Development Of Distribution Infrastructure At Mandi District Of Himachal Pradesh Under Revamped Reforms-Based And Results-Linked, Distribution Sector Scheme , Schedule-I ( Supply Part ) , New Dtr 11 / 22 Kv ( Hvds, Feeder Bifurcation, , mandi-Himachal Pradesh

Himachal Pradesh State Electricity Board-HPSEB has published Development Of Distribution Infrastructure At Mandi District Of Himachal Pradesh Under Revamped Reforms-Based And Results-Linked, Distribution Sector Scheme , Schedule-I ( Supply Part ) , New Dtr 11 / 22 Kv ( Hvds, Feeder Bifurcation, . Submission Date for this Tender is 10-10-2022. Coats and Jackets Tenders in mandi Himachal Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

34041226
Corrigendum : Development Of Distribution Infrastructure At Mandi District Of Himachal Pradesh Under Revamped Reforms-Based And Results-Linked, Distribution Sector Scheme , Schedule-I ( Supply Part ) , New Dtr 11 / 22 Kv ( Hvds, Feeder Bifurcation,
Open Tender
Indian
Himachal Pradesh
mandi
10-10-2022

Tender Details

Development Of Distribution Infrastructure At Mandi District Of Himachal Pradesh Under Revamped Reforms-Based And Results-Linked, Distribution Sector Scheme , Schedule-I ( Supply Part ) , New Dtr 11 / 22 Kv ( Hvds, Feeder Bifurcation, Feeder Segregation And Extension Of New Ht, Dt, Lt As Per Technical Specification, Approved Drawings And Scope Of Work. , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Is 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Pre-Fabricated Galvanised Steel ( Zinc Coating 610Gms / Sqm ) , Items Like Dc Cross Arm ( 100X50x6 Mm ) , Back Clamps ( 50X6 Mm ) , Pole Clamp ( 65X8 Mm ) , Do Fuse Mounting Channel ( 75X40x6 Mm ) , Transformer Mounting Channel ( 100X50x6 Mm ) , Transformer Clamping Set ( 50X50x6 Mm ) , Transformer Belting Set ( 50X50x6 Mm ) As Per Technical Specification, Approved Drawings And Scope Of Work. , Gs Nuts, Bolts With Washers As Per Technical Specification, Approved Drawings And Scope Of Work. , Stay Set ( Galvanised ) With 50X8 Mm Stay Clamp, Guy Insulator ( 1Nos. ) , Anchor Plate ( 200X200x6mm ) , Nut Bolts, 2 Nos Turn-Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Complete As Per Technical Specification, Approved Drawings And Scope Of Work. , 11 Kv Disc Insulator B&S Type Conformimg To Is-731 / 1971 All Latest Version Thereof For Suspension & Tension String Ball And Socket Type Having Pin Ball. The Minumum And Maximum Creepage Distance With Diameter Of Insulator- 255 Mm & Having Electromechanical Strength 90Kn. The Insulator Shall Have W Type Phosphors Bronze Security Clips For Ball Socket Porcelain Conforming Is: 2486-1971 ( 90Kn ) Complete In All Respect. Heavilypolluted Atmospheres Creepage Distance-400 Mm , 22 Kv Disc Insulator B&S Type ( 2 Nos. Disc ) Conformimg To Is-731 / 1971 All Latest Version Thereof For Suspension & Tension String Ball And Socket Type Having Pin Ball. The Minumum And Maximum Creepage Distance With Diameter Of Insulator- 225 Mm & Having Electromechanical Strength 90Kn. The Insulator Shall Have W Type Phosphors Bronze Security Clips For Ball Socket Porcelain Conforming Is: 2486-1971 ( 90Kn ) Complete In All Respect. Heavily Polluted Atmospheres Creepage Distance400 Mm , Distribution Transformer Substation Using New Outdoor Type, Oil Immersed, Distribution Transformer Up To And Including 630 Kva As Per Is1180 ( Part-1 ) : 2014 And Its Amendments 1, 2, 3 And 4, Rgo / Amorphous Core, Energy Efficiency Level 1, Carrying Bureau Of Indian Standard Certificate Mark, In Following Preferred Ratings As Per Detailed Scope Of Work And Technical Specifications: , 22 / 0.230 Kv Distribution Transformer 10 Kva 3Phase Dtr , 11 / 0.230 Kv Distribution Transformer 16 Kva 3 Phasedtr , 11 / 0.4 Kv Distribution Transformer 25 Kva 3 Phasedtr , 22 / 0.4 Kv Distribution Transformer 25 Kva 3 Phase Dtr , 11 / 0.4 Kv Distribution Transformer 63 Kva 3 Phasedtr , 22 / 0.4 Kv Distribution Transformer 63 Kva 3 Phasedtr , 11 / 0.4 Kv Distribution Transformer 100 Kva 3 Phasedtr , 22 / 0.4 Kv Distribution Transformer 100 Kva 3 Phasedtr , 11 / 0.4 Kv Distribution Transformer 250 Kva 3 Phasedtr , Outdoor Mounting Type Distribution Box Made Of Ms Sheet Of Thickness Not Less Than 18 Swg Crca Sheet / Smc Distribution Box, Dust And Moisture Vermin, Weather Proof With Degree Of Protection With Suitable Bus Bars, Earthing Cum Neutral Bus, Earthing Terminals, Box Illumination, Front Door Operated With Proper Locking Arrangement, Lugs, Mounting Channel Frame, Internal Wiring With Frls Cables, Danger Plate, Numbering, Back Clamps, Hardware As Per Scope Of The Work, Technical Specifications And Approved Drawings Suitable For Following Transformer: , 3 Ph 10Kva Transformer 80 A Tpn Mccb ( Incomer ) And 2 Nos. 50 A Sp Mccb ( Outgoing ) , 3 Ph 16 Kva Transformer 80 A Tpn Mccb ( Incomer ) And 2 Nos. 50 A Sp Mccb ( Outgoing ) , 3 Ph 25 Kva Transformer 40 A Tpn Mccb ( Incomer ) And 6 Nos. 25 A Sp Mccb ( Outgoing ) , 3 Ph 63 Kva Transformer Having 200 A Tpn Isolator, 100 A Hrc Fuse ( Incomer ) And 6 Nos. 60 A Sp Mccb ( Outgoing ) , 3 Ph 100 Kva Transformer Having 200 A Tpn Isolator, 160A Hrc Fuse ( Incomer ) And 6 Nos. 90 A Sp Mccb ( Outgoing ) , Lt Distribution Panel Box Suitable For 250Kva S / Stn Of Size 1100X800x275mm + / - 5% Made Of Steel Sheet Of 1.63 Mm Thickness Having Doubledoor Locking Arrangement Duly Powder Coated Painted Complete With 2 No. Mccbs ( 1Main + 1 Spare ) Rating 400Amp, 3 Poles Having Following Specifications ( 1 ) Minimum Frame Size 400Amp ( 2 ) Type Variable Trip Free, ( 3 ) Breaking Capacity- Isu & Lcs At 415, 50 Hz ( Ka: Not Less Than 50 Ka ) ( 4 ) , Thermal Release Range: 320-440Amp ( 5 ) Mecanicallife ( Operation ) 20000 No. ( 6 ) Electrical Life ( Operation ) 4000 No. ( 7 ) Rated Insulation Voltage ( V ) 690V ( 8 ) Tripping Thermal Releasing Setting : Thermal-O / L Variable Setting ( 9 ) Tripping Magnetic Releasing Setting : Magnetic- S / C Fixed Setting ( 12 ) In ( 10 ) ( Operation ) Volatge 415V, Ac ( 11 ) Caliberation Temperature: 40 Degree C ( 12 ) High Voltage Withstand Voltage : 3Kv For 1 Minute ( 13 ) Confirming To Is : 1993 / 60947-2, 1989 ( 14 ) Make L&T / Havells / Abb / Hpl / Schneider ( 15 ) Ics : 100% Icu , 9Kv, 10 Ka Porcelain Station Surge Arrestor / Lightening Arrestorcomplete With Accessories For 11Kv System , 18 Kv, 10 Ka Porcelain Station Surge Arrestor / Lightening Arrestorcomplete With Accessories For 22 Kv System , 11 Kv, 3-Ph, 400 A, 3 Pin Type, Horizontal / Vertical Mounting Type ( As Desired By Discom ) , Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 22 Kv, 3-Ph, 400 A, 3 Pin Type, Horizontal / Vertical Mounting Type ( As Desired By Discom ) , Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 11 Kv, 3-Ph, Drop Out Fuse Units ( Set Of 3 Units ) Along With Support Insulators, Base Channel, Fuse Barrel Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 22 Kv, 3-Ph, Drop Out Fuse Units ( Set Of 3 Units ) Along With Support Insulators, Base Channel, Fuse Barrel Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 3 Nos Pipe Earthing Using 40Mm Dia Gi Pipe 3000 Mm Long, Making Earth Grid Using 50X6mm Gi Flat And Riser As Per Scope Of Work Of Distribution Transformer Substations, As Per Scope Of Work, Approved Drawings And Technical Specifications, , 8 Swg Gi Wire For Earthing As Per Technical Specifications, Approved Drawings And Scope Of Works. , 3.5 Cx16 Sqmm Aluminium Conductor Cable , 3.5 Cx35 Sqmm Aluminium Conductor Cable , 3.5Cx70 Sqmm Aluminium Conductor Cable , 3.5Cx120 Sqmm Aluminium Conductor Cable , 3.5Cx185 Sqmm Aluminium Conductor Cable , Danger Plate Size: 250X200x1.6 Mm Made Of Mild Steel Plates 1.6 ( Minimum ) Thick Vitreous Enameled White Letter Figure, Conventional Skill And X-Boxes And Signal Red Colour On Front Side For Use In Hpsebl. The Rear Side Of The Plate Shall Be Black Enameled And Conforming To Is Specifiction No. Is-1351 / 1982 Suitable For 11 / 22Kv System , Galvanised Steel Barbed Wire Of 9.8 Kg / 100Metre , Aluminium Paint For All Poles And Steel Fitting , Red Oxide , 3 Kvar Power Factor Correction Capacitor Along With Mc O Capacitor Duty Contractorfor New 25 Kva , 11 / 0.4 Kv Dtr , 7 Kvar Power Factor Correction Capacitor Along With Mc O Capacitor Duty Contractorfor New 63 Kva , 11 / 0.4 Kv Dtr , 10 Kvar Power Factor Correction Capacitor Along With Mc O Capacitor Duty Contractorfor New 100 Kva , 11 / 0.4 Kv Dtr , Acsr Rabbit Conductor For Jumpering Including Pg Clamps, Bi- Metallic Connectors, Hardware Etc As Per Technical Specifications, Approved Drawings And Scope Of Works. , New Lt Line 3 Ph 4 Wire Rabbit , Support For Lt Overhead Line As Per Technical Specification, Approved Drawings And Scope Of Work. , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Is 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Galvanised Stay Set With Anchor Plate ( 200X200x6mm ) , 50X8mm Stay Clamp, Stay Guy Insulator, Nut Bolts, 2 Nos Turn Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Etc As Required As Per Technical Specification, Approved Drawings And Scope Of Work. , Earthing As Per Approved Drawings, Technical Specifications And Scope Of Work , 40 Mm Dia., 3000 Mm Long Gi Pipe Earth Electrode With Test Link, Rcc Pit, Rcc Cover Plates On Gi Frame, Bentonite Powder And Spike Earthing 20Mm Solid Rod I / C Other Accessories Complete , 8 Swg Gi Wire For Earthing & Gi Nuts, Bolts & Washers , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 6 / 3.35 + 1 / 3.35 Mm ( 50 Mm² Al. Area ) - Rabbit , Angle Iron ( 75X75x6 ) [ Length- 1.50 Mtr + 0.02 Mtr ] , Shackle Insulator ( 16 Kn ) , D-Iron ( U- Clamps ) , Earth Knob , Kit Kat I.C , Full Clamps [ 2 No For A.I + 1 No For Stay Set ] , Spool Tie , Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16 Mm F Or More ( With Flat And Spring Washers ) ] , Aluminium Paint , Spiral Pvc Spacer , Red Oxide , New Lt Line 1 Ph 2 Wire Rabbit , Support For Lt Overhead Line As Per Technical Specification, Approved Drawings And Scope Of Work. , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Is 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Galvanised Stay Set With Anchor Plate ( 200X200x6mm ) , 50X8mm Stay Clamp, Stay Guy Insulator, Nut Bolts, 2 Nos Turn Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Etc As Required As Per Technical Specification, Approved Drawings And Scope Of Work. , Earthing As Per Approved Drawings, Technical Specifications And Scope Of Work , 40 Mm Dia., 3000 Mm Long Gi Pipe Earth Electrode With Test Link, Rcc Pit, Rcc Cover Plates On Gi Frame, Bentonite Powder And Spike Earthing 20Mm Solid Rod I / C Other Accessories Complete , 8 Swg Gi Wire For Earthing & Gi Nuts, Bolts & Washers , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 6 / 3.35 + 1 / 3.35 Mm ( 50 Mm² Al. Area ) - Rabbit , Angle Iron ( 75X75x6 ) [ Length- 1.50 Mtr + 0.02 Mtr ] , Shackle Insulator ( 16 Kn ) , D-Iron ( U- Clamps ) , Earth Knob , Kit Kat I.C , Full Clamps [ 2 No For A.I + 1 No For Stay Set ] , Spool Tie , Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16 Mm F Or More ( With Flat And Spring Washers ) ] , Aluminium Paint , Spiral Pvc Spacer , Red Oxide , Augmentation & Renovation Of 11 / 0.4 Kv Distribution Transformer Substation , Augmentation Of Distribution Transformer Substation Using New Outdoor Type, Oil Immersed, Distribution Transformer Up To And Including 630 Kva As Per Is1180 ( Part-1 ) : 2014 And Its Amendments 1, 2, 3 And 4, Crgo / Amorphous Core, Energy Efficiency Level 1, Carrying Bureau Of Indian Standard Certificate Mark, In Following Preferred Ratings As Per Detailed Scope Of Work And Technical Specifications Under: , New 63 Kva ( 11 / 0.4 Kv ) Dtr ( Replacing 25Kva Old Dtr ) , , New 63 Kva ( 22 / 0.4 Kv ) Dtr ( Replacing 25Kva Old Dtr ) , , New 100 Kva ( 11 / 0.4 Kv ) Dtr ( Replacing 63 Kva Old Dtr ) , , New 100 Kva ( 22 / 0.4 Kv ) Dtr ( Replacing 63 Kva Old Dtr ) , , New 250 Kva ( 11 / 0.4 Kv ) Dtr ( Replacing 100 Kva Old Dtr ) , , New 250 Kva ( 22 / 0.4 Kv ) Dtr ( Replacing 100 Kva Old Dtr ) , , New 400 Kva ( 11 / 0.4 Kv ) Copper Wound Dtr ( Replacing 250 Kva Old Dtr ) , , New 400 Kva ( 22 / 0.4 Kv ) Copper Wound Dtr ( Replacing 250 Kva Old Dtr ) , , New 630 Kva ( 11 / 0.4 Kv ) Copper Wound Dtr ( Replacing 400 Kva Old Dtr ) , , New 630 Kva ( 22 / 0.4 Kv ) Copper Wound Dtr ( Replacing 400 Kva Old Dtr ) , , Augmentation Of Dtr Substation By Using New 3.5 C Pvcaluminium Conductor, Stranded, Unarmoured Cable For Connection Of Transformer Lv Bushing To Distribution Box And Distribution Box To Overhead Line As Per Scope Of Work, Technical Specification And Approved Drawings. Replaced Cables To Be Deposited In Employers Store. , 3.5 Cx70 Sqmm Aluminium Conductor Cable , 3.5Cx120 Sqmm Aluminium Conductor Cable , 3.5Cx185 Sqmm Aluminium Conductor Cable , 3.5Cx300 Sqmm Aluminium Conductor Cable , 3.5Cx400 Sqmm Aluminium Conductor Cable , Augmentation Of Dtr Substation By Using New Outdoor Mounting Type Distribution Box Made Of Ms Sheet Of Thickness Not Less Than 1.8 Mm / Smc Distribution Box, Dust And Moisture Vermin, Weather Proof With Degree Of Protection Ip 33 As Per Is 13947 With Suitable Bus Bars, Earthing Bus, Earthing Terminals, Box Illumination, Front Door Operated With Proper Locking Arrangement, Non Magnetic 4 Mm Thick Gland Plate, Double Compression Brass Cable Glands, Lugs, Mounting Channel Frame, Internal Wiring With Frls Cables, Danger Plate, Numbering, Back Clamps, Hardware As Per Scope Of The Work, Technical Specifications And Approved Drawings Suitable For Following Transformer: , 3 Ph 63 Kva Transformer Having 200 A Tpn Isolator, 100 A Hrc Fuse ( Incomer ) And 6 Nos. 60 A Sp Mccb ( Outgoing ) , 3 Ph 100 Kva Transformer Having 200 A Tpn Isolator, 160A Hrc Fuse ( Incomer ) And 6 Nos. 90 A Sp Mccb ( Outgoing ) , Lt Distribution Panel Box Suitable For 250Kva S / Stn Of Size 1100X800x275mm + / - 5% Made Of Steel Sheet Of 1.63 Mm Thickness Having Doubledoor Locking Arrangement Duly Powder Coated Painted Complete With 2 No. Mccbs ( 1Main + 1 Spare ) Rating 400Amp, 3 Poles Having Following Specifications ( 1 ) Minimum Frame Size 400Amp ( 2 ) Type Variable Trip Free, ( 3 ) Breaking Capacity- Isu & Lcs At 415, 50 Hz ( Ka: Not Less Than 50 Ka ) ( 4 ) , Thermal Release Range: 320-440Amp ( 5 ) Mecanicallife ( Operation ) 20000 No. ( 6 ) Electrical Life ( Operation ) 4000 No. ( 7 ) Rated Insulation Voltage ( V ) 690V ( 8 ) Tripping Thermal