| Sl. No. | Item Description |
| 1 | Wiring point for light with 1.5 Sq. mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit on surface with 1.5 Sq. mm FRLSH PVC insuleted multistrand copper conductor cable as earth wire drawn inside. continuity wire, Modular type switch & ceiling rose/angle/ batten holder on 3mm thick phenolic laminated backelite sheet etc. complete in all respect. with Modular Box & Cover plate. |
| 2 | Wiring point for fan/fresh air fan (light duty exhaust fan) with 1.5 Sq. mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit on surface with 1.5 Sq. mm FRLSH PVC insuleted multistrand copper conductor cable as earth wire drawn inside. continuity wire, Modular type switch & ceiling rose on 3mm thick phenolic laminated backelite sheet etc. complete in all respect. with Modular Box & Cover plate. |
| 3 | Wiring point for plugwith 1.5 Sq. mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit on surface with 1.5 Sq. mm FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit, Modular type switch & socket etc. complete in all respect with Modular Box & Cover plate. |
| 4 | Wiring point for light with 1.5 Sq. mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 Sq. mm FRLSH PVC insuleted multistrand copper conductor cable as earth wire drawn inside. continuity wire, Modular type switch & ceiling rose/angle/ batten holder on 3mm thick phenolic laminated backelite sheet etc. complete in all respect. with Modular Box & Cover plate. |
| 5 | Wiring point for fan/fresh air fan (light duty exhaust fan) with 1.5 Sq. mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 Sq. mm FRLSH PVC insuleted multistrand copper conductor cable as earthwire drawn inside the conduit, Modular type switch & ceiling rose on 3 mm. thick backelite sheet etc. complete in all respect with Modular Box & Cover plate. |
| 6 | Wiring point for plugwith 1.5 Sq. mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 Sq. mm FRLSH PVC insuleted multistrand copper conductor cable as earthwire drawn inside the conduit, Modular type switch & socket etc. complete in all respect with Modular Box & Cover plate. |
| 7 | Wiring point for call bellwith 1.5 Sq. mm FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 Sq.mm FRLSH PVC insuleted multistrand copper conductor cable as earthwire drawn inside the conduit. Modular type bell push or 2 pin socket etc. complete in all respect with Modular Box & Cover plate. etc on Surface. |
| 8 | Supplyfixingand concealing of20mm dia.2mm thick PVC conduit pipe with ISI mark embossed and with PVC acessories confirming to IS No. 3419 for drawing wires duly sealed at joints with original resin/ adhesive to make the complete piping rigid,plastering with cement sand mortar finished to level with matching colour including cost of material labour and T & P etc required for proper completion of work. |
| 9 | Supply and wiring of submain 2 number 4 sqmm . FRLSH PVC insulated 1100 V grade multistranded single core copper conductor cable in heavy duty( 2 mm thick ) 20mm dia PVC conduit partly concealed in wall and partly laid in slab along with reinforce,ment before concreting with one number 2.5 sqmm FRLSH PVC insulated multistranded copper conductor. cable as earth contunity wire drawn inside the conduit etc. complete in all respects. |
| 10 | Supply and wiring of submain 2 number 6 sqmm . FRLSH PVC insulated 1100 V grade multistranded single core copper conductor cable in heavy duty( 2 mm thick ) 25mm dia PVC conduit partly concealed in wall and partly laid in slab along with reinforce,ment before concreting with reinforce,ment before concreting with one number 4 sqmm FRLSH PVC insulated multistranded copper conductor cable as earth contunity wire etc. complete in all respects. |
| 11 | Supply and wiring of submain 4 number 10 sqmm . FRLSH PVC insulated 1100 V grade multistranded single core copper conductor cable in heavy duty ( 2 mm thick ) 32mm dia PVC conduitalong with reinforce,ment before concreting with two numbers 6 sqmm FRLSH PVC insulated multistranded copper conductor cable as earth contunity wire etc. complete in all respects. |
| 12 | Supply and wiring of submain 4 number 16 sqmm . PVC insulated 1100 V grade single core copper conductor cable in 40mm dia PVC conduitalong with reinforce,ment before concreting with two numbers 10 sqmmsingle core PVC insulatedcopper conductor cable as earth contunity wire etc. complete in all respects. |
| 13 | Supply and laying of aluminium conducter, PVC insulated armoured, served, sheeted cable 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75mm thick sand alround and protected with burnt bricks on sides and top on surface, the cable run shall be fixed on M.S. clamps etc. of suitable size.as per direction of Engineer-Incharge.complete in all respect The armouring of the cable shall be properly connected with the earth conductor by clamps etc. a300 sqmm3.5 core |
