdetailedDrawing&InstructionsEngineerin charge with 1 year warranty. Rate to include wire manager system of approved quality.SIZE: 1200 x 600 x 750/1200.
74CubicleTable -CubicleTableProviding& Supplyingatsite,comprisingofmodular1200mm height,60mmthickness partitionsystemwithpowder coatedAluminiumframingwithpowdercoated aluminiumcaping..RatetoincludeTable,25mm thick Postformed Top made out ofCalibrated plywood (IS : 710) BWP finishedwith P/F 0.6mm laminate with edge binding, wire management, Raceway- Double raceway Soft board+White board combination.In workstation table One side of table understructure 50 X 50full frame metal structure considerwithonesidemetalmodesty(600x450ht). Provisionfornecessarywiremanagementasdirected. Complete with All necessary hardware & Fixture. Note:AllFurnituretoBeMadeOutof Calibrated plywood (IS : 710) BWP, AllInternal & External Surfaces of Plywood Finished with LaminateComplete, asperdetailedDrawing&InstructionsEngineerin charge.with 1 year warranty. Rate to include wire managersystemofapprovedquality. SIZE: 1800/1800 x 600 x 750/1200/700 x 1800
75ConferenceTable- Providing and fixing Conference Table to be made out of 19mm x 2 = 38mm top/ /12mm thk boxing supports of BWP (IS710) marine plycladded with 4mmthk veneer&finishedwith melamine from outside & 0.8mm thk Laminate finished from inside. All expose surfaces to be 4mm Veneer with 48x48mmedgelipping fortabletop&100x 25mm teakwoodedgelippingforsupportingboxingfinish. CompletewithAllnecessaryhardware& Fixture. Provision for necessary wire management and 6 Nosofdeskportof8 moduleas directed (Without electrical).Complete with All necessary hardware & Fixture. Etched glass to be installed if required. Note:AllFurnituretoBeMadeOutof Calibrated plywood(IS:710)BWP,AllInternal&External SurfacesofPlywoodFinishedwith4mmveneerand3 coatsofP.U.Coating, AllHardware Complete,asper detailed Drawing & Instructions directed by Engineer in charge.Includingloading,unloading, transportation, installation. With1yearwarranty.Ratetoincludeall provisionofinstallationconcealedspeakersystemand 12mmthickBWPMarine plyApronwith4mmthick veneerfinishonbothsideand20x12mmteakwood edgelipping.Ratetoincludewiremanagersystemof approved quality. SIZE: 5500 x 1200 x 750.
76Meeting Table - Providing and fixing Meeting Table tobemadeoutof19mmplus12mmtabletopand 12mmthickboxingsupportsBWP(IS710)marineply cladded with 4mm thk veneer & finished with melamine from outside & 0.8mm thk Laminate finished from rear side.All expose surfacesto be 4mmVeneer with37 x 37mmedgelippingfortabletop.CompletewithAll necessaryhardware&Fixture. Provisionfornecessary wire management and deskport of 8 module as directed (Withoutelectrical).CompletewithAllnecessary hardware & Fixture. Note:.AllFurnituretoBeMadeOutof Calibrated plywood(IS:710)BWP,AllInternal&External Surfaces of Plywood Finished with Laminate and veneer of . All Hardware , Complete as per detailed Drawing & InstructionsdirectedbyEngineerincharge.Including loading, unloading, transportation, installation. With 1 yearwarranty.Rate to includewiremanagersystemof approved quality. SIZE:2700 x1050 x 750.mm/ 600mm dia
77CafeteriaTable-CafeteriaTable-Providing& Supplyingatsite31mmthick CafeteriaTable comprisingof 25mmthickBWPGrademarineply TableTopwith12mmthk Corianfinish &37x 12mmcorianedgebindingthetabletopissupported with S.S.304gradebaseUnderstructurecomprising of 75mm diapipe&4pronged withPVCLeveller. Complete with All necessary hardware & Fixture. SIZE: 900 x 900 x 750.mm/ 900 x 2970mm
78ReceptionTable-Providing&Supplyingatsite Custom made reception table & Apron in 19mm marine ply construction inclusive of support framing,table,counter top & drawer box with key board tray asper architect drawing &design. Rate to include 19mm thick Italian marblecounter top & Edging62 x 19mminclusiveofedgepolishing&finishing.Basic Rate of Italian Marble Rs.800/-Sqft. Facia to be finish with 12mm thick corian with polishing & Buffing, Edge Bindingwith12mmcorian.ConcealedLEDlighting strips with drivers to be installed in pelmet ( LED Strip is19mmx 12mmwithpolycarbonatecover.All other surfacesinternal&Externaltobefinishwithveneer inclusiveofteakwoodedgelippingof10mm thickness. Provisionfornecessarywiremanagementas directed(Withoutelectrical).CompletewithAll necessary hardware & Fixture. Note:AllFurnituretoBeMadeOutof Calibrated plywood(IS:710)BWP,AllInternal&External Surfaces of Plywood Finished with Laminate . All Hardware Complete,as perdetailedDrawing & InstructionsdirectedbyEngineerincharge.Including loading, unloading,transportation,etc. complete. SIZE: 1800 x 750 x 1050mm ht
79Medium ht storage - Providing & Supplying at site, Med ht Storage Unit 18 mmthick top, all sides, shelf, bottom made out of Calibrated plywood (IS : 710) BWP with P/F 0.6mm laminate, other edges finished with 2.0 mm thick PVC edgeband for exposed edges & 0.8 mm thick for non exposed edges t.Complete as per Architects detailed Note :All Furniture to Be Made Out ofCalibrated plywood (IS : 710) BWP, All Internal & External Surfaces of Plywood Finished with Laminate . All HardwareComplete, as per detailed Drawing & Instructions directed by Engineer in charge. Including loading, unloading,transportation, installation., With 1 year warranty. SIZE : 900 x 450 x1200mm
80Lockers -Providing & Supplying at site, locker Storage Unitof8compartments18mm thicktop,allsides, shelf, bottom& Shutters made out of Calibrated plywood(IS:710)BWPwithP/F0.6mmlaminate, other edges finished with 2.0mm thick PVC edgeband forexposededges&0.8mmthickfornonexposed edges Complete, as per Architects detailed Note:AllFurnituretoBeMadeOutof Calibrated plywood(IS:710)BWP,AllInternal&External Surfaces of Plywood Finished with Laminate . All Hardware Complete,as perdetailedDrawing & InstructionsdirectedbyEngineerincharge.Including loading, unloading,transportation, installation, With 1 year warranty. Rate to include Locking arrangement with Hinges,Handles&Hardware.SIZE :1050x450x 2400mm.
