Comprehensive Repair Maint Of Dg Sets Amf Control Panels Distribution Panels Connected Cables Pcc Plateform And Connected Items At Akhnoor Under Ge N Akhnoor, akhnoor-Jammu And Kashmir

Military Engineer Services-MES has published Comprehensive Repair Maint Of Dg Sets Amf Control Panels Distribution Panels Connected Cables Pcc Plateform And Connected Items At Akhnoor Under Ge N Akhnoor. Submission Date for this Tender is 20-10-2022. Diesel Generators Tenders in akhnoor Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

34057670
Corrigendum : Comprehensive Repair Maint Of Dg Sets Amf Control Panels Distribution Panels Connected Cables Pcc Plateform And Connected Items At Akhnoor Under Ge N Akhnoor
Open Tender
Indian
Jammu And Kashmir
akhnoor
20-10-2022

Tender Details

Comprehensive Repair Maint Of Dg Sets Amf Control Panels Distribution Panels Connected Cables Pcc Plateform And Connected Items At Akhnoor Under Ge N Akhnoor

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Oct-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 20-10-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 50000.0 /-
Tender Value
INR 25 Lakhs /-

BOQ Items

Name of Work : COMPREHENSIVE REPAIR/ MAINT OF DG SETS, AMF CONTROL PANELS,DISTRIBUTION PANELS, CONNECTED CABLES, PCC PLATEFORM AND CONNECTED ITEMS AT AKHNOOR UNDER GE (N) AKHNOOR
Sl. No. Item Description
1Earthing complete with galvanized steel earth plate electrode 600mm x600mm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground leel, connecting to the Galvanised earthing lead strip 32x6mm size, by means of bolts, nuts, heck nuts and washers of galvanized iron andearth lead protected by provision of GI medium grade pipe 65mm bore incl provision of concrete pit in PCC 1:2:4 type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC 1:2:4 reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 25x25x6mm with lugs 02 Nos and with 6mm dia MS bar handle made to shape GI medium grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt & charcoal filling, test point made out of 40mm x 8mm FI with fixing arrangement, funnel, wire mesh and earth work in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 mtrs, all as per electrical plate No 3 of SSR-1991 Part I and connected to earth test point all as specified or indicated incl testing on completion.
2Taking down unserviceable Panel and accessories like burnt MCCB, bus bars and Supply, Installation and commissioning and testing LT paneloutdoor cubical floor mounted channel typeopenable to front and back both side made out of 3.15 mm thick CRCA sheet dulypowder coated complete with bus barsize not less than 40x5mm made of Aluminium strip duly drillled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50Hz power supply system including the following. Make of panel- Indian Transformers & Electricals Pvt Ltd. Gurgaon, Legrand, Schnieder, L&TNote:- Panel shall be as per IEC -61439 part I & IIand TTA approved
3INCOMER i) MCCBDU 200 Amp 4 Pole 50 Hz 415 Vwith rupturing capacity 25 KA. -01 Nos as incomer Make L&T Cat part No CM90634OOPO Conforms to IS/IEC 60947-2 & IEC 60947-2 l Adjustable Overload Setting: 0.8 - 1.0 x In
4(B) OUTGOING ii) MCCB DU 125 Amp 4 Pole 50 Hz 415 Vwith rupturing capacity 25 KA. -02 Nos as outgoing Make L&T Cat part No CM90634OOMO Conforms to IS/IEC 60947-2 & IEC 60947-2 l Adjustable Overload Setting: 0.8 - 1.0 x In
5(iii) On load changeover 200 Amp 4 pole Make L&T -01 No
6iv) Indicator set RYB 01 set of 3 pcs,
7v) Digital votmeter of size 96 x 96 mm range 30 to 600 volts of AE Make or equivalent of Make L&T with in built in selector switch 01 Set.
8vi)Digital ammeter of size 96 x 96 mm range 0 to 500 amps of AE Make or equivalent of Make L&T with in built in selector switch complete with CTs of appropriate ratio 01 Set.
9All accessories prewired with suitable size copper conductor cable/strip and suitable foundation as per manufactrur"s recomendation. Note:-(i) Drawing of the panel will be approved by the Engr-in-charge (ii) Factory testing will be carried by the manufacturer in the presence of Engr-in-charge.
10Taking down unserviceable Panel and accessories like burnt MCCB, bus bars and Supply, Installation, commissioning and testing LT paneloutdoor cubical floor mounted channel typeopenable to front and back both side made out of 3.15 mm thick CRCA sheet dulypowder coated complete with bus barsize not less than 40x5mm made of Aluminium strip duly drillled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50Hz power supply system suitable for including the following. Make of panel- Indian Transformers & Electricals Pvt Ltd. Gurgaon, Legrand, Schnieder , L&T Note:- Panel shall be as per IEC -61439 part I & IIand TTA approved
11(A) INCOMER (i) MCCB DU 160 Amp 4 Pole 50 Hz 415 V with rupturing capacity 25KA. -01 Nos as outgoing Make L&T Cat part No CM90634OONO Conforms to IS/IEC 60947-2 & IEC 60947-2 l Adjustable Overload Setting: 0.8 - 1.0 x In
12(B) OUTGOING (ii) MCCB DU 125 Amp 4 Pole 50 Hz 415 Vwith iii) MCCB DU 125 Amp 4 Pole 50 Hz 415 Vwith rupturing capacity 16 KA. -02 Nos as outgoing Make L&T Cat part No CM90634OOMO Conforms to IS/IEC 60947-2 & IEC 60947-2 l Adjustable Overload Setting: 0.8 - 1.0 x In
13(iii) On load changeover 160 Amp 4 pole Make L&T -01 No
14iv) Indicator set RYB 01 set of 3 pcs,
15v) Digital votmeter of size 96 x 96 mm range 30 to 600 volts of AE Make or equivalent of Make L&T with in built in selector switch 01 Set.
16vi)Digital ammeter of size 96 x 96 mm range 0 to 500 amps of AE Make or equivalent of Make L&T with in built in selector switch complete with CTs of appropriate ratio 01 Set.
17All accessories prewired with suitable size copper conductor cable/strip and suitable foundation as per manufactrur"s recomendation. Note:-(i) Drawing of the panel will be approved by the Engr-in-charge (ii) Factory testing will be carried by the manufacturer in the presence of Engr-in-charge, Any changes in the design will be incorporated.
18Taking down unserviceable Panel and accessories like burnt MCCB, bus bars and Supply, Installation, commissioning and testing LT paneloutdoor cubical floor mounted channel typeopenable to front and back both side made out of 3.15 mm thick CRCA sheet dulypowder coated complete with bus barsize not less than 40x5mmrating made of Aluminium strip duly drillled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50Hz power supply system suitable for and including the following. Make of panel- Indian Transformers & Electricals Pvt Ltd. Gurgaon, Legrand, Schnieder , L&T Note:- Panel shall be as per IEC -61439 part I & IIand TTA approved
19(A) INCOMER (i) MCCB DU 250 Amp 4 Pole 50 Hz 415 V with rupturing capacity 25KA. -01 Nos as outgoing Make L&T Cat part No CM90634OONO Conforms to IS/IEC 60947-2 & IEC 60947-2 l Adjustable Overload Setting: 0.8 - 1.0 x In
20(B) OUTGOING (ii) MCCB DU 125 Amp 4 Pole 50 Hz 415 Vwith iii) MCCB DU 125 Amp 4 Pole 50 Hz 415 Vwith rupturing capacity 16 KA. -03 Nos as outgoing Make L&T Cat part No CM90634OOMO Conforms to IS/IEC 60947-2 & IEC 60947-2 l Adjustable Overload Setting: 0.8 - 1.0 x In
21(iv) On load changeover 250 Amp 4 pole Make L&T -01 No
22v) Indicator set RYB 01 set of 3 pcs,
23vi) Digital votmeter of size 96 x 96 mm range 30 to 600 volts of AE Make or equivalent of Make L&T with in built in selector switch 01 Set.
24vii)Digital ammeter of size 96 x 96 mm range 0 to 500 amps of AE Make or equivalent of Make L&T with built in selector switch complete with CTs of appropriate ratio 01 Set.
25All accessories prewired with suitable size copper conductor cable/strip and suitable foundation as per manufactrur"s recomendation. Note:-(i) Drawing of the panel will be approved by the Engr-in-charge (ii) Factory testing will be carried by the manufacturer in the presence of Engr-in-charge, Any changes in the design will be incorporated.
26Taking down burnt cable and Supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 70 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. Make:- KEI/ Gloster/ Polycab
27Taking down burnt cable and Supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 95 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. Make:- KEI/ Gloster/ Polycab
28Taking down burnt cable and Supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 120 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. Make:- KEI/ Gloster/ Polycab
29Taking down burnt cable and Supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 185 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. Make:- KEI/ Gloster/ Polycab
30M&L for 80mm dia bore galvanised iron light grade for cable protection and sealing both ends including taking out old pipe complete all as specified and as directed. Make:- Tata/ Jindal/ Prakash Surya.
31M&L for 100mm dia bore galvanised iron light grade for cable protection and sealing both ends including taking out old pipe complete all as specified and as directed. Make:- Tata/ Jindal/ Prakash Surya.
32Supply, fabrication and fixing feeder pillarbox of size 500x 450x500 mmmade out of MS sheet of 3.15 mm thick bent to shape & size factory made with welding, bending works suitable for including 200 Amps ratedaluminium bus bars (length of bus bar not less than 40 cm) 4no"s ,makingholes of any size and mounted on porcelain/epoxy based post insulators of appropriate sizewith suitable size of nuts, bolts and washers complete with mounting leg of size 40x40x5 mm and length of angle iron not less than 1 mtr, 0.5 mtr to be embeded in PCC below G.L and 0.5 mtr above ground including painting of complete structure with two coats of super enamelled synthetic paint over a coat of red oxide and incoming/out going cable connections with required size of cable lugs with proper crimping. Make :- Indian Transformers & Electricals Pvt Ltd. Gurgaon, DVEPL, Electrifield, Siemen.
33Excavation in tranches not exceeding1.5 m wideand not exceeding 1.5 m deep for foundationof laying cable including gettingout in soft/loosesoil complete all as specified and directed.
34Returning filling in including spreadingwateringand well ramming in layers not exc25cmcomplete all as specifed .
35Removing surplus soilto distance not exceeding50 m and depositing where directed at a level notexceeding 1.5 m above the starting pointcomplete all asspecifiedand directed .
36M & L for protection to cable with one layer of brick laid flat across the cable using all size sub class "B" Bricks.
37Sand cushioning to under ground electric cables including watering and consolidation all as per clause 19.75 of SSR Part-I
38Surface excavation n exc 30cm deep and averaging 15 cm any type of soil all as specified and directed.
39M&L for rolling and consolidating of soling of broken bouldersnot exceeding 15cm thick with power roller exc 5 tonne and n" exc 8 Tonne.
40M&L for broken stone boulder hardcore of guage exc 63mm but n exc 100mm deposited, spread and levelled in layers n exc 15cm thick watered and rolled/rammed to a true surface.
41M&L for cement concrete in foundation, filling and mass concrete type D2 1:4:8, 40 mm graded aggregate all as specified and directed.
42M&L for 40mm thick plain cement concrete 1:2:4 type B1 using 20mm graded stone aggregrate as in floors , finishing surface even and smooth by using extra cement all as specified and directed.
43M&L for machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60mm thickness with grey cement and pigment M35 Grade all as specified and directed.
44M&L for sand filling under floors or in foundation incl watering and consolidation all as specified and directed.