Provision Of Clean Room At Chess Facility Kanchanbagh Campus Hyderabad => Limited, hyderabad-Telangana

Defence Research And Development Organisation -DRADO has published Provision Of Clean Room At Chess Facility Kanchanbagh Campus Hyderabad => Limited. Submission Date for this Tender is 05-12-2022. Laboratory Enclosures and Accessories Tenders in hyderabad Telangana. Bidders can get complete Tender details and download the document.




Tender Notice

34225384
Corrigendum : Provision Of Clean Room At Chess Facility Kanchanbagh Campus Hyderabad => Limited
Open Tender
Indian
Telangana
hyderabad
05-12-2022

Tender Details

Provision Of Clean Room At Chess Facility Kanchanbagh Campus Hyderabad => Limited

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 17-Oct-2022 CORRIGENDUM 2 Date 09-11-2022
2 09-Nov-2022 CORRIGENDUM 4 Date 22-11-2022
3 21-Nov-2022 CORRIGENDUM 5 Date 05-12-2022

Key Value

Document Fees
INR 2000 /-
EMD
INR 1360520.0 /-
Tender Value
INR 6.80 Crore /-

BOQ Items

Name of Work: PROPOSED CLEAN ROOMS ATCHESS FACILITY, KANCHANBAGH CAMPUS,HYDERABAD
Sl. No. Item Description
1Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.
2In cement mortar
3Making the opening in brick masonry including dismantling in floor or walls by cutting masonry and making good the damages to walls, flooring and jambs complete, to match existing surface i/c disposal of mulba/ rubbish to the nearest municipal dumping ground, all complete as per direction of Engineer-in-Charge.
4For door/ window/ clerestory window
5Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead :
6Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge.
7Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
8Providing of wall opening for duct and making good with plastering in 1:6 cm including painting of dismantling area etc complete.
9Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:4 (1 cement : 4 coarse sand).
10Cement mortar 1:4 (1 cement : 4 coarse sand)
1152 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer"s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
1215 mm cement plaster on the rough side of single or half brick wall of mix 1:6 (1 cement: 6 fine sand).
131:4 (1 cement: 6 fine sand)
1418 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge.
15Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers.
16Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour.
17Two coats
18Finishing walls with Acrylic Smooth exterior paint of required shade :
19New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
20White washing with lime to give an even shade : New work (three or more coats)
21Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
22Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):
23With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm)
24Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil.
25Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil
26Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
27Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand)
28HVAC
29CLEAN ROOM
30AIR COOLED SCREW CHILLERS:
31Supply, Installation, Testing and Commissioning of the 90TR net capacity at actual condtions for R 134a, Air cooled screw chillers including itsdrive motors, condensors, condensor fans, expansion device, micro processor control with RS-485 port,nessary operational and safety devices, placed on the concrete pedestal, including loading, unloading, rigging and transportation upto chiller location with necessary spring vibration isolators, flow switch, victaulic couplings, canopy for chiller control panel,etc. at the following conditions. Ambient temperature 106 °F / 78°F WBT, chilled water inlet temp is 52.8° F and outlet tempis 42.8°F, Fouling Factor 0.0005 ft2/h/°F/BTU for Chiller as per specification. (2W)
32CHILLED WATER PRIMARYPUMPS :
33Supply, installation, testing and commissioning ofcentrifugal End Suction Long Coupled Top Discharge Chilled Water Primary Pumps with high efficency (EFF#1) electric drive motor, as per technicalspecifications (impellers and wearing rings made of bronze, priming funnel and air purging provision with valves and with necessary grouting, foundation bolts, etc.)including customs clearance and transportation to site. Inertia base Foundation for pumps shall be carried out by hvac contractor until or unless stipulated else where otherwise. Allpumpsshallbemountedwith necessary vibration isolators. Each Pump capacity shall be216USGPM @ 15 mt. head as per specifications and approved drawings (2 working + 1 standby)
34CHILLED WATER SECONDARY PUMPS ( VARIABLE SPEED) :
35Supply, installation, testing and commissioning ofcentrifugal End Suction Long Coupled Top Discharge Chilled Water Secondary Pumps with high efficency (EFF#1) electric drive motor, as per technicalspecifications (impellers and wearing rings made of bronze, priming funnel and air purging provision with valves and with necessary grouting, foundation bolts, etc.)including customs clearance and transportation to site. Inertia base Foundation for pumps shall be carried out by hvac contractor until or unless stipulated else where otherwise. Allpumpsshallbemountedwith necessary vibration isolators. Each Pump capacity shall be240USGPM @ 20 mt. head as per specifications and approved drawings (2 working + 1 standby)
36VARIABLE FREQUENCY DRIVES & LOGIC CONTROL PANEL:
37Supply, Installation, Testing & Commissioning fo variable speed pumping system comprising of following accessories. The system shall be complete in all respects including electrical components for motor of Secondarychilled water pumps. Each pump shall have an independent adjustable frequency drive. Common Panel with suitable controller to control 3 Nos. Pumps separately. as per specs and drawing. Including sensor, transmiter, control wiring etc complete in all respect. It shall be also BMS compatible. Panel should be IP 55 Rated.
38For Secondarychilled water pumps
39Variable frequency drive (VFD): 2 Nos
40Micro processor based pump controller : 1 No
41Differential pressure sensors/Transmitters : 2 Nos
42Software down loaded in pump controller : Job
43Control wiring : Lot
44Variable speed pumping system described above
45AIR & DIRT SEPERATOR
46Supply Installation Testing and Commissioning of In-line Air & Dirt Separator. removing of free air, bubbles and microbubbles in combination with separation and removal of dirt particles within chilled water system. The acceptable design shall incorporate a separating element to force water into tranquillity zones for air and dirt removal.A nozzle shall force de-aerated water into the main flow to divert contaminated water through the separating element.A high capacity, conical brass automatic air vent shall be installed on the top of the vessel for air discharge. Drain valve for removal of floating debris and dirt. Heavier than water dirt particles shall be removed via a blow down valve on the base of the vessel whilst ferrous particles down to 4 µm shall be captured by a magnetic device in the lower part of the vessel. Manufactured and designed in accordance with European Pressure Equipment Directive. The Microbubble Air and Dirt Separator shall be sized appropriate to the maximum operating pressure and flow velocity 216 USGPM of the system.as per the specifications and approved drawings.
47PRESSURIZATION SET:
48Supply, Installation, Testing and Commissioning of Insulated Pressurisation Unit (1000 L) of requisite capacity with necessary makeup, quick fill, drain and over flow connection, valves, fittings, suitable rating pump(1W+1S),expansion vessel (1000 L), necessary pump connection along with valves,stariner and compleate panel etc. Allpump"sshallbemountedwith necessary vibration isolators, etc. as per the specifications and approved drawings.
49CALORIFIERS
50Design,Supply installation testing and commissioning of 100 LIT capacity galvanised steel shellwith removable electric water element of min 15KW, designed for inlet temp of 60deg C and70 deg C water out let with nessary fittings , valves, mounting brakets as per specification.
51HOT WATER PUMPS
52Design,Supply, installation and testing and commissioning of Horizontal Multistage monoblock Centrifugal pump with necessary grouting, foundation bolts, etc. including customs clearance and transportation to site , testing and commissioning of constant speed hot waterpumps. Each Pump capacity shall be 30 USGPM @ 15 mt. head, mounted on frame with factory fitted nessary fittings, valves , pressure guages,header , control panel and expansion tank (100 L) as per specification(1 working + 1 stand by).
53HOT WATER PIPES
54Supply, Installation, Testing and Commissioning of MS "C" Classhot water pipe with fittings, flanges, valves,reducers ,sockets for probe meter, support hangers with vibration isolation hanger etc with Supply, Installation, Testing and Commissioning of chilled water pipe insulation with44mm thick closed cell elastrometric nitrile rubber of density 43 Kg/m3, Thermal conductivity not exceeding 0.035 W/M°K Class 1, fire performance to pass class 1 as per BS 476 part 6& class O as per BS 476 part 7 & use recommended adhesive. the insulation finished with treated woven glass fiber reinforced covering & further finished with 24G Aluminium cladding as per the specifications and approved drawings.
55Ø 50 mm
56AIR HANDLING SYSTEM:
57Design,Supply, installation and testing and commissioning of double Skin AHU"s With 50 mm Sand witched PUF Insulation, Thermal break profile with 0.8mm GI pre painted outer skin and 0.8mm GIinner skin comprising ofMixing box section for fresh air module and RA connections, reactivation module complete with filter, blower, Electric Heaters, pre filter section with 10 micron washable filters of 90% efficiency, fine filter section, 5 micron filters of 97% efficiency , Pre / Post cooling coil module section complete with necssaryand drift eliminator of ABS construction, Fan section with Plug Fan, TEFC(IE-3) motor, Variable speed drive with flow controller, spring isolators & fire retardant canvass connection at the outlet of fan, and provision to fix damper at the inlet/outlet of AHU etc as per Specification ,AHU should meet Cleanroom specifications so that the validation process as per ISO 14644 is achieved by the contractor. Standard as applicable for Clean Rooms. Digital Thermostat with remote sensing element to be included, Magnehellic gauges for measuring the differential pressure across HEPA filters for the AHUs of range 0 to 50mm as per specification, consisting of energy efficient imported desiccant rotor, controls, filters, total frame work is provided 4 -20m Amps RH and temperature transmitter for +/- % accurate control,microprocessor based Mitsubishi PLC module or equivalent with color HMI for system fault indication etc.Pre cooling coil module with in double skinned casing for treated fresh air with 8 row coil, damper and pre filter is considered. All internal blankoffs, filter frame, fan/motor base shall be made of Powder coated GI including 100mm powder coated GI baseframe.
58Nominal Cooling Capacity at ARI/Eurovent conditions
59AHU - 1 - CAP : 28.0TR / Selected SA CFM : 9140 CFM / 150 mm TSP.