81Revolving type chair with wheels : SEAT ASSEMBLY :- The Cushioned seat is made of Injection moulded Plastic outer & inner. Plastic Inner is upholsteredwithleatherette andmouldedHighResilience (HR) Polyurethane foam ofDensity45±2 kg/m³ and hardness load 16 ± 2 kgf as per IS:7888 for 25% compression * Seat Size : 47.0 cm (W) x 48.0 cm (D) BACKASSEMBLY:-TheCushionedbackismadeofPU Foam with insitu moulded MS moulded E.R.W.Round Tube of size1.9±0.03Cm x0.16±0.0128cm.Itupholsteredwith leatherette.*MID BACK SIZE :- 47.7 cm(W) x 60.1cm (D) ARMRESTS:-Thearmresttopismouldedfrom Polyurethane (PU) and mounted on to a drop lift adjustable type tubular armrest support made ofØ 3.81 ± 0.03 cmx 0.2 ± 0.01cm thk M.S.E.R.Wtube having chrome plated finish . Thearmrestheightadjustableupto6.5±0.5cm in5 steps. SEATDEPTHADJUSTMENT:-Seatdepthadjustmentis integrated in the seat through a sliding mechanism. Seat depth adjustmentrangeisof6.0±0.5cm.ADJUSTABLE BACK SUPPORT :- Back frame is connected to the Up/ Dn mechanismhousedinplasticTSpine.Itcanbeadjustedin the range of 7.42 ± 0.5 cm for the comfortable back support to suit individual need .ACTIVE BIO -SYNCHRO MECHANISM:- The adjustable tilting mechanism is designedwiththefollowing features:- • 360°revolving type . DJUSTMENT :- The pneumatic height. adjustment has anadjustment stroke of 10.0 ± 0.3 cm .
82Revolving type chair with wheels: SEAT/BACK ASSEMBLY :- The seat & backis made up of 1.2±0.1cmthk. HotpressedplywoodmeasuredasperQA method describedin QCP-OLTA-PL14-18:upholstered with synthetic leather over moduled High Resilience Polyurethane foam. • High Back Size : 51.8 cm (W) X 75.2cm (H) • Seat Size : 49.0 cm (W) x 48.8 cm (D) HIGH RESILIENCE (HR) POLYURETHANE FOAM :- The HR Polyurethanefoam ismoduledwithdensity=55+/-2 kg/m³andhardnessload16±2 kgfasIS:7888for25% compression. ARMRESTS :- The adjustable armrest is designedwiththefollowing features • UP- Down Adjustment- 8 steps (8.0 ± 0.5cm range )• Height adjustable armreststructurewhichischromeplatedandfittedwithan armrest top • Fixed armrests topisPU moulded over metal insert. BACKHEIGHTADJUSTIBALITY:-Backcanbe adjusted in 5 positions by manually .Stroke of height adjustable spine is 7cm.Back height adjustability is applicable for High back & Mid Back chairs .PNEUMATIC HEIGHT ADJUSTMENT :- The pneumatic height. adjustment has anadjustment stroke of 10.0 ± 0.3 cm .
83Bean BagChairs XXL size of approved colour, shade and material as per the direction of Engineer in charge
84Providing,Fixing,Installing & putting in place& in proper condition, as per layout & as per direction of the Engineer in charge.Seating Asperfollowingdetails. Basicratefor Fabric Upholstery RS 450 /-.per Mtr: 1Seater Sofa size:- (860W x 905D x 855H ) SEATFOAM:theSeatismadeupofPUfoaminDensity 28±2 kg/cu. Mtr with an additional top layer of supersoft Pu foam in density 32±2 kg/cu, upholstered with fabric or leatherette. BACKFOAM:ThebackismadeupofPUfoamDensity 28±2kg/cu,mtrwithtwoadditionaltoplayerofsupersoft foam ofdensity 32±2kg/cu,mtr,upholstered withfabric or leatherette. UNDERSRUCTURE:Understructureismade upof 1.2±0.1 cm. thick hot pressed plywood (moisture resistance & termite proof as per IS:303) & pinewood of cross sections devoid of majorknots&surfacedefects.6nosperseat&3.8mm Dia Zigzagspringassemblyismountedoverunderstructurefor cushioning purpose. LEG ASSEMBLY: It is a welded Assembly made in stainless steel (grade SS 202) tube & plate with plastic endcap The product to be tested and passed the quality standards as laid down under ISO 9001,1S014001,ISO18001,OHSAS andBIFMAcertificationsforqualityassurance.Ithasa Green Assurance card validated by TUV India. LOCATION - STAFF & WHEREVER REQUIRED,
85Electrical
86DG SET
87Supply ,Installation,Testing & Commisioning of Diesel Generating(D.G.) set with CLASS G3 governing (40% step load) , alternator of 325 kVA output at 0.8 PF continuous rating with 10% overload capacity for 1 hour in 12 hours, 3 phase, 415 V, 50c/s, radiator cooled,multi-cylinder diesel engine at 1500 rpm , seperately excited AMG having Class H, SPDP alternator (with battery charging generator),with Static AVR +/- 1% & THD<3%, running at 1500 rpm. Both the engine and alternator shall be direct coupled on a common fabricated steel base frame anti vibrating pad mounted with controller suitable for full parallel operation of multiple generators having Engine & generator protection(including REF & RPR)/ parameter display/ operator interface/Power Command 3.3 control system/AMF panel/ Synchronization/Dedicated earthing system/RS 485 Modbus connectivity, etc. The complete set shall be enclosed in composite acoustic enclosure as fully assembled integral unit in silenced accoustic canopy, giving 75 dB at 1 meter,made of 16/14 swg CRCA sheet, complete with first filling of Lube oil/diesel/coolant & fuel hoses, battery,990 liter external fuel tank, residential silencers,mounted on plinth & obtaining necessary approval from electrical inspector. a. AMF panel comprising of suitable rating FP EDO ACB for Mains and D.G., Auto/Manual selector switch, engine start /stop push button, indication lamps, Voltmeter/Ammeter/KWH meter/RPM meter/Hour meter/Announciator/Relays/Battery charger/DC Ammeter/Voltmeter, etc. b) Exhaust piping to be raised upto terace level of nearest building. c) Power/control cabling, terminations, etc. d) 990 ltr. capacity external diesel tanke). Height of Stack to be maintained as= Height of building + 0.2 * vkVA . f) Factory testing to be carried out in present of ACTREC engineering before despatch of equipments.
88Supply, Installation, testing and commissioning of Following all Indoor Panels comprising below points. 1)-Panels shall be fabricated out of 16/14 swg CRCA sheet steel, with necessory structural supports in form of structural steel sections. 2)-Floor mounted, IP-52 degree protection, Top bus duct or cable entry as per the case & top cable exitsteel, 2mmframe, 1.6 mm compartments & tank process treated & 2- times Epoxy painted. 3)-The panel shall be compartmental, Form 3B type, with suitable size of bus bar and separate cable and busbar chambers. 4)-Proper gland size holes to be provided bythe manufacturer with proper sticker and danger sign on all sides of panel. 5)-The cable chambers shall be free from any live open connections and minimum cleareance to be provided for termination. 6)-Current Density- 1.2 Ampere/1 Sq.mm for Copper and 0.8 Ampere/1 Sqmm for Aluminium(IS-8623 for factory built assembly). specification of copper for copper bush bar C11000 - Electrolytic-Tough-Pitch (ETP). 7) Earthing terminal.8) fault level 50KA / sec.9) Panel Inside illumination to be provided10) Receptacles , space heater provided as per standard. 11) Epoxy paint colour type RAL 7032 to be use.