Releasing Setting : Thermal-O / L Variable Setting ( 9 ) Tripping Magnetic Releasing Setting : Magnetic- S / C Fixed Setting ( 12 ) In ( 10 ) ( Operation ) Volatge 415V, Ac ( 11 ) Caliberation Temperature: 40 Degree C ( 12 ) High Voltage Withstand Voltage : 3Kv For 1 Minute ( 13 ) Confirming To Is : 1993 / 60947-2, 1989 ( 14 ) Make L&T / Havells / Abb / Hpl / Schneider ( 15 ) Ics : 100% Icu , Lt Distribution Panel Box Suitable For 400Kva S / Stn. Made Of Steel Sheet Of 1.63 Mm Thickness Having Doubledoor Locking Arrangement Duly Powder Coated Pained Complete With Acb Rating 1000Amp, Duty Circle 0.3 Sec, Rating Symmetrical Breaking Capacity 50Ka, Service Breaking Capacity 100% Icu, Rating Making Capacity 105Ka Peak, Short Circuit Time For Seconds ( Ka Rms ) 50Ka, Thermal Current Set Value 1000 Amp, Time For Which Breaker Can Carry Its Rating Breaking Current <40 Ms, Endurance ( Co ) Cycle Mechanical Not Less Than 8000 Operations, Electrical Not Less Than 5000 Operations, Electrical Life For Arcing Contacts Not Less Than 2500 Operations, Insultion Voltage 1100 Volts, Impulse With Stand Voltage 8Kv, Closing Mechanism Mannual Independent Mannual, Version Required Fixed And Make L&T / Havells / C&S / Hpl / Schneider , Lt Distribution Panel Box Suitable For 630Kva S / Stn. Made Of Steel Sheet Of 1.63 Mm Thickness Having Doubledoor Locking Arrangement Duly Powder Coated Pained Complete With Acb Rating 1000Amp, Duty Circle 0.3 Sec, Rating Symmetrical Breaking Capacity 50Ka, Service Breaking Capacity 100% Icu, Rating Making Cap. 105Ka Peak, Short Circuit Time For Seconds ( Ka Rms ) 50Ka, Thermal Current Set Value 1000 Amp, Time For Which Breaker Can Carry Its Rating Breaking Current <40 Ms, Endurancec ( Co ) Ciycle Mechanical Not Less Than 8000 Operations, Electrical Not Less Than 5000 Operations, Electrical Life For Arcing Contacts Not Less Than 2500 Operations, Insulation Voltage 1100 Volts, Inpulse With Stgand Voltage 8Kv, Closing Mechanism Mannual Independent Mannual, Version Required Fixed And Make L&T / Havells / C&S / Hpl / Schiender. , Renovation Of Dtr Substation Earthing As Per Technical Specification, Approved Drawings And Scope Of Work: , Revamping Of Distribution Transformer Substation Earthing By Using 40 Mm Dia 3 Meter Long Gi Pipe Earthing, Using 50X6 Mm Gs Flat For Earth Mat And Riser And 25X3mm Gs Flat For Connecting Equipment, Using 200 Kg Bentonite Powder Of Substation In Normal Soil , Augmentation Of Dtr Substation By New Pre-Fabricated Galvanised Steel Items Like Dc Cross Arm ( 100X50x6 Mm ) , Back Clamps ( 65X8 Mm ) , Pole Clamp ( 65X8 Mm ) , Do Mounting Channel ( 75X40x6 Mm ) , Transformer Mounting Channel ( 100X50x6 Mm ) , Transformer Clamping Set ( 50X50x6 Mm ) , Transformer Belting Set ( 50X50x6 Mm ) As Per Technical Specification, Approved Drawings And Scope Of Work. , Augmentation Of Dtr Substation By New Galvanised Steel ( Gs ) Nuts, Bolts With Washers As Per Technical Specification, Approved Drawings And Scope Of Work. , Augmentation Of Dtr Substation By New 9Kv, 11 Ka Distribution Class Lightening Arrester For Dt As Per Technical Specification, Approved Drawings And Scope Of Work. , Augmentation Of Dtr Substation By 18 Kv, 10 Ka Porcelain Station Surge Arrestor / Lightening Arrestorcomplete With Accessories For 22 Kv System , Augmentation Of Dtr Substation By New 11 Kv, 3-Ph, 200 A, 3 Pin Type, Vertical Mounting Type, Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , Augmentation Of Dtr Substation By New22 Kv, 3-Ph, 400 A, 3 Pin Type, Horizontal / Vertical Mounting Type ( As Desired By Discom ) , Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , Aluminium Paint For Substaion Structure And Steel Fitting , 11Kv, 200 A, 3-Ph Drop Out Fuse Assembly Including Insulators And Mounting Arrangements, Jumpering From Bus Bar, Hardware, Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , 22 Kv, 3-Ph, Drop Out Fuse Units ( Set Of 3 Units ) Along With Support Insulators, Base Channel, Fuse Barrel Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , Conversion Of Existing Lt Bare Conductor Line With Following Arrangements Using New Areal Bunched Xlpe Cable, Tension Clamps For Dead End, Suspension Clamps, Clamps For Neutral, Piercing Connectors Type-I & Type-Ii, 16 Mm Dia Ms Nuts & Bolts, Pole Clamps, Spring Loaded Bus Bar Suitable For Single Phase And Three Phase Systems Etc. As Required As Per Technical Specification, Approved Drawings And Scope Of Work: , Aerial Bunchedcable 3 X 70+50+16 Sq.Mm , Lt Ab Cable Cable On Poles [ Size: 3 X 70+50+16 Sq.Mm { Additional 1% Sagging & Wastage ) , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Is 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Galvanised Stay Set With Anchor Plate ( 200X200x6mm ) , 50X8mm Stay Clamp, Stay Guy Insulator, Nut Bolts, 2 Nos Turn Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Etc As Required As Per Technical Specification, Approved Drawings And Scope Of Work. , Half Clamp For Cross Arm , Anchoring Assembly For Lt , Suspension Assembly For Lt , Facade Hooks For Lt , Distribution Boxes , Earthing Set Complete , Red Oxide , Aluminium Paint , Augmentation Of 33 / 11 Kvfully Outdoor Type Substation , 33 / 11 Kv, 3 Ph, 50 Hz, Onan, Cu Wound, Outdoor Conventional Type Power Transformer Along With Transformer Oil, Buchholtz Relay, Breather, Oti & Wti, Marshalling Box, Conservator Tank, Oil Level Indicator, Valves, 2 Sets Of 50X8 Mm Gs Neutral Earthing Strips { ( With Braided Conductor On Bushing End ) , Isolating Link, Isolation With Insulators } , Vent Explosion Plug, Control Wiring Between Sensing Equipment And Marshalling Box, Cable Supporting Tray On The Body Of Transformer, Transformer Wheels, Lv / Hv Bushing Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Work. , 3.15 Mva Without Tap Changer , 6.30 Mva With Off Load Tap Changer , 33Kv Superstructure Andequipment Structure , Galvanised Super Structure Comprisinggantries And Columns , Galvanised Equipment Structure For Mounting 33Kv Isolators And Post Insulators , 36Kv, 1250A, 25Ka For 3 Seconds, 3-Ph, Outdoor Type Vacuum Circuit Breaker Along With 36Kv, 1-Phase, 25Ka / 3 Seconds, 200-100 / 5-5 Amps Or 300-150 / 5-5 Amps 1 Set ( 3 Nos ) Outdoor Type Current Transformers Along With Junction Box ( 1 No Junction Box For 3 No Of 1-Phase Cts ) , Jumpers, Earthing, Supporting Structures, Bi- Metallic Clamps, Permanent Maintenance Platform, Marshalling Box Etc Required As Per Technical Specifications, Scope Of Works And Approved Drawings , 33 Kv , 1250A , 25 Ka For 3Sec Auto Reclosure ( O / D Channel Mounted ) With Built In Feederprotections, Communicable For Remote Operation Through Scada System Iec 61850 , 104Compatible , 33 Kv , 1250A , 25 Ka For 3Sec Auto Reclosure ( O / D Channel Mounted ) With Built In Power Transformer Protections, Communicablefor Remote Operation Through Scada System Iec 61850 , 104 Compatible , 33Kv, Indoor, Control & Relay Panel Along With E / F & O / C Relays, Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays And Other Components Etc As Per Approved Drawings, Specifications And Scope Of Works Controlling: , 33 Kv Feeder Panel ( 33 Kv Incomer Bus ) [ Numeric Relay, Iec 61850 ] , Power Transformerprotection Panel ( With Numericdifferential Relay / Ref Relay , Iec 61850 ) , 36Kv, 1250A, 25Ka For 3 Seconds, 3-Ph Double Break Center Rotating Type ( Dbcr ) , Gang Operated Motorised Isolator Along With Support Insulators, Operating Mechanism, Base Channel Down Pipe And All Required Accessories Complete As Per Technical Specifications, Scope Of Works And Approved Drawings With Out Earth Switch. , 36Kv, 1250A, 25Ka For 3 Seconds, 3-Ph Double Break Center Rotating Type ( Dbcr ) , Gang Operated Motorised Isolator Along With Support Insulators, Operating Mechanism, Base Channel Down Pipe And All Required Accessories Complete As Per Technical Specifications, Scope Of Works And Approved Drawings With Earth Switch , 30 Kv, 10Ka, 1-Ph Station Class Lightening Arrester With Surge Counter, Mounting Platform, Jumpering From Bus Bar, Earthing Connection Using 50X6mm Gs Flat, Hardware Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , 9Kv, 10Ka, 1-Ph Station Class Lightening Arrester With Mounting Platform, Jumpering From Bus Bar, Earthing Connection Using 50X6mm Gs Flat, Hardware, Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , Indoor Type Control And Relay Panel As Per Technical Specifications, Approved Drawings And Scope Of Works: , Indoor Type Control And Relay Panel For 11Kv, 3Phase, 1250 A Vcb ( Transformer Breaker ) Consisting Of Ct 800-400 / 1-1-1 A, Pt 11000 / 110 V-Meter, Volt-Meter, Relays & Accessories Complete As Per Specifications For Transformer Breaker Protection ( 12 Kv, 1250 A, 25Ka ) [ Numeric Relay, Iec 61850 ] , Indoor Type Control And Relay Panel For 11 Kv 3 Phase, 1250 A Vcb ( Feeder Breakers ) Consisting Of Ct 400-200 / 1-1-1 A , 11000 / 110 V -Meter, Volt-Meter, Relays, Energy Meter ( Tvm ) & Accessories Complete As Per Specifications For Feeder Breaker Protection ( 12 Kv, 1250 A, 25Ka ) [ Numeric Relay, Iec 61850 ] , 12 Kv, 1250 A, 25Ka For 3 Seconds, 3-Ph, Indoor Typevacuum Circuit Breakeralong With 12 Kv, 1-Phase, 800-400 / 1-1-1 , 3 Nos Indoor Type Current Transformer, Indoor Mounting Type Control Panel For Bus Coupler, Control Cabling Between Vcb And Indoor Control Panel And Required Accessories, Bi-Metallic Clamps, A-Meter, Volt-Meter, 3- Phase Electronic Energy Meter, Relay & Accessories Complete As Per Specifications For Bus Coupler Protection ( 12 Kv, 1250 A, 25Ka ) ( Numeric Relay , Iec 61850 ) , Numerical Directional Relay For 33 Kv Feeder Protectionwith Iec 61850 Complitant With Rj 45 Port , Numerical Directional Relay For 11 Kv Feeder Protectionwith Iec 61850 Complitant With Rj 45 Port , Numerical Differentialrelay For Transformer Protection On 11 Kv Incomer With Iec 61850 Compliant With Rj 45 Port , 11 Kv , 800 A , 25 Ka For 3Sec Auto Reclosure ( O / D Channel Mounted ) With Built In Feederprotections, Communcablefor Remote Operation Through Scada System Iec 61850 , 104 Compatible , 30 V, 100 Ah Pb Acid Battery, Battery Stand Made Of Teak Wood Duly Painted With Anti Rusting Paint, Battery Insulators, Inter-Battery Wiring Using 30 Sqmm, 1.1 Kv, Copper Single Core Multi Strand Cable, Terminal Connectors, & All Other Accessories And Connectors And 30V, 40 Amp. ( Or As Per State Practice ) Float-Cum-Boost Battery Charger With Six Wave Rectification For 440 V, 3 Phase, 50 Hz Ac Input Supply As Per Technical Specifications, Approved Drawings And Scope Of Works , Acsr Conductor For Bus-Bars & Jumpers / Droppers / Terminations Including Hardware Fittings, Hardware, T-Claimp Etc As Per Technical Specifications, Approved Drawings And Scope Of Works , 30 / 3.00 + 7 / 3.00 Mm ( 200 Mm² Al. Area ) - Panther , Earthing & Grounding Conductor As Per Approved Electrical Layout For Each Sub-Station As Per Technical Specifications, Approved Drawings And Scope Of Works With , 65 X 8 Mm Gi Flat For Ground Mat , 50 X 6 Mm Galvanized Gi Flat ( Risers ) , 25Mm Dia Gi Rod 3 M Long For Earth Mat , 50 Mm Dia., 3000 Mm Long Gi Pipe Earth Electrode With Test Link, Rcc Pit, Rcc Cover, Placed On Gi Frame, Bantonide Powder And Other Accessories Complete As Per Technical Specification. ( For Power Transformer Neutral, Station Transformer Neutral And Lightening Arresters Direct Earthing ) As Per Technical Specifications, Approved Drawings And Scope Of Works. , 33 Kv Post Insulators Along With Strurcture, Suitable Hardware & Accessories Suitable For Panther / Dog Conductors As Per Approved Drawings & Specifications. , Control Cables Including Their Termination Materials Like Glands, Lugs Etc. As Per Technical Specifications, Approved Drawings And Scope Of The Work. , 2 Core 2.5 Sqmm Armoured, Stranded Copper Conductor, Pvc Insulated And Pvc Sheathed Cable , 10 Core 2.5 Sqmm Armoured, Stranded Copper Conductor, Pvc Insulated And Pvc Sheathed Cable , 12 Core 2.5 Sqmm Armoured, Stranded Copper Conductor, Pvc Insulated And Pvc Sheathed Cable , 7Core 6.0 Sqmm Armoured, Stranded Copper Conductor, Pvc Insulated Screened And Pvc Sheathed Cable , 4 Core 6.0 Sqmm Armoured, Stranded Copper Conductor, Pvc Insulated Screened And Pvc Sheathed Cable , 3Core 400 Sqmm Xlpe , Al , Armoured , Cable , Lt Power Cable Pvc 1.1 Kv , 4 Core, Al , 16 Mm2, Un-Armoured , 11Kv , Xlpe , Outdoor Type 3X 400Sqmm Termination Kit , 11Kv , Xlpe , Indoor Type 3X400sqmm Termination Kit , 11 Kv Isolator Motorised ( 12 Kv, 630A, 25 Ka With Earthswitch Outdoor ) , 11.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-56. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Is 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) , Extension Of 33Kv And 11 Kv Yard , Rs Joists Size 12800X250x125 , Ms Channel Iron 125X65x6, X-Arms @ 12.1 Kg / M, 7 Mtr Long, 5.5Mtr Long, Msai 50X50x6 Mmfor 33 And 11 Kv Yard , Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) ( With Flat And Spring Washers ) ] , Bus Bar , I ) 33 Kvdisc Insulator Tension Stringcomplete , Ii ) 33 Kv Disc Suspension Tension String Complete , Acsr Conductor 200Sqmm @ 10% , Pg Clamps , Sub Station Automation System ( Scada ) With Necessary Hardware And Software And Any Modification / Retro-Fitting In Existing Control And Monitoring System Of 33Kv / 11Kv Switch Gears And Equipments , Field Sensors , Transducers , Limit Switches And Wiring, Ups Having Capacity Of 02 Kva With 1 Hour Battery Backupfor Complete Control, Monitoring And Data Logging Ofsub-Stations Along With Substattion Survelliance System Including Ip Cameras And Nvri P Phones Etc. At Thalout Substationand Sandhole Substation , Sub Station Automation System ( Scada ) With Necessary Hardware And Software And Any Modification / Retro-Fitting In Existing Control And Monitoring System Of 33Kv / 11Kv Switch Gears And Equipments , Field Sensors , Transducers , Limit Switches And Wiring, Ups Having Capacity Of 02 Kva With 1 Hour Battery Backupfor Complete Control, Monitoring And Data Logging Ofsub-Stations Along Along With Adss , Fo Cable Link 15 Km With Accesories On Existiing Poles Between Thalout Substationand Nagwain Substation , With Substatation Survelliance System Including Ip Cameras And Nvr, I P Phones Etc. , New 11Kv Ht Line , Support For 11 Kv Overhead Line As Per Technical Specification, Approved Drawings And Scope Of Work , 11.