| 14 | 150 sqmm3.5 core |
| 15 | 50 sqmm3.5 core |
| 16 | 25 sqmm4 core |
| 17 | 16 sqmm4 core |
| 18 | 10 sqmm4 core |
| 19 | Supply & fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respects. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. a 300 sqmm3.5 core |
| 20 | 240 sqmm3.5 core |
| 21 | 150 sqmm3.5 core |
| 22 | 50 sqmm3.5 core |
| 23 | 25 sqmm4 core |
| 24 | 16 sqmm4 core |
| 25 | 10 sqmm4 core |
| 26 | Supplying and fixing of Palm / pin type copper tin plated cables sockets (lugs) to the cable leads, insuslating with tape and making of connections etc. complete in all respects as per direction of Engineer-Incharge.a300 Sq.mm |
| 27 | 240 Sq.mm |
| 28 | 150 Sq.mm |
| 29 | 50 Sq.mm |
| 30 | 25 Sq.mm |
| 31 | 16 Sq.mm |
| 32 | 10 Sq.mm |
| 33 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130 mm and base plate 12 mm thik) having 3mm thikness with Single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. |
| 34 | Supply and burying of 600mm x 600 mmx3mm Copper plate, vertically for earthing with its top atleast 3 mts. below ground level complete with 20mm G.I.pipe and funnel for watering and two earthing leads of No.8SWG G.I.wire in 15mm dia G.I. pipe upto switch board (from apron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm. square C.I. frame with hinged cover, masonary housing, alternate layers/of charcoal/ coke and salt at least 150mm thick alround etc. complete in all respects. |
| 35 | Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respects. |
| 36 | Supply and Laying of 32mm X 6 mm Copper strip from earth electrode directly in the ground as required complete in all respects.. |
| 37 | Supply and fixing of one number 8 SWG G.I wire in 15mm dia. G.I pipe for earthing laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of the work as directed at site. |
| 38 | Supply and burring of Safe Earthing Electrode T-19, (Hot Dip Galvanized), Length up to 3000 mm, Outer Dia 50 mm, inner Dia 25, terminal Dia 12 mm, outer G.I. pipe of 16 swg and inner G.I. pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity and one earthing lead of 25 mm x 3mm G.I. strip upto switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. |
| 39 | Supply and fixing of 240 volts \"L\" series miniature circuit breaker 6 Amp. To 32 Amp. (10 K A ) in existing MCB, DB complete with connections as required. (CAT: A) |
| 40 | Supply and fixing of 6 Amp to 32 Amp DP MCB (10KA) (C curve) for poles |
| 41 | S/F of 40 Amp. FP MCB(10 KA) C Curve |
| 42 | S/F of 63 Amp. FP MCB(10 KA) C Curve |
| 43 | Supply and fixing of flush/surface mounting 4 ways TPN distribution board without MCB with additional metal door complete in all respects. |
| 44 | Supply and fixing of flush/surface mounting 6 ways TPN distribution board without MCB with additional metal door complete in all respects. |
| 45 | Supply and fixing sheet steel enclosure for T.P./F.P.MCB |
| 46 | Supply and fixing danger board fabricated from 10 gauge MS sheet as per IE Rules |
| 47 | S/F of fan hook fabricated from MS rod for ceiling fan each |
| 48 | Supply and fixing of fire extinguishers, ABC Type 6.00 kg. capacity(ISI Marked IS : 15683 & TAC approved)complete with initial charges and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 49 | Supply and fixing of CO2 typefire extinguishers, 4.50 kg. capacity(ISI Marked IS : 2878 & TAC approved)complete with initial charges and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 50 | Supplying andFixing of Fire buckets, round bottom made of G.I. Sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-charge. |
| 51 | S/F of shock treatment chart (prescribed under I.E.rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T & Pfor proper completion of work. |
| 52 | Supplying & Layingof 1800 mm x 900 mm X 12 mm thick chequered rubber matting of tested quality |
| 53 | Supply and fixing of power plug with 20A/250 V flush type modular switch and 5 Pin 20 A/250 Volt flush type universal modular socket switch on concealedM.S. box including supply of all material, labour T & P etc required for proper completion of work. |
| 54 | S/F of hexagonal fan box with hexagonal side of approx 80mm in length fabricated from 16SWGM.S. sheet incorporating 10mm dia, M.S. round barduly bent for supporting fan hanger dully painted withred oxide and screwing arrangement with wiring conduit laid in the R.C.C. roof before concreting along with supply of all materials, labour T & P etc., for proper completion of work. |
| 55 | Supplyfixingofelectronic fan regulator(modular) 120-280 V. ISImarked, on the existing switch board including making connetion, required material, labour T/P etc for proper completion of work to the satisfaction of Engineer in charge of work. |