89L.T. Panel 1 & 2 (As per SLD attached)
90Office Panel (As per SLD attached)
91Utility Panel 1 & 2 (As per SLD attached)
9230KVA UPS O/P Panel (As per SLD attached)
93PDU 1 & 2 (As per SLD attached)
945KVA UPS O/P DB for Emergrncy Lighting and IBMS Load. (As per SLD attached)
95Automatic changeover switch (ATS)
9632A 4P Automatic changeover switch (ATS)
97UPS System
98Supply ,Installation,Testing & Commisioning of 80KVA ONLINE, pure sine wave Modular UPS System, 3 phase input and 3 phase output with UPF, 0.96% efficiency, IGBT Based rectifier technology, Isolation Transformer, suitable capacity SMF batteries for minimum 20 minutes backup, battery Rack, cables for interconnections. UPS should have provision of Auto & Manual bypass in case of any internal fault in UPS system.80% DOD is accepted for Li battery , Acceptable inputTHD 5%
99Supply ,Installation,Testing & Commisioning of 30KVA ONLINE, pure sine wave Modular UPS System, 3 phase input and 3 phase output with UPF, 0.96% efficiency, IGBT Based rectifier technology, Isolation Transformer, suitable capacity SMF batteries for minimum 20 minutes backup, battery Rack, cables for interconnections. UPS should have provision of Auto & Manual bypass in case of any internal fault in UPS system.80% DOD is accepted for Li battery , Acceptable inputTHD 5%
100Supply ,Installation,Testing & Commisioning of 5KVA ONLINE, pure sine wave Modular UPS System, 1 phase input and 1 phase output with UPF, 0.96% efficiency, IGBT Based rectifier technology, suitable capacity SMF batteries for minimum 20 minutes backup, battery Rack, cables for interconnections. UPS should have provision of Auto & Manual bypass in case of any internal fault in UPS system.80% DOD is accepted for Li battery , Acceptable inputTHD 5%
101Distribution Boards
102Supply and fixing of TPN, double door Power Distribution Board having 63 amps TPN MCB--1 No. /// 40 amps , 10KA ,DP ELCB(30 mA)--3 Nos /// 20/32 amps SP MCB (8ways)--24 Nos. IP 55, IK 08,
103Supply and fixing of TPN, double door Lighting Distribution Board having 63 amps TPN MCB--1 No. /// 40 amps, 10KA ,DP ELCB(30 mA)--3 Nos /// 10 amps SP MCB (12ways)--36 Nos.IP 55 , IK 08
104Supply and fixing of SPN, double door Power Distribution Board having 32Amps , 10KA DP ELMCB--1 No. /// 16 amps , 10KA DP MCB--6 Nos. , IP 55 , IK 08
105Supply and fixing of SPN, double door Lighting Distribution Board having 16Amps 10KA , DP ELMCB--1 No. /// 10 amps , 10KA SP MCB--6 Nos., IP 55 , IK 08
106MAINS WIRING
107Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
1082 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1092 X 4 sq. mm + 1 X 4 sq. mm earth wire
110POINT WIRING
111Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
112Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
113Wiring for plug on board, Switch with multi-socket concealed type and copper wiring, earthing and with modular accessories.
114Providing fan regulator on board with modular Switch and regulator.
115Switches, Sockets & accessorie
116Supplying and fixing of 3/4 module switch box with modular plate including connections but excluding modular plate etc. as required.
11715 amps switch
1185pin 5/15 amp socket outlet
11932A 3P+N+E Socket with plug AC Powerenclosure and MCB
12016A 1P+N+E Mobile Socket with plug AC Power
121Lighting Fixtures / Exhaust fans / Ceiling fans
122Supplying and erecting of recessed type square shaped CRCA / die-cast aluminum powder coated housing LED Panel light 600X600mm of PREMIUM RANGE suitable for upto 36 W with provision for plane front frame with translucent cover fixed to the housing complete.Lumens output >3200 , CRI more than 80 , CCT 6500K, THD <10%
123Supplying and erecting LED square / circular 13 to 18 W PREMIUM RANGE down lighter having pressure die-cast aluminum housing with white front frame with opal translucent cover with provision for spring loaded mounting clips complete. Lumens output 900/935/980 , CRI more than 85 , CCT 3000K to 6000K, THD <10%
124Supply and erecting of box type LED light fitting with 1 X22W led tube light complete with all accessories.
125Standerd 230V ceiling mounted Day light cum occupancy sensor.
126Supply and fixing of call bell with all accessories.
127Supply and fixing of 225mm sweep exhaust fans.
128Supply and fixing of 1200mm sweep ceiling fans.
129Cable Tray
130Supply ,Installation,Testing & Commisioning of Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 50 mm height complete with necessary coupler plates, support & hardware in approved manner.coating thickness of Hot dip galvanized cable trays will be 80 TO 100 MICRONS or 610 GRAMS PER SQUARE METER(depends on thickness) and follows IS: 2629,1985&IS 4759.
131Supply ,Installation,Testing & Commisioning of Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 75 mm height complete with necessary coupler plates, support & hardware in approved manner. coating thickness of Hot dip galvanized cable trays will be 80 TO 100 MICRONS or 610 GRAMS PER SQUARE METER(depends on thickness) and follows IS: 2629,1985&IS 4759.
132Supply ,Installation,Testing & Commisioning of Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 750mm width & 75 mm height complete with necessary coupler plates, support & hardware in approved manner.coating thickness of Hot dip galvanized cable trays will be 80 TO 100 MICRONS or 610 GRAMS PER SQUARE METER(depends on thickness) and follows IS: 2629,1985&IS 4759.
133LT Cables
134Supply and laying of 1.1KV, FRLS, XLPE armoured cable 3.5Cx300 sqmm Aluminium conductoron wall/ in provided tray as per instructions.
135Supply and laying of 1.1KV, FRLS, XLPE armoured cable 3.5Cx185sqmm Aluminium conductoron wall/ in provided tray as per instructions.
136Supply and laying of 1.1KV, FRLS, XLPE armoured cable 3.5Cx150sqmm Aluminium conductoron wall/ in provided tray as per instructions.
137Supply and laying of 1.1KV, FRLS, XLPE armoured cable 3.5Cx70 sqmm Aluminium conductoron wall/ in provided tray as per instructions.
138Supply and laying of 1.1KV, FRLS, XLPE armoured cable 3.5Cx50 sqmm Aluminium conductoron wall/ in provided tray as per instructions.
139Supply and laying of 1.1KV, FRLS, XLPE armoured cable 3.5Cx35 sqmm Aluminium conductoron wall/ in provided tray as per instructions.
140Supply and laying of 1.1KV, FRLS, XLPE armoured cable 3.5Cx25 sqmm Aluminium conductoron wall/ in provided tray as per instructions.
141Supply and laying of 1.1KV, FRLS multicore flexible cable 1Cx70sqmm Copper conductoron wall/ in provided tray as per instructions.
142Supply and laying of 1.1KV, FRLS multicore flexible cable 1Cx35 sqmm Copper conductoron wall/ in provided tray as per instructions.
143Supply and laying of 1.1KV, FRLS multicore flexible cable 1Cx10 sqmm Copper conductoron wall/ in provided tray as per instructions.
144Supply and laying of 1.1KV, FRLS multicore flexible cable 3Cx6 sqmm Copper conductoron wall/ in provided tray as per instructions.
145Supply and fixing of end termination with brass double compression gland andlugs of copperor aluminiumor Bi metallic lugswhich are suitable at sitefor following size of FRLS insulated and XLPE aluminium conductor cable of 1.1 KV grade as required.
1463.5C X 300 Sq.mm.
1473.5C X 185 Sq.mm.
1483.5C X 150Sq.mm.
1493.5C X 70Sq.mm.
1503.5C X 50Sq.mm.
1513.5C X 35 Sq.mm.
1523.5C X 25 Sq.mm.
1531C X 70 Sq.mm.
1541C X 35 Sq.mm.
1551C X 10 Sq.mm.
1563C X 6 Sq.mm.
157EARTHING
158Supply and fixing of 50 mm x 6 mm COPPER strip on surface or in cable tray for connections etc as required.
159Supply and fixing of 40 mm x 5 mm COPPER strip on surface or in cable tray for connections etc as required.
160Supply and fixing of 25 mm x 3 mm COPPER strip on surface or in cable tray for connections etc as required.
161Supply and fixing of 8 SWG COPPER wire on surface or in cable tray for connections etc as required.
162Tinned copper earth plate electrode 600 x 600 x 3.15 mm earth station, 2.5 mtr below ground level as per drawing complete with all required materials like Cole, charcoal, salt, brass nut bolts & washers, watering arrangements, GI pipe (B class), concrete chamber, heavy duty cast iron cover plate & excavation in all types of soil in ground refilling & removal excess earth within a radius of 500 mtr. The chamber cover & plate shall be of heavy-duty hinged type & it shall weigh approx. 65 to 75 Kgs. Plastering shall be done both inside & out side.The measurement of resistance of earth station & resistance of complete scheme of earthing layout shall be measured, recorded & got approved by Engg-in-charge.
163Chemical Earthing / Maintenance free Earthpits having better earth resistance value.
164ADDRESSABLE FIRE ALARM SYSTEMS & DETECTION SYSTEMS :
165Supply , Installation , Testing and Commissioning of Addressable -Automatic Dual LED smoke detector with two integrated light-scattering smoke sensors using LED"S with different colors/wavelengths(blue/infrared) to avoid False alarm & should comply to test fire 1,including mounting base with LED,Drift compensation feature & automatic addressing.High resistance to electromagnetic effects in accordance with EFSG AGREEMENT EFSG/F/97/005 Shall be EN54/Vds/UL certification.2Isolators(one for incoming & one for outgoing line)integrated in detector for maintaining operational availability of all elements in the loop ,even in the evennt of a short circuit,BOSCH model FAP 0 420 or equivalent.
166SITC of addressable thermal detector including mounting base with LED..etc complete as required with inbuilt isolator.Temprature sessor triggers@ 54deg C or 69 deg C & drift compensation feature.Shall have UL/Vds certification BOSCH model FAH T 420.
167Supply,Installation, Testing & Commissioning of addressable, UL listed, Duct smoke detector comprisingsplash & hose proof, UV resistant, housing assembly with sampling tubes & Photoelectric detector with Heat element(57Deg C), suitable for air speeds of 100 -4000 FPM,loop powered, class A wired, low profile, temper resistant, low quiescent current,Rotary/DIP decimal address setting switch,24V DC(15-32V), wiring box, In/Out cable glands.
168Supply,Installation, Testing & Commissioning of addressable, UL listed, Control Module for switching power supply to hooter & strobe, loop powered, class A wired, low quiescent current,Rotary/DIP decimal address setting switch,24V DC(15-32V), suitable for surface / recess installation, wiring box, In/Out cable glands.
169Supply,Installation, Testing & Commissioning of addressable, UL listed, Control Module with relay for AHU/damper/switchgear operation, loop powered, class A wired, low quiescent current,Rotary/DIP decimal address setting switch,24V DC(15-32V), suitable for surface / recess installation, wiring box, In/Out cable glands.
170Supply at site, Installing in proper position testing and commissioning of 2 Core x 1.5 sqmm FRLS armouredCopper Conductor Cable of approved quality all complete as required and as per final direction.
171Removing and refixing of detectors, Isolators, monitor moduls, control moduls, etc.
172Supply and fixing of junction boxes with cable glands, lugs, etc.
173FIRE SUPPRESSION SYSTEM COMPRISING OF FOLLOWING
174NOVEC 1230 BASED FIRE SUPPRESSION SYSTEM COMPRISING OF THE FOLLOWING ITEMS:
175SITC of CCOE Approved UL Listed Seamless Novec 1230 Cylinder and Valve Assembly,120 Ltrs. capacity, OEM Factory filled with Novec 1230 Suppression Liquid (item No. 2), pressurised to 25 / 42 bar. Along with Hydraulic Flow Calculations for the Suppression areas, and vetting of the Software Results from the OEM Factory Engineer.
176SITC of CCOE Approved UL Listed Seamless Novec 1230 Cylinder and Valve Assembly,80 Ltrs. capacity, OEM Factory filled with Novec 1230 Suppression Liquid (item No. 2), pressurised to 25 / 42 bar. Along with Hydraulic Flow Calculations for the Suppression areas, and vetting of the Software Results from the OEM Factory Engineer.
177SITC of Novec 1230 Fire Protection Fluid, OEM Factory Filled per Kgs.
178SITC of Tank Bracket Assembly complete with C- Channel Stand and Supports for above Cylinder. The Price Shall include MS Fabricated Floor Supported Cylinder Support Stand, wherever Required. Complete with 1 coat of Primer and 2 coat of Black Enamel Paint. (Refer Drawing for Cylinder Locations).
179SITC of UL Listed Discharge hose withManifold Check Valve (Check Valve if More than one Cylinder in Bank)for above Cyilnders, complete with Listed Adapters & Accesories as required.
180SITC of UL Listed Electrical Actuator for Master Cylinder.
181SITC ofUL Listed Local Manual Actuator
182SITC ofUL Listed Pneumatic Actuator Shipping Assembly with actuation hose & Elbow.
183SITC ofUL ListedNozzles, 360 Deg / 180 Deg Throw, selection as per approved hydraulic flow calculations.
184SITC of Warning Sign Board with Marking "GAS DISCHARGE. DO NOT ENTER". Shall Operate on 24 V DC, Driven Through Gas Release Panel.(for use outside room)
185SITC of Warning Sign Board with Marking "GAS DISCHARGE. EVACUATE IMMEDIATELY". Shall Operate on 24 V DC, Driven Through Gas Release Panel.(for use inside room)
186SITC of UL Listed Cylinder Low Pressure Switch
187SITC of UL Listed Cylinder Discharge Pressure Switch, Shall be install on the Novec piping after discharge hose.
188SITC of NOVEC Piping & Manifold as required,Sch 40; ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold,position & Support the Manifold and Piping properly. Pressure testing for piping with nitrogen as per NFPA 2001.
189Supply installation Testing & commissioning ofUL Listed Single zone Gas Release Panel facility to connect Manual Abort/Release switches. The Panel shall provide Potential free contacts for First knock, second knock, Trouble / Fault Status. The Panel shall be Complete with Red Colour Housing, Monitored Power supply unit, Battery charger & batteries.
190Supply installation Testing & commissioning ofManual Abort Stations, shall be fitted with transparent hinged covers to avoid the possibility of accidental operation. The Abort will be monitored simultaneously by Fire Alarm or BMS System.
191Supply installation Testing & commissioning of Manual Release Stations, shall be fitted with transparent hinged covers to avoid the possibility of accidental operation. The Release switch will be monitored simultaneously by Fire Alarm or BMS System.
192Towards Conducting Room Integrity Test : Door Fan test to meet the Requirements of the NFPA 2001, and predicting the efficacy of the Protected Area Enclosure from the perspective of Fire Suppression.
193Supply installation of 2 Core x 1.5 mm2, Multistranded AT Copper, FRLS Armoured cable, RED in Colour. The cable shall belaid on surface with GI saddle-spacers every 0.3 meters. Complete with GI Junction Box, lugs, cable compression glands, cable tags and Ferruling.
194Public Address System
195Supply, Installation, Testing and Commssioining offollowing items
196UL listed, 6 Watt Ceiling mount Speaker with junction box for ceiling mount
197Goosneck micro Phone
198CD/MP3 Player
1996 Zone Selection panel for PA announcement
200Rack to mount amplifier,CD player and console
2012 core 1 sq.mm copper conducter cable with 20 mm dia PVC conduits
202LANNETWORK
203Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed PVC conduit as required.
204Supplying, installing & testing UTP Connector (RJ-45) as per specification No. WG-NAS/UTPC.
205Supplying and fixing following 3 module, GI box along with modular base & cover plate as required.
206Supplying and fixing 1 meter length, UTP Patch cord of Cat 6 type in position as per requirement.
207Supplying and fixing 24 port Patch Panel with tool-less keystone jacks in provided U Rack complete as per requirement.
208Supply & fixing of 25mm PVC conduit with accessaries.
209SITC of IT rack -19" Wall mounted President quality rack 15U(double section)with acrylic glass door with the accessories -[Two Fan position tray with two 90 CFM fans(AC 230V),3 Horizontal cable manager- 3nos, AC power panel strip with 5 X 5 AMP sockets ,fuse and on/off switch, 1 packet mounting hardware
210Supplying and fixing 7 ft length, UTP Patch cord of Cat 6 type in position as per requirement for end point device (PC/laptop etc)
211SITC of Lazr SPEED 300 Fiber, 6 Core- Indoor Application, MultiMode, to be laid through conduit and flexible with all the connectors, couplers, pigtels, LIUs at both end
212TELEPHONENETWORK
213Supplying & erecting Jelly filled armoured Telephone Cable 20 pair with 0.5 mm dia.
214Supplying, erecting & commissioning of telephone tag block with crone module suitable for 20 pairs as required.
215Supplying and fixing of RJ-11/RJ-45 modular telephone socket with G.I. switch box, modular plate including connections as required.
216Supplying, installing, testing & commissioning approved type Push button telephone instrument desk top/wall mount unit as per specification in approved manner. (Panasonic model No KX-TS 580)
217Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed PVC conduit as required for IP Phone.
218IP Telephone Instrument.
21924 Port PoE Network Switch’s, Gigabit Ethernet Web Smart chassis in a 1U form factor with 24x10/100/1000PoEBase-Tports,2fixedSFP(1G)withinternalpowersupply(192WPoE budget).
2208 Port PoE Network Switch’s, Gigabit Ethernet Web Smart chassis in a 1U form factor with 24x10/100/1000PoEBase-Tports,2fixedSFP(1G)withinternalpowersupply(192WPoE budget).
22112U wall mounted double section rack with acrylic glass door having 2 Nos. 90 CFM fans, cable managers, 5A Sockets, fuse, ON/OFF Switch, 1 Packet mounting hardware, etc.
222Supply & fixing of CAT 6 ,24 Port Patch Panel loaded.
223Supply & fixing of 2 Mtr. Patch cord.
224Supply & fixing of 25mm PVC conduit with accessaries.
225CCTV SYSTEM
226Supply, Installation, Testing and Comissioningof the following equipment for CCTV System
227IndoorIP base Day & Night,2MP HD resolution with IR illumination, varifocal lens CMOS, Resolution 1920x1080p @ 25 fps, WideDynamicRange @ 90 dB, WDR CCD dome Cameras, 2.8mm to 12mm IR lense, min. 15mtr coverage, SD/SDHC memory Card Slot., Camera should be POE Enabled. The camera should be ONVIF compliant.
228IndoorIP base Day & Night,fixed dome Cameras, 2.8 mm IR lens, Minimum 110 degree of horizontal field of view, resolution 1920 x 1080p @ 25 fps, 10 mtr coverage, Camera should be POE Enabled. The camera should be ONVIF compliant.
229Supply, installation, testing and commissioning of 16 port 10/100T managed poe access switch with 2 SFP uplinks (Layer 2). Configuration to be decided by Vendor base on real time image transmission from camera / encoder to server. All the Switches should be in Racks.
230Supply, installation, testing and commissioning of 16 Ports 10/100/1000T managed poe switch (Layer 3) along with SFP module. Configuration to be decided by Vendor base on real time image transmission from camera / encoder to server. All the Switches should be in Racks.
231NVR /NAS & VMS
232Supply, installation, connfiguration, testing & commissioning of Video Networked Recorder (NVR) of suitable channel with 30 days motion based storage at 20 FPS, along with Vedio Management Software (VMS) along with required camera license.
233Supply , Installation , Testing and commisioing ofCAT-6 cable for Power/ Data Cabling from camera to switchwith 25 mm PVC conduit.
234Supply, installation, testing and commissioning of color high resolution LED TV comprising of 42"" display, full HD,HDMI input provision; complete with all supports and accessories.
235SITC of 6pair multimode Fiber optical cable with termination all necessary accessories and termination as required.
236Cat-6 IOwith back box & surface plate
237Cat-6 patch cords
238ACCESS CONTROL SYSTEM COMPRISING OF FOLLOWING
239Supplying, Installing, Testing & Commissioning of the access control system consisting of the following:
240Supply , installation, testing and commissioning of 4 Reader IP based Door Controller for Controlling the above card readers as per specification mentioned including all accessories.Max. 4 Reader combition (Tenderer to mention quantity of controllers based on their system.) System should have capability to expand up toadditional 100 doors in future.
241Supply , installation, testing and commissioning of 2 Reader IP based Door Controller for Controlling the above card readers as per specification mentioned including all accessories.Max. 4 Reader combition (Tenderer to mention quantity of controllers based on their system.) System should have capability to expand up toadditional 100 doors in future.
242SITC of BIOMETRIC Fingerprint + PINPADReader
243Supply , installation, testing & commissioning of proximity card readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories
244SITC of Panic Bar with egress switch
245Supply , installation, testing and commissioning of Smart cards as per specification.
246SITC of Break Glass Unit for Access Doors
247SITC of Single Leaf electromagnet door holder (fail safe type) of 600 lb holding force
248SITC of Double Leaf electromagnet door holder (fail safe type) of 600 lb holding force
249SITC of Door Contact sensor
250SITC ofTime, attendance and visitor Management Software for Access Control with seamless integration with BMS module, Visitor Management Module and time and attendance module as per the specifications. Software shall be capable of handelling additional 10 nos. of access readers.
251Supply , Installation , Testing and commisioing ofClient Workstation Processor -Intel Core i-7 OS -Genuine Windows XP/7Prof Colour Monitor -21" Flat Panel LCD/ LED Monitor RAM -16 GB DDR3 SDRAM Memory -1 TB HDD A4 laser jet printer Network: 100/1000 Mb Ethernet network card Resolution Support: 1024 by 768; 1280 by 1024; 2048 by 768; 2560 by 1024
252CABLES & ACCESSORIES FOR ACS SYSTEM
253Supply , laying ,testing and commissioning of the following cables signal & communication cablesfor security access control, alarm monitoring System with all accessories including glanding and termination.
2546 Cx 1SqmmShielded armouredsheilded Cable
2554Cx 1SqmmShielded armouredsheilded Cable
2562Cx 1SqmmShielded armouredsheilded Cable
257CAT 6 cable for Network controllers with 25 mm pvc conduit
258Building Management system comprising of following:
259The rate of each item of work for BAS shall also include the following : 1. All materials, fixing materials, accessories, appliances, tools and equipment. 2. Approvedcoverplates for inspection, junctionandoutlet boxes. 3. 2 mm thick outlet boxes and junction boxes. 4. All fixing accessories such as clips, nails, screws etc. 5. Providing and fixing approved saddles, hooks and grouting the same as required, in the case of all exposed cable work. 6. Embeddingcablesand accessories inwall,floorsetc.duringconstruction and / or cutting chases and makinggood as in the case of all concealed cables work. 7. Testing and commissioning of each device as per ApprovedDesign Concept
260SITC ofDuel Core2 Quad, 80GB HDD, 2GHZ Processor, 8GB RAM, 52X CD ROM drive 1.44 FDD, 17" colour monitor, Microsoft Bus Mouse, 2 serial, 1 parallel port & Windows XP operating system
261SITC of Colour Inkjet Printer
262Supply of Necessary Software Packages containing Building Management & Control Software Programmes with Dynamic Graphics interfaces
263Software and Hardware required for Integration of following third party system with BMS
264Energy meters - 5 nos.
265UPS - 4 nos.
266DG (2 nos) & transformer ( 1 no.)
267Cooling Unit8 nos.
268PDU - 2 nos.
269Supply, installation, testing & commissioning of Stand alone, intelligent, UL Listed, Interoperable DDC .
270DDC Controller For monitoring as per IO summary
271Room Temperature cum Rh Sensor
272Room Temperature Sensor
273Outside Temperature and RH Sensor
274Hydrogen sensor
275Wi-fi modem for tap off box meters data connectivity.
276Signal cable 2 core 1.5 sq.mm PVC Insulated Cu Armoured Cable
277Communication Cabling (Cat-6) for BMS in PVC conduit
278Supply , Installation , Testing and comissioning of 16 port unmanaged network poe switch with accessories.
279Rodent Repellent system comprising of following:
280Digital Master Console catering LP 12 satellites for Rodent Repellent system
281Satellites (Streem)
282Wall Mount Bracket
2832 core 1 sq.mm Cu. Flexible Shielded cable bundle (300 yards) with 20mm pvc conduit
284RRP software
285Water Leak Detection (WLD) system:
286SITC of Water Leak Detection Panel with Modbus connectivity( for all data center server area , UPS locations and Electrical control rooms )
287SITC of Water Leak detection Module
288Water Leak detection Cable Sensor
289Electronic Hooter
2902 core x 1.5 Sqmm FRLS armoured copper cableas per technical specification
291Miscellaneous Items
292150x150x3mm Danger Notice Board & 415 Enameled Danger Board
293150x150x3mm Danger Notice Board & 11kV Enameled Danger Board
294Shock Treatment chart with Frame In Local & English Language
295First Aid Medical Box
296Supplyandinstallationof9 kgcapacityCO2 typefire extinguishers conforming to IS : 2171
297ABC type – manual fire extinguishers with 6kgs.
298Providing of set of 4 Nos.9.5 Litre capacity G.I. buckets painted in post office red colour with prior coat of red-oxide paint and written with white paint "FIRE" and , mounted on MS angle iron frame with bracket of appropriate size and capacity including
2991000 x1000 mm wide 2.5mm thick Rubber Matting suitable for 1100 Grade
300Providing pair of duly tested rubber hand gloves as per IS:340715 suitable for working on 11kV and 415V supply.
30150mm size PVC Flexible conduit
30225mm size PVC Flexible conduit
30350mm size PVC rigid conduit with accessories
3041 year warranty is included in the above items. CMC Rate (Electrical components) post 1-year Warranty period will be fixed at 5% of the of the cost of the equipment for each year for up to Six years without any escalation clause
305HVAC
306Variable Refrigerant Volume (VRV)
307SITC of Variable Refrigerant Volume modular type air-conditioning Equipment complete with indoor and out door units with Central control system unit shall have Central Controller for controlling all the indoor and outdoor units and should be capable of integration with the Computer System based Building Management System of HVAC
308Outdoor Unit
309Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air-cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14HP modules, microprocessor based Controller ,top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Condition sand work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V+/-10%, 3Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5
310system 1 : 18 HP ( COLD Type)
311System-2 : 10 HP ( COLD Type) (2W+1S)
312Indoor Units (VRV/VRF compitable)
313Supply, installation, testing and commissioning of following minimum capacity 4- way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multi speed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cordless remote control etc., suitable for operation on single phase 230V±10%, 50Hz AC supply, complete, asr equired. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System.The cooling capacity of indoor unit wil be at air inlet conditions of 27 DegreeC DB and 19 Degree C WB temperature.
314Cassette Unit with inbuilt drain pump
3152.8 TR
3162.4 TR
3171.6 TR
318Supply, installation, testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multi speed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, cordless remote control, drain pan, necessary accessories etc., suitable for operation on 230V±10%, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision incase of fire on receiving signal from BMS System. The cooling capacity of indoor unit will beat air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
3192 TR
3201.65 TR
3210.8 TR
322Floor mounted AHU Vertical/Horizotal
323Supply, installation, testing & commissioning of double Skin floor mounted horizontal/vertical AHU having 50 mm Sandwiched PUF Insulation ( 0.80 mm thk inner skin & 0.80 mm thk outer plasticized GI). It shall have Pre-filter (90% down to 10 micron) of washable type > 6ROW VRV/VRF DX cooling coil having 12-13 FPI and anti corrosion coatingfins with face velocity of 500 FPM > DIDW kruger quality backward Curved fan with TEFC squirrel cage induction motor with drive set. Other accessories like inspection Door, vibration isolator, limit switch, marine light, outlet mouth damper for supply to be provided. Insulated SS 18G drain pan with 19mm thich class "O" nitrile rubber insulation. The outlet velocity not more than 7.5 m/sec. Motor shall be IE3, class F insulation, IP55 rating, & suitable for 415 ± 10 % volts, 3 phase, 50 cycles AC supply. The noise level should be less than 65 dBA at 1.5 m distance. Unit to be tripped on receipt signal from fire damper installed in the room and interconnection with fire damper shall be provided. Note:- AHU should supply with inbuit control panel which is BMS compititble.
32414 TR / 5600 CFM / 50 MM ESP (External static pressure) (Vendor to verify the ESP as per drawing for supply and calculate the total including internal pressure drops -filter/coil/ etc.)AHU should have 1working +1 standby motor.
325AHU Connecting Kit
326Refnet joints and other fittings
327Supply and Installation of hard drawn 16G Copper tubing insulated with 19 mm thick class "o" Nitrile rubber insulation with GC cloth Insulation shall be provided with weather proof additional cover for exposed areas. For indoor units tubing of appropriate diameter to be provided. All piping inside the room shall be properly supported with hanger and all external piping shall run in covered cable tray. Piping quantity is mentioned is for pair of suction and discharge pipes.
328Gas Charging and Testing & Commissioning of the system
329Supply & Installation of Transmission & Control Wiring with GI conduit between indoor and out door unit.
330(2 core x 1.5 Sq mm cu.cable )
3314 core x 4 sqmm cu cable
332Supply & Installation of support arrangement for out door units, AHU with necessary Vibration isolation arrangement, MS Frame for mounting the units to be provided with rubber pads, the frame should be painted with two coats Black Colour synthetic enamel paint.
333Supply & Installation of GI class c drain pipe with 13 mm thk nitrile rubber insulation
33432 mm dia
33525 mm dia
336Supply & installation of Perforated type Powder coated M.S. cable trays of 50 mm in Height & 2.5mmthick with two coats of red-oxide and with necessarysupporting frame etc
337200 mm wide
338300 mm wide
339Supply & Installation of BMS integration charges for the VRV outdoor unit/indoor units from central controller to BMS. All the outdoor/indoor unit parameters will be integrated through BMS & required hardware/software to be included via Modbus/Bacnet.
340Supply , Installation ,testing & Commissioning of Split type Airconditioners with Scroll Compressor comprising Indoor Air , Outdoor Condensing unit, with stand and all other necessary hardware for proper hanging of units.
341Hiwall split 2.0TR AC (3 star rating)
342Hiwall split 1.5TR AC (3 star rating)
343All refrigerant piping shall be of copper, complete with supports between indoor & outdoor units duly insulated with 13mm Nitrile rubber insulationwith GC cloth.RMT indicated is for set of piping between indoor and outdoor machine, individual piping will not be measured.
3441/4,5/8 or equivalent to the unit
3451/4,1/2 or equivalent to the unit
346AIR DISTRIBUTION SYSTEM
347Design, Supply, fabrication and installation of G.S.S. ductingon every branch if there is, with required hardware’s, supports, wooden frame and painting on ducts, MS parts etc as per the SMACNA Standard, approved drawings and instructions of Engineer-in-charge with the following gauges. The ducts shall be fabricated from galvanized steel sheets class VIII - Light coating of Zinc conforming to ISS: 277-1962 (REVISED) with accompanying Mill test Certificates.Galvanizing shall be of 120gms/sq.m. (total coating on both sides).exposed duct should provide with 26G Aluminium cladding.
34824 G (0-750)
34922 G(751-1500)
35020 G(1501-2250)
35118 G(2250 Above & Plenums)
352Supply, installation, testing and commissioning of GI volume control duct damper with bronze bush bearing complete with neoprene rubber gaskets,nuts, bolts, screws linkages, flanges etc, as per specifications.
35318G GI Constructed VCD
354Supply, installation, testing & commissioning of Back Draft Damper
35518G GI Constructed BDD
356Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
357Supply, installation, testing and balancing of powder coated Extruded Aluminium Return air diffusers with removable core in accordance with the as directed and as instructed by OIC-ES
358Supply, installation of Extruded Al. Powder coated louvers for fresh air intake & exhaust complete withSS bird screen mesh.
359Supply, installation, testing and balancing of Extruded Al. powder coated Supply/Return/Exhaust Air grilles with Bronze bush bearing sleeve of different sizes
360Without collar damper
361150 x 150 with collar damper for toilet exhaust
362Supply installation testing and commissioning of motorised fire & smoke damper , casing made of 16G GI with factory fitted GI Sleeve of 18G, 120 min fire rating complete with standard accessories as per UL-555S.
363Total area - Fire Damper with Pvc gear ( only damper price)
364Smoke / Fire sensors with all controls, accessories, actuators, extended sleeve for wall mounted (actuator outside wall)and other accessories - Torque 5 Nm
365Supply, fabrication, installation and testing of the flexible connections constructed out of fire resistant double canvas sleeve as per instructed and as directed by OIC-ES
366Supply, installation, testing and balancing of Extruded Al. profile powder coated Supply & Return slot diffuser of diiferent sizes.
3674 slot of 25 mm slot opening
368Hit & miss damper
369Inline fan
370Supply, installation, testing & commissioning of cabinet type/ in line fan complete with forward curved/DIDW centrifugal fans, motor and drive. It shall be suitable for 230 ± 10% V,1 phase, 50Hz AC supply.. Other accessories like inspection Door, vibration isolator outlet mouth damper to be provided.
371Cap:500 cfm/ 12 mm wc
372INSULATION
373Supply and installation of external thermal insulation Class "O" closed cell elastomeric nitrile rubber insulation with adhesives on ducts, tapes as per instuction and as directed by OIC-ES
37413 mm thick for supply air duct in return air path
37519 mm thick for supply air duct
376Supply, installation and testing of Acoustic lining for supply and return air ducts of following thickness of rigid fiber glass of 50Kg/Cum density covered with factory laminated RP Tissue and finished with 26G Perforated Aluminium sheet as per the specifications.
37725 mm
3781 year warranty is included in the above items. CMC Rate (HVAC components) post 1-year Warranty period will be fixed at 5% of the of the cost of the equipment for each year for up to Six years without any escalation clause
379PART – B: HPC, CDC AND OTHER RELATED WORK
380Research cluster - Head node-1 (1+1 redundency): Dual Intel Xeon Gold 5320 26 core, 2.2 GHz; 128 GB ECC DDR4 RAM; Shared storage – RAID-5/6 usable 10 TiB Read Intensive SSDs or SAS 10k RPM HDD with hot-spare, HA configuration
381Research cluster - Login -1(1+1 redundency): Dual Intel Xeon Gold 5320 26core, 2.2 GHz; 512 GB ECC DDR4 RAM; Shared storage – RAID-5/6 usable 1.9 TiB Read Intensive SSDs or SAS 10k RPM HDD with hot-spare, load sharing with DNS server
382Research cluster - General nodes-1: Dual Intel Xeon Gold 6348 28 core, 2.6 GHz; 256 GB ECC DDR4-3200 RAM in 100% balanced memory configuration; 2 x 960GB mixed use SSDs
383Research cluster - High memory nodes-1: Dual EPYC 7763 64 core, 2.45 GHz; 2048 GB ECC DDR4-3200 RAM in 100% balanced memory configuration; 2 x 1.9TB mixed use SSDs
384Research cluster - GPU nodes-1: Dual Intel Xeon Gold 6348 28 core, 2.6 GHz; (or equivalent/better AMD CPU); 256 GB ECC DDR4-3200 RAM in 100% balanced memory configuration; 2 x 960GB mixed use SSDs; 2 x Tesla A100 (80 GB) NVLink/bridge
385Research cluster - GPU nodes-2: Dual Intel Xeon Gold 6348 28 core, 2.6 GHz; 256 GB ECC DDR4-3200 RAM in 100% balanced memory configuration; 2 x 960GB mixed use SSDs; 2 x RTX A6000/A40 NVLink or PCIe
386Research cluster - Interconnect/network-1: a) Gigabit switch with all the compatible cables for managing all the cluster components with sufficient ports. Managed Switches with RPS and redundant fans need to be offered in the solution. b) Gigabit switch with 10G SFP+ uplink ports , all the structured cabling and other required components for connecting all the client devices (approximately 40 clients) in the office area; 100G HDR Infiniband off-loading fat tree internally managed network on HDR-200 switches, secondary cluster management 1G network switches, remote management 1G network switch. Managed Switches with RPS and redundant fans need to be offered in the solution. KVM switch with display, keyboard/mouse and adequate ports is required at each site for easy monitoring and troubleshooting of installed servers.
387Research cluster - Storage - scratch-1 lustre: 1 PiB usable on RAID-6 (8+2) as per below :-200TiB(50 GiB/s write/read each individually) must be offered using Flash drives and 800 TiB (10 GiB/s write/read each individually) must be offered using SSD / NL-SAS drives; scalable; all SSD/NL-SAS components should be high-endurance enterprise grade; The metadata-based file-type wise policy for data-backup/movement should be provided. 1 disk hot-spare every 30 disks. The metadata/object storage array should be separate for both storage. Metadata/object storage should be redundant and with SSDs only of suitable capacity as per solution requirement with minimum 90000 files/sec.
388Research cluster - Linux licence (RHEL or equivalent) for proposed cluster
389Research cluster - PCM Professional Cluster Manager Solution for proposed cluster - perpetual licence with OEM’s support for 5yrs
390Research cluster - Compiler : Latest version of Intel One API HPC Toolkit (2 concurrent users) - with 5 Yrs support from OEM Professional Workload/Scheduler Solution - perpetual licence with support
391Research cluster - PBS pro Schedular Professional Workload/Scheduler Solution for proposed cluster + 2 nodes - perpetual licence with support for 5 yrs
392Research cluster - Linux MN (RHEL or equivalent) for proposed cluster
393Virtual servers (1+1 redundancy): Dual Intel Xeon Gold 6326 16 core, 2.9 GHz; 512 GB ECC DDR4 RAM in 100% balanced memory configuration ; Latest Windows Data Centre edition - Virtual environment with Windows HyperV service; expandable shared 50 TB Usable RAID-5/6 (8+2) SAN storage (1 disk hot-spare every 30 disks); scalable with all the cables and interface cards to establish the connectivity with redundant host server.
394Display:at-least 42" 1080p/4k LED wall-mount smart TV with HDMI & USB, 20 watts sound, X-Protection Pro outside the data centre for monitoring & management.
395WiFi and LAN : Dedicated 1GigE LAN connectivity to each office seating space (~ 60 ports/users) and other room. Managed WiFi connectivity for entire area (~ 100 concurrent users) is to be installed in compliance with ACTREC IT infrastructure. Briefly, two DGS-1010P-E switches and five AC1750 Aps could be installed for this requirement.
396Software solution for Comprehensive building, cluster, interconnect, network & data centre resource management
397Man Power & Support (1 system administrator for day to day administration of I.T. infra, container/tool installation/maintenance, web/FTP-servers, back-up scheduling etc. + 1 Data centre management engineer), all in 3 shifts for 24 X 7 X 365 days support covered by OEM/Vendor for 5 years. ACTREC will advertise and select support staff on behalf of the vendor for HPC and CDC management and administration. Experienced employees of the vendors could also be qualified for the interview based upon the experience.
398Computational data centre (CDC) turn-key: Any other work required for complete and all inclusive functioning of project considering turn-key project should be described by the vendor. Additional items included here should be justified and detailed at the time of submission.
399Amenities: Projector, interactive display, wall-art, plants, recreation room accessories etc as per the details in tender document
4005 years warranty is included in the above items. CMC Rate (HPC, CDC AND OTHER RELATED WORK) post 1-year Warranty period will be fixed at 5% of the of the cost of the equipment for each year for up to Two years without any escalation clause
401Total Equipment and Works Cost :PART – A: CORE INFRASTRUCTURE (Civil+Electrical+HVAC)+PART – B: HPC, CDC AND OTHER RELATED WORK including CMC as applicable
Disclaimer :