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-56 , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Pre-Fabricated Steel Items Like V Cross Arm, Top Clamp, Dc Cross Arm, Bracket, Clamps, Cross Bracings, Bracings, Strain Plate, Guarding Channels, Back Clamp, Mounting Structure , Angle Iron For Road Crossings Etc Made Of Ms Channels ( 100X50x6mm ) , Ms Angle ( 65X65x6mm ) , Ms Flats ( 50X6 Mm ) Of Given Sizes For Over Head Structures As Per Technical Specification, Approved Drawings And Scope Of Work. , Ms Nuts, Bolts With Washers As Per Technical Specification, Approved Drawings And Scope Of Work. , Stay Set ( Galvanised ) With 50X8 Mm Stay Clamp, Stay Insulator ( 1 Nos. ) , Anchor Plate ( 200X200x6 ) , Nut Bolts, 2 Nos Turn-Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Strandedwire Complete As Per Technical Specification, Approved Drawings And Scope Of Work. , 11 Kv Disc Insulator B&S Type Conformimg To Is-731 / 1971 All Latest Version Thereof For Suspension & Tension String Ball And Socket Type Having Pin Ball. The Minumum And Maximum Creepage Distance With Diameter Of Insulator- 255 Mm & Having Electromechanical Strength 90Kn. The Insulator Shall Have W Type Phosphors Bronze Security Clips For Ball Socket Porcelain Conforming Is: 2486-1971 ( 90Kn ) Complete In All Respect. Heavilypolluted Atmospheres Creepage Distance400 Mm , 11 Kv Pin Insulator Brownglazed Porcelain Insulator Alongwith Gi Pin Confirming To Is-731 / 1971 Or Latest Version Thereof With Minimum And Maximum Creepage Distance Distance & Duly Fitted With Lead / Zinc Thimble Suitable For Use With Gi Forged Pin Having Small Steel Head As Per Is:2486 ( Part-I & Ii ) Of 1993 & Latest Amendment If Any. Moderately Polluted Atmospheres Creepage Distance- 320Mm , Ht Earthing Set ( Rec Construction Standard J-1 ) , 8 Swg Gi Wire, Gi Nuts, Bolts & Washers For Earthing And Guarding , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 6 / 3.35 + 1 / 3.35 Mm ( 50 Mm² Al. Area ) - Rabbit , 11 Kv, 3-Ph, 400 A, 3 Pin Type, Horizontal / Vertical Mounting Type ( As Desired By Discom ) , Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 11 Kv, 3-Ph, Drop Out Fuse Units ( Set Of 3 Units ) Along With Support Insulators, Base Channel, Fuse Barrel Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , Danger Plate Size: 250X200x1.6 Mm Made Of Mild Steel Plates 1.6 ( Minimum ) Thick Vitreous Enameled White Letter Figure, Conventional Skill And X-Boxes And Signal Red Colour On Front Side For Use In Hpsebl. The Rear Side Of The Plate Shall Be Black Enameled And Conforming To Is Specifiction No. Is-1351 / 1982 Suitable For 11Kv , Eye Hook For Earth Wire , Galvanised Steel Barbed Wire Of 9.8 Kg / 100Metre , Aluminium Paint For All Poles And Steel Fitting , Red Oxide , New 22Kv Ht Line , Support For 22Kv Overhead Line As Per Technical Specification, Approved Drawings And Scope Of Work , 11.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-56 , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Pre-Fabricated Steel Items Like V Cross Arm, Top Clamp, Dc Cross Arm, Bracket, Clamps, Cross Bracings, Bracings, Strain Plate, Guarding Channels, Back Clamp, Transformer Mounting Structure Etc Made Of Ms Channels ( 100X50x6mm ) , Ms Angle ( 65X65x6mm ) , Ms Flats ( 50X6mm ) Of Given Sizes For Over Head Structures As Per Technical Specification, Approved Drawings And Scope Of Work. , Ms Nuts, Bolts With Washers As Per Technical Specification, Approved Drawings And Scope Of Work. , Stay Set ( Galvanised ) With 50X8 Mm Stay Clamp, Stay Insulator ( 1 Nos. ) , Anchor Plate ( 200X200x6 ) , Nut Bolts, 2 Nos Turn-Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Strandedwire Complete As Per Technical Specification, Approved Drawings And Scope Of Work. , 22 Kv Disc Insulator B&S Type ( 2 Nos. Disc ) Conformimg To Is-731 / 1971 All Latest Version Thereof For Suspension & Tension String Ball And Socket Type Having Pin Ball. The Minumum And Maximum Creepage Distance With Diameter Of Insulator- 225 Mm & Having Electromechanical Strength 90Kn. The Insulator Shall Have W Type Phosphors Bronze Security Clips For Ball Socket Porcelain Conforming Is: 2486-1971 ( 90Kn ) Complete In All Respect. Heavily Polluted Atmospheres Creepage Distance400 Mm , 22Kv Pin Insulator Brownglazed Porcelain Insulator Alongwith Gi Pin Confirming To Is-731 / 1971 Or Latest Version Thereof With Minimum And Maximum Creepage Distance Distance & Duly Fitted With Lead / Zinc Thimble Suitable For Use With Gi Forged Pin Having Small Steel Head As Per Is:2486 ( Part-I & Ii ) Of 1993 & Latest Amendment If Any. Moderately Polluted Atmospheres Creepage Distance- 560Mm , Ht Earthing Set ( Rec Construction Standard J-1 ) , 8 Swg Gi Wire, Gi Nuts, Bolts & Washers For Earthing And Guarding , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 6 / 3.35 + 1 / 3.35 Mm ( 50 Mm² Al. Area ) - Rabbit , 22 Kv, 3-Ph, 400 A, 3 Pin Type, Horizontal / Vertical Mounting Type ( As Desired By Discom ) , Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 22 Kv, 3-Ph, Drop Out Fuse Units ( Set Of 3 Units ) Along With Support Insulators, Base Channel, Fuse Barrel Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , Danger Plate Size: 250X200x1.6 Mm Made Of Mild Steel Plates 1.6 ( Minimum ) Thick Vitreous Enameled White Letter Figure, Conventional Skill And X-Boxes And Signal Red Colour On Front Side For Use In Hpsebl. The Rear Side Of The Plate Shall Be Black Enameled And Conforming To Is Specifiction No. Is-1351 / 1982 Suitable For 22Kv , Eye Hook For Earth Wire , Galvanised Steel Barbed Wire Of 9.8 Kg / 100Metre , Aluminium Paint For All Poles And Steel Fitting , Red Oxide , Augmentation / Reconductoring Of Lt Lines -2Phase To 3-Phasewith 50 Sq. Mm Rabbit Conductor , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 6 / 3.35 + 1 / 3.35 Mm ( 50 Mm² Al. Area ) - Rabbit , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32 , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Shackle Insulator ( 16 Kn ) , D-Iron ( U- Clamps ) , Earth Knob , Lt Stay Set , Stay Wire ( 7 / 3.15 Mm ) ( 6.0 Kg Per Stay Set ) , Full Clamps 1 No For Stay Set , Earthing Set Complete , Spool Tie , Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16 Mm F Or More ( With Flat And Spring Washers ) ] , Aluminium Paint , Spiral Pvc Spacer , Red Oxide , Augmentation / Reconductoring Of Lt Lines -2Phase To 3-Phasewith 50 Sq. Mm Rabbit Conductor , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 6 / 3.35 + 1 / 3.35 Mm ( 50 Mm² Al. Area ) - Rabbit , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32 , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Shackle Insulator ( 16 Kn ) , D-Iron ( U- Clamps ) , Earth Knob , Lt Stay Set , Stay Wire ( 7 / 3.15 Mm ) ( 6.0 Kg Per Stay Set ) , Full Clamps 1 No For Stay Set , Earthing Set Complete , Spool Tie , Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16 Mm F Or More ( With Flat And Spring Washers ) ] , Aluminium Paint , Spiral Pvc Spacer , Red Oxide , Reconductoring Of Lt Lines -1 Phase 2 Wire With 50 Sq. Mm Rabbit Conductor , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 6 / 3.35 + 1 / 3.35 Mm ( 50 Mm² Al. Area ) - Rabbit , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32 , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Shackle Insulator ( 16 Kn ) , D-Iron ( U- Clamps ) , Earth Knob , Lt Stay Set , Stay Wire ( 7 / 3.15 Mm ) ( 6.0 Kg Per Stay Set ) , Full Clamps 1 No For Stay Set , Earthing Set Complete , Spool Tie , Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16 Mm F Or More ( With Flat And Spring Washers ) ] , Aluminium Paint , Spiral Pvc Spacer , Red Oxide , Reconductoring Of Lt Lines -3 Phase 4 Wire With 50 Sq. Mm Rabbit Conductor , Acsr Conductors Of Following Sizes With Jointing Sleeves, Binding Materials, Pg Clamps, Bi-Metallic Clamp, Hardware Etc For Overhead Line And Jumpers As Required As Per Technical Specification, Approved Drawings And Scope Of Work , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32 , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Shackle Insulator ( 16 Kn ) , D-Iron ( U- Clamps ) , Earth Knob , Lt Stay Set , Stay Wire ( 7 / 3.15 Mm ) ( 6.0 Kg Per Stay Set ) , Full Clamps 1 No For Stay Set , Earthing Set Complete , Spool Tie , Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16 Mm F Or More ( With Flat And Spring Washers ) ] , Aluminium Paint , Spiral Pvc Spacer , Red Oxide , Cabling Of Lt Line With Ab Cable , Lt Ab Cable On Poles [ Size: ( 3X95 Sq, Mm ) { Additional 1% Sagging & Wastage ) , Lt Ab Cable On Poles [ Size: ( 3X95 Sq, Mm ) { Additional 1% Sagging & Wastage ) , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Pre-Fabricated Steel Items Like Cross Arm, Clamps, Knee-Bracings, Belts, Back Clamp Etc. Made Of Ms Channels ( 600X100x50x6mm ) , Ms Angle ( 750X50x50x6mm ) , Ms Flats ( 50X6 Mm ) Of Given Sizes For Over Head Structures As Per Technical Specification, Approved Drawings And Scope Of Work And Clapmps For Hangiing Assembles, Nut & Bolts , Galvanised Stay Set With Anchor Plate ( 200X200x6mm ) , 50X8mm Stay Clamp, Stay Guy Insulator, Nut Bolts, 2 Nos Turn Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Stranded Wire Etc As Required As Per Technical Specification, Approved Drawings And Scope Of Work. , Full Clamp For Stay , Anchoring Assembly For Lt , Suspension Assembly For Lt , Facade Hooks For Lt , Distribution Boxes , T-Jointing Kit , Lt Earthing Set Complete ( Preferbly Coil Earthing ) , Red Oxide , Aluminium Paint , Ipc , Pvc 2 Core 10 Sqmm , Lt , Abcable3x185 Sq. Mm { Additional 1% Sagging & Wastage ) , Lt , Ab Cable3x185 + 16+70 Sq. Mm , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Pre-Fabricated Steel Items Like Cross Arm, Clamps, Knee-Bracings, Belts, Back Clamp Etc. Made Of Ms Channels ( 600X100x50x6mm ) , Ms Angle ( 750X50x50x6mm ) , Ms Flats ( 50X6 Mm ) Of Given Sizes For Over Head Structures As Per Technical Specification, Approved Drawings And Scope Of Work And Clapmps For Hangiing Assembles, Nut & Bolts , Stay Set ( Galvanised ) With 50X8 Mm Stay Clamp, Stay Insulator ( 1 Nos. ) , Anchor Plate ( 200X200x6 ) , Nut Bolts, 2 Nos Turn-Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Strandedwire Complete As Per Technical Specification, Approved Drawings And Scope Of Work. , Full Clamp For Stay , X-Arm ( Horizontal ) - Ms Channel Iron: 100X50x6, Length [ 600 Mm ] , Half Clamp For Cross Arm , Anchoring Assembly For Lt , Suspension Assembly For Lt , Facade Hooks For Lt , T-Jointing Kit , Lt Earthing Set Complete ( Preferbly Coil Earthing ) , Red Oxide , Aluminium Paint , Distribution Boxes , Ipc , Pvc 3.5 Core 10 Sqmm , Ht , Abcable 11 / 22 Kv3x95+70Sqmm Sq. Mm { Additional 1% Sagging & Wastage ) , 11 Kv Ht Ab Cable On Poles [ Size: ( 3X95+70Sqmm ) { Additional 1% Sagging & Wastage ) , 22 Kv Ht Ab Cable On Poles [ Size: ( 3X95+70 Sq, Mm ) { Additional 1% Sagging & Wastage ) , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Stay Set ( Galvanised ) With 50X8 Mm Stay Clamp, Stay Insulator ( 1 Nos. ) , Anchor Plate ( 200X200x6 ) , Nut Bolts, 2 Nos Turn-Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Strandedwire Complete As Per Technical Specification, Approved Drawings And Scope Of Work. , Pre-Fabricated Steel Items Like Cross Arm, Clamps, Knee-Bracings, Belts, Back Clamp Etc. Made Of Ms Channels ( 600X100x50x6mm ) As Per Technical Specification, Approved Drawings And Scope Of Work. , Anchoring Assembly For Ht , Suspension Assembly For Ht , Facade Hooks For Ht , Heat Shrinkable Straight Through Jointing Kit Suitable For 11 Kv Cable Size ( 3X95 ) , Heat Shrinkable Straight Through Jointing Kit Suitable For 22 Kv Cable Size ( 3X95 ) , Cable Termination Kit Suitable For 11 Kv Cable Size ( 3X95 ) , Cable Termination Kit Suitable For 22 Kv Cable Size ( 3X95 ) , Ht Earthing Set Complete ( Preferbly Coil Earthing ) , Red Oxide , Aluminium Paint , Ht 22 / 11Kv Xlpecable3x120 Sq. Mm { Additional 1% Sagging & Wastage ) , Ht Xlpecable11 Kv On Poles [ Size: ( 3X120 Sq, Mm ) { Additional 1% Sagging & Wastage ) , Ht Xlpecable22 Kv On Poles [ Size: ( 3X120 Sq, Mm ) { Additional 1% Sagging & Wastage ) , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Stay Set ( Galvanised ) With 50X8 Mm Stay Clamp, Stay Insulator ( 1 Nos. ) , Anchor Plate ( 200X200x6 ) , Nut Bolts, 2 Nos Turn-Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Strandedwire Complete As Per Technical Specification, Approved Drawings And Scope Of Work. , Pre-Fabricated Steel Items Like Cross Arm, Clamps, Knee-Bracings, Belts, Back Clamp Etc. Made Of Ms Channels ( 600X100x50x6mm ) , Ms Angle ( 750X50x50x6mm ) , Ms Flats ( 50X6 Mm ) Of Given Sizes For Over Head Structures As Per Technical Specification, Approved Drawings And Scope Of Work And Clapmps For Hangiing Assembles, Nut & Bolts , Heat Shrinkable Straight Through Jointing Kit 11 Kv , Heat Shrinkable Straight Through Jointing Kit 22 Kv , Cable Termination Kit 11 Kv , Cable Termination Kit 22 Kv , Ht Earthing Set Complete ( Preferbly Coil Earthing ) , Aluminium Paint , Steel Rope Of Suitable Size For Holding Of Xlpe Cable 3X120 Sqmmalongwithfixing Clampsand Allied Material. , Ht Ab Cable On Poles [ Size: ( 3X120 +95 Sq, Mm ) { Additional 1% Sagging & Wastage ) , 11 Kv Abcablesize: ( 3X120 +95 Sqmm. ) { Additional 1% Sagging & Wastage ) , 9.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. , Rcc Pipe ( Muff ) Isi Marked Suitable For Different Sizes Of Steel Poles. 