60AHU - 2 - CAP : 41TR / Selected SA CFM : 20000 CFM / 150 mm TSP.
61AHU - 3 - CAP : 43TR / Selected SA CFM : 15200 CFM / 150 mm TSP.
62AIR HANDLING SYSTEM:
63Design,Supply, installation and testing and commissioning of double Skin AHU"s With 50 mm Sand witched PUF Insulation, Thermal break profile with 0.8mm GI pre coated outer skinand 0.8mm GI inner skin comprising ofMixing box section for fresh air module and RA connections, pre filter section with 10 micron washable filters of 90% efficiency, fine filter section, 5 micron filters of 97% efficiency, coil section with 6 Row chw Coil and 2 row hot water coil complete with necssary drift eliminator of ABS construction, Fan section with Plug Fan, TEFC(IE-3) motor, Variable speed drive with flow controller, spring isolators & fire retardant canvass connection at the outlet of fan, and provision to fixdamper at the inlet/outlet of AHU etc as per Specification, Digital Thermostat with remote sensing element to be included Magnehellic gauges for measuring the differential pressure across HEPA filters for the AHUs of range 0 to 50mm, as per specification. AHU should meet Cleanroom specifications so that the validation process as per ISO 14644 is achieved by the contractor. All internal blankoffs, filter frame, fan/motor base shall be made of Powder coated GI including 100mm powder coated GI baseframe.
64AHU - 4 - CAP : 36TR / Selected SA CFM : 14200 CFM / 150 mm TSP.
65DRAIN:
66Supply, Installation, Testing and Commissioning of CPVC (Chlorinated Poly Vinyl Chloride) pipes condensate drain piping insulated using 9 mm thick nitrile rubber tubes including fitting and supports as per specified .
67Ø 32 mm
68Ø 40 mm
69AIR FILTRATION SYSTEM
70Supply, Installation, Testing and Commissioning of Box type HEPA filters of capacity 1000 CFM & size 610 x 610 x 305mm deep with an efficiency 99.97% down to 0.3 micron particles and the filter to be openable from bottom of ceiling panel.
71Supply, Installation, Testing and Commissioning of HEPA filter modules in CRCA powder coated finish with provision for DOP & pressure drop measurement suitable for following size filters.
72610 x 610 x 305mm deep
73Supply, Installation, Testing and Commissioning of Fire retardant canvass connections with MS Epoxy painted / Al. Powder coated finish angle flanges on both sides
74AIR DISTRIBUTION SYSTEM
75Supply, Installation, Testing and Commissioning of factory fabricated GSS Ductingas per SMACNA/DW standards with splitters, bends, elbows, vanes, supports,neoprene of minimum 6mm thick gasket, nuts, bolts angle iron flanges, soildered longitudinal joints, GI full threaded rods hung to minimum 12 mm dia HILTI make anchor fastner as required and epoxy painted slotted rail supports, as per the specifications and approved drawings.
7624 G (0.6mm thick)
7722 G (0.8 mm thick)
7820G (1.0mm thick)
79Supply, Installation, Testing and Commissioning of Fire retardant canvass connections with MS Eoxy painted / Al powdercoated finish angle flanges on both sides as per the specifications and approved drawings.
80INSULATION
81Supply, Installation, Testing and Commissioning Thermal Insulation of Supplyair ducting with 19mm thick closed cell elastrometric Nitrile rubber with factory laminated aluminium foil of density minimum 43Kg/m3 and fire perfromance to pass Class 1 as per BS 476 Part 7 & class O as per BS 476 part 6 and use recommended adhesives and finished with 0.05mm thick 3" wide aluminium foil faced self adesive tape at all joints as per the specifications and approved drawings.
82Supply, Installation, Testing and Commissioning Thermal Insulation of Supplyair ductingfor Outdoor with 25 mm thick closed cell elastrometric Nitrile rubber withof density minimum 43Kg/m3, antimicrobial with EPA USA approved and fire perfromance to pass Class 1 as per BS 476 Part 7 & class O as per BS 476 part 6 and use recommended adhesives / SR Fevicol 505 grade and covered with 7 mil thick chemically treated woven glass cloth having density 205+/- 10 g/sqm and affixed using synthetic contact adhesive of approved make and protective coating of starbond 30-36 finished with 24G Aluminium cladding for outdoor as per the specifications and approved drawings.
83Supply, Installation, Testing and Commissioning Thermal Insulation of Returnair ducting with 13mm thick closed cell elastrometric Nitrile rubber with factory laminated Aluminium foil of density minimum 43Kg/m3 and fire perfromance to pass Class 1 as per BS 476 Part 7 & class O as per BS 476 part 6 and use recommended adhesives and finished with 0.05mm thick 3" wide aluminium foil faced self adesive tape at all joints as per the specifications and approved drawings
84Supply, Installation, Testing and Commissioning Thermal Insulation of Return air ductingfor Outdoor with19 mm thick closed cell elastrometric Nitrile rubber withof density minimum 43Kg/m3, antimicrobial with EPA USA approved and fire perfromance to pass Class 1 as per BS 476 Part 7 & class O as per BS 476 part 6 and use recommended adhesives / SR Fevicol 505 grade and covered with 7 mil thick chemically treated woven glass cloth having density 205+/- 10 g/sqm and affixed using synthetic contact adhesive of approved make and protective coating of starbond 30-36 finished with 24G Aluminium cladding for outdoor as per the specifications and approved drawings.
85Supply, Installation, Testing and Commissioning of Under deck insulation type of a non fibrous ,closed cell , Elastometric Nitrile Rubber of density 43 kg/m3/ chemically cross- linked polyethylene foam (with class-1 as per BS476 part-I ) of density 33kg/m3 of 19mm thk with factory laminated Alfoil fixed to roof slab using adhesive SR Fevicol505 grade and fastened using GI washers, screws /nylon wire , and joints sealed with tape .
86DAMPERS, GRILLES & DIFFUSERS
87Supply, Installation, Testing and Commissioning of Opposed type GIVolume Control dampers with matching flanges of sizes as per the approved drawings
88Supply and Installationof Fire dampers with fusible links&Eletronic actuators connected to FA system with frame etc. (Dampers should be of wall / duct mounted) as per the specifications and approved drawings.
89Supply, Installation, Testing and Commissioningof Extruded Al. Powder coatedReturn air GrillwithAl. Collar Dampers as per the specifications and approved drawings.(Colour to be aproved by dept)
90Supply, Installation, Testing and Commissioning of stainless steel (s.s.) 18G (SS316) perforated sheets for HEPA filter modules in all cleanrooms as per the specifications and approved drawings.
91Supply, Installation, Testing and Commissioning of weather proof extruded aluminium powder coated fresh air louver of non vision type of Perforated Al net,VCD etc as per the specifications and approved drawings.
92Controls
93Supply, Installation, Testing and Commissioning of On / off actuator with sensor & also connected to FA panel(Two sets for one damper).
94Dismantlling of following capacity existing de humidifier and re Installation, Testing and Commissioning of the same with necessary control cable and starter required with all necessary accessories etc.
95CFM : 600 CMH, Process ESP : 200pa , Reactivation ESP : 150pa
96Supply, Installation, Testing and commissioning of Exhaust system of following
971)Chemical resistant fire restardant ducting for 75sft approximately of 200mm dia,with manual dampers bends,flanges,reducers etc & suitable rating chemical resistant exhaust unit.2)Positive pressure module in 3 : 1 ratio as compared with exhaust with suitable rating air blower assemblies,Hepa Filters,Pre Filter - so as to repenish exhaust air .3)Dry scrubber for exhaust air with proper filters and suitable cfm capacitywit hmanual dampers etc.
98Supply, Installation, Testing and Commissioning of Portable type Hydrogen chloride detector (HCI) gas detector with portable pumping single gas detector (Measuring range - 0-10PPM)and (Resolution - 0.01ppm, Alarm with sound,light and vibration,alarm point is settable, large capacity of lithium polymer battery, internal sampling pump, fast response and reliabe withnecessary control wiring and supports etc.
99Supply,Installation, Testing and Commissioningof Fixed type Hydrogen chloride detector (HCI) gas detector with portable pumping single gas detector (Measuring range - 0-10PPM)and (Resolution - 0.01ppm, electrochemical, remote control, data display with one set of relay output, power supply 24VDC,SINGLE OUTPUT 4 -20 mA, working temperature, Humidity 0-95%RH, protection IP 65 withnecessary control wiring and supports etc.
100Supply,Installation, Testing and Commissioningof cabinet type inline Exhaust FANwith motorforExhaust air with TEFC Motor and starter panel with all supports and other accessories complete of following capacities .
101CFM : 2000 CFM,TSP : 30MM
102CHILLED WATER PIPING WITH VALVES AND ACCESSORIES:
103Supply, Installation, Testing and Commissioning of MS "C" Class as per IS -1239 chilled water pipe with fittings, flanges, valves,reducers ,sockets for probe meter, support hangers with vibration isolation hanger including PUR/PIR inserted self closing insulated single piece pipe supports, including painting ,etc. with insulation of44mm thick for exposed piping with closed cell elastrometric nitrile rubber of density 43 Kg/m3, Thermal conductivity not exceeding 0.035 W/M°K Class 1, fire performance to pass class 1 as per BS 476 part 6& class O as per BS 476 part 7 & use recommended adhesive / SR Fevicol505 gradeand Insulation covered with 7 mil thick chemically treated woven glass cloth having density 205+/- 10 g/sqm and affixed using synthetic contact adhesive of approved make and protective coating of starbond 30-36 finished with 24G Aluminium cladding for outdoor as per the specifications and approved drawings.
104Ø 200 mm
105Ø 125 mm
106Ø 100 mm
107Ø 80 mm
108Ø 65 mm
109Supply, Installation, Testing and Commissioning ofbalancing (Manual) with matching flanges , bolt, nuts, insulation and suitable for working pressure of PN16. The insulation covered with treated woven glass fiber reinforced covering & finished with (24G Aluminium cladding for Exposed), all etc., complete as per specifications and approved drawings.