| 56 | Supply & wiring of submains with 2 nos. 2.5 sq.mm & with 1 no. earth wire of 1.5 sq.mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in heavy duty( 2 mm thick ) 20mm dia PVC conduit partly concealed in wall and partly laid in slab along with reinforce,ment before concreting with one number 1.5 sqmm FRLSH PVC insulated multistranded copper conductor. cable as earth contunity wire drawn inside the conduit etc. complete in all respects. |
| 57 | Supply & fixing of 36 Watt to 46 Watt indoor recess/Surface mounting LED Square Fitting for Armstrong ceiling having powder die cast aluminium housing body with extended heat sink and diffuser os special polycorbonate meterial and driver set,complete in all respects. |
| 58 | Supply & fixing of LED Tube Light witH Metal heavy duty Box type batten light fitting 1 x 22 watt suitable for upto 1X22 W LED Polycarbonate tube light complete including tube etc on surface complete in all respects.(CAT: AAA) |
| 59 | Supply & fixing of LED Tube Light witH Metal heavy duty Box type batten light fitting 2 x 22 watt suitable for upto 2X22W LED Polycarbonate tube light complete including tube etc on surface complete in all respects.(CAT: AAA) |
| 60 | Supply & Fixing of Single LED light Wall bracket 3 to6W on matching M.D.F.E.G.Board base etc complete in all respect. |
| 61 | Supply and fixing of LED street light fitting having die cast aluminium body and diffuser with driver set suitable for 90 watt. Confirming to IP 66 and above protection complete in all respect. |
| 62 | Supply and Ceiling fan with fan motor of AC permanent insulation, capacitor rating conforming BEE 5 star rating and IS: 374/79 and also comply with IS:1709/1984 with latest amendment. The rated voltage 220/240 volt 50Hz, 1-ph AC the fan assemble should consist of down rod blades, shackle canopies etc and with double ball breaing systemBEE 5 star rated-1200 mm sweep |
| 63 | Supply and erection of AC 230/250 Volts, 50 Hz exhaust fans including providing nuts, bolts, mounting frame and other accessories including connections etc. complete as required300mm sweep. |
| 64 | MAIN L.T. PANELDesign, Manufacturing, Supply, Commissioning & Testing of Main LT Panel. The panel will be totally enclosed type with, free standing, floor mounted, indoor duty, dust & vermin proof, , front operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, ammeter, ammeter selector switch, voltmeter, voltmeter selector switch, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness. The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers, FSU\"s as per the drawing and specification.interlocking, buscouplerswitching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers, FSU\"s as per the drawing and specification.Each incoming breaker will have microprocessor based releases and all outgoing breaker will have minimum electrostatic releases or mention as mention in BOQ. The Panel will be made as per detailed specifications & drawings forming part of this document. Fault level of panel shall be 35 MVA. INCOMING1 Nos. 630 Amp FP ACB 2 Nos. 400 Amp FP ACB 1 Nos.160 Amp FP MCCBBUSBARS2 Nos. 630 Amp TPN busbars of aluminium alloy as per SLD.OUTGOING2 Nos. 200 Amp FP MCCB 4 Nos. 125 Amp FP MCCB 1 Nos. 100 Amp FP MCCB 7 Nos. 63Amp FP MCB 3 Nos. 40 Amp FP MCB INSTRUMENTS4 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers.4 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).4 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for each incoming breaker).4 Sets auto trip indicating lamp .Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.RELAYS AS PER SLD |
| 65 | STREET LIGHTING FEEDER PILLARSupplying assembling erecting connecting, testing and commissioning of sizes of 3.15mm thick sheet metal enclosed outdoor type feeder pillars with water proof dust and vermin proof hinged and lockable doors including rain protection cover complete with interconnections, with aluminium wire, tapes, bonding to earth and painting complete as required.The feeder pillar shall consist of 63 Amp MCB as incoming and MCCB/MCB as outgoing.(Note : This panel shall be a FRONT operated, with cable entry from the top/bottom.The fault with standing capacity shall be 10 KA.Earth busbar shall be part of the L.T. Panel). INCOMING1No. Of 100 Amps TPN MCCB of 10KA service breaking capacity and 100 Amp trip setting.BUS BAR1 Set of 100 Amps TPN Aluminium Bus Bars of suitable length and of cross section . Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints.Bus bar shall be designed to with stand a fault level of 10 KA at 415 volts.3Nos. Phase indicating lamp each lamp shall have one toggle switch .OUTCOMING 63 Amp TP MCB (10 kA) - 3 Nos.32Amp TPMCB (10kA) - 4 Nos.32Amp SPMCB (10kA) - 1 No. Spare |