2000 Mm In Length And 25 Mm Thick With 250 Mm Internal Dia Duly Fabricated By Using Un-Galvanized Ms Wires Of 12 Swg Rings And 6 Mm Ms Round In Vertical Direction Conforming To Isi 458-1988 Or Latest Version If Anyincluding Cement Concrete Filling 1:3:6 ( 1 Cement : 3 Sand : 6 Aggrigate 20 Mm Nominal Size ) . , Stay Set ( Galvanised ) With 50X8 Mm Stay Clamp, Stay Insulator ( 1 Nos. ) , Anchor Plate ( 200X200x6 ) , Nut Bolts, 2 Nos Turn-Buckles, 1.8 M Long, 16 Mm Diameter Solid Gs Stay Rod & 7 / 3.15 Mm Dia Gi Strandedwire Complete As Per Technical Specification, Approved Drawings And Scope Of Work. , Pre-Fabricated Steel Items Like Cross Arm, Clamps, Knee-Bracings, Belts, Back Clamp Etc. Made Of Ms Channels ( 600X100x50x6mm ) As Per Technical Specification, Approved Drawings And Scope Of Work. , Anchoring Assembly For Ht , Suspension Assembly For Ht , Facade Hooks For Ht , Heat Shrinkable Straight Through Jointing Kit , Cable Termination Kit , T-Jointing Kit , Ht Earthing Set Complete ( Preferbly Coil Earthing ) , Red Oxide , Aluminium Paint , Erection Part , Complete Survey Ofdivision Wise Scope Of Work I.E. Preliminary, Actual Surveying Profiling And Final Survey, Stacking Of Materials, Camp Shifting And Geo Tagging Of Newly Constructed Assetson Gis Portaletc. Complete Job , Ed Thalout , Ed Mandi , Ed J / Nagar , Eds / Ghat , Ed Gohar , Ed Dharampur , Ed Sunder Nagar , Ed Karsog , New Dtr 11 / 22 Kv ( Hvds, Feeder Bifurcation, Feeder Segregation And Extension Of New Ht, Dt, Lt As Per Technical Specification, Approved Drawings And Scope Of Work. , Erection Of 10 Kva, 16Kva, 25 Kva, 63 Kva, 100 Kva 11 / 0.2Kv Dtr, Complete Viz Digging Of Pit For Poles & Earthing ( 2 No. For Pole & 3 No. For Earthing ) , Drilling Of Holes In X Arms & Poles Prepration Of Plateformstructure Member Ci, Ai I.E. X-Arm & Knee Bracing Set, Erection Ofdouble Pole Structure, Concreting Of Rcc Muffs , Erection Of Plateform, Erection Of X-Arms, Erection Of G.O. Switch, Erection Ofdrop-Out Fuse Unit, Erection Of Lightning Arrestor, Erection Of Lt Box, Providingearthing Connection Including G.I.Wire To G.O Switch, Transformer, Lightning Arrestor, Etc , Erection Of 4 Nos. Stay Set , Erection Of Jumper, Pipe Earthing 3 No. Sets , Layingof Lt Cable, Barbed Wire & Painting Complete In All Respect , Erection Of 250Kva, 400Kva , 630Kva 11 / 0.433Kv Dtr, Complete Viz Digging Of Pit For Poles & Earthing ( 2 No. For Pole & 3 No. For Earthing ) , Drilling Of Holes In X Arms & Poles Prepration Of Plateformstructure Member Ci, Ai I.E. X-Arm & Knee Bracing Set, Erection Ofdouble Pole Structure, Concreting Of Rcc Muffs , Erection Of Plateform, Erection Of X-Arms, Erection Of G.O. Switch, Erection Ofdrop-Out Fuse Unit, Erection Of Lightning Arrestor, Erection Of Lt Box, Providingearthing Connection Including G.I.Wire To G.O Switch, Transformer, Lightning Arrestor, Etc , Erection Of 4 Nos. Stay Set , Erection Of Jumper, Pipe Earthing 3 No. Sets , Layingof Lt Cable, Barbed Wire & Painting Complete In All Respect , New Lt Line , 3 Ph 4 Wire Rabbit , Support For Lt Overhead Line As Per Technical Specification, Approved Drawings And Scope Of Work. , Erection Of 3 Phase Overhead Lt Line I / C Complete In All Respect I.E. Erction Of Pole , Stay Set Earthig , Rcc Muff, Jumpering, Earth Wire Etc ( Punching Of The Poles Is Stricitly Not Allowed ) , 1 Ph 2 Wire With Rabbit , Erection Of Single Phase Overhead Lt Line I / C Complete In All Respect I.E. Erction Of Pole , Stay Set Earthig , Rcc Muff, Jumpering, Earth Wire Etc ( Punching Of The Poles Is Stricitly Not Allowed ) , Augmentation & Renovation Of 11 / 0.4 Kv Distribution Transformer Substation , Augmentation Of Distribution Transformer Substation Using New Outdoor Type, Oil Immersed, Distribution Transformer Up To And Including 630 Kva As Per Is1180 ( Part-1 ) : 2014 And Its Amendments 1, 2, 3 And 4, Crgo / Amorphous Core, Energy Efficiency Level 1, Carrying Bureau Of Indian Standard Certificate Mark, In Following Preferred Ratings As Per Detailed Scope Of Work And Technical Specifications Under: , Dismantling Of Old 25Kva, 63, Kva Dtr A / W Lt Box, Meter & Cableand Erection Of New 63, 100, Kva Dtr A / W Lt Box, Meter & Cable And Transportation Of Dismantled Material From Site Of Work To Concerned Divisional Store , Dismantling Of Old 100, 250Kva, 400Kva Dtr A / W Lt Box, Meter & Cableand Erection Of New 250, 400Kva, 630Kva Dtr A / W Lt Box, Meter & Cable And Transportation Of Dismantled Material From Site Of Work To Concerned Divisional Store , Renovation Of Dtr Substation Earthing As Per Technical Specification, Approved Drawings And Scope Of Work: , Revamping Of Distribution Transformer Substation Earthing By Using 40 Mm Dia 3 Meter Long Gi Pipe Earthing, Using 50X6 Mm Gs Flat For Earth Mat And Riser And 25X3mm Gs Flat For Connecting Equipment, Using 200 Kg Bentonite Powder Of Substation In Normal Soil , Augmentation Of Dtr Substation By New Pre-Fabricated Galvanised Steel Items Like Dc Cross Arm ( 100X50x6 Mm ) , Back Clamps ( 65X8 Mm ) , Pole Clamp ( 65X8 Mm ) , Do Mounting Channel ( 75X40x6 Mm ) , Transformer Mounting Channel ( 100X50x6 Mm ) , Transformer Clamping Set ( 50X50x6 Mm ) , Transformer Belting Set ( 50X50x6 Mm ) As Per Technical Specification, Approved Drawings And Scope Of Work. , Augmentation Of Dtr Substation By New 9Kv, 11 Ka Distribution Class Lightening Arrester For Dt As Per Technical Specification, Approved Drawings And Scope Of Work. , Augmentation Of Dtr Substation By 18 Kv, 10 Ka Porcelain Station Surge Arrestor / Lightening Arrestorcomplete With Accessories For 22 Kv System , Augmentation Of Dtr Substation By New 11 Kv, 3-Ph, 400 A, 3 Pin Type, Vertical Mounting Type, Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , Augmentation Of Dtr Substation By New22 Kv, 3-Ph, 400 A, 3 Pin Type, Horizontal / Vertical Mounting Type ( As Desired By Discom ) , Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 11Kv, 200 A, 3-Ph Drop Out Fuse Assembly Including Insulators And Mounting Arrangements, Jumpering From Bus Bar, Hardware, Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , 22 Kv, 3-Ph, Drop Out Fuse Units ( Set Of 3 Units ) Along With Support Insulators, Base Channel, Fuse Barrel Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , Conversion Of Existing Lt Bare Conductor Line With Following Arrangements Using New Areal Bunched Xlpe Cable, Tension Clamps For Dead End, Suspension Clamps, Clamps For Neutral, Piercing Connectors Type-I & Type-Ii, 16 Mm Dia Ms Nuts & Bolts, Pole Clamps, Spring Loaded Bus Bar Suitable For Single Phase And Three Phase Systems Etc. As Required As Per Technical Specification, Approved Drawings And Scope Of Work: , Aerial Bunched Xlpe Cable 3 X 70+50+16 Sq.Mm , Laying, Installtion Of Suspension & Tension Assembly Etc., Sagging Of Lt Ab Cable Of Size: 3 X 70+50+16 Sqmm, Jointing And Termination Kits Etc. Complete , Erection Of Steel Tubular Pole 9Mtr Long ( Single Pole ) For Lt Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms & Ab Cable Fitting, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of Stay Set Lt ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Erection Of Lt Distibution Box Complete , Augmentation Of 33 / 11 Kvfully Outdoor Type Substation , Erection Of 33 / 11 Kv, 3 Ph, 50 Hz, Onan, Cu Wound, Outdoor Conventional Type Power Transformer Along With Transformer Oil, Buchholtz Relay, Breather, Oti & Wti, Marshalling Box, Conservator Tank, Oil Level Indicator, Valves, 2 Sets Of 50X8 Mm Gs Neutral Earthing Strips { ( With Braided Conductor On Bushing End ) , Isolating Link, Isolation With Insulators } , Vent Explosion Plug, Control Wiring Between Sensing Equipment And Marshalling Box, Cable Supporting Tray On The Body Of Transformer, Transformer Wheels, Lv / Hv Bushing Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Work. , 3.15 Mva Without Tap Changer , 6.30 Mva With Off Load Tap Changer , Erection Of 33Kv Gantries Structure / Super Structure Andequipment Structure For Mounting Isolators And Post Insulators, Bas Bar, Jumper Set , T-Sets Cross Arm Etc. , Erection Of 36Kv, 1250A, 25Ka For 3 Seconds, 3-Ph, Outdoor Type Vacuum Circuit Breaker Along With 36Kv, 1-Phase, 25Ka / 3 Seconds, 200-100 / 5-5 Amps Or 300-150 / 5-5 Amps 1 Set ( 3 Nos ) Outdoor Type Current Transformers Along With Junction Box ( 1 No Junction Box For 3 No Of 1-Phase Cts ) , Jumpers, Earthing, Supporting Structures, Bi- Metallic Clamps, Permanent Maintenance Platform, Marshalling Box Etc Required As Per Technical Specifications, Scope Of Works And Approved Drawings , Erection Of 33 Kv , 1250A , 25 Ka For 3Sec Auto Reclosure ( O / D Channel Mounted ) With Built In Feederprotections, Communicable For Remote Operation Through Scada System Iec 61850 , 104Compatible , Erection Of 33 Kv , 1250A , 25 Ka For 3Sec Auto Reclosure ( O / D Channel Mounted ) With Built In Power Transformer Protections, Communicablefor Remote Operation Through Scada System Iec 61850 , 104 Compatible , Erection Of 33Kv, Indoor, Control & Relay Panel Along With E / F & O / C Relays, Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays And Other Components Etc As Per Approved Drawings, Specifications And Scope Of Works Controlling: , Erection Of 33 Kv Feeder Panel ( 33 Kv Incomer Bus ) [ Numeric Relay, Iec 61850 ] , Erection Of Power Transformerprotection Panel ( With Numericdifferential Relay / Ref Relay , Iec 61850 ) , Erection Of 36Kv, 1250A, 25Ka For 3 Seconds, 3-Ph Double Break Center Rotating Type ( Dbcr ) , Gang Operated Motorised Isolator Along With Support Insulators, Operating Mechanism, Base Channel Down Pipe And All Required Accessories Complete As Per Technical Specifications, Scope Of Works And Approved Drawings With Out Earth Switch. , Erection Of 36Kv, 1250A, 25Ka For 3 Seconds, 3-Ph Double Break Center Rotating Type ( Dbcr ) , Gang Operated Motorised Isolator Along With Support Insulators, Operating Mechanism, Base Channel Down Pipe And All Required Accessories Complete As Per Technical Specifications, Scope Of Works And Approved Drawings With Earth Switch , Erection Of 30 Kv, 10Ka, 1-Ph Station Class Lightening Arrester With Surge Counter, Mounting Platform, Jumpering From Bus Bar, Earthing Connection Using 50X6mm Gs Flat, Hardware Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , Erection Of 9Kv, 10Ka, 1-Ph Station Class Lightening Arrester With Mounting Platform, Jumpering From Bus Bar, Earthing Connection Using 50X6mm Gs Flat, Hardware, Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , Erection Of Indoor Type Control And Relay Panel As Per Technical Specifications, Approved Drawings And Scope Of Works: , Erection Of Indoor Type Control And Relay Panel For 11Kv, 3Phase, 1250 A Vcb ( Transformer Breaker ) Consisting Of Ct 800-400 / 1-1-1 A, Pt 11000 / 110 V-Meter, Volt-Meter, Relays & Accessories Complete As Per Specifications For Transformer Breaker Protection ( 12 Kv, 1250 A, 25Ka ) [ Numeric Relay, Iec 61850 ] , Erection Ofindoor Type Control And Relay Panel For 11 Kv 3 Phase, 1250 A Vcb ( Feeder Breakers ) Consisting Of Ct 400-200 / 1-1-1 A , 11000 / 110 V -Meter, Volt-Meter, Relays, Energy Meter ( Tvm ) & Accessories Complete As Per Specifications For Feeder Breaker Protection ( 12 Kv, 1250 A, 25Ka ) [ Numeric Relay, Iec 61850 ] , Erection Of 12 Kv, 1250 A, 25Ka For 3 Seconds, 3-Ph, Indoor Typevacuum Circuit Breakeralong With 12 Kv, 1-Phase, 800-400 / 1-1-1 , 3 Nos Indoor Type Current Transformer, Indoor Mounting Type Control Panel For Bus Coupler, Control Cabling Between Vcb And Indoor Control Panel And Required Accessories, Bi-Metallic Clamps, A-Meter, Volt-Meter, 3- Phase Electronic Energy Meter, Relay & Accessories Complete As Per Specifications For Bus Coupler Protection ( 12 Kv, 1250 A, 25Ka ) ( Numeric Relay , Iec 61850 ) , Erection Ofnumerical Directional Relay For 11 Kv Feeder Protectionwith Iec 61850 Complitant With Rj 45 Port , Erection Ofnumerical Differentialrelay For Transformer Protection On 11 Kv Incomer With Iec 61850 Compliant With Rj 45 Port , Erection Of 11 Kv , 800 A , 25 Ka For 3Sec Auto Reclosure ( O / D Channel Mounted ) With Built In Feederprotections, Communcablefor Remote Operation Through Scada System Iec 61850 , 104 Compatible , Erection Of30 V, 100 Ah Pb Acid Battery, Battery Stand Made Of Teak Wood Duly Painted With Anti Rusting Paint, Battery Insulators, Inter-Battery Wiring Using 30 Sqmm, 1.1 Kv, Copper Single Core Multi Strand Cable, Terminal Connectors, & All Other Accessories And Connectors And 30V, 40 Amp. ( Or As Per State Practice ) Float-Cum-Boost Battery Charger With Six Wave Rectification For 440 V, 3 Phase, 50 Hz Ac Input Supply As Per Technical Specifications, Approved Drawings And Scope Of Works , Erection Of 33 & 11 Kv Bus-Bars & Jumpers / Droppers / Terminations Including Hardware Fittings, Hardware, T-Claimp Etc As Per Technical Specifications, Approved Drawings And Scope Of Works , Erection Of 33 & 11 Kv Yard And Switch Gear Earthing & Grounding Conductor Etc. As Per Approved Electrical Layout For Each Sub-Station As Per Technical Specifications, Approved Drawings And Scope Of Works With , Erection Of Laying Dressing And Erection Of Control Cables, Power Cables Including Their Termination Materials Like Glands, Lugs, Ferruls Etc. As Per Technical Specifications, Approved Drawings And Scope Of The Work. , Erection Of 11 Kv Isolator Motorised ( 12 Kv, 630A, 25 Ka With Earthswitch Outdoor ) , Erection Of11.00 Mtr. Long Isi Marked Swaged Steel Tubular Pole / Joists As Per Is: 2713 / 1980 ( Part-Ii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-56. With Earthing And Jumper Isolator Etc Of 11 Kv Bay , Sub Station Automation System ( Scada ) With Necessary Hardware And Software And Any Modification / Retro-Fitting In Existing Control And Monitoring System Of 33Kv / 11Kv Switch Gears And Equipments , Field Sensors , Transducers , Limit Switches And Wiring, Ups Having Capacity Of 02 Kva With 1 Hour Battery Backupfor Complete Control, Monitoring And Data Logging Ofsub-Stations Along With Substattion Survelliance System Including Ip Cameras And Nvri P Phones Etc. At Thalout Substationand Sandhole Substation , Sub Station Automation System ( Scada ) With Necessary Hardware And Software And Any Modification / Retro-Fitting In Existing Control And Monitoring System Of 33Kv / 11Kv Switch Gears And Equipments , Field Sensors , Transducers , Limit Switches And Wiring, Ups Having Capacity Of 02 Kva With 1 Hour Battery Backupfor Complete Control, Monitoring And Data Logging Ofsub-Stations Along Along With Adss , Fo Cable Link 15 Km With Accesories On Existiing Poles Between Thalout Substationand Nagwain Substation , With Substatation Survelliance System Including Ip Cameras And Nvr, I P Phones Etc. , Dismantling Works , Dismantling Of Old Power Transformers Along With Associated Material From Substation To Concerned Divisional Store , 3.15 Mva Without Tap Changer , 6.30 Mva With Off Load Tap Changer , Dismantling Of Old 33 Kv Cr&M Panels Along With Associated Material And Its Transportationfrom Substation To Concerned Divisional Store , Dismantling Of Old 33Kvcircuit Breakersalong With Associated Material And Its Transportationfrom Substation To Concerned Divisional Store , Dismantling Of Old 33Kvauto -Reclosers Along With Associated Material And Its Transportationfrom Substation To Concerned Divisional Store , Dismantling Of Old 11 Kv C&M Panels Along