Orissa Industrial Infrastructure Development Corporation-IDCO has published Construction Of 33Kv Line Carrying 148Mm2aaac Overhead Line With 13Mtr Long Wpb From Chainpal 132 / 33 Kv Grid To Nalco Aluminium Park Premises ( Front Gate ) For Route Length Of 11 Km And Supply And Laying Of 33Kv 1C X 400Mm2 Xlpe Ug Cable ( Pkg-03 ). Submission Date for this Tender is 29-10-2022. Overhead Line Tenders in angul Odisha. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Construction of 33KV OH line with 13mtr WPB and 148 sqmm AAAC from Chainpal 132/33KV Grid to NALCO Aluminium Park premises (front gate). |
2 | WPB 160x152 (13Mtr. Long, 30.44KG/Mtr.) |
3 | Top Channel 100 x 50 x 6mm, 9.56 KG/Mtr., each channel length 3 mtr., 2 no"s channel required =( 2x9.56x3) |
4 | Fish Plate 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no"s required = (6x2.36x0.280) |
5 | Double Pole Belting Channel 75X40X 4.8mm.7.14KG/Mtr., each channel length 1.66 Mtr., 5 no"s channel required = (5 x 7.14 x 1.96) |
6 | 50x50x6mm.GI Bracing Angle, 4.5Kg./mtr., each angle length 3.432 mtr, 4 nos angle required = (4 x 4.5 x 3.432) |
7 | Danger Plate, 2 no"s. |
8 | Back Clamp for danger Plate 25 x 3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 2 no"s = (2x0.59x0.510) |
9 | H.T. Stay clamp, 50x8 mm. flat, 3.14Kg/Mtr., 0.551 Mtr. Length, 2 no"s qty. required (1 Pair) |
10 | H.T. Stay set (Complete ) |
11 | H.T. Stay Insulator Type-C (2 no"s) |
12 | 7/8 SWG Stay Wire 15kg /stay |
13 | Gi Pipe Earthing 40mm. 3 Mtr. Long |
14 | 50x6mm GI Flat for earthing, 2.36kg/mtr. (2.5 mtr. For mesh iformation and 2.5 mtr. For raising)= 5x2.36 |
15 | GI barbed wire anticlimbing device 3 Kg. Per support. |
16 | Back Clamp for anticlimbing device 25 x 3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 8 no"s = (8x0.59x0.510) |
17 | 33 KV pin insulator polymer |
18 | H W fitting(B&S) 90KN, 4 Bolt |
19 | Disc insulator (B&S) 90 KN polymer |
20 | PG Clamp for 148 sq.mm AAA conductor |
21 | GI Nut , Bolt & Washer of different sizes (12.251 Kg each DP without Isolator) |
22 | Black Paint |
23 | Yellow Colour Paint for Background |
24 | CIVIL & SERVICES. |
25 | Fixing of 33KV line Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5) Stay clamps with Nuts & bolts, including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size (500mmx500mmx 800mm) using 20mm BHG metal with all labour and material (Excavation of earth will be done of size 500 x 500 x 1500mm) |
26 | Concreting ratio 1:1, 5:3 (500mm x 500mm x 2200mm) = 0.55Cu. Mtr |
27 | Couping ratior 1:1, 5:3 with diemnsion (500 x 500 x 450) = 0.1125 Cu. Mtr. |
28 | Installation of Earth pit, charcoal, salt etc. including construction of earthing chamber (Size: 2" x 2") and RCC slab cover. |
29 | Construction of 33KV DP with Isolator. |
30 | WPB 160x152 (13tr. Long, 30.44KG/Mtr.) |
31 | Top Channel 100 x 50 x 6mm, 9.56 KG/Mtr, each channel length 4.3 mtr., 2 no"s channel required =(2 x 9.56 x 4.3) |
32 | Fish Plate 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no"s required = (6x2.36x0.280) |
33 | Insulator Support Channel 75 x 40 x 4.8mm, 7.14KG/Mtr, each channel length 4.3 Mtr., 1 no"s channel required = (1x7.14x4.3) |
34 | Isolator Support Channel 75 x 40 x 4.8mm, 7.14KG/Mtr, each channel length 4.3 Mtr., 2no"s channel required = (2x7.14x4.3) |
35 | Double Pole Belting Channel 75 x 40 x 4.8mm.7.14KG/Mtr., each channel length 4.3Mtr., 4 no"s channel required =(4 x 7.14 x 4.3) |
36 | 50 x 50 x 6mm.GI Bracing Angle, 4.5Kg./mtr., each angle length 4.927 mtr., 4 nos angle required = (4 x 4.5 x 4.927) |
37 | Isolator Operating Down Pipe support channel 75 x 40 x 4.8mm. 7.14KG/Mtr., each channel length 0.8 Mtr. 1 no"s channel required =(1 x 7.14 x 0.8) |
38 | Down Pipe Diagonal Support Angle, 4.5Kg./mtr., each angle length 0.388mtre 1 nos angle required . (1x4.5x0.388) |
39 | Down Pipe Base Support Angle, 4.5Kg,/mtr„ each angle length 0.34rntr., 1 nos angle required = (1x4.5x0,340) |
40 | Isolator Support Side Channel 100X50X6rnm, 9.56 KG/Mtr., each channel length 0.5 mtr., 2 no"s channel required (2x9.56x0,5) |
41 | Danger Plate, 2 no"s. |
42 | Back Clamp for danger Plate 25 x 3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 2 no"s e (2x0.59x0,510) |
43 | H.T. Stay clamp, 50x8 rnm. flat, 3.14Kg/Mtre 0.511 Mtr.Length, 2 no"s qty. required ( 1 Pair) |
44 | H.T. Stay set.(Complete ) |
45 | H.T. Stay. Insulator Type-C (2 No"s.). |
46 | 7/8 SWG Stay Wire 15 kg /stay |
47 | Gi Pipe Earthing 40mm, 3 Mtr. Long |
48 | 50 x 6mm GI Flat for earthing, 2.36kg/rntr., (15 Mtr. For L.A. 4 Mtr for Isolator Body, 2.5 mtr. For mesh formation and 2.5 mtr. For raising). 24 x2.36 |
49 | GI barbed wire anticlimbing device 3 Kg. Per support |
50 | Back Clamp for anticlimbing device 25 x 3mm, flat 0.59Kg/ Mtr. Flat of 0.510mtr length 8 no"s = (8x0.59x0.510) |
51 | Lightning Arrester(30KV,10KA) (Station Ctass,class-2) |
52 | 33 KV 630 AMP Double break (Turn & twist center rotating) isolator without earth switch with PI(Polymer) |
53 | 33KV pin insulator polymer |
54 | H W fitting (B&S) 90KN, 4 Bolt |
55 | Disc insulator (B&S) 90 KN polymer |
56 | PG Clam. for 148sqmm AAA conductor |
57 | GI Nut, Bolt & Washer of different sizes (22,15 Kg each DP with Isolator) |
58 | Black Paint |
59 | Yellow Colour Paint for Background |
60 | CIVIL WORK. |
61 | Fixing of 33KV line Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5)Stay clamps with Nuts & bolts, including excvation, supply of 0,5Cum cement concrete foundation 1:2:4 size (500rnm x 500mm x 800rnm) using 20mm BHG metal with all labour and material (Excavation of earth will be done of size 500 x 500 x 1500 mm.) |
62 | Concreting ratio 1:1,5:3 (500mm x 500mm x 2200mm) = 0 55Cu.mtr |
63 | Couping ratio 1:1,5:3 with dimension(500 x 500 x 450)= 0.1125 Cu mtr |
64 | Installation of Earth Pit, Charcoal, Salt etc: including construction of earthing chamber (Size: 2"x2") and RCC slab cover |
65 | 33KV Cut point with 180 degree angle. |
66 | WPB 160x152 (13tr. Long, 30.44KG/Mtr.) |
67 | Straight Cross Arm Channel 100 x 50 x 6 mm, 9.56 KG/rntr, each channel length 1.7 Mtr, 2 No"s of Channel = (2x 9.56 x1.7) |
68 | Fish Plate 50x6 mm., 2.36 kg/Mtr., each 0,280 mtr. length, 8 no"s required = (8x2.36x0.280) |
69 | Straight Cross Arm Top Channel 100 x 50 x 6 mm, 9.56 KG/mtr, each channel length 0.306 Mtr., 2 No"s of Channel = (2x 9 56x0,306) |
70 | Danger Plate, 1 no"s, |
71 | Back Clamp for danger Plate 25 x 3 mm. flat, 0.59Kg/Mtr. Flat of 0,510mtr length 1 no"s = (1x0.59x0.510) |
72 | GI barbed wire anticlimbing device 3 Kg. Per support |
73 | Back Clamp for anticlimbing device 25 x 3 mm. flat, 0.59Kg/Mtr, Flat of 0.510mtr length 4 no"s = (4x0.59x0.510) |
74 | 33KV pin insulator polymer |
75 | H W fitting B&S 90KN 4 Bolt |
76 | Disc insulator (B&S) 90 KN polymer |
77 | Earthing of Support ( Coil Type ) |
78 | No-8 GI wire (Dia 4,6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing |
79 | PG Clamp for 148 sqmm AAA conductor |
80 | GI Nut , Bolt & Washer of different sizes (4.879 Kg each 180 deg. Cut point) |
81 | Black Paint |
82 | Yellow Colour Paint for Background |
83 | CIVIL WORK. |
84 | Concreting ratio1:1,5:3 (500mmX500mmX2200mm)= 055Cu.mtr |
85 | Couping ratio 1:1,5:3 with dimension (500X500X450)= 0.1125 Cu mtr |
86 | 33KV Cut point with 90 degree angle. |
87 | WPB 160x152 (13tr. Long, 30.44KG/Mtr.) |
88 | Straight Cross Arm Channel 100 x 50 x 6 mm, 9.56 KG/rntr, each channel length 1.7 Mtr., 4 No"s of Channel = (4x 9.56x1.7) |
89 | Fish Plate 50x6 mm. 2.36 kg/Mtr., each 0.280 mtr. length, 16 no"s required = (16 x 2.36 x 0.280) |
90 | Straight Cross Arm Top Channel 100 x 50 x 6 mm, 9.56 KG/mtr, each channel length 0.306 Mtr., 4 No"s of Channel = (4x 9 56x0.306) |
91 | Danger Plate, 1 no"s, |
92 | Back Clamp for danger Plate 25 x 3 mm. flat, 0.59Kg/Mtr. Flat of 0,510mtr length 1 no"s = (1x0.59x0.510) |
93 | GI barbed wire anticlimbing device 3 Kg. Per support |
94 | Back Clamp for anticlimbing device 25X3 mm. flat, 0.59Kg/Mtr, Flat of 0.510mtr length 4 no"s = (4x0.59x0.510) |
95 | 33KV pin insulator polymer/ 4nos each 90Deg cut point. |
96 | H W fitting B&S 90KN 4 Bolt |
97 | Disc insulator (B&S) 90 KN polymer |
98 | Earthing of Support (Coil Type ) |
99 | No-8 GI wire (Dia 4,6mm) 0.131 KG/ Mtr- 2 Mtr for connecting pole with Coil earthing |
100 | PG Clamp for 148 sqmm AAA conductor |
101 | H.T. Stay clamp, 50x8 rnm. flat, 3.14Kg/Mtre 0.511 Mtr.Length, 2 no"s qty. required ( 1 Pair) |
102 | H.T. Stay set.(Complete ) |
103 | H.T. Stay. Insulator Type-C (2 No"s.). |
104 | 7/8 SWG Stay Wire 15 kg /stay |
105 | GI Nut , Bolt & Washer of different sizes (11.31 Kg each 90deg. Cut point) |
106 | Black Paint |
107 | Yellow Colour Paint for Background |
108 | CIVIL WORK. |
109 | Concreting ratio 1:1,5:3 (500mmX500mmX2200mm) = 0 55Cu.mtr |
110 | Couping ratio 1:1,5:3 with dimension( 500X500X450)= 0.1125 Cu mtr |
111 | Fixing of 33KV line Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5) Stay clamps with Nuts & bolts, including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size (500rnm x 500mm x 800rnm) using 20mm BHG metal with all labour and material (Excavation of earth will be done of size 500 x 500 x 1500 mm.) |
112 | 33KV line length in km with 50mtr span. |
113 | WPB 160x152 (13tr. Long, 30.44KG/Mtr.) |
114 | 33 KV V cross Arm (GI) 22Kg each |
115 | Top bracket 100x50x6mrn GI channel ( 2kg each) |
116 | Danger Plate, 1 no"s. |
117 | Back Clamp for danger Plate 25x3 mm. flat, 0.59Kg/Mtr. Flat of 0.510intr length 1 no"s = (1x0.59x0.510) |
118 | GI barbed wire anticlimbing device 3 Kg. Per support |
119 | Back Clamp for anticlimbing device 25 x 3 mm. flat, 0.59Kg/ Mtr. Flat of 0.510mtr length 4 no"s = (4x0.59x0.510) |
120 | 33KV pin insulator polymer |
121 | Earthing of Support (Coil Type ) |
122 | No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing |
123 | GI Nut , Bolt & Washer of different sizes (1.45 Kg/ Pin Point) |
124 | 148 sqmm AAA conductor |
125 | Black Paint |
126 | Yellow Colour Paint for Background |
127 | CIVIL WORK. |
128 | Concreting ratio 1:1,5:3 (500mmX500mmX2200mm) = 0 55Cu.mtr |
129 | Couping ratio 1:1,5:3 with dimension (500X500X450) = 0.1125 Cu mtr |
130 | PART-C: Supply and laying of 33KV 1C x 400sqmm XLPE UG cable for road crossing and railway crossing from NALCO Premises to NALCO 33/11KV S/S (front gate) and NALCO Premises to NALCO 33/11KV S/S (front gate). |
131 | Supply of materials for 33KV 1c x 400sqmm Al. XLPE insulation UG cable (along with 1core spare cable) with accessories. |
132 | Supply of 1C x 400 sqmm, 33 KV, XLPE, Power cable Armored, aluminium conductor, stranded, including the irtermination materials like glands, lugs, tagging etc. as required as per technical specifications and scope of the works. |
133 | Supply of 33 KV 1C X 400 sq.mm. Heat Shrink In Door cable termination kit complete with all accessories and tagging etc. as per technical specifications and scope of the works. |
134 | Supply of 33 KV 1C X 400 sq.mm. Heat Shrink Out Door cable termination kit complete with all accessories and tagging etc. as per technical specifications and scope of the works. |
135 | Supply of 33 KV, 1C X 400 sqmm Heat Shrink type termination kit complete with all accessories and tagging etc. as per technical specifications and scope of the works. |
136 | Erection, commissioning & testing of 33KV new line by 3c x 1core, 400sqmm XLPE UG cable with one spare. |
137 | Laying, commissioning & testing of 1C 4runs x 400 sqmm, 33 KV, XLPE insulation (extruted type) UG cable (with one single 1core, 400sqmm XLPE cable as spare) in trefoil formation by open trench method. |
138 | Erection of Straight through jointing kits Heat Shrinkable type suitable for 33KV, 1core 400sqmm aluminium UG cable kits. |
139 | Erection of outdoor termination kits Heat Shrinkable type suitable for 33KV, 1core 400sqmm aluminium UG cable kits. HT UG cable kits. |
140 | Erection of indoor termination kits Heat Shrinkable type suitable for 33KV, 1core 400sqmm aluminium UG cable kits. HT UG cable kits. |
141 | Laying, commissioning & testing of 33KV, 1Core, 4runs, 400sqmm, XLPE insulation (extruted type) UG cable (with one single 1core, 400sqmm, XLPE cable as spare) including looping at cable terminations and straight through joints by HDD method with HDPE pipe for laying of individual run of UG cable at main road and unaccessable place. |
142 | CIVIL PORTION. |
143 | Civil works with supply of all materials like cement, MS tor rod, brick, coarse & fine aggregates and labour, T&P, etc for UG Cable trench. |
144 | Earth work excavation of soil (2mtr. Width x 1.65mtr. Depth) |
145 | Earth work excavation of normal soil Trench Dimenstion: (2mtr. Width x 1.65mtr. Depth) |
146 | Earth work excavation of hard rock Trench Dimenstion: (2mtr. Width x 1.65mtr. Depth) |
147 | Shifting of excavated soil to a lead distance of 10km. |
148 | Filling with fine river sand after laying of cable inside the trench. |
149 | Back filling with excavated soil outside and above the trench. |
150 | Supply and erection of prefabricated RCC partition slab 950mm x 450mm x 50mm (M-30 grade) |
151 | Supply and erection of prefabricated RCC trench (1.050mtrD), 150mm thick (M-30 grad) cast-in SITU. |
152 | Supply of rod, bending, cutting and binding of prefabricated RCC trench (0.898 Qunit/cum)-Cast-in-SITU. |
153 | Supply of rod, bending, cutting and binding of prefabricated RCC slab (0.687Qunit/cum). |
154 | Damage of asphalt/tar rod and other utilities and reconstructing to bring to its original shape after laying of cable in open trench (1mtr width) |
155 | Bedding with fine river sand after laying of cable below trench (width 1500mm, thickness 100mm througout) |
156 | PCC (1:3:6) below trench (width 1500mm, thickness 100mm throughout) |
157 | Supply and erection of GI Pipe of dia, 150mm Class-B (8mtr) |
158 | Supply and erection of cable route marker along the cable route at an interval of 30 mtrs with civil works. |
159 | N.B: The bidders are required to Quote their rates excluding of Goods & Service Tax (GST). GST as applicable will be paid extra. The existing rule of Govt. and any amendment made in future will be followed. |