| 66 | Supplying fixing and commissioning of SILENTDG Set with electronic governer with one Diesel Engine with 200 KVA rated capacity at 0.8 P.F. 1500 RPM, 4 stroke multi-cylinder coupled to brush less type 415 volts 50 cycle/ second self exited alternator completed with cushy pads. Domestic silencer exhaust pipe complete with Alternator auxiliaries, Radiator, 24 volts chargeable battery including initial charging of batteries.suitable for synchronizing complete as per specification. |
| 67 | Supplying fixing and commissioning of SILENTDG Set with electronic governer with one Diesel Engine with 100 KVA rated capacity at 0.8 P.F. 1500 RPM, 4 stroke multi-cylinder coupled to brush less type 415 volts 50 cycle/ second self exited alternator completed with cushy pads. Domestic silencer exhaust pipe complete with Alternator auxiliaries, Radiator, 24 volts chargeable battery including initial charging of batteries.suitable for synchronizing complete as per specification. |
| 68 | Supply of 14W LED Mirror light Similar to Crompton Greaves Cat Ref. LCL-14-CDL or equivalent. |
| 69 | Drilling of 150 mm dia T/W bore suitable for 110mm dia pipe/200mm dia T/W bore suitable for 140 mm dia pipe all complete with labour T/P as per direction of engineer incharge |
| 70 | Supply and lowering of 110 mm dia 6kg/cm2 PVC pipe/140mm dia 10kg/cm2 with plastic net cover slots of pvc pipe by UPIN(phenolex or apb by E/I) all complete (ISI mark only) SOR 2017-18 |
| 71 | Supply and pouring of pee gravels suitable for T/W bore all complete as per direction of engineer incharge |
| 72 | S/F of 110mm PVC pipe adopter suitable for item no. 2 |
| 73 | Supply of 1HP submersible pump set with starter UPIN 65m head ( Pluga/Crompton Greeves/KSB) |
| 74 | Supply and fitting of 4sqmm 3 core copper wired cable (ISI mark) complete in all respect |
| 75 | Supply and lowering of 40 mm dia ribbed screen Ashirvad PVC pipe (ISI marked)/ 32 mm dia G.I. Pipe by UPIN and fixed with boat site threaded SS nipple all complete. |
| 76 | Transportation of all material T&P etc to the site of work, loading, unloading and proper stacking at the site including return cartage of unused material with the diging the pit of boring work including supply all labour T&P with with arrangement of water required etc all complete. |
| 77 | Installation of 1.00HP submersible motor pump with 32mm G.I. Lowering, submersible cable 4sqmm & installation of starter including supply of labpur, T&P etc complete in all respect |
| 78 | devlopment of bore hole till the discharges of water become free from sand and turbidity by compression and disinfection of bore including supply of all labour T&P |
| 79 | Chemical & bacteriological testing of water sample |
| 80 | S/F of 32 Amp. 240V SPN metal clad rewireable type switch fuse unit on MDFEG/Teak wood board complete in all respect. |
| 81 | S/B of 600mm x 600mm x 6.0mm GI plate vertically for ear thing with its top at least 3 meters below ground level complete with 20mm dia G.I. pipe and funnel for watering and one ear thing leadof one no. 8 to 10 SWG GI wire in15mm dia G.I. pipe up to switch board (from apron to switch board the coast of G. I. pipe and GI wire will be extra) 30 cm square C.I frame with hinged cover masonry housing alternate layers of charcoal /coke and salt at least 150 mm thick all-round etc. as per directions of E/I complete in all respects. |
| 82 | Supply and fixing of one number 8 to 6 SWG G.I.Wire in 15 mm dia G.I. pipe for ear thing ,laid in ground or in wall duly concealed including the cost of cement ,sand .lab our , T&P other material required for proper completion of the work as directed at site. |
| 83 | S/F of 25mm dia G. I. Pipe complete with G. I. Fittings,clamps including all materials, Labour etc complete in all respects. |
| 84 | S/F of 32mm dia G. I. Pipe complete with G. I. Fittings,clamps including all materials, Labour etc complete in all respects. |
| 85 | Providing, laying and fixing 50mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc |
| 86 | S/L of aluminim conductor PVC insulated armored, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by Engineer-In-Charge, complete in all respects The armoring of the cable shall be properly connected with the earth conductor by clamps etc. (i) 10sqmm 2 core |
| 87 | S/F of CP brass stop cock 15mm of approved make complete in all respects. |
| 88 | S/F of 6 Amp to 32 Amp SPMCB (10 KA) C Curve Cat A |
| 89 | S/F of 6 Amp to 32 Amp. DPMCB (10 KA) C curve Cat A |
| 90 | S/F surface/flush mounting 4 way SPN distribution board with additional metal door without MCB complete in all respect and as directed at site. Cat A |
| 91 | S/F of CP brass bib cock 15mm of approved make complete in all respects. |
| 92 | S/F of gun metal non return valve 32mm of approved make complete in all respects. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender