| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Group -B) |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings) |
| 7 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\" curve including connections, painting etc. as required |
| 8 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 6 way Double door |
| 9 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 10 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole |
| 11 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole & Neutral |
| 12 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 13 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 14 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 15 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 16 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 17 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 18 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 19 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 20 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 16 sq. mm (22mm) |
| 21 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 6 sq. mm (19mm) |
| 22 | Supplying and laying of 2x6 sqmm PVC insulated and PVC sheathed /XLPE armoured power cable of 1.1 KV grade conform to IS 7098 (part I) 1988 with upto date amendents if any existing DWC pipe etc complete as required |
| 23 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. a) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 24 | Providing and making steel pole collar with cement concrete (1 cement : 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to be deducted) |
| 25 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete |
| 26 | Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels |
| 27 | Supplying and laying of HDPE pipe of 50 mm dia in existing cable trench / pole muff for protection of UG Cable etc as required. |
| 28 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE armourd power cable of 1.1 KV grade of following size direct in groundin existing RCC hume/ metal/ DWC HDPE pipe (of item No -11) including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. The cable should conform to IS 7098 (Part1) 1988 with upto date amendents if any. a) 2x16 Sqmm |
| 29 | Providing and laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) a) 2x16 Sqmm |
| 30 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 31 | Providing and fixing of 1200 mm sweep BLDC ceiling fan , including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 32 | Supply and fixing of 12 watt white light LED surface/recessed mounted downlight with integrated electronic driver/ bulk head fitting in ceiling/surface complete with all accessories including connections etc. as required. |
| 33 | Supplying and fixing of 10 Watt LED Bulk Head luminaire including wiring with 1.5 sqmm FRLS PVC insulated,copper conductor, single core cable and earthing etc. as required. |
| 34 | Supply and fixing of 6 watt white light LED surface/recessed mounted downlight with integrated electronic driver in ceiling/surface complete with all accessories including connections etc. as required. |
| 35 | Supply and fixing of 9/10 Watt Mirror LED Light surface/recessed mounted with integrated electronic driver in ceiling/surface complete with all accessories including connections etc. as required. |
| 36 | Providing and fixing of300 mm sweep metal blade light duty exhaust fanincluding louvers/ shutters and making/drilling hole, connections with 1.5 sqmm copper wire etc. as required and directed by engg incharge. |
| 37 | Supplying of 450 VA capacity sine wave inverter unit suitable for 230 V, 50 Hz A.C. supply . |
| 38 | Supplying of 12 volt, 100AH tubular type lead acid batteries suitable for inverter unit with trolly. |
| 39 | Supply and fixing of 9 watt white light LED surface/recessed mounted downlight with integrated electronic driver in ceiling/surface complete with all accessories including connections etc. as required. |
| 40 | Providing and fixing of 1 HP/0.75 Kw Mini self priming single phase Monoblock pump sets of pipe size 25 mm x25 mm, head range 6-37 mtr with50 hz 230 V AC Supply, Complete all accessoriesetc i/c connections etc as required. |
| 41 | Providing and Fixing of DOL motor starter suitable for 0.75 KW/1.0 HP single phase monoblock motor pump set complete with overload relay (6-9 Amp), limit switch for autocut during over flow water i/c connection etc as required at site. |
| 42 | S/F following size U-PVC column pipe complete with socket , heavy duty , in the suction/ delivery line i/c cutting , threading etc as required. a) 40 mm |
| 43 | Supplying, Installation, testing & Commissioning of 1.5 KW capacity Off Grid solar system with 8 hours battery back-up (Life of battery 5 Yrs min), using 350 Wp, Polycrystalline silicon PV modules mounted on fixed axis structure fabricated from hot dip galvanized steel on suitable size concrete base foundation, including inverters, all electrical connection should be made with suitable size of copper conductor cable as required, all specification should confirms to MNRE specifications. |
| 44 | Supplying, Installation, testing & Commissioning of 2 KW capacity Off Grid solar system with 8 hours battery back-up (Life of battery 5 Yrs min), using 350 Wp, Polycrystalline silicon PV modules mounted on fixed axis structure fabricated from hot dip galvanized steel on suitable size concrete base foundation, including inverters, all electrical connection should be made with suitable size of copper conductor cable as required, all specification should confirms to MNRE specifications. |
| 45 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying as per solar plate i/c a priming coat of approved steel primer all complete as per drawing & design approved by Engg. In charge. |
| 46 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the drawing/design of Engineer-in-charge. Made of G.I. wire of dia 4 mm |
| 47 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade. One or more coat as per approval of Engg. In charge. |