110Ø 125 mm (For Chiller)
111Ø 80 mm(Ahu)
112Ø 65 mm (Ahu)
113Supply, Installation, Testing and Commissioning ofbutterfly/ isolation valve"s with matching flanges , bolt, nuts, insulation and suitable for working pressure of PN16. The insulation covered with treated woven glass fiber reinforced coveringetc., complete as per specifications and approved drawings.
114Ø 125 mm
115Ø 80 mm
116Ø 65 mm
117Supply, Installation, Testing and Commissioning of Motorised butterfly valve"s (IP55)with actuator ,mating flanges, bolt, nuts, insulation and suitable for working pressure of PN16. The insulation covered with treated woven glass fiber reinforced covering & finished with 24G Aluminium cladding, all etc., complete as per specifications and approved drawings.
118Ø 125 mm (chiller)
119Ø 100 mm (For Decoupler Line)
120Supply, installation, testing & commissioning of 2 - Way MotorisedControl Valve with matching flanges,necessary digitalthermostat And control wiring as per specification and approved drawings.
121Ø 80mm
122Ø 65 mm
123Supply, Installation, Testing and Commissioning off Y Strainers consisting of magnetic screen with insulation & matching flanges suitable for hot water, as per the specifications and approved drawings.
124Ø 125mm
125Ø 80mm
126Ø 65mm
127Supply, Installation, Testing and Commissioning ofNon return valves with matching flanges , bolt, nuts, insulation and suitable for working pressure of PN16. The insulation covered with treated woven glass fiber reinforced covering & finished with 24G Aluminium cladding, all etc., complete as per specifications and approved drawings. .
128Ø 125mm
129Supply, Installation, Testing and Commissioning of flexible connections(Bellows)suitable for working pressure of PN16.as per the specifications and approved drawings.
130Ø 125 mm(for pumps & CHILLER )
131Ø 80 mm(for AHU )
132Ø 65 mm(for AHU )
133Supply & Installation of other accessories:
1346 inch dia dial typethermometers with thermowell and mounting box.as per the specifications and approved drawings.
1356 inch dia dial typepressure gauge with isolating gate valve / cock with insulation (Chillers, Pumps , CSU"s ) as per the specifications and approved drawings.
136Gate valve for drain with insulation as per the specifications and approved drawings.
137Ø 25 mm
138Ø 32 mm
139Ø 40 mm
140Double float Automatic air vents as per the specifications and approved drawings.
141Ø 25 mm
142Ø 32mm
143ELECTRICAL WORKS:
144MV Panels
145Supply, installation,Testing and Commissioning of 3 phase and Neutral 415V, 4 wire Free Standing Floor mounted MV panel made out of 14 SWG MS sheet after seven tank process and painting with Epoxy powder coating.
146The panel shall consist of suitable rating TPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and color coded with Heat shrinkable sleeves.
147The Metering shall be provided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below.
148The panel shall be got fabricated from manufacturers with CPRI Test certificate only. The PCC shall have at least two spare cubicles of the maximum rating. The size of all Panel Mounting Meters shall be 96X96mm.
149The Panels shall be mounted on U channels including supply and fixing of the same. Every ACB shall be provided with ON/OFF /Trip Indication lamps of LED type. For all Electrically operated Breakers, Local Remote Selector switches shall be provided for controlling the Breakers remotely.
150M.V.PANEL ( OUTDOOR )
151Incoming : 1000A FP 50KA EDO ACB with Microprocesser Based releases for Overload, S/Cand earth fault- 1 set
152BUSBARS : 1250A, TPN Aluminium busbars – 1set
153Metering for Incomer
154Phaseindicating lamps - 1 set withtoggle switch
155Voltmeter (0-500V) with selector switch - 1 set
156Ammeter (0-1000A) with selector switch - 1 set
157Multifunction Meter -1Set
1581000/5A, CL-1, 15VA CT"s with resin cast- 30Nos.
159Outgoing Feeders :-
160250A TP 36KA MCCB As Outgoing Feeder (Air Cooled Screw Chiller) -2Nos
161100A TP 25KA MCCB As Outgoing Feeder (Dehumidifier 1,2,3) -4Nos
16215KW Star delta /DOL Feeder with Type II Coordination MCCB, Contactor, OLR, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (AHU Feeder) - 1Set
16322KW Star delta /DOL Feeder with Type II Coordination MCCB, Contactor, OLR, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (AHU Feeder) - 2Set
16430KW Star delta /DOL Feeder with Type II Coordination MCCB, Contactor, OLR, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (AHU Feeder) - 1Set
1655.5KW DOL Feeder with Type II Coordination MpCB, Contactor, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (Primary Chilled Water Pumps) - 2Sets
1665.5KW DOL Feeder with Type II Coordination MpCB, Contactor, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (Secondary Chilled Water Pumps) - 2Sets
1672.2KW DOL Feeder with Type II Coordination MpCB, Contactor, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (Pressurisation set) - 1Set
168250A TP 36KA MCCB As Outgoing Feeder (Spare) -2Nos
169100A TP 25KA MCCB As Outgoing Feeder (Spare) -2Nos
170Supply, Installation, Testing and Commissioning of following size 1.1 KV Grade Aluminum / Copper conductor XLPE insulated PVC sheathed armoured cable and shall be laid on cable traywith all installation materials. the cable shall conform to IS 7098 / part-I.
1711R X 3.5Core X 50Sqmm (Copper) (Un Armoured)(for Chillers) - 2No"s
1721R x 3.5C X 35Sqmm (Aluminimum)(fordehumidifier) - 4No"s
1732R X 3Core X 10Sqmm(Copper)(Armoured) (for Ahu"s ) - 1No
1742R X 3Core X 16Sqmm (Copper)(Armoured) (for Ahu"s ) - 2Nos
1752R X 3Core X 16Sqmm (Copper)(Armoured) (for Ahu"s ) - 1Nos
1761R X 3Core X 4Sqmm - (Copper)(Armoured) (for Primary Pumps ) - 2Nos
1771R X 3Core X 4Sqmm - (Copper)(Armoured) (for Secondary Pumps ) - 2Nos
1781R X 3Core X 4Sqmm - (Copper)(Armoured) (for Pressurisation Set ) - 1No
179Supply, Installation, Testing and Commissioning of following size ELECTRICAL TERMINATIONS WITH SINGLECOMPRESSION GLANDS / LUGS:
1801R X 3.5Core X 50Sqmm . - (Copper)(for Chillers)
1811R X 3Core X 4Sqmm - (Copper)(for chilled water Primary & Secondary Pumps )
1821R x 3.5C X 35Sqmm(Aluminimum)(for dehumidifier )
1832R X 3Core X 10Sqmm(Copper)
1842R X 3Core X 16Sqmm (Copper)
1852R X 3Core X 16Sqmm (Copper)
1863C x 4 Sq.mm. - (Copper)
187Supply, Installation, Testing and Commissioning of powder coated GI Cable tray of perforated type 300mm wide with GI cover (both 2mm thick) including suitable powder coated MS supports as per the specifications and approved drawings.
188Supply, Installation, Testing and Commissioning of powder coated GI Cable tray of perforated type 150mm wide with GI cover (both 2mm thick) including suitable powder coated MS supports as per the specifications and approved drawings.
189CLEAN ROOM INTERNAL FINISHES:
190Supply, Installation, Testing and Commissioning of Solid 100 mm thick Double Skin Walkable Ceiling panels(with load bearing 300 kg/m2) made up of 0.8 mm thick GI Precoated Sheet (appliance white colour), Infill material PUF ceiling grid withplexi glass , tacky ment,coving, anti static flooring ,pass bos , air curtain andall accessories as per standards
191Supply, Installation, Testing and Commissioning of Solid 80 mm thick Double Skin Clean Room Wall panels made up of 0.8 mm thick GI Precoated sheet (appliance white colour), Infill material PUF with all accessories as per standards
192Supply, Installation, Testing and Commissioning ofPU painting on walls in outer corridor
193Supply, Installation, Testing and Commissioning of 2mm thick, self levelingconductive vinyl flooring
194Supply, Installation, Testing and Commissioning ofwall to floor andwall to ceiling coving
195Supply, Installation, Testing and Commissioning of 3-d corner cove pieces
196Supply, Installation, Testing and Commissioning of Cutouts for filters, Light fixtures, powersockets, PA System, Smoke detectors
197Supply, Installation, Testing and Commissioning of CleanroomcompatibleDoubleLeafDoors 1500(W)x 2100mm (H) as per specification without door closure
198Supply, Installation, Testing and Commissioning of Cleanroomcompatible SingleLeafEmergencyDoors 1000(W)x 2100mm (H) as per specification without door closure
199Supply, Installation, Testing and Commissioning of Cleanroomcompatible SingleLeafDoors 1000(W)x 2100mm (H) as per specification without door closure
200Supply, Installation, Testing and Commissioning of Doubleglazedwindowswith5mmthickglassonbothsidesincluding necssarydoubleadhesivetapes&siliconsealantprovidingin:Internal modular panels of size 900mm x 900mm.
201Supply, Installation, Testing and Commissioning of Air shower of CRCA powder coated (size 1.2 m X 1.0 m X 2.85m (H))
202Supply, Installation, Testing of Lockers for personal belongings (20 cubicles)
203Supply, Installation, Testing of Garment cubicle of 15 pairs CRCA powder coated
204Supply, Installation, Testing of Shoe Rack (size: 1000mm(L) X340 mm (W)X500 mm (H))
205Supply and Installation of Aircurtain of size 2100(W) with sensor and necessary fittings.
206Validation and documentation of the complete facility as per the ISO 14644 Clean Room standardsfor ISO Class 6 "at rest" conditions . This shall include - Air Particulate count using Laser Particle counter, temp & RHchecks, differential pressures,air changes,filter integrity tests,air flow pattern (by VEDIO) ,duct leak test ,by department approved third party.Standard as applicable for Clean Rooms.
207SUBHEAD- : INTERNAL ELECTRIFICATION
208Lights Points
209Wiring for light point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed heavy class FRLS PVC conduit, with modular switch, Stainless Steel modular plate, suitable GI box and earthing the point with 1.5 sq.mm.FRLS PVC insulated copper conductor single core cable etc as required.
210Group-C
211Point Wiring for Light/ Fan/ exhaust fan with2runs of 1100V grade 1.5 Sq.mm & 1 run of1.5 Sq.mm FRLS insulated multistranded Copper wires, run in & including 25mm dia, 2mm thickness FRLS PVC ISI mark conduits concealed in wall after necessary chase cutting with finishing/surface in wall / ceiling conforming to IS 732 including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI Switch box withmodular switch and the box coveredwith Stainless Steel front plate.
212Two Lights point controlled by one 6A switch.
213Three Lights point controlled by one 6A switch.
214Four Lights point controlled by one 6A switch.
215Supplying and fixing suitable size GI box with modular Stainless Steelplate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
216Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class FRLS PVC conduit as required
2172 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2182 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2194 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
2204 X 6 sq. mm + 2 X 6 sq. mm earth wire
221Light/Fan Fixtures
222Supply, Installation, Testing & Commissioning of the following clean room / non clean room LEDLight Fixture with lamp, Control Gear & All necessary accessories. Luminaries with all electrical accessories & it should be energy efficient, etc are prewired up to the terminal block & mounted on a removable control gear module for ease of maintenance. All electrical connections of the control gear module with the rest of the luminaries should be click fix & require use of no tools. Mounting options should be for both lateral as well as pole top mounting with Lamp Control Gear & Fixing Accessories.All fixtures shall be white colour & supplied with white lamps. All the light fixtures will be finally approved by Architect / Consultant/ Department. Architect / Consultant / Department reserves the right to reject the fittings suggested by the contractor.
22336W LED PureSpace CleanRoom Range fixture similar toCat no.CR652B LED36S-6500 PSU CA BO W60L60 WH, Philips make
224Supply Installation Testing and commissioning of TPN MCB Double door Distribution boards dust and verminprotected and rated for 415V Three Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/ surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be "C" Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
2254Way TPNMCBDB with 40A, 30mA 4Pole RCBO as incomer and 9 nos 6-25A SPMCBs and 3nos 8KA SP SPDs as outgoings. (LDBs)
226SUBHEAD- POWER WIRING
227Supply and fixing of modular type single phase 16A 6pin shuttered type Socket with switch with stainless steel front plate and anodized GI box including all fixing accessories.
228Supply and fixing offabricated IP 44 20 A 2p+e Polycarbonate Industiral Plug and socket with bottom MS enclosure and Stainless steel front plate with 20A 2P MCB including all fixing accessories.
229Supply and fixing offabricated IP 44 32 A 2p+e Polycarbonate Industiral Plug and socket with bottom MS enclosure and Stainless steel front plate with 32A 2P MCB including all fixing accessories.
230Supply and fixing offabricated IP 44 20 A 3p+e Polycarbonate Industiral Plug and socket with bottom MS enclosure and Stainless steel front plate with 20A 3P MCB including all fixing accessories.
231Supply and fixing offabricated IP 44 32 A 3p+N+e Polycarbonate Industiral Plug and socket with bottom MS enclosure and Stainless steel front plate with 32A 3P MCB including all fixing accessories.
232Supply and fixing offabricated IP 44 63 A 3p+N+e Polycarbonate Industrial Plug and socket with bottom MS enclosure and Stainless steel front plate with 63A 3P MCB including all fixing accessories.
233Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class FRLS PVC conduit as required
2342 X 4 sq. mm + 1 X 4 sq. mm earth wire
2352 X 6 sq. mm + 1 X 6 sq. mm earth wire
2364 X 4 sq. mm + 2 X 4 sq. mm earth wire
2374 X 6 sq. mm + 2 X 6 sq. mm earth wire
2384 X 10 sq. mm + 2 X 10 sq. mm earth wire
239Supply Installation Testing and commissioning of TPN MCB Double door Distribution boards dust and verminprotected and rated for 415V Three Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/ surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be "C" Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
2404Way TPNMCBDB with 63A, 300mA 4Pole RCBO as incomer and 9 nos 6-25A SPMCBs and 3nos 8KA SP SPDs as outgoings. (PDBs)
241Supplying and fixing12 Way MCB VTPN DB complete with connections, testing and commissioning etc. as required with 250A, 25KA 4Pole MCCB as incomer and 12 nos 16- 63A 10KA TPMCBs as outgoings including cable end boxes on top and bottom.
242Supplying and fixing 8 Way MCB VTPN DB complete with connections, testing and commissioning etc. as required with 160A, 25KA 4Pole MCCB as incomer and 8 nos 16-63A 10KA TPMCBs as outgoingsincluding cable end boxes on top and bottom..
243Supply, testing & commisioning of following size 1.1KV grade XLPE insulated armoured copper conductor cable.The cable shall conform to IS 7098/ Part I.
2443.5C X 35 Sq.mm Copper
2453.5C X 95 Sq.mm Copper
246Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
247Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
248Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
249Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated andPVC sheathed / XLPEaluminium conductor cable of 1.1kV grade as required.
2503.5C X 35 Sq.mm Copper
2513.5C X 95 Sq.mm Copper
252SUBHEAD- UPS WIRING
253Supply and fixing of modular type single phase 2nos 16A/6A6pin shuttered type Socket with switch with stainless steel front plate and anodized GI box including all fixing accessories.
254Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class FRLS PVC conduit as required
2552 X 4 sq. mm + 1 X 4 sq. mm earth wire
2564 X 6 sq. mm + 2 X 6 sq. mm earth wire
2574 X 16 sq. mm + 2 X 16 sq. mm earth wire
258Supply Installation Testing and commissioning of TPN MCB Double door Distribution boards dust and verminprotected and rated for 415V Three Phase AC supply operation including incoming MCB /ELCB as per specifications and required capacity Neutral bar and Earth terminal complete as required and installed in concealed in wall after necessary chase cutting with finishing/ surface in wall including all fixing materials required. MCBs shall conform to IS : 8828 and ELCB shall conform to IS :12640. All MCBs shall be "C" Curve. DBs shall be provided along with required wire adopter boxes around the DB as required and dummys for spare ways in the DB (No claim shall be allowed for the same).
2594Way TPNMCBDB with 40A, 10KA 4Pole MCB as incomer and 12 nos 6-25A SPMCBs andas outgoings. (UPSSDBs)
260Supplying and fixing4 Way MCB VTPN DB complete with connections, testing and commissioning etc. as required with 125A, 25KA 4Pole MCCB as incomer and 4 nos 40 TPMCBs as outgoings. (UPS OUTPUT DB)
261Supply, fixing, testing and commissioning of 125 A, 4 Pole, 25 KA MCCB in an factory made enclosures with all requored accessories etc complete.
262Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
263Supplying and laying 25 mm X 5 mm copper strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50 mm)
264SHOP ELECTRICS
265Supply and fixing of following HOT DIPP GALVANIZED(GC) AS PER EN-ISO 1461, Steel wire mesh cable trays with internal dimensions & load bearing capacities as given below,including couplers, mounting accessories with including all fixing accessories and including 2runs of 25x5mm GI strip along with cable tray etc., complete as required.
266150mm x 54mm
267Supply, testing & commisioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor cable.The cable shall conform to IS 7098/ Part I.
2683.5C X 240 Sq.mm
269Laying of one number PVC insulated and PVC sheathed I XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
270Above 185 sq. mm and upto 400 sq. mm
271Laying of one number additionalPVCinsulated and PVC sheathed I XLPEpower cable of 1.1kV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
272Above 185 sq. mm and upto 400 sq. mm
273Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.l. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
274Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated andPVC sheathed / XLPEaluminium conductor cable of 1.1kV grade as required.
2753.5C X 240 Sq.mm
276Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
277Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
278Supply & laying in existing trench / hume pipe
279Supply and laying of following size earth strips including excavation and refilling ofearth when laid inground and with all fixing accessories when laid in trench with necessary interconnections with earth stationand equipments.
28050 X 5mm GI strip
281Supply & laying in ground
282Supply & laying in existing trench / hume pipe
283Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
284Supplying and laying 25 mm X 5 mm copper strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50 mm)
285SUBHEAD: TELEPHONE CONDUITING
286Supplying and fixing of following sizes of heavy class FRLS PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
28725 mm
288Supply and fixing of Telephone outlet (RJ11) with anodised GI box of withStainless steel front plate and telephone socket
289Supply and fixing of LAN outlet (RJ45) with anodised GI box of withStainelss Steel front plate and telephone socket
290Supplying and drawing following pair 0.5 sq mm FR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
2912 pair
292Supply and laying of CAT-6 LAN cable in the in the existing surface/ recessed steel/ PVC conduit as required.
293Supply and installation of following size Krone connectors in MS box complete as required.
29410pair
295Supply and laying of following size 0.5mm dia Jelly filled copper conductor armoured Cables in ground at 600mm below ground level including excavation, and refilling of earth, laying of cables, providing protection with sand and bricks on topand sides and Telephone cable route markers at every 50mtrs interval complete with including all terminations as required and as directed by Engr-in-charge. The cable shall be as per the DOT specifications.
29620pair
297Supply and laying of 80mm dia Class "B" GI pipes laid 750mm below ground level including excavation, back filling etc., complete.
298SUBHEAD: SPECIAL EARTHING
299Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
300Supply and laying of following size earth strips including excavation and refilling ofearth when laid inground and with all fixing accessories when laid on the wall with necessary interconnections with earth stationand equipments.
30125 X 5mm Copper strip with DMC Insulated Supports
30225 X 5mm Copper Strip laid in Ground
30350X5mm GI Strip
304Welding using Bi Metallic strips between copper and GI / MS Rod
305Supply and fixing of Static Discharge Handles made out of 20mm dia & 600mm length Copper rod fixed on wall with brass spacers andconected to 25x5mm copper strip.
306Brass or bronze flat bar 6x32x250mm mounted on two DMC Insulators (such as acro type 4649) holes of 8mm dia to accomidate 1/4" connection blots with washersand butterfly nuts all made of brass or copper.
307SUBHEAD: LIGHTNING PROTECTION
308Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
309Supply and laying of following size earth strips including excavation and refilling ofearth when laid inground and with allfixing accessories when laid on the parapet with necessary interconnections with earth stationand equipments.
31050 X 5mm GI Strip laid in Ground
31132 X 5mm Aluminium strip conductor with DMC Insulated Supports
31232 X 5mm Aluminium strip conductor with DMC Insulated Supports & including PCC Blocks.
313Supply and installation of vertical air termination with 40mm dia copper hollow sphere with spikes, fixed on 1000mm length 25mm dia Copper rod including PCC block and all fixing accessories.
314SUBHEAD: FIRE ALARM SYSTEM
315Supply, fixing, testing and commissioning of the following number of Loops Microprocessor based analogue addressable type (UL approved) intrinsically safe networkable Fire Control panelwith Zonal Indications, Zener barriers, Signal booster for network connectivity modules with Optic Fiber cable, patch cords and Fiber optic media converters for both sides of the panels along with automatic speech dialer facility and where ever is required and withBattery Power pack as per specifications.
316Single loop with loop card
317Supply and laying of twisted pair 2.5sq.mm shielded FRLS insulated copper conductor flexible wire through existing MS Conduit.
318Supply and fixing of 25mm dia 16SWG MS conduit concealed/ Surface in wall/ Ceiling/ above false ceilingincluding painting with 2 coats of Red colour paint for exposed part and all fixing accessories/ materials
319Supply, installation, testing and commissioning of analogue addressable type multi sensor (smoke/ Heat)photo electric detectors with base andLED indication lamp along with all fixing accessories.
320Supply, installation, Testing and commissioning of Response indicators with LEDIndication lamp along with all fixing accessories.
321Supply, installation, testing and commissioning of AddressablePull type Manual call stations with monitor module with all fixing accessories.
322Supply, installation, testing and commissioning of addressableloop sounders with all fixing accessories.
323Supply, installation, testing and commissioning of Fault Isolators along with all fixing accessories.
324Supply, installation, testing and commissioning of Addressable control modules along with all fixing accessories.
325Supply, installation, testing and commissioning of Addressable Monitor module along with all fixing accessories.
326Supply, installation, testing and commissioning of Addressable analogue type duct-able smoke detectors for AHU rooms with dual chamber, with all fixing accessories.
327Supply, installation, testing and commissioning of weather proof type analogue addressable Manual call pointswith glass and hammer on Stand post made out of 1500 mm long 50x50x6mm Galvanised channel fixed in ground with concrete coping as required.
328Supply, installation, testing and commissioning of 8 Way Wago/ Phonix terminal connector in weather proof MS Junctionbox including painting and all installation materials etc as required.
329Supply, installation, testing and commissioning of 2.5 Km range Siren with Weather proof motor with 220V 50HZ AC Supply operation with required power contactor, MPCB for control all in a weather proof enclosure near motor including all installation materials as required.
330Supply and laying of 3 core 2.5sq.mm Copper conductor PVC insulated armoured cable in built up cable trench/ already laid RCC hume pipe or on cable tray with all installation materials for provison of power supply to Fire Alarm Panel, Repeater Panel, Siren, Exit signage"s, Signalling modules etc complete.
331SUB HEAD : EXTERNAL POWER SUPPLY
332Supply, Fabrication, Transportation and erection of DP structure made with 2 Nos 175mm x 85mm (ISMB Modified ) or equivalent about 30"-0 length / 9.1 Mtrs length RS joist pole erection of the same Including excavation of pit in all kinds of soil including breaking stones, concreting with (1:3:6) mixture base plate, coil earthing back filling, 1:2:4 for coping including red oxide primary painting and two coats of aluminium painting etc., complete as required with following as per CEIG norms. a). 400A AB Switch-1No b) HG Fuse sets-1No c) LAS-1set. d) Required Number of 11KV pin and disc insulators. e) Required length of 100X50mm and 75X40 mm ISMC channel iron including two coats of red oxide and two coats of enamel paint etc for finished item of work. f) 11KV pin insulators and disc insulators. g) AB switch operating pipe with handle and lock and key arrangements. h). "0" SWG or 8.25 mm dia hard drawn bare copper wire including copper binding wire etc., complete as required including connections. i) 40X6mm GI strip for the DP structure earthing. j) 25X6mm copper strip for lightning arrestors earthing. k) 600X600mmX3,15mm thick copper plate earthing as per NEC with brick masonry chambers - 2 Nos l) GI pipe earthing for the Double pole structure with brick masonry chambers as per IS - 2 Nos
333Design Manufacture, Routine Inspection/Testing, and Supplying,installation and commissioning of Outdoor 11kV VCB HT Panels as under: 11kV, 25kA for 3Sec, Rating panel with 1 No VCB incomer and 2 nos VCB Outgoing and 1 No. LBS Outgoing panel with Cable Earthing Truck andBus Earthing Truck
334VCB
33511kV,25kA for 3Sec. 800A HT Vaccum Circuit Breaker with CC / TC –110V DC, Motor- 230 AC, with manual trip, anti pumping device, closing device, operation counter, Rack in & out handle, Trip Rod ( Incoming 1Nos)
33611kV,25kA for 3Sec. 630A HT Vaccum Circuit Breaker with CC / TC –110V DC, Motor- 230 AC, with manual trip, anti pumping device, closing device, operation counter, Rack in & out handle, Trip Rod,(-Outgoing 2Nos, Outgoing Trafo-1Nos, Spare-1 No.)
337Load break switch: 11KV,630A, 25 KA with fuse trip, earth switch, manually operated spring charged mechanism with 2 no + 2 NC.with HT HRC fuse up to 63A - 3 nos. Indication lamps.Manual trip Push button. Make :(Outgoing 1No, Outgoing Trafo-1Nos)
338Busbars
339Al Busbars with Suitable Rating 800amps
340Current Transformer and Potential Transformer
341Single Phase Current transformer STC 26.3kA/1S Ratio: 150/5-5A , Core1: 10VA, CL-1, Core 2: 10VA, CL 5P10 ( Incoming3Nos, Outgoing 6Nos)
342Single Phase Current transformer STC 26.3kA/1S Ratio: 30/5-5A , Core1: 5VA, CL-1, Core 2: 5VA, CL 5P10( Outgoing Trafo 3Nos)
343Single phase Voltage transformer with ratio of 11kV/RT3/110V/RT3/, 50VA, CL-0.2,100VA,3P Open delta( Incoming 3Nos)
344Meters
345Digital Ammeter with inbuilt selector switch( Incoming1Nos,Outgoing 2Nos, Outgoing Trafo-1Nos, Spare-1 No)
346Digital Voltmeter with inbulit selector switch(- Incoming 1Nos)
347Digital Multifunction Meter (Incoming 1Nos,Outgoing 2Nos, Outgoing Trafo-1Nos, Spare-1 No)
348Annunciator with Hooter
3498 Window Annunciator with Hooter (Incoming 1Nos, Outgoing 2Nos)
35012 Window Annunciator with Hooter ( Outgoing Trafo 1Nos, Spare-1 No)
351Power pack with 230AC Input and 110V DC Output(Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos, Spare-1 No)
352Surge Arrester( Outgoing Trafo 3Nos)
353Relays
354Numerical protection 50,51,67,50HS,49,50N,51N,67N,32,37,27,59,59N,81,81U, 81R,68F2,68H5,50BF,25,CTS,VTS,TCS,with RS485 P3U30/Equiv (- Incoming 1Nos)
355Numerical protection 50 / 51 / 50 N / 51 N /50G, 95 with Trip Circuit Supervision with RS485 (Outgoing 2Nos, Outgoing Trafo 1Nos, Spare-1 No)
356Master Trip Relay(86) VAJH13 (Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos)
357Aux contactor relay for Antipumping & DC Fail.(-Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos, Spare-1 No)
358Auxilliary Relay for Trafo faults(Outgoing Trafo 3Nos)
359Switches and other items
360RYB Indication Lamp ( Incoming 1Nos)
361LED indicating Lamp, 110V DC, for CB ON, OFF, TRIP, TCH , SPRING CHARGE, (Incoming set1,Outgoing Set2, Outgoing Trafo 1set, Spare-1 No)
362Local Remote selector switch(Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos)
363TNC switch(Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos, Spare-1 No)
364Emergency Trip push button(Incoming-Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos)
365MCBs For Control Ckt. As required( Incoming lot1, Outgoing Lot2,Outgoing Trafo 1lot)
366Thermostat & Spaceheater( Incoming set1,Outgoing Set2,Outgoing Trafo 1set, Spare-1 No)
367Panel Light LED TYPE, with DLS ( Incoming set1,Outgoing Set2,Outgoing Trafo 1set, Spare-1 No)
368LT Chamber Sheetmetal, Terminals, Wires and other BOC(Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos, Spare-1 No)
369HT Panel enclosure suitable for 11kV, 25KA for 1Sec Outdoor type-RAL 7032(Incoming 1Nos, Outgoing 2Nos,Outgoing Trafo 1Nos, Spare-1 No)
370Supply, Erection, Testing and Commissioning of Outdoor 11KV/0.433KV,800 KVA, 3phase,50 C/S, ONAN OIL FILLED TRANSFORMER WITHALL OTHER ACCESSORIES with On load tap changer OLTC+RTCC+AVRas per the I.S. - 2026 and load losses as per IS.1180 Level2 Outdoor type copper wound transformer connected delta on H.V. side and star on L.V. sidehaving additional neutral brought out on load side,with HV tapping +5% to -15% @1.25%(16-Steps / 17-Positions), continuously rated for full load, impedance shall be 5% and with the following standard mounting as per SLD and Technal specifiations
3711) Thermometer pocket for both OTI and WTI
3722) Lifting arrangements
3733) Two earthing terminals
3744) Diagram and rating plate
3755) base frame
3766) Air vent plug for both main tank and On Load tap changer
3777) Conservator Oil Filling Hole With Cap
3788) Oil Level IndIncomingator With Min. Marking & Max. Marking and Alarm
3799) Dehydrating SilIncominga Gel Breather
38010)Conservator With Drain Plugs
38111) Air Release DevIncominge
38212) Explosion Vent With Diaphragm
38313) Uni-directional Flanged Rollers
38414) Detachable Radiators
38515) H.V. cable box
38616) L.V. cable box
38717) Separate Neutrtal Terminal
38818) Radiator with cut-off valves
38919) Marshalling box containing the following items
390a) Dail type oil temperature indIncomingator with alarm trip contacts with RSD
391b) Dail type Winding temperature indIncomingator with alarm trip contacts with RSD
392c) supports
393d) Terminal mounting channel
394e) Terminal connectors
395f) Fixing Angles
396g) Detatchable Gland plates
397h) Cable Glands
398i) Earth terminal
39920) Surge Oil Relay
40021) Oil Drain Valve
40122) Oil Filter Valve
40223) ONAN Cooling
40324) Vector Group DYn 11
40425) HV Bushings with inspection covers
40526) LV Bushings with inspection covers
40627) On Load Tap Changer switch with locking devIncominge
40728) Additional Neutral Terminal bought out side the LV One
40829) Bucholtz relay (GOR) with shut off valves
40930) MagnetIncoming oil level guage
41031) Routine tests required (Preshipement and On site)
41132) Earth Resistance Box
41233) Tests to conduct
413a) BDV Test
414b) Moisture content test
415c) Measurement of Winding resistance
416d) Voltage ratio test
417e) No load loss at 100% voltage
418f) load loss and impedance measurement
419g) Vector group Measuremnt
420h) Insulation Resistance Measurement
421i) Seperate source withstand test
422The terminal arrangements bushing with lugs/ cable end box on HV side and bus duct arrangement on LV side complete with test certifIncomingate from manufacturer and completely erected on provided plinth as per direction of site incharge.
423Supply, Installation, Testing and Commissioning of 1600A rating of the Sandwich BBT. IP65 with Canopy for outdoor applications with necessaryStraight Feeder, 90 deg Elbow, Flange End,Copper Flexibles (braided),Adapter Box &Termination links.
424Supply, testing and commissioning of HT cable of size 3Cx 240 Sqmm as per IS standard. The cable shall conform to IS7098/ Part I.
425Laying of one number PVC insulated and PVC sheathed / XLPE"power cable of 11 KV grade of following size direct in ground"including excavation, sand cushioning, protective covering and"refilling the trench etc as required.
426Above 120 sq. mm and upto 400 sq.
427supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required
428240 Sqmm
429Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
430240 Sqmm
431Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
432240 Sqmm
433Main PCC panel
434Supply, installation, Testing andCommissioning of 3 phase and Neutral415V 4 wire Free Standing Floor mounted outdoor type weather proof double door with canopy on top MV panel made out of 3mm thick CRCA/Galvanised steel enclosurefor main frame and 2mm thick partitions after seven tank process and painting with Epoxy powder coating. The panel shall consist of suitable ratingTPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMCbarriers and color coded with Heat shrinkable sleeves. The Metering shall beprovided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below. Outdoor panels shall have IP-55 degree of protection wiith external door . Enclosure shall be modular with bolted design. Enclosure shall be powder coated with RAL-7035 coat with matt finish. Design ambient temperature shall be 50 degree centrigrade. No use of hygroscopic material like FRP/Hylam/Bakellite sheet inside the panel for partitions or any other purpose.
435The PCC shall have at least twospare cubicles. The size of all Panel Mounting Meters shall be 96X96mm. The Panels shall be mounted on U channels including supply and fixing of the same. Every ACB shall be provided with ON/OFF /Trip Indication lamps of LED type. For all Electrically operated Breakers, Local Remote Selector switches shall be provided for controlling the Breakers remotely.ACB"s shall have built-inAll ACBs shall be provided with Digital type Ammeter of suitable range along with CTs. All ACBs shall be provided with ON/OFF/TRIP indication lamps and shunt trip coils. All MCCB/ACBs of rating 160Aand above shall be with Micro processor releases All MCCBs below 160A shall be with adjustable thermal magnetic based releases. All MCCBs shall be with spreader links and rotary handle. All MCCBs shall be over load & short circuit releases withIcu=100% Ics. All CTs/CBCT shall be resin cast type. All Controlling wiring shall be FRLS cables, all the bus bar sleeves shall be Heat shrinkable kits.Panels shall have form 4b/form 3b construction as per the requirement. ACBs shall conform to IEC 60947 (part 1&2), shall be suitable for rated system voltage 690V, Insulation voltage 1000V and Impulse withstand of 12KV.
436For MCCB with Microprocessor based release : A common indication LED for internal temp/ fault/alarm . MCCB should have in-built feature of logical selectivity by which it can give a time delay of 50msec between upstream and downstream MCCB The microprocessor based release should have the following settings: • Overload Settings: 0.4 to 1 times of Ir • Short Circuit Settings: 1.25 to 10 times of Ir. • Earth fault Settings: 0.2 to 1 times of In. • Neutral protection settings: 0 – 50% – 100%Ir. • Manually closing mechanism should be accommodated in a Moulded housing of robust and vermin-proof construction. • MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open) • The tripping devices shall be ambient temperature compensated type. The insulating case shall be made of high strength heat resistant and flame retardant thermosetting insulating material.
437The panel shall have CO2 gas flooding system with including all required accessories
438EB Incoming :
4391600A FP, 50kA, electrically drawout Air Circuit Breaker Confirms toIEC 60947-2 and equipped with rogowksi current sensors and micro processor based protection release having adjustable over load, short circuit and earth fault protection. ACB shall be provided with electrical "Ready to Close" indication, LCD/LED display with HMI bar graph for percentage loading of phases, separate indication LED for L S/I G faults and dedicated Ethernet port for communication for ON/OFF/Trip status, trip and event history, breaker position in chassis, THD-I & THD-V, percentage ageing and contact wear
440DG Incoming-1
4411600A TPN, 50kA, electrically drawout Air Circuit Breaker Confirms toIEC 60947-2 and equipped with rogowksi current sensors and micro processor based protection release having adjustable over load, short circuit and earth fault protection. ACB shall be provided with electrical "Ready to Close" indication, LCD/LED display with HMI bar graph for percentage loading of phases, separate indication LED for L S/I G faults and dedicated Ethernet port for communication for ON/OFF/Trip status, trip and event history, breaker position in chassis, THD-I & THD-V, percentage ageing and contact wear
442Busbars :1600A TPN Aluminiumbusbars - 1 set
443(Neutral shall be 100% Phase busbar)
444Outgoings :
4451250A TPN, 50kA, electrically drawout Air Circuit Breaker Confirmsand micro processor based protection release having adjustable over load, short circuit and earth fault protection. ACB shall be provided with electrical "Ready to Close" indication, LCD/LED display with HMI bar graph for percentage loading of phases, separate indication LED for L S/I G faults and dedicated Ethernet port for communication for ON/OFF/Trip status, trip and event history, breaker position in chassis, THD-I & THD-V, percentage ageing and contact wear 1 No ( for HVACpanel )
446630A TPN, 50kA, electrically drawout Air Circuit Breaker Confirmsand micro processor based protection release having adjustable over load, short circuit and earth fault protection. ACB shall be provided with electrical "Ready to Close" indication, LCD/LED display with HMI bar graph for percentage loading of phases, separate indication LED for L S/I G faults and dedicated Ethernet port for communication for ON/OFF/Trip status, trip and event history, breaker position in chassis, THD-I & THD-V, percentage ageing and contact wear 2 Nos ( for APFC Paneland AO Beam Compensator )
447400A TPN, 50kA, electrically drawout Air Circuit Breakerand micro processor based protection release having adjustable over load, short circuit and earth fault protection. ACB shall be provided with electrical "Ready to Close" indication, LCD/LED display with HMI bar graph for percentage loading of phases, separate indication LED for L S/I G faults and dedicated Ethernet port for communication for ON/OFF/Trip status, trip and event history, breaker position in chassis, THD-I & THD-V, percentage ageing and contact wear - 1No.
448Supply of200A 3 Pole MCCB, 36KA Adjustable, having Breaking Capacity Ics= 36KA with thermal magnetic release Panel Mounted. -3Nos.
44963A TPN MCCB - 2 Nos - Spare
450Metering :
4510-500V Digital Voltmeter withselector switch and Fuses - 2 sets
4520-1600A Digital Ammeter with CTs ofratio 1600/5A,Class 1 Accuracy and15VA burden and selector switch - 2sets
453LED Phase indication lamps with individuals Fuses and control withtoggle switches- 2sets
454CT Operated Load Manager with RS 485 port ( Similar to EM-6400) – 2sets
455Note: Electrical & Mechanical Interlocking shall be provided for all incomers
456350KVAR APFC Panel-1Nos
457Supply, Fabrication,transpotation, erection and Commissioing of modular 350kVAr, 3Ph, 440V, 50Hz, 7% detuned APFC outdoor type weather proofPanel with double door and canopy andHeavy Duty Capacitorssuitable for 415V, 3 Phases, 4wire, 50Hz AC Supply system fabricated in comparmentalized design from CRCA sheet steel of 3mm thick from frame work and covers, 3mm thick for gland plate including cleaning and finishing complete with seven tank process for powder coating to thickness not less than 60 microns in approved shade having busbar 630A capacity equal in size for phase and neutral, extensible type TPN alluminum alloy busbars of high conductivity, DMC/SMC/Busbar supports with shortcircuit withstand capacity of 50KA for 1 sec, Impulse Withstand of 12kV, Impact Strength of IK10, metallic separators/partitions of IP2X preventing access to live parts as per type tested design, bottom based channel of MS section not less than 75mm x 50mm x 5mm thick, fabrication done in transportable section, entire panel shall have a common GI earth bar of size of two runs 25 x 6 mm at rear with 2Nos earth stud, solid connections from main Busbar to switchgears with required size of alumium busbars with control wiring, Auto/ Manual selector switches, control fuses, MCB"setc complete with providing following switchgears.
458All CTs shall be resin cast of 15VA burden
459Incoming
460630A TPN, 50kA, electrically drawout Air Circuit Breaker Confirms toIEC 60947-2 and equipped with rogowksi current sensors and micro processor based protection release having adjustable over load, short circuit and earth fault protection. ACB shall be provided with electrical "Ready to Close" indication, LCD/LED display with HMI bar graph for percentage loading of phases, separate indication LED for L S/I G faults and dedicated Ethernet port for communication for ON/OFF/Trip status, trip and event history, breaker position in chassis, THD-I & THD-V, percentage ageing and contact wear
461Supply and erection of L.T. 3phase Digital multifunctionmeter Class I, Ethernet port, with LCD display for measuring all the parameters (Voltage, Current, Frequency, Power factor, KW, KVA, KWH, KVA, KVAH, KVAR and THD Events) on existingpanel board including connections etc., complete. - 1No
462Supply and erection of LED step indicating lamps on the existing panel board- 24 Nos.
463Supply and erection of Push buttons on the existing panel board. Makes : SCHNEIDER / ABB / SIEMENS MAKE. - 24Nos
46496 x 96 mm sq. 630A digitalammeter - 1 No.
465Supply and erection of LT current transformer with bar primary630 / 5A ratio, Cl- 1.0, 10VAin the existing panel including connections etc., complete. MAKE : SCHNEIDER / ABB / SIEMENS - 3 Nos
4660-500 Voltdigital voltmeter - 1 No.
467Supply and erection of Auto / Manual selector switche on the existing panel board Makes : SCHNEIDER / ABB / SIEMENS. - 1 No.
468Supply and fixing of 12 stage APFC Relay with connection etc complete. Makes : SCHNEIDER / ABB / SIEMENS - 1 No.
469For 25KVAr – 2 STEPS
470Supply and fixing of 25KVAR Rating capacitor duty contactor - 2 Nos
471Supply and fixing of detuned reactor 7% 3 phase 440V range 25.0 KVAR- 2 Nos
472Supply of 63A 3 Pole MCCB,Adjustable, Confirms to IS/IEC 60947-2having Breaking Capacity Ics=36KA with thermal magnetic release Panel Mounted. - 2No"s
473Supply of MPP type heavy duty capacitor of not less than 480V of box type of 25KVAR operating voltage
474For 50KVAr – 4 STEPS
475Supply and fixing of 50KVAR Rating capacitor duty contactor- 4 Nos
476Supply and fixing of detuned reactor 7% 3 phase 440V range 50.0 KVAR- 4 Nos
477Supply of100A 3 Pole MCCB, 36KA Adjustable, Confirms to IS/IEC 60947-2 having Breaking Capacity Ics=36KA with thermal magnetic release Panel Mounted. - 4 Nos
478Supply of MPP type heavy duty capacitor of not less than 480V of box type ofKVAR to 50KVAR operating voltage - 4 Nos
479For 100KVAr – 1 STEPS
480Supply and fixing of 100KVAR Rating capacitor duty contactor - 1No.
481Supply and fixing of detuned reactor 7% 3 phase 440V range 100.0 KVAR-1No
482Supply of200A 3 Pole MCCB, 36KA Adjustable, Confirms to IS/IEC 60947-2 having Breaking Capacity Ics= 36KA with thermal magnetic release Panel Mounted. -1N0.
483Supply of MPP type heavy duty capacitor of not less than 480V of box type of 5 KVAR to 100KVAR operating voltage-1No.
484Supply, installation, Testing andCommissioning of 3 phase and Neutral415V 4 wire Free Standing Floor mountedMV panel made out of 2mm thick CRCA/Galvanised steel enclosurefor main frame and 1.6mm thick partitionsafter seven tank process and painting with Epoxy powder coating. The panel shall consist of suitable ratingTPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMCbarriers and color coded with Heat shrinkable sleeves. The Metering shall beprovided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below.. Indoor panels shall have IP-4X degree of protection and outdoor panels shall have IP-55 degree of protection wiith external door . Enclosure shall be modular with bolted design. Enclosure shall be powder coated with RAL-7035 coat with matt finish. Design ambient temperature shall be 50 degree centrigrade. No use of hygroscopic material like FRP/Hylam/Bakellite sheet inside the panel for partitions or any other purpose.
485The Panel shall have at least twospare cubicles. The size of all Panel Mounting Meters shall be 96X96mm. The Panels shall be mounted on U channels including supply and fixing of the same. Every ACB shall be provided with ON/OFF /Trip Indication lamps of LED type. For all Electrically operated Breakers, Local Remote Selector switches shall be provided for controlling the Breakers remotely.ACB"s shall have built-inAll ACBs shall be provided with Digital type Ammeter of suitable range along with CTs. All ACBs shall be provided with ON/OFF/TRIP indication lamps and shunt trip coils.All MCCBs shall be with spreader links and rotary handle. All MCCBs shall be over load & short circuit releases withIcu=100% Ics. All CTs/CBCT shall be resin cast type. All Controlling wiring shall be FRLS cables, all the bus bar sleeves shall be Heat shrinkable kits.Panels shall have form 4b/form 3b construction as per the requirement. ACBs shall conform to IEC 60947 (part 1&2), shall be suitable for rated system voltage 690V, Insulation voltage 1000V and Impulse withstand of 12KV.
486For MCCB with Microprocessor based release : A common indication LED for internal temp/ fault/alarm . MCCB should have in-built feature of logical selectivity by which it can give a time delay of 50msec between upstream and downstream MCCB The microprocessor based release should have the following settings: • Overload Settings: 0.4 to 1 times of Ir • Short Circuit Settings: 1.25 to 10 times of Ir. • Earth fault Settings: 0.2 to 1 times of In. • Neutral protection settings: 0 – 50% – 100%Ir. • Manually closing mechanism should be accommodated in a Moulded housing of robust and vermin-proof construction. • MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open) • The tripping devices shall be ambient temperature compensated type. The insulating case shall be made of high strength heat resistant and flame retardant thermosetting insulating material.
487Incoming :
488400A TPN, 50kA, electrically drawout Air Circuit Breakerand micro processor based protection release having adjustable over load, short circuit and earth fault protection. ACB shall be provided with electrical "Ready to Close" indication, LCD/LED display with HMI bar graph for percentage loading of phases, separate indication LED for L S/I G faults and dedicated Ethernet port for communication for ON/OFF/Trip status, trip and event history, breaker position in chassis, THD-I & THD-V, percentage ageing and contact wear - 1No.
489Busbars :400A TPN Aluminiumbusbars - 1 set
490(Neutral shall be 100% Phase busbar)
491Outgoings :
49232A 10KA FP MCB – 6nos
49363A 10KA FP MCB – 12nos
49416A 10KA FP MCB – 20nos
495Metering :
4960-500V Digital Voltmeter withselector switch and Fuses - 1 set
4970-400A Digital Ammeter with CTs ofratio 400/5A,Class 1 Accuracy and15VA burden and selector switch - 1set
498LED Phase indication lamps with individuals Fuses and control withtoggle switches- 1set
499CT Operated Load Manager with RS 485 port ( Similar to EM-6400) – 1set
500Supply, installation, Testing andCommissioning of 3 phase and Neutral415V 4 wire Free Standing Floor mountedMV panel made out of 2mm thick CRCA/Galvanised steel enclosurefor main frame and 1.6mm thick partitionsafter seven tank process and painting with Epoxy powder coating. The panel shall consist of suitable ratingTPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMCbarriers and color coded with Heat shrinkable sleeves. The Metering shall beprovided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below.. Indoor panels shall have IP-4X degree of protection and outdoor panels shall have IP-55 degree of protection wiith external door . Enclosure shall be modular with bolted design. Enclosure shall be powder coated with RAL-7035 coat with matt finish. Design ambient temperature shall be 50 degree centrigrade. No use of hygroscopic material like FRP/Hylam/Bakellite sheet inside the panel for partitions or any other purpose.
501The Panel shall have at least twospare cubicles. The size of all Panel Mounting Meters shall be 96X96mm. The Panels shall be mounted on U channels including supply and fixing of the same. Every ACB shall be provided with ON/OFF /Trip Indication lamps of LED type. For all Electrically operated Breakers, Local Remote Selector switches shall be provided for controlling the Breakers remotely.ACB"s shall have built-inAll ACBs shall be provided with Digital type Ammeter of suitable range along with CTs. All ACBs shall be provided with ON/OFF/TRIP indication lamps and shunt trip coils.All MCCBs shall be with spreader links and rotary handle. All MCCBs shall be over load & short circuit releases withIcu=100% Ics. All CTs/CBCT shall be resin cast type. All Controlling wiring shall be FRLS cables, all the bus bar sleeves shall be Heat shrinkable kits.Panels shall have form 4b/form 3b construction as per the requirement. ACBs shall conform to IEC 60947 (part 1&2), shall be suitable for rated system voltage 690V, Insulation voltage 1000V and Impulse withstand of 12KV.
502For MCCB with Microprocessor based release : A common indication LED for internal temp/ fault/alarm . MCCB should have in-built feature of logical selectivity by which it can give a time delay of 50msec between upstream and downstream MCCB The microprocessor based release should have the following settings: • Overload Settings: 0.4 to 1 times of Ir • Short Circuit Settings: 1.25 to 10 times of Ir. • Earth fault Settings: 0.2 to 1 times of In. • Neutral protection settings: 0 – 50% – 100%Ir. • Manually closing mechanism should be accommodated in a Moulded housing of robust and vermin-proof construction. • MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open) • The tripping devices shall be ambient temperature compensated type. The insulating case shall be made of high strength heat resistant and flame retardant thermosetting insulating material.
503Incoming :
504Supply of200A 3 Pole MCCB, 36KA Adjustable, Confirms to IS/IEC 60947-2 having Breaking Capacity Ics= 36KA with thermal magnetic release Panel Mounted. -1N0.
505Busbars :200A TPN Aluminiumbusbars - 1 set
506(Neutral shall be 100% Phase busbar)
507Outgoings :
50816A 10KA FP MCB – 12nos
50932A 10KA FP MCB – 10nos
51063A 10KA FP MCB – 5nos
511Metering :
5120-500V Digital Voltmeter withselector switch and Fuses - 1 set
5130-200A Digital Ammeter with CTs ofratio 200/5A,Class 1 Accuracy and15VA burden and selector switch - 1set
514LED Phase indication lamps with individuals Fuses and control withtoggle switches- 1set
515CT Operated Load Manager with RS 485 port ( Similar to EM-6400) – 1set
516MV Cables
517SUBSTATION ACCESSORIES
518Supply and laying of 2.0mm thick 3.3KV Rubber Mats as per IS 15652 of size1000mm x2000mm
519Supply and erecting 4.5KG Carbon Dioxide (CO2) Fire Extiguisher with necessary clamps made from 50 x 6mm M.S. Flat with Nut & Bolts growted in wall complete.
520Providing printed instruction chart both in English, Hindi and local launguage and duly framed with front glasses, for treatment of person suffering from Electric shock.
521Supply and Fixing of Laminated SLD-A1size
522Providing pair of rubber hand gloves suitable for working on 11 KV
523Supply, testingand commissioning of following size 1.1KV grade XLPE insulatedarmoured aluminium conductor cable.The cable shall conform to IS 7098/ Part I.
5243.5C X240 Sq.mm
5253.5C X120 Sq.mm
5263.5C X70 Sq.mm
527Laying of one number PVC insulated and PVC sheathed I XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUMEI METAL pipe as required.
528Above 70 sq. mm and upto 185 sq. mm
529Above 185 sq. mm and upto 400 sq. mm
530Supplying and making end termination with brass compression gland and aluminium lugs for followingsize of PVCinsulatedandPVCsheathed /XLPE aluminium conductor cable of 1.1kV grade as required.
5313.5C X240 Sq.mm
5323.5C X120 Sq.mm
5333.5C X70 Sq.mm
534Supply and laying of following dia. NP2 grade RCC hume pipes with collars for road crossings, laid 750mmbelow ground level including excavation,back filling etc., complete.
535300mm dia.
536SUBHEAD: DG SETS
537Supply, Transportation, erection and commissioning (Excluding Foundation) of 3 Phase, 415, 50Hz, water cooled multi cylinder diesel generator set with alternator of 500 KVA/ 400 KW output continuous rating directly coupled Engine and Alternator with guard and mounted on a common base plate of Robust construction and complete with AMF panel having IP-52 protection, Acoustic Enclosure as per CPCB norms , sound absorbing material, to restrict sound level up to 75 dB up to 1 Mtr distance and as per CPCB norms etc as per following specifications mentioned below..
538A. Alternator :The alternator of the output rating shall be 3 Phase, 415V, 50Hz, Ac , 0.8 P.F. lagging at 1500 RPM. The alternator is self-excited, self-regulated, and shall confirm to IS: 13364 of 1992 or latest version with regulation of +5% from no load to full load. degree of protections shall be IP23.
539B.Diesel Engine : Diesel Engine start, developing suitable 608 BHP output at 1500 RPM with mechanical / electronic governing so as to enable the alternator to give 500KVA continuous output at 0.8 P.F. lagging at NTP conditions. The diesel engine shall be capable of providing 10% O/L for 1 Hr for every 11 Hrs. of continuous running at full load. The engine with 1st filling of oil and Diesel etc.
54001. Exhaust pipe of required size and length with insulation as per the site condition with aluminum cladding.
54103. Residential Silencer.
54204. SMF Batteries with leads as per the Manufacturer standards
543C. AMF Control Panel:- AMF control panel shall be fabricated with 16SWG CRCA sheet shall be totally enclosed with dust and Vermin proof, floor mounted / wall mounted type and shall be comprising the following. 01. Voltmeter with selector switch. 02. 4 Pole ACB incomer of 1000A rating offor EB and DG . 03. Ammeter with selector switch with CTs. 04. PF Meter and frequency Meter. 05. Indicator lamps (set Run, Load ON) with fuses. 06. KWH Meter of required rating. 07. Set of control fuses and current transformer. 08. Input Terminal board and output Terminal Board. 09. Battery charger with transformer rectifier unit. 10. Alternator supply air break contactor of L&T make. 11. Main supply air break contactor of L&T make. 12. Audio Visual annunciation . 13. Main supply voltage set of control relays and timers with one mode selector switch, set of push buttons.14.Control cable up to 15 Mtrs 2.5Sq.mm 6 Core
544500 KVA, 3 Phase, 415, 50 Hz, not less than 608 BHP, water cooled multi-cylinder diesel generator set with alternator of 500 KVA output continuous rating at 0.8 p.f. Batteries.
545MV Cables
546Supply, testing and commissioning of following size 1.1KV grade XLPE insulatedarmoured aluminium conductor cable.The cable shall conform to IS 7098/ Part I.
5473.5C X240 Sq.mm
548Laying of one number PVC insulated and PVC sheathed I XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUMEI METAL pipe as required.
549Above 185 sq. mm and upto 400 sq. mm
550Supplying and making end termination with brass compression gland and aluminium lugs for followingsize of PVCinsulatedandPVCsheathed /XLPE aluminium conductor cable of 1.1kV grade as required.
5513.5C X240 Sq.mm
552Supply and Fixing of MS Exhaust Pipe of suitable size for following DG sets cladded with 50mm thick Glass wool insulation covered with 24SWG Aluminium sheet and provided with rain cap
553500KVA
554Supply and fabrication of supports for Residential silencer/ exhaust pipe made out of MS channels/angles includingcutting, welding and fabrication to the required size and painting with 2 coats of anti corrsoive paint and 2 coats of synthetic enamel paint of Gey/ Blackcolour complete as required
555Supply, laying and commissioning of following size1.1KV grade PVC insulated armoured multi strand copper conductor under ground cable,in built up cable trench/already laid RCC hume pipe or on cable tray with all installation materials.The cable shallconform to IS 1554/Part I.
55610core 2.5sq.mm
5574core 2.5sq.mm
5584core 4sq.mm
559Providing single compression end terminations for the cablespecifiedabove with compression typesteel gland,lugs using crimping tool,Insulation tape,Identification tags etc.,including endtermination and Earthingof Gland.
56010core 2.5sq.mm
5614core 2.5sq.mm
5624core 4sq.mm
563Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
564Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
565Supply and laying of following size strips including excavation in any type of soil including SDR & hard rock and refilling of earth when laid in ground and with all fixing accessories when laidinside the buildingincluding all necessary interconnections withearth station and equipments.
56650 X 5mm Galvanised GI strip
567Supply & laying in ground
568Supply & laying in existing trench / hume pipe
56940X5mm Copper strip with sleeve
570Supply & laying in ground
571Supply & laying in existing trench / hume pipe
572AREA LIGHTING
573Supply and erection of steel stepped and swaged tubler poles of 9mtr. Long (410 SP25) (1.5mtr below Ground) with base plate, earthing studs,1.5Mtr out reach single arm, FRP terminal box, 2nos 50mm diaclass B GI Pipe, 1.5mtr. Long for incoming and outgoings cables, including PCC Pedestal complete with painting with black bitumin paint inside the coping for embedded portion andtwo coats of Zinc chromate primer and two coats of Aluminium paint externally for length above the ground. The pole shall be with Junction box consisting of MCB. The wiring from Junction box to Light fixture shall be carried out with 3core 2.5sq.mm multistrand conductor cable. The Pole shall be fixed with 72W LED Lamp with fixture including supply of Controlgear/driver and lamp(Philips : BRP410 LED CW 072 MR FG S1 PSU GR )
574Supply, testing & commisioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor cable.The cable shall conform to IS 7098/ Part I.
5754Core 6 sq.mm
576Laying of one number PVC insulated and PVC sheathed I XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
577Up to 35Sq.mm
578Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUMEI METAL pipe as required.
579Upto 35 sq. mm
580Supplying and fixing cable route marker with 10 em X 10 em X 5 mm thick G.l. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cmlong and fixing the same in ground as required.
581Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated andPVC sheathed IXLPEaluminium conductor cable of 1.1kV grade as required.
5824Core 6 sq.mm
583Providing Spiral coil earthing with 8 SWG GI wire including spreading of salt and charcoal as per IS 3043/87 with latest amendments.
584Supply and laying of following dia. NP2 grade RCC hume pipes with collars for road crossings, laid 750mmbelow ground level including excavation,back filling etc., complete.
585150mm dia.
586WATER COOLERS
587Supply, Installation, Testing and Commissioning of Storage Water Coolers with Storage capacity of 80 litres and cooling capacity of 40 litres suitable for operation on 230 V +/- 10%, 50 Hz, full stainless steel body including multi stage RO purification system, 2 kVA voltage stabiliser etc., complete