With Associated Material And Its Transportationfrom Substation To Concerned Divisional Store , Dismantling Of Old 11Kvauto -Reclosers Along With Associated Material And Its Transportationfrom Substation To Concerned Divisional Store , Dismantling Of Old 33Kvisolatorsalong With Associated Material And Its Transportationfrom Substation To Concerned Divisional Store , Dismantling Of Old 11Kvisolatorsalong With Associated Material And Its Transportationfrom Substation To Concerned Divisional Store , New 11Kv Ht Line , Support For 11 Kv Overhead Line As Per Technical Specification, Approved Drawings And Scope Of Work , Erection Charges Of 11 Kv Ht Line I / C Erction Of Single And Double Pole Strc, Stay Set , Earthing, Concreting Of Rcc Muff , Jumpering And Earth Wire Complete In All Respectsof Ht Line ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of Steel Tubular Pole 10 / 11 Mtr Long For Ht Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms And Fixing Of Insulators, Kneebracing Set, X-Bracing Set , Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete In All Respect ( Punching Of The Poles Is Stricitly Not Allowed ) , Laying, Stringing , Sagging& Binding With Insulator Of Acsr Rabbit Conductor Of Size6 / 1 / 3.35 Mm ( 50Mm2 ) I / C Jumpering Etc. Complete , Erection Of Stay Set Ht ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Laying, Stringing , Sagging& Bindingof Gi Wire 8Swg , Erection Of 11 Kv, 3-Ph, 400 A, 3 Pin Type, Vertical Mounting Type, Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 11Kv, 3-Ph Drop Out Fuse Assembly Including Insulators And Mounting Arrangements, Jumpering From Bus Bar, Hardware, Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , New 22Kv Ht Line , Support For 22Kv Overhead Line As Per Technical Specification, Approved Drawings And Scope Of Work , Erection Charges Of 22 Kv Ht Line I / C Erction Of Single And Double Pole Strc, Stay Set , Earthing, Concreting Of Rcc Muff , Sagging , Stringing, , Jumpering And Earth Wire Complete In All Respectsof Ht Line ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of 11 Kv, 3-Ph, 400 A, 3 Pin Type, Vertical Mounting Type, Gang Operated, Ab Switch Along With Support Insulators, Base Channel, Down Pipe, Arcing Horns Etc. Complete As Per Technical Specifications, Scope Of Works And Approved Drawings , 11Kv, 3-Ph Drop Out Fuse Assembly Including Insulators And Mounting Arrangements, Jumpering From Bus Bar, Hardware, Etc As Required As Per Technical Specifications, Approved Drawings And Scope Of The Works. , Augmentation Of Lt Lines -1 Phase To 3-Phasewith 50 Sq. Mm Rabbit Conductor , Erection Of Steel Tubular Pole 9Mtr Long ( Single Pole ) For Lt Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms And Shackle Insulators, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Laying, Stringing , Sagging& Binding With Insulator Of Acsr Rabbit Conductor Of Size6 / 1 / 3.35 Mm ( 50Mm2 ) I / C Jumpering Etc. Complete , Erection Of Stay Set Lt ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Augmentationof Lt Lines -2Phase To 3-Phasewith 50 Sq. Mm Rabbit Conductor , Erection Of Steel Tubular Pole 9Mtr Long ( Single Pole ) For Lt Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms And Shackle Insulators, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Laying, Stringing , Sagging& Binding With Insulator Of Acsr Rabbit Conductor Of Size6 / 1 / 3.35 Mm ( 50Mm2 ) I / C Jumpering Etc. Complete , Erection Of Stay Set Lt ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Reconductoring Of Lt Lines -1 Phase 2 Wire With 50 Sq. Mm Rabbit Conductor , Erection Of Steel Tubular Pole 9Mtr Long ( Single Pole ) For Lt Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms And Shackle Insulators, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Laying, Stringing , Sagging& Binding With Insulator Of Acsr Rabbit Conductor Of Size6 / 1 / 3.35 Mm ( 50Mm2 ) I / C Jumpering Etc. Complete , Erection Of Stay Set Lt ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Dismantling Of Old Conductor I / C Rolling Of Conductor , De-Stringing& Lifting Ofall Dismantled Material From Site Of Work To Concerned Divisional Store ( Per Km Single Wire ) , Reconductoring Of Lt Lines -3 Phase 4 Wire With 50 Sq. Mm Rabbit Conductor , Erection Of Steel Tubular Pole 9Mtr Long ( Single Pole ) For Lt Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms And Shackle Insulators, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Laying, Stringing , Sagging& Binding With Insulator Of Acsr Rabbit Conductor Of Size6 / 1 / 3.35 Mm ( 50Mm2 ) I / C Jumpering Etc. Complete , Laying, Stringing , Sagging& Binding With Insulator Of Acsr Rabbit Conductor Of Size6 / 1 / 4.72 Mm ( 100Mm2 ) I / C Jumpering Etc. Complete , Erection Of Stay Set Lt ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Dismantling Of Old Conductor I / C Rolling Of Conductor , De-Stringing& Lifting Ofall Dismantled Material From Site Of Work To Concerned Divisional Store ( Per Km Single Wire ) , Cabling Of Lt Line With Ab Cable , Laying, Installtion Of Suspension & Tension Assembly Etc., Sagging Of Lt Ab Cable Of Size: 3 X 95 Sqmm, Jointing And Termination Kits Etc. Complete , Erection Of Steel Tubular Pole 9Mtr Long ( Single Pole ) For Lt Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms & Ab Cable Fitting, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of Stay Set Lt ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Erection Of Lt Distibution Box Complete , Erection Of Ipc , Erection Of Pvc 3.5 Core 16 Sqmm , Lt , Abcable3x185 Sq. Mm { Additional 1% Sagging & Wastage ) , Laying, Installtion Of Suspension & Tension Assembly Etc., Sagging Of Lt Ab Cable Of Size:3X185 Sq. Mm, Jointing And Termination Kits Etc. Complete , Erection Of Steel Tubular Pole 9Mtr Long ( Single Pole ) For Lt Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms & Ab Cable Fitting, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of Stay Set Lt ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Erection Of Lt Distibution Box Complete , Erection Of Ipc , Erection Of Pvc 3.5 Core 16 Sqmm , Ht , Abcable3x95+70 Sq. Mm { Additional 1% Sagging & Wastage ) , Laying, Installationof Suspension & Tension Assembly Etc., Sagging Of 11 Kv Ht , Abcable3x95+70 Sq. Mm, Jointing And Termination Kits Etc. Complete , Laying, Instalhtion Of Suspension & Tension Assembly Etc., Sagging Of 22 Kv Ht , Abcable3x95+70 Sq. Mm, Jointing And Termination Kits Etc. Complete , Erection Of Steel Tubular Pole 9Mtr Long For Ht Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms & Ab Cable Fitting, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of Stay Set Ht ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Ht Xlpecable3x120 Sq. Mm { Additional 1% Sagging & Wastage ) , Laying, Installationof Suspension & Tension Assembly Etc., Sagging Of Ht Xlpecable3x120 Sq. Mm, Jointing And Termination Kits Etc. Complete , Erection Of Steel Tubular Pole 9Mtr Long For Ht Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms & Xlpecable Fitting, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of Stay Set Ht ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Erection Of Steel Ropefor Holding Of Xlpe Cable 3X120 Sqmmalongwithfixing Clampsand Allied Material. , Ht Ab Cable On Poles [ Size: ( 3X120 +95 Sq, Mm ) { Additional 1% Sagging & Wastage ) , Laying, Installation Of Suspension & Tension Assembly Etc., Sagging Of 11 Kv Ht , Abcable ( 3X120 +95Sq. Mm ) , Jointing And Termination Kits Etc. Complete , Erection Of Steel Tubular Pole 9Mtr Long For Ht Line Viz Digging Of Pit, Drilling Of Holes In X-Arms, Erection Of Pole, Erection Of X-Arms & Ab Cable Fitting, Filling Of Pit & Ramming , Painting Of Pole & Filling Of Concrete In Rcc Muffcomplete ( Punching Of The Poles Is Stricitly Not Allowed ) , Erection Of Stay Set Ht ( Digging Of Pit, Fixing Of Stay Rod, Filling Of Pit , Nozzeling & Tighting ) , Erection Of Earthing Set ( Digging Of Pit, Fixing Of Gi Wire To The Earth System & Filling Of Pit ) , Civil Works , Construction Offoundation For 6.30Mva Sub-Station, 33 / 11Kv Power Transformer, Baffle Wall , R.S. Joist Foundation, Vcb Foundation, Ct / Pt, Oil Sump, Cable Trenches, Screening And Spreading Stone Shingle On Pcc And Foundation & Fencing For 250 To 630Kva Dtrs. Etc. , Earth Work In Excavation By Mechanical Means ( Hydraulic Excavator ) / Manual Means In Foundation Trenches Or Drains ( Not Exceeding 1.5 M In Width Or 10 Sqm On Plan ) , Including Dressing Of Sides And Ramming Of Bottoms, Lift Upto 1.5 M, Including Getting Out The Excavated Soil And Disposal Of Surplus Excavated Soil As Directed, Within A Lead Of 50 M. All Kinds Of Soil. , Earth Work In Excavation By Mechanical Means ( Hydraulic Excavator ) / Manual Means Over Areas ( Exceeding 30 Cm In Depth, 1.5 M In Width As Well As 10 Sqm On Plan ) Including Getting Out And Disposal Of Excavated Earth Lead Upto 50 M And Lift Upto 1.5 M, As Directed By Engineer-Incharge.:-Hard Rock ( Blasting Prohibited ) , Providing And Laying In Position Cement Concrete Of Specified Grade Excluding The Cost Of Centering And Shuttering - All Work Up To Plinth Level. 1:3:6 ( 1 Cement : 3 Coarse Sand ) : 6 Graded Stone Aggregate 40 Mm Nominal Size ) , Providing And Laying In Position Cement Concrete Of Specified Grade Excluding The Cost Of Centering And Shuttering - All Work Up To Plinth Level : 1:4:8 ( 1 Cement : 4 Coarse Sand ) : 8 Graded Stone Aggregate 40 Mm Nominal Size ) , Centering And Shuttering Including Strutting, Propping Etc. And Removal Of Form For: , Foundations, Footings, Bases Of Columns, Etc. For Mass Concrete. , Walls ( Any Thickness ) Including Attached Pilasters, Butteresses, Plinth And String Courses Etc. , Providing And Laying In Position Specified Grade Of Reinforced Cement Concrete, Excluding The Cost Of Centering, Shuttering, Finishing And Reinforcement - All Work Up To Plinth Level 1:1.5:3 ( 1 Cement : 1.5 Coarse Sand ) : 3 Graded Stone Aggregate 20 Mm Nominal Size ) , Reinforced Cement Concrete Work In Walls ( Any Thickness ) , Including Attached Pilasters, Buttresses, Plinth And String Courses, Fillets, Columns, Pillars, Piers, Abutments, Posts And Struts Etc. Above Plinth Level Up To Floor Five Level, Excluding Cost Of Centering, Shuttering, Finishing And Reinforcement 1:1.5:3 ( 1 Cement : 1.5 Coarse Sand ) : 3 Graded Stone Aggregate 20 Mm Nominal Size ) , Steel Reinforcement For R.C.C. Work Including Straightening, Cutting, Bending, Placing In Position And Binding All Complete Upto Plinth Level Thermo-Mechanically Treated Bars Of Grade Fe-500D Or More. , Steel Work Welded In Built Up Sections / Framed Work, Including Cutting, Hoisting, Fixing In Position And Applying A Priming Coat Of Approved Steel Primer Using Structural Steel Etc. As Required. In Gratings, Frames, Guard Bar, Ladder, Railings, Brackets, Gates And Similar Works , Providing And Fixing Unplasticised -Pvc Pipe Clips Of Approved Design To Unplasticised - Pvc Rain Water Pipes By Means Of 50X50x50 Mm Hard Wood Plugs, Screwed With M.S. Screws Of Required Length, Including Cutting Brick Work And Fixing In Cement Mortar 1:4 ( 1 Cement : 4 Coarse Sand ) And Making Good The Wall Etc. Complete. 110 Mm. , Supplying, Filling, Spreading & Leveling Gravels Of Approved Size In Required Thickness, For All Leads & Lifts, All Complete As Per Direction Of Engineer-Incharge. , Providing And Laying In Position Cement Concrete Of Specified Grade Excluding The Cost Of Centering And Shuttering - All Work Up To Plinth Level : 1:1½:3 ( 1 Cement: 1½ Coarse Sand ) : 3 Graded Stone Aggregate 20 Mm Nominal Size ) , Providing And Fixing G.I. Chain Link Fabric Fencing Of Required Width In Mesh Size 50X50 Mm Including Strengthening With 2 Mm Dia Wire Or Nuts, Bolts And Washers As Required Complete As Per The Direction Of Engineer-In-Charge. Made Of G.I. Wire Of Dia 4 Mm , Providing And Fixing Isi Marked M.S. Pressed Butt Hinges Bright Finished With Necessary Screws Etc. Complete :100X58x1.90 Mm , Providing And Fixing Isi Marked Oxidised M.S. Sliding Door Bolts With Nuts And Screws Etc. Complete :250X16 Mm , Providing And Fixing On Wall Face Unplasticised Rigid Pvc Rain Water Pipes Conforming To Is : 13592 Type A, Including Jointing With Seal Ring Conforming To Is : 5382, Leaving 10 Mm Gap For Thermal Expansion, ( I ) Single Socketed Pipes For Weep Holes In Fire Protection Wall Complete In All Respect.75 Mm Diameter. , Providing And Laying In Position Cement Concrete Of Specified Grade Excluding The Cost Of Centering And Shuttering - All Work Up To Plinth Level:- 1:5:10 ( 1 Cement : 5 Coarse Sand: 10 Graded Stone Aggregate 40 Mm Nominal Size ) , Demolishing Cement Concrete Manually / By Mechanical Means Including Disposal Of Material Within 50 Metres Lead As Per Direction Of Engineer - In - Charge Nominal Concrete 1:3:6 Or Richer Mix ( I / C Equivalent Design Mix )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 03-Oct-2022 extension of bid submission Date 10-10-2022

Key Value

Document Fees
INR 2950 /-
EMD
INR 38730211.0 /-
Tender Value
INR 193.65 Crore /-

BOQ Items

Name of Work: Tender for Development of Distribution Infrastructure for “Loss Reduction in District Mandi, Himachal Pradesh under RDSS (Revamped Reforms-Based and Results-Linked, Distribution Sector Scheme)
Sl. No. Item Description
1SCHEDULE-I (SUPPLY PART)
2New DTR 11/22 kV (HVDS, Feeder Bifurcation, Feeder Segregation and Extension of New HT, DT, LT as per technical specification, approved drawings and scope of work.
39.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
4RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to IS 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
5Pre-fabricated galvanised steel (zinc coating 610gms/sqm), items like DC cross arm (100x50x6 mm), back clamps (50x6 mm), pole clamp (65x8 mm), DO fuse mounting channel (75x40x6 mm), transformer mounting channel (100x50x6 mm), transformer clamping set (50x50x6 mm), transformer belting set ( 50x50x6 mm) as per technical specification, approved drawings and scope of work.
6GS Nuts, Bolts with Washers as per technical specification, approved drawings and scope of work.
7Stay Set (Galvanised) with 50x8 mm stay clamp, Guy insulator ( 1Nos.), anchor plate (200x200x6mm), nut bolts, 2 Nos turn-buckles,1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete as per technical specification, approved drawings and scope of work.
811 KV Disc insulator B&S type conformimg to IS-731/1971 all latest version thereof for suspension & tension string ball and socket type having pin ball. The minumum and maximum creepage distance with diameter of insulator- 255 mm & having electromechanical strength 90KN. The insulator shall have W type phosphors bronze security clips for ball socket porcelain conforming IS: 2486-1971 (90KN) complete in all respect. Heavilypolluted atmospheres Creepage distance-400 mm
922 KV Disc insulator B&S type ( 2 nos. disc)conformimg to IS-731/1971 all latest version thereof for suspension & tension string ball and socket type having pin ball. The minumum and maximum creepage distance with diameter of insulator- 225 mm & having electromechanical strength 90KN. The insulator shall have W type phosphors bronze security clips for ball socket porcelain conforming IS: 2486-1971 (90KN) complete in all respect. Heavily polluted atmospheres Creepage distance400 mm
10Distribution Transformer Substation using new outdoor type, oil immersed, distribution transformer up to and including 630 KVA as per IS1180 (Part-1): 2014 and its amendments 1, 2, 3 and 4,RGO/Amorphous core, Energy Efficiency Level 1, carrying Bureau of Indian Standard Certificate mark, in following preferred ratings as per detailed scope of work and technical specifications:
1122/0.230 kV Distribution Transformer 10 KVA 3Phase DTR
1211/0.230 kV Distribution Transformer 16 KVA 3 PhaseDTR
1311/0.4 KV Distribution Transformer 25 KVA 3 phaseDTR
1422/0.4 KV Distribution Transformer 25 KVA 3 phase DTR
1511/0.4 KV Distribution Transformer 63 KVA 3 phaseDTR
1622/0.4 KV Distribution Transformer 63 KVA 3 phaseDTR
1711/0.4 KV Distribution Transformer 100 KVA 3 phaseDTR
1822/0.4 KV Distribution Transformer 100 KVA 3 phaseDTR
1911/0.4 KV Distribution Transformer 250 KVA 3 phaseDTR
20Outdoor mounting type Distribution box made of MS sheet of thickness not less than 18 SWG CRCA sheet/ SMC Distribution Box, dust and moisture vermin, weather proof with degree of protection with suitable bus bars, earthing cum neutral bus, earthing terminals, box illumination, front door operated with proper locking arrangement, lugs, mounting channel frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work, technical specifications and approved drawings suitable for following transformer:
213 Ph 10KVA transformer 80 A TPN MCCB (incomer) and 2 Nos. 50 A SP MCCB (outgoing)
223 Ph 16 KVA transformer 80 A TPN MCCB (incomer) and 2 Nos. 50 A SP MCCB (outgoing)
233 Ph 25 KVA transformer 40 A TPN MCCB (incomer) and 6 Nos. 25 A SP MCCB (outgoing)
243 Ph 63 KVA Transformer having 200 A TPN isolator, 100 A HRC fuse (incomer) and 6 Nos. 60 A SP MCCB (outgoing)
253 Ph 100 KVA Transformer having 200 A TPN isolator, 160A HRC fuse (incomer) and 6 Nos. 90 A SP MCCB (outgoing)
26LT Distribution Panel Box suitable for 250KVA S/Stn of size 1100x800x275mm +/- 5% made of steel sheet of 1.63 mm thickness having doubledoor locking arrangement duly powder coated painted complete with 2 no. MCCB"s ( 1main + 1 spare) Rating 400Amp, 3 Poles having following specifications (1) Minimum frame size 400Amp (2) Type variable trip free, (3) Breaking capacity- Isu & LCS at 415, 50 Hz (KA: not less than 50 KA) (4) , Thermal release range: 320-440Amp (5) Mecanicallife (operation) 20000 No. (6) Electrical life (operation) 4000 No. (7) Rated insulation voltage (V) 690V (8) Tripping thermal releasing setting : Thermal-O/L variable setting (9) Tripping magnetic releasing setting : Magnetic- S/C fixed setting (12) in (10) (Operation) volatge 415V, AC (11) Caliberation temperature: 40 degree C(12) High voltage withstand voltage : 3KV for 1 minute (13) Confirming to IS : 1993/60947-2, 1989 (14) Make L&T/ Havells/ABB/ HPL/ Schneider (15) ICS : 100% ICU
279kV, 10 kA Porcelain Station Surge Arrestor/Lightening Arrestorcomplete with accessories for 11KV system
2818 kV, 10 kA Porcelain Station Surge Arrestor/Lightening Arrestorcomplete with accessories for 22 KV system
2911 kV, 3-ph, 400 A, 3 Pin type, Horizontal/Vertical Mounting type (as desired by DISCOM), Gang Operated, AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
3022 kV, 3-ph, 400 A, 3 Pin type, Horizontal/Vertical Mounting type (as desired by DISCOM), Gang Operated, AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
3111 kV, 3-ph, Drop Out fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete as per technical specifications, scope of works and approved drawings
3222 kV, 3-ph, Drop Out fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete as per technical specifications, scope of works and approved drawings
333 Nos pipe earthing using 40mm dia GI pipe 3000 mm long, making earth grid using 50x6mm GI Flat and riser as per scope of work of Distribution Transformer Substations, as per scope of work, approved drawings and technical specifications,
348 SWG GI wire for earthing as per technical specifications, approved drawings and scope of works.
353.5 Cx16 sqmm aluminium conductor cable
363.5 CX35 sqmm aluminium conductor cable
373.5Cx70 sqmm aluminium conductor cable
383.5Cx120 sqmm aluminium conductor cable
393.5Cx185 sqmm aluminium conductor cable
40Danger Plate Size: 250x200x1.6 mm made of mild steel plates 1.6 (minimum) thick vitreous enameled white letter figure, conventional skill and X-Boxes and signal red colour on front side for use in HPSEBL. The rear side of the plate shall be black enameled and conforming to IS specifiction no. IS-1351/1982 suitable for 11/22KV System
41Galvanised steel barbed wire of 9.8 kg /100metre
42Aluminium Paint for all poles and steel fitting
43Red Oxide
443 kVAR power factor correction capacitor along with MC O capacitor duty contractorfor new 25 kVA , 11/0.4 kV DTR
457 kVAR power factor correction capacitor along with MC O capacitor duty contractorfor new 63 kVA , 11/0.4 kV DTR
4610 kVAR power factor correction capacitor along with MC O capacitor duty contractorfor new 100 kVA , 11/0.4 kV DTR
47ACSR Rabbit Conductor for jumpering including PG Clamps, bi- metallic connectors, hardware etc as per technical specifications, approved drawings and scope of works.
48New LT Line 3 Ph 4 Wire Rabbit
49Support for LT overhead Line as per technical specification, approved drawings and scope of work.
509.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
51RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to IS 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
52Galvanised Stay Set with anchor plate (200x200x6mm), 50x8mm stay clamp, Stay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work.
53Earthing as per approved drawings, technical specifications and scope of work
5440 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover plates on GI frame, bentonite powder and Spike Earthing 20mm solid Rod i/c other accessories complete
558 SWG GI wire for earthing & GI nuts, bolts & washers
56ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
576/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit
58Angle Iron (75x75x6) [Length- 1.50 Mtr + 0.02 Mtr]
59Shackle Insulator (16 kN)
60D-Iron (U- Clamps)
61Earth Knob
62Kit kat I.C
63Full Clamps [ 2 No for A.I + 1 No for Stay Set]
64Spool Tie
65Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm F or more(with flat and spring washers)]
66Aluminium Paint
67Spiral PVC Spacer
68Red Oxide
69New LT Line 1 Ph 2 Wire Rabbit
70Support for LT overhead Line as per technical specification, approved drawings and scope of work.
719.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
72RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to IS 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
73Galvanised Stay Set with anchor plate (200x200x6mm), 50x8mm stay clamp, Stay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work.
74Earthing as per approved drawings, technical specifications and scope of work
7540 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover plates on GI frame, bentonite powder and Spike Earthing 20mm solid Rod i/c other accessories complete
768 SWG GI wire for earthing & GI nuts, bolts & washers
77ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
786/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit
79Angle Iron (75x75x6) [Length- 1.50 Mtr + 0.02 Mtr]
80Shackle Insulator (16 kN)
81D-Iron (U- Clamps)
82Earth Knob
83Kit kat I.C
84Full Clamps [ 2 No for A.I + 1 No for Stay Set]
85Spool Tie
86Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm F or more(with flat and spring washers)]
87Aluminium Paint
88Spiral PVC Spacer
89Red Oxide
90Augmentation & Renovation of 11/0.4 kV Distribution Transformer Substation
91Augmentation of Distribution Transformer Substation using new outdoor type, oil immersed, distribution transformer up to and including 630 KVA as per IS1180 (Part-1): 2014 and its amendments 1, 2, 3 and 4, CRGO/Amorphous core, Energy Efficiency Level 1, carrying Bureau of Indian Standard Certificate mark, in following preferred ratings as per detailed scope of work and technical specifications under:
92New 63 KVA (11/0.4 kV) DTR (Replacing 25KVA old DTR),
93New 63 KVA (22/0.4 kV)DTR (Replacing 25KVA old DTR),
94New 100 KVA (11/0.4 kV) DTR (Replacing 63 KVA old DTR),
95New 100 KVA (22/0.4 kV)DTR (Replacing 63 KVA old DTR),
96New 250 KVA (11/0.4 kV) DTR (Replacing 100 KVA old DTR),
97New 250 KVA (22/0.4 kV) DTR (Replacing 100 KVA old DTR),
98New 400 KVA (11/0.4 kV) Copper wound DTR (Replacing 250 KVA old DTR),
99New 400 KVA (22/0.4 kV) Copper wound DTR (Replacing 250 KVA old DTR),
100New 630 KVA (11/0.4 kV) Copper wound DTR (Replacing 400 KVA old DTR),
101New 630 KVA (22/0.4 kV) Copper wound DTR (Replacing 400 KVA old DTR),
102Augmentation of DTR Substation by using new 3.5 C PVCAluminium Conductor, Stranded, unarmoured cable for connection of transformer LV bushing to Distribution Box and Distribution box to overhead line as per Scope of work, technical specification and approved drawings. Replaced cables to be deposited in Employer"s store.
1033.5 Cx70 sqmm aluminium conductor cable
1043.5Cx120 sqmm aluminium conductor cable
1053.5Cx185 sqmm aluminium conductor cable
1063.5Cx300 sqmm aluminium conductor cable
1073.5Cx400 sqmm aluminium conductor cable
108Augmentation of DTR Substation by using new outdoor mounting type Distribution box made of MS sheet of thickness not less than 1.8 mm/ SMC distribution box, dust and moisture vermin, weather proof with degree of protection IP 33 as per IS 13947 with suitable bus bars, earthing bus, earthing terminals, box illumination, front door operated with proper locking arrangement, non magnetic 4 mm thick gland plate, double compression brass cable glands, lugs, mounting channel frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work, technical specifications and approved drawings suitable for following transformer:
1093 Ph 63 KVA Transformer having 200 A TPN isolator, 100 A HRC fuse (incomer) and 6 Nos. 60 A SP MCCB (outgoing)
1103 Ph 100 KVA Transformer having 200 A TPN isolator, 160A HRC fuse (incomer) and 6 Nos. 90 A SP MCCB (outgoing)
111LT Distribution Panel Box suitable for 250KVA S/Stn of size 1100x800x275mm +/- 5% made of steel sheet of 1.63 mm thickness having doubledoor locking arrangement duly powder coated painted complete with 2 no. MCCB"s ( 1main + 1 spare) Rating 400Amp, 3 Poles having following specifications (1) Minimum frame size 400Amp (2) Type variable trip free, (3) Breaking capacity- Isu & LCS at 415, 50 Hz (KA: not less than 50 KA) (4) , Thermal release range: 320-440Amp (5) Mecanicallife (operation) 20000 No. (6) Electrical life (operation) 4000 No. (7) Rated insulation voltage (V) 690V (8) Tripping thermal releasing setting : Thermal-O/L variable setting (9) Tripping magnetic releasing setting : Magnetic- S/C fixed setting (12) in (10) (Operation) volatge 415V, AC (11) Caliberation temperature: 40 degree C(12) High voltage withstand voltage : 3KV for 1 minute (13) Confirming to IS : 1993/60947-2, 1989 (14) Make L&T/ Havells/ABB/ HPL/ Schneider (15) ICS : 100% ICU
112LT Distribution Panel Box suitable for 400KVA S/Stn. made of steel sheet of 1.63 mm thickness having doubledoor locking arrangement duly powder coated pained complete with ACB Rating 1000Amp, Duty Circle 0.3 Sec, Rating Symmetrical breaking capacity 50KA, Service Breaking Capacity 100% Icu, Rating Making Capacity 105KA Peak, Short circuit time for seconds (KA rms) 50KA, Thermal Current set value 1000 Amp, Time for which breaker can carry its rating breaking current <40 MS, Endurance (CO) Cycle Mechanical not less than 8000 operations, Electrical Not less than 5000 operations, Electrical life for Arcing contacts not less than 2500 operations,Insultion Voltage 1100 Volts, Impulse with stand voltage 8KV, Closing Mechanism Mannual independent mannual, Version required fixed and make L&T/Havells/C&S/HPL/Schneider
113LT Distribution Panel Box suitable for 630KVA S/Stn. made of steel sheet of 1.63 mm thickness having doubledoor locking arrangement duly powder coated pained complete with ACB Rating 1000Amp, Duty Circle 0.3 Sec, Rating Symmetrical breaking Capacity 50KA, Service Breaking Capacity 100% Icu, Rating Making Cap. 105KA Peak, Short circuit time for seconds (KA rms) 50KA, Thermal Current Set Value 1000 Amp, Time for which breaker can carry its rating breaking current <40 MS, Endurancec (CO) Ciycle Mechanical not less than 8000 operations,Electrical Not less than 5000 operations, Electrical life for Arcing Contacts not less than 2500 operations, Insulation Voltage 1100 Volts, Inpulse with stgand voltage 8KV, Closing Mechanism Mannual independent mannual, Version Required Fixed and Make L&T/Havells/C&S/HPL/Schiender.
114Renovation of DTR substation Earthing as per technical specification, approved drawings and scope of work:
115Revamping of Distribution Transformer substation earthing by using 40 mm dia 3 meter long GI pipe earthing, using 50x6 mm GS flat for earth mat and riser and 25x3mm GS flat for connecting equipment, using 200 kg bentonite powder of substation in normal soil
116Augmentation of DTR substation by new Pre-fabricated galvanised steel items like DC cross arm (100x50x6 mm), back clamps (65x8 mm), pole clamp (65x8 mm), DO mounting channel (75x40x6 mm), transformer mounting channel (100x50x6 mm), transformer clamping set (50x50x6 mm), transformer belting set ( 50x50x6 mm) as per technical specification, approved drawings and scope of work.
117Augmentation of DTR substation by new Galvanised Steel (GS) Nuts, Bolts with Washers as per technical specification, approved drawings and scope of work.
118Augmentation of DTR substation by new 9KV, 11 KA Distribution Class Lightening Arrester for DT as per technical specification, approved drawings and scope of work.
119Augmentation of DTR substation by 18 kV, 10 kA Porcelain Station Surge Arrestor/Lightening Arrestorcomplete with accessories for 22 KV system
120Augmentation of DTR substation by new 11 kV, 3-ph, 200 A, 3 Pin type, Vertical Mounting type, Gang Operated,AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
121Augmentation of DTR substation by new22 kV, 3-ph, 400 A, 3 Pin type, Horizontal/Vertical Mounting type (as desired by DISCOM), Gang Operated, AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
122Aluminium Paint for substaion Structure and steel fitting
12311kV, 200 A, 3-ph Drop Out fuse assembly including insulators and mounting arrangements, jumpering from bus bar, hardware, etc as required as per technical specifications, approved drawings and scope of the works.
12422 kV, 3-ph, Drop Out fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete as per technical specifications, scope of works and approved drawings
125Conversion of existing LT bare conductor line with following arrangements using new areal bunched XLPE cable,tension clamps for dead end, suspension clamps, clamps for neutral, piercing connectors type-I & type-II, 16 mm dia MS nuts & bolts, pole clamps, spring loaded bus bar suitable for single phase and three phase systems etc. as required as per technical specification, approved drawings and scope of work:
126AERIAL BUNCHEDCABLE 3 X 70+50+16 SQ.MM
127LT AB Cable Cable on poles [Size: 3 X 70+50+16 SQ.MM {additional 1% sagging & wastage)
1289.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
129RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to IS 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
130Galvanised Stay Set with anchor plate (200x200x6mm), 50x8mm stay clamp, Stay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work.
131Half Clamp for Cross Arm
132Anchoring Assembly for LT
133Suspension Assembly for LT
134Facade Hooks for LT
135Distribution Boxes
136Earthing Set complete
137Red Oxide
138Aluminium paint
139Augmentation of 33/11 KVFully outdoor type substation
14033/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power Transformer along with transformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end), isolating link, isolation with insulators}, Vent explosion plug, control wiring between sensing equipment and marshalling box, cable supporting tray on the body of transformer, transformer wheels, LV/HV bushing etc as required as per technical specifications, approved drawings and scope of the work.
1413.15 MVA without tap changer
1426.30 MVA with off load tap changer
14333KV Superstructure andequipment structure
144Galvanised super structure comprisinggantries and columns
145Galvanised equipment structure for mounting 33KV Isolators and Post insulators
14636kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker along with 36kV, 1-Phase, 25kA/3 seconds, 200-100/5-5 Amps or 300-150/5-5 Amps 1 Set( 3 nos) outdoor type Current Transformers along with junction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting structures, bi- metallic clamps, permanent maintenance platform, marshalling box etc required as per technical specifications, scope of works and approved drawings
14733 kV , 1250A , 25 kA for 3sec Auto reclosure(o/d channel mounted) with built in feederprotections,communicable for remote operation through SCADA system IEC 61850 , 104compatible
14833 kV , 1250A , 25 kA for 3sec Auto reclosure (o/d channel mounted) with built in power transformer protections,communicablefor remote operation through SCADA system IEC 61850 , 104 compatible
14933kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other components etc as per approved drawings, specifications and scope of works controlling:
15033 kV feeder panel (33 kV Incomer Bus) [Numeric Relay, IEC 61850]
151Power transformerprotection Panel (with NumericDifferential Relay / REF Relay , IEC 61850)
15236kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), Gang Operated motorised isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per technical specifications, scope of works and approved drawings with out earth switch.
15336kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), Gang Operated motorised isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per technical specifications, scope of works and approved drawings with earth switch
15430 kV, 10kA, 1-ph Station Class Lightening Arrester with Surge Counter,mounting platform, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware etc as required as per technical specifications, approved drawings and scope of the works.
1559kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware, etc as required as per technical specifications, approved drawings and scope of the works.
156Indoor type control and relay panel as per technical specifications, approved drawings and scope of works:
157Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of CT 800-400/1-1-1 A, PT 11000/110 V-meter, volt-meter, Relays & accessories complete as per specifications for transformer breaker protection (12 kV, 1250 A, 25KA) [Numeric Relay, IEC 61850]
158Indoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers) consisting of CT 400-200/1-1-1 A , 11000/110 V -meter, volt-meter, Relays, energy meter (TVM) & accessories complete as per specifications for feeder breaker protection(12 kV, 1250 A, 25KA) [Numeric Relay, IEC 61850]
15912 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breakeralong with 12 kV, 1-Phase, 800-400/1-1-1 , 3 Nos indoor type Current Transformer, indoor mounting type control panel for bus coupler, control cabling between VCB and indoor control panel and required accessories, bi-metallic clamps, A-meter, volt-meter, 3- phase electronic energy meter, Relay & accessories complete as per specifications for bus coupler protection (12 kV, 1250 A, 25KA)(Numeric relay , IEC 61850)
160Numerical directional relay for 33 KV feeder Protectionwith IEC 61850 complitant with RJ 45 Port
161Numerical directional relay for 11 KV feeder Protectionwith IEC 61850 complitant with RJ 45 Port
162Numerical Differentialrelay for transformer protection on 11 KV incomer with IEC 61850 compliant with RJ 45 Port
16311 kV ,800 A , 25 kA for 3sec Auto reclosure(o/d channel mounted) with built in feederprotections,communcablefor remote operation through SCADA system IEC 61850 , 104 compatible
16430 V, 100 AH Pb Acid battery, battery stand made of teak wood duly painted with anti rusting paint, battery insulators, inter-battery wiring using 30 sqmm, 1.1 kv, copper single core multi strand cable, terminal connectors, & all other accessories and connectors and 30V, 40 Amp. (or as per State practice) Float-cum-Boost Battery Charger with six wave rectification for 440 V, 3 phase, 50 Hz AC Input Supply as per technical specifications, approved drawings and scope of works
165ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware fittings, hardware, T-claimp etc as per technical specifications, approved drawings and scope of works
16630/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther
167Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works with
16865 x 8 mm GI flat for ground mat
16950 x 6 mm Galvanized GI flat (risers)
17025mm dia GI rod 3 m long for earth mat
17150 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover, placed on GI frame, bantonide powder and other accessories complete as per technical specification. (for Power Transformer Neutral, Station Transformer Neutral and Lightening Arresters direct earthing) as per technical specifications, approved drawings and scope of works.
17233 KV Post insulators along with Strurcture, suitable hardware & accessories suitable for Panther/Dog conductors as per approved drawings & specifications.
173Control cables including their termination materials like glands, lugs etc. as per technical specifications, approved drawings and scope of the work.
1742 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable
17510 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable
17612 Core 2.5 sqmm armoured, stranded copper conductor, PVC insulated and PVC sheathed cable
1777Core 6.0 sqmm armoured, stranded copper conductor, PVC insulated screened and PVC sheathed cable
1784 Core 6.0 sqmm armoured, stranded copper conductor, PVC insulated screened and PVC sheathed cable
1793Core 400 sqmm XLPE , Al , armoured , Cable
180LT power cable PVC 1.1 KV ,4 core, Al ,16 mm2, un-armoured
18111kV , XLPE , outdoor type 3x 400sqmm termination kit
18211kV , XLPE , indoor type 3x400sqmm termination kit
18311 kV Isolator motorised (12 kV, 630A, 25 kA with Earthswitch outdoor)
18411.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-56.
185RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to IS 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size)
186Extension of 33kV and 11 KV yard
187RS Joists size 12800x250x125
188MS Channel Iron 125x65x6, X-Arms @ 12.1 kg/m, 7 mtr long, 5.5mtr long, MSAI 50x50x6 mmfor 33 and 11 KV yard
189Nuts and Bolts of Various Sizes (Galvanised / Coated)(with flat and spring washers)]
190Bus Bar
191i) 33 kVDisc Insulator Tension Stringcomplete
192ii) 33 kV Disc Suspension Tension String complete
193ACSR Conductor 200sqmm @ 10%
194PG Clamps
195Sub Station Automation System ( SCADA)with necessary hardware and software and any modification/retro-fitting in existing control and monitoring system of 33KV/11KV switch gears and equipments , field sensors , transducers , limit switches and wiring, UPS having capacity of 02 KVA with 1 hour Battery backupfor complete control, monitoring and data logging ofSub-Stations along with substattion survelliance system including IP cameras and NVRI P phones etc. at thalout substationand Sandhole Substation
196Sub Station Automation System ( SCADA)with necessary hardware and software and any modification/retro-fitting in existing control and monitoring system of 33KV/11KV switch gears and equipments , field sensors , transducers , limit switches and wiring, UPS having capacity of 02 KVA with 1 hour Battery backupfor complete control, monitoring and data logging ofSub-Stations along along with ADSS , FO cable link 15 kM with accesories on existiing poles between Thalout substationand Nagwain Substation , with substatation survelliance system including IP cameras and NVR, I P phones etc.
197New 11KV HT Line
198Support for 11 KV overhead line as per technical specification, approved drawings and scope of work
19911.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-56
200RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
201Pre-fabricated steel items like V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, mounting structure , angle iron for road crossings etc made of MS Channels (100x50x6mm), MS angle (65x65x6mm), MS flats (50x6 mm) of given sizes for over head structures as per technical specification, approved drawings and scope of work.
202MS Nuts, Bolts with Washers as per technical specification, approved drawings and scope of work.
203Stay Set (Galvanised) with 50x8 mm stay clamp, stay insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 2 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work.
20411 KV Disc insulator B&S type conformimg to IS-731/1971 all latest version thereof for suspension & tension string ball and socket type having pin ball. The minumum and maximum creepage distance with diameter of insulator- 255 mm & having electromechanical strength 90KN. The insulator shall have W type phosphors bronze security clips for ball socket porcelain conforming IS: 2486-1971 (90KN) complete in all respect. Heavilypolluted atmospheres Creepage distance400 mm
20511 kV Pin Insulator BrownGlazed Porcelain insulator alongwith GI Pin confirming to IS-731/1971 or latest version thereof with minimum and maximum creepage distance distance & duly fitted with lead/zinc thimble suitable for use with GI forged pin having small steel head as per IS:2486 (Part-I & II) of 1993 & latest amendment if any. Moderately polluted atmospheres Creepage distance- 320mm
206HT Earthing set (REC Construction Standard J-1)
2078 SWG GI wire, GI nuts, bolts & washers for earthing and guarding
208ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
2096/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit
21011 kV, 3-ph, 400 A, 3 Pin type, Horizontal/Vertical Mounting type (as desired by DISCOM), Gang Operated, AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
21111 kV, 3-ph, Drop Out fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete as per technical specifications, scope of works and approved drawings
212Danger Plate Size: 250x200x1.6 mm made of mild steel plates 1.6 (minimum) thick vitreous enameled white letter figure, conventional skill and X-Boxes and signal red colour on front side for use in HPSEBL. The rear side of the plate shall be black enameled and conforming to IS specifiction no. IS-1351/1982 suitable for 11KV
213Eye Hook for earth wire
214Galvanised steel barbed wire of 9.8 kg /100metre
215Aluminium Paint for all poles and steel fitting
216Red Oxide
217New 22KV HT Line
218Support for 22KV overhead line as per technical specification, approved drawings and scope of work
21911.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-56
220RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
221Pre-fabricated steel items like V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, transformer mounting structure etc made of MS Channels (100x50x6mm), MS angle (65x65x6mm), MS flats (50x6mm) of given sizes for over head structures as per technical specification, approved drawings and scope of work.
222MS Nuts, Bolts with Washers as per technical specification, approved drawings and scope of work.
223Stay Set (Galvanised) with 50x8 mm stay clamp, stay insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 2 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work.
22422 KV Disc insulator B&S type ( 2 nos. disc)conformimg to IS-731/1971 all latest version thereof for suspension & tension string ball and socket type having pin ball. The minumum and maximum creepage distance with diameter of insulator- 225 mm & having electromechanical strength 90KN. The insulator shall have W type phosphors bronze security clips for ball socket porcelain conforming IS: 2486-1971 (90KN) complete in all respect. Heavily polluted atmospheres Creepage distance400 mm
22522kV Pin Insulator BrownGlazed Porcelain insulator alongwith GI Pin confirming to IS-731/1971 or latest version thereof with minimum and maximum creepage distance distance & duly fitted with lead/zinc thimble suitable for use with GI forged pin having small steel head as per IS:2486 (Part-I & II) of 1993 & latest amendment if any. Moderately polluted atmospheres Creepage Distance- 560mm
226HT Earthing set (REC Construction Standard J-1)
2278 SWG GI wire, GI nuts, bolts & washers for earthing and guarding
228ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
2296/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit
23022 kV, 3-ph, 400 A, 3 Pin type, Horizontal/Vertical Mounting type (as desired by DISCOM), Gang Operated, AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
23122 kV, 3-ph, Drop Out fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete as per technical specifications, scope of works and approved drawings
232Danger Plate Size: 250x200x1.6 mm made of mild steel plates 1.6 (minimum) thick vitreous enameled white letter figure, conventional skill and X-Boxes and signal red colour on front side for use in HPSEBL. The rear side of the plate shall be black enameled and conforming to IS specifiction no. IS-1351/1982 suitable for 22KV
233Eye Hook for earth wire
234Galvanised steel barbed wire of 9.8 kg /100metre
235Aluminium Paint for all poles and steel fitting
236Red Oxide
237Augmentation / Reconductoring of LT Lines -2phase to 3-phasewith 50 Sq. mm Rabbit conductor
238ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
2396/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit
2409.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32
241RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
242Shackle Insulator (16 kN)
243D-Iron (U- Clamps)
244Earth Knob
245LT Stay Set
246Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set)
247Full Clamps 1 No for Stay Set
248Earthing Set complete
249Spool Tie
250Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm F or more(with flat and spring washers)]
251Aluminium Paint
252Spiral PVC Spacer
253Red Oxide
254Augmentation / Reconductoring of LT Lines -2phase to 3-phasewith 50 Sq. mm Rabbit conductor
255ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
2566/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit
2579.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32
258RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
259Shackle Insulator (16 kN)
260D-Iron (U- Clamps)
261Earth Knob
262LT Stay Set
263Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set)
264Full Clamps 1 No for Stay Set
265Earthing Set complete
266Spool Tie
267Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm F or more(with flat and spring washers)]
268Aluminium Paint
269Spiral PVC Spacer
270Red Oxide
271Reconductoring of LT Lines -1 phase 2 wire with 50 Sq. mm Rabbit conductor
272ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
2736/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit
2749.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32
275RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
276Shackle Insulator (16 kN)
277D-Iron (U- Clamps)
278Earth Knob
279LT Stay Set
280Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set)
281Full Clamps 1 No for Stay Set
282Earthing Set complete
283Spool Tie
284Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm F or more(with flat and spring washers)]
285Aluminium Paint
286Spiral PVC Spacer
287Red Oxide
288Reconductoring of LT Lines -3 phase 4 wire with 50 Sq. mm Rabbit conductor
289ACSR Conductors of following sizes with Jointing sleeves, binding materials, PG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification, approved drawings and scope of work
2909.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32
291RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
292Shackle Insulator (16 kN)
293D-Iron (U- Clamps)
294Earth Knob
295LT Stay Set
296Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set)
297Full Clamps 1 No for Stay Set
298Earthing Set complete
299Spool Tie
300Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm F or more(with flat and spring washers)]
301Aluminium Paint
302Spiral PVC Spacer
303Red Oxide
304Cabling of LT line with AB Cable
305LT AB Cable on poles [Size: (3x95 Sq, mm ) {additional 1% sagging & wastage)
306LT AB Cable on poles [Size: (3x95 Sq, mm ) {additional 1% sagging & wastage)
3079.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
308RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
309Pre-fabricated steel items like cross arm,clamps, Knee-Bracings, belts,back clamp etc. made of MS Channels (600x100x50x6mm), MS angle (750x50x50x6mm),MS flats (50x6 mm) of given sizes for over head structures as per technical specification, approved drawings and scope of work and clapmps for hangiing assembles, nut & bolts
310Galvanised Stay Set with anchor plate (200x200x6mm), 50x8mm stay clamp, Stay guy insulator, nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work.
311Full Clamp for stay
312Anchoring Assembly for LT
313Suspension Assembly for LT
314Facade Hooks for LT
315Distribution Boxes
316T-Jointing kit
317LT Earthing set complete (preferbly coil earthing)
318Red Oxide
319Aluminium paint
320IPC
321PVC 2 Core 10 sqmm
322LT ,ABCable3x185 Sq. mm {additional 1% sagging & wastage)
323LT ,AB Cable3x185 + 16+70 Sq. mm
3249.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
325RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
326Pre-fabricated steel items like cross arm,clamps, Knee-Bracings, belts,back clamp etc. made of MS Channels (600x100x50x6mm), MS angle (750x50x50x6mm),MS flats (50x6 mm) of given sizes for over head structures as per technical specification, approved drawings and scope of work and clapmps for hangiing assembles, nut & bolts
327Stay Set (Galvanised) with 50x8 mm stay clamp, stay insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 2 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work.
328Full Clamp for stay
329X-Arm (Horizontal) - MS Channel Iron: 100X50x6, Length [600 mm]
330Half Clamp for Cross Arm
331Anchoring Assembly for LT
332Suspension Assembly for LT
333Facade Hooks for LT
334T-Jointing kit
335LT Earthing set complete (preferbly coil earthing)
336Red Oxide
337Aluminium paint
338Distribution Boxes
339IPC
340PVC 3.5 Core 10 sqmm
341HT ,ABCable 11/ 22 KV3x95+70sqmm Sq. mm {additional 1% sagging & wastage)
34211 kV HT AB Cable on poles [Size: (3x95+70sqmm ) {additional 1% sagging & wastage)
34322 kV HT AB Cable on poles [Size: (3x95+70 Sq, mm ) {additional 1% sagging & wastage)
3449.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
345RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
346Stay Set (Galvanised) with 50x8 mm stay clamp, stay insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 2 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work.
347Pre-fabricated steel items like cross arm,clamps, Knee-Bracings, belts,back clamp etc. made of MS Channels (600x100x50x6mm)as per technical specification, approved drawings and scope of work.
348Anchoring Assembly for HT
349Suspension Assembly for HT
350Facade Hooks for HT
351Heat Shrinkable Straight Through Jointing Kit suitable for 11 kV Cable Size (3x95)
352Heat Shrinkable Straight Through Jointing Kit suitable for 22 kV Cable Size (3x95)
353Cable Termination kit suitable for 11 kV Cable Size (3x95)
354Cable Termination kit suitable for 22 kV Cable Size (3x95)
355HT Earthing set complete (preferbly coil earthing)
356Red Oxide
357Aluminium paint
358HT 22/11KV XLPECable3x120 Sq. mm {additional 1% sagging & wastage)
359HT XLPECable11 kv on poles [Size: (3x120 Sq, mm ) {additional 1% sagging & wastage)
360HT XLPECable22 kv on poles [Size: (3x120 Sq, mm ) {additional 1% sagging & wastage)
3619.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
362RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
363Stay Set (Galvanised) with 50x8 mm stay clamp, stay insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 2 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work.
364Pre-fabricated steel items like cross arm,clamps, Knee-Bracings, belts,back clamp etc. made of MS Channels (600x100x50x6mm), MS angle (750x50x50x6mm),MS flats (50x6 mm) of given sizes for over head structures as per technical specification, approved drawings and scope of work and clapmps for hangiing assembles, nut & bolts
365Heat Shrinkable Straight Through Jointing Kit 11 kv
366Heat Shrinkable Straight Through Jointing Kit 22 kv
367Cable Termination kit 11 Kv
368Cable Termination kit 22 Kv
369HT Earthing set complete (preferbly coil earthing)
370Aluminium paint
371Steel Rope of suitable size for holding of XLPE Cable 3x120 sqmmalongwithfixing clampsand allied material.
372HT AB Cable on poles [Size: (3x120 +95 Sq, mm ) {additional 1% sagging & wastage)
37311 kV ABCableSize: (3x120 +95 sqmm.) {additional 1% sagging & wastage)
3749.00 Mtr. Long ISI marked swaged steel tubular pole as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
375RCC pipe (Muff) ISI marked suitable for different sizes of steel poles. 2000 mm in length and 25 mm thick with 250 mm internal dia duly fabricated by using un-galvanized MS wires of 12 SWG rings and 6 mm MS round in vertical direction conforming to ISI 458-1988 or latest version if anyincluding cement concrete filling 1:3:6 (1 cement : 3 sand : 6 aggrigate 20 mm nominal size).
376Stay Set (Galvanised) with 50x8 mm stay clamp, stay insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 2 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work.
377Pre-fabricated steel items like cross arm,clamps, Knee-Bracings, belts,back clamp etc. made of MS Channels (600x100x50x6mm)as per technical specification, approved drawings and scope of work.
378Anchoring Assembly for HT
379Suspension Assembly for HT
380Facade Hooks for HT
381Heat Shrinkable Straight Through Jointing Kit
382Cable Termination kit
383T-Jointing kit
384HT Earthing set complete (preferbly coil earthing)
385Red Oxide
386Aluminium paint
387Erection Part
388Complete Survey ofDivision wise Scope of Work i.e. preliminary, actual surveying profiling and final survey, stacking of materials, camp shifting and Geo tagging of newly constructed assetson GIS Portaletc. complete job
389ED Thalout
390ED Mandi
391ED J/Nagar
392EDS/Ghat
393ED Gohar
394ED Dharampur
395ED Sunder Nagar
396ED Karsog
397New DTR 11/22 kV (HVDS, Feeder Bifurcation, Feeder Segregation and Extension of New HT, DT, LT as per technical specification, approved drawings and scope of work.
398Erection of 10 KVA, 16KVA, 25 KVA, 63 KVA, 100 KVA 11/0.2KV DTR, complete viz digging of pit for poles & earthing (2 No. for pole & 3 no. for earthing), Drilling of holes in X arms & poles Prepration of plateformstructure member CI, AI i.e. X-arm & Knee bracing set, Erection ofDouble Pole Structure, Concreting of RCC Muffs , Erection of plateform, Erection of x-arms, Erection of G.O. Switch, Erection ofDrop-Out Fuse Unit, Erection of Lightning arrestor, Erection of LT Box, ProvidingEarthing connection including G.I.Wire to G.O Switch, Transformer, Lightning arrestor,etc , Erection of 4 Nos. Stay set , Erection of Jumper, Pipe Earthing 3 No. sets , Layingof LT Cable, Barbed wire & painting complete in all respect
399Erection of 250KVA, 400KVA , 630KVA 11/0.433KV DTR, complete viz digging of pit for poles & earthing (2 No. for pole & 3 no. for earthing), Drilling of holes in X arms & poles Prepration of plateformstructure member CI, AI i.e. X-arm & Knee bracing set, Erection ofDouble Pole Structure, Concreting of RCC Muffs , Erection of plateform, Erection of x-arms, Erection of G.O. Switch, Erection ofDrop-Out Fuse Unit, Erection of Lightning arrestor, Erection of LT Box, ProvidingEarthing connection including G.I.Wire to G.O Switch, Transformer, Lightning arrestor,etc , Erection of 4 Nos. Stay set , Erection of Jumper, Pipe Earthing 3 No. sets , Layingof LT Cable, Barbed wire & painting complete in all respect
400New LT Line
4013 Ph 4 Wire Rabbit
402Support for LT overhead Line as per technical specification, approved drawings and scope of work.
403Erection of 3 phase overhead LT line i/c complete in all respect i.e. erction of pole ,stay set earthig , rcc muff, jumpering, earth wire etc (Punching of the poles is stricitly not allowed)
4041 Ph 2 Wire with Rabbit
405Erection of Single phase overhead LT line i/c complete in all respect i.e. erction of pole ,stay set earthig , rcc muff, jumpering, earth wire etc (Punching of the poles is stricitly not allowed)
406Augmentation & Renovation of 11/0.4 kV Distribution Transformer Substation
407Augmentation of Distribution Transformer Substation using new outdoor type, oil immersed, distribution transformer up to and including 630 KVA as per IS1180 (Part-1): 2014 and its amendments 1, 2, 3 and 4, CRGO/Amorphous core, Energy Efficiency Level 1, carrying Bureau of Indian Standard Certificate mark, in following preferred ratings as per detailed scope of work and technical specifications under:
408Dismantling of old 25KVA, 63, KVA DTR a/w LT Box, meter & cableAnd Erection of new 63, 100, KVA DTR a/w LT Box, meter & cable and transportation of Dismantled material from site of work to concerned Divisional store
409Dismantling of old 100, 250KVA, 400KVA DTR a/w LT Box, meter & cableAnd Erection of new 250,400KVA, 630KVA DTR a/w LT Box, meter & cable and transportation of Dismantled material from site of work to concerned Divisional store
410Renovation of DTR substation Earthing as per technical specification, approved drawings and scope of work:
411Revamping of Distribution Transformer substation earthing by using 40 mm dia 3 meter long GI pipe earthing, using 50x6 mm GS flat for earth mat and riser and 25x3mm GS flat for connecting equipment, using 200 kg bentonite powder of substation in normal soil
412Augmentation of DTR substation by new Pre-fabricated galvanised steel items like DC cross arm (100x50x6 mm), back clamps (65x8 mm), pole clamp (65x8 mm), DO mounting channel (75x40x6 mm), transformer mounting channel (100x50x6 mm), transformer clamping set (50x50x6 mm), transformer belting set ( 50x50x6 mm) as per technical specification, approved drawings and scope of work.
413Augmentation of DTR substation by new 9KV, 11 KA Distribution Class Lightening Arrester for DT as per technical specification, approved drawings and scope of work.
414Augmentation of DTR substation by 18 kV, 10 kA Porcelain Station Surge Arrestor/Lightening Arrestorcomplete with accessories for 22 KV system
415Augmentation of DTR substation by new 11 kV, 3-ph, 400 A, 3 Pin type, Vertical Mounting type, Gang Operated,AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
416Augmentation of DTR substation by new22 kV, 3-ph, 400 A, 3 Pin type, Horizontal/Vertical Mounting type (as desired by DISCOM), Gang Operated, AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
41711kV, 200 A, 3-ph Drop Out fuse assembly including insulators and mounting arrangements, jumpering from bus bar, hardware, etc as required as per technical specifications, approved drawings and scope of the works.
41822 kV, 3-ph, Drop Out fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete as per technical specifications, scope of works and approved drawings
419Conversion of existing LT bare conductor line with following arrangements using new areal bunched XLPE cable,tension clamps for dead end, suspension clamps, clamps for neutral, piercing connectors type-I & type-II, 16 mm dia MS nuts & bolts, pole clamps, spring loaded bus bar suitable for single phase and three phase systems etc. as required as per technical specification, approved drawings and scope of work:
420AERIAL BUNCHED XLPE CABLE 3 X 70+50+16 SQ.MM
421Laying, Installtion of Suspension & Tension assembly etc., Sagging of LT AB Cable of size: 3 X 70+50+16 sqmm, jointing and termination kits etc. complete
422Erection of steel tubular pole 9mtr long (Single pole) for LT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms & AB cable fitting, filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
423Erection of Stay Set LT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
424Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
425Erection of LT Distibution box complete
426Augmentation of 33/11 KVFully outdoor type substation
427Erection of 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power Transformer along with transformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on bushing end), isolating link, isolation with insulators}, Vent explosion plug, control wiring between sensing equipment and marshalling box, cable supporting tray on the body of transformer, transformer wheels, LV/HV bushing etc as required as per technical specifications, approved drawings and scope of the work.
4283.15 MVA without tap changer
4296.30 MVA with off load tap changer
430Erection of 33KV gantries structure/super structure andequipment structure for mounting Isolators and post insulators, bas bar, jumper set ,t-sets cross Arm etc.
431Erection of 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker along with 36kV, 1-Phase, 25kA/3 seconds, 200-100/5-5 Amps or 300-150/5-5 Amps 1 Set( 3 nos) outdoor type Current Transformers along with junction box (1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting structures, bi- metallic clamps, permanent maintenance platform, marshalling box etc required as per technical specifications, scope of works and approved drawings
432Erection of 33 kV , 1250A , 25 kA for 3sec Auto reclosure(o/d channel mounted) with built in feederprotections,communicable for remote operation through SCADA system IEC 61850 , 104compatible
433Erection of 33 kV , 1250A , 25 kA for 3sec Auto reclosure (o/d channel mounted) with built in power transformer protections,communicablefor remote operation through SCADA system IEC 61850 , 104 compatible
434Erection of 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other components etc as per approved drawings, specifications and scope of works controlling:
435Erection of 33 kV feeder panel (33 kV Incomer Bus) [Numeric Relay, IEC 61850]
436Erection of Power transformerprotection Panel (with NumericDifferential Relay / REF Relay , IEC 61850)
437Erection of 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), Gang Operated motorised isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per technical specifications, scope of works and approved drawings with out earth switch.
438Erection of 36kV, 1250A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), Gang Operated motorised isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per technical specifications, scope of works and approved drawings with earth switch
439Erection of 30 kV, 10kA, 1-ph Station Class Lightening Arrester with Surge Counter,mounting platform, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware etc as required as per technical specifications, approved drawings and scope of the works.
440Erection of 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware, etc as required as per technical specifications, approved drawings and scope of the works.
441Erection of Indoor type control and relay panel as per technical specifications, approved drawings and scope of works:
442Erection of Indoor type control and relay panel for 11kV, 3phase, 1250 A VCB (Transformer Breaker)consisting of CT 800-400/1-1-1 A, PT 11000/110 V-meter, volt-meter, Relays & accessories complete as per specifications for transformer breaker protection (12 kV, 1250 A, 25KA) [Numeric Relay, IEC 61850]
443Erection ofIndoor type control and relay panel for 11 KV 3 phase, 1250 A VCB (Feeder Breakers) consisting of CT 400-200/1-1-1 A , 11000/110 V -meter, volt-meter, Relays, energy meter (TVM) & accessories complete as per specifications for feeder breaker protection(12 kV, 1250 A, 25KA) [Numeric Relay, IEC 61850]
444Erection of 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breakeralong with 12 kV, 1-Phase, 800-400/1-1-1 , 3 Nos indoor type Current Transformer, indoor mounting type control panel for bus coupler, control cabling between VCB and indoor control panel and required accessories, bi-metallic clamps, A-meter, volt-meter, 3- phase electronic energy meter, Relay & accessories complete as per specifications for bus coupler protection (12 kV, 1250 A, 25KA)(Numeric relay , IEC 61850)
445Erection ofNumerical directional relay for 11 KV feeder Protectionwith IEC 61850 complitant with RJ 45 Port
446Erection ofNumerical Differentialrelay for transformer protection on 11 KV incomer with IEC 61850 compliant with RJ 45 Port
447Erection of 11 kV ,800 A , 25 kA for 3sec Auto reclosure(o/d channel mounted) with built in feederprotections,communcablefor remote operation through SCADA system IEC 61850 , 104 compatible
448Erection of30 V, 100 AH Pb Acid battery, battery stand made of teak wood duly painted with anti rusting paint, battery insulators, inter-battery wiring using 30 sqmm, 1.1 kv, copper single core multi strand cable, terminal connectors, & all other accessories and connectors and 30V, 40 Amp. (or as per State practice) Float-cum-Boost Battery Charger with six wave rectification for 440 V, 3 phase, 50 Hz AC Input Supply as per technical specifications, approved drawings and scope of works
449Erection of 33 & 11 Kv Bus-Bars & Jumpers/Droppers/Terminations including hardware fittings, hardware, T-claimp etc as per technical specifications, approved drawings and scope of works
450Erection of 33 & 11 Kv yard and switch gear Earthing & Grounding conductor etc. as per Approved Electrical Layout for each sub-station as per technical specifications, approved drawings and scope of works with
451Erection of laying dressing and erection of Control cables, power cables including their termination materials like glands, lugs, ferruls etc. as per technical specifications, approved drawings and scope of the work.
452Erection of 11 kV Isolator motorised (12 kV, 630A, 25 kA with Earthswitch outdoor)
453Erection of11.00 Mtr. Long ISI marked swaged steel tubular pole/ joists as per IS: 2713/1980(Part-II) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-56. with earthing and jumper isolator etc of 11 kV bay
454Sub Station Automation System ( SCADA)with necessary hardware and software and any modification/retro-fitting in existing control and monitoring system of 33KV/11KV switch gears and equipments , field sensors , transducers , limit switches and wiring, UPS having capacity of 02 KVA with 1 hour Battery backupfor complete control, monitoring and data logging ofSub-Stations along with substattion survelliance system including IP cameras and NVRI P phones etc. at thalout substationand Sandhole Substation
455Sub Station Automation System ( SCADA)with necessary hardware and software and any modification/retro-fitting in existing control and monitoring system of 33KV/11KV switch gears and equipments , field sensors , transducers , limit switches and wiring, UPS having capacity of 02 KVA with 1 hour Battery backupfor complete control, monitoring and data logging ofSub-Stations along along with ADSS , FO cable link 15 kM with accesories on existiing poles between Thalout substationand Nagwain Substation , with substatation survelliance system including IP cameras and NVR, I P phones etc.
456Dismantling Works
457Dismantling of old power transformers along with associated material from substation to concerned divisional store
4583.15 MVA without tap changer
4596.30 MVA with off load tap changer
460Dismantling of old 33 kV CR&M panels along with associated material and its transportationfrom substation to concerned divisional store
461Dismantling of old 33kVCircuit Breakersalong with associated material and its transportationfrom substation to concerned divisional store
462Dismantling of old 33kVAuto -Reclosers along with associated material and its transportationfrom substation to concerned divisional store
463Dismantling of old 11 kV C&M panels along with associated material and its transportationfrom substation to concerned divisional store
464Dismantling of old 11kVAuto -Reclosers along with associated material and its transportationfrom substation to concerned divisional store
465Dismantling of old 33kVisolatorsalong with associated material and its transportationfrom substation to concerned divisional store
466Dismantling of old 11kVisolatorsalong with associated material and its transportationfrom substation to concerned divisional store
467New 11KV HT Line
468Support for 11 KV overhead line as per technical specification, approved drawings and scope of work
469Erection charges of 11 KV Ht line i/c erction of single and double pole strc, stay set ,earthing, concreting of rcc muff ,jumpering and earth wire complete in all respectsof HT line (Punching of the poles is stricitly not allowed)
470Erection of steel tubular pole 10/11 mtr long for HT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms and fixing of Insulators,kneebracing set, X-bracing set , Filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete in all respect (Punching of the poles is stricitly not allowed)
471Laying, stringing , sagging& binding with Insulator of ACSR rabbit conductor of size6/1/3.35 mm (50mm2) i/c jumpering etc. Complete
472Erection of Stay Set HT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
473Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
474Laying, stringing , sagging& bindingof GI wire 8SWG
475Erection of 11 kV, 3-ph,400 A, 3 Pin type, Vertical Mounting type, Gang Operated,AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
47611kV, 3-ph Drop Out fuse assembly including insulators and mounting arrangements, jumpering from bus bar, hardware, etc as required as per technical specifications, approved drawings and scope of the works.
477New 22KV HT Line
478Support for 22KV overhead line as per technical specification, approved drawings and scope of work
479Erection charges of 22 KV Ht line i/c erction of single and double pole strc, stay set ,earthing, concreting of rcc muff , sagging , stringing, ,jumpering and earth wire complete in all respectsof HT line (Punching of the poles is stricitly not allowed)
480Erection of 11 kV, 3-ph,400 A, 3 Pin type, Vertical Mounting type, Gang Operated,AB Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete as per technical specifications, scope of works and approved drawings
48111kV, 3-ph Drop Out fuse assembly including insulators and mounting arrangements, jumpering from bus bar, hardware, etc as required as per technical specifications, approved drawings and scope of the works.
482Augmentation of LT Lines -1 phase to 3-phasewith 50 Sq. mm Rabbit conductor
483Erection of steel tubular pole 9mtr long (Single pole) for LT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms and Shackle Insulators, Filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
484Laying, stringing , sagging& binding with Insulator of ACSR rabbit conductor of size6/1/3.35 mm (50mm2) i/c jumpering etc. Complete
485Erection of Stay Set LT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
486Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
487Augmentationof LT Lines -2phase to 3-phasewith 50 Sq. mm Rabbit conductor
488Erection of steel tubular pole 9mtr long (Single pole) for LT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms and Shackle Insulators, Filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
489Laying, stringing , sagging& binding with Insulator of ACSR rabbit conductor of size6/1/3.35 mm (50mm2) i/c jumpering etc. Complete
490Erection of Stay Set LT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
491Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
492Reconductoring of LT Lines -1 phase 2 wire with 50 Sq. mm Rabbit conductor
493Erection of steel tubular pole 9mtr long (Single pole) for LT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms and Shackle Insulators, Filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
494Laying, stringing , sagging& binding with Insulator of ACSR rabbit conductor of size6/1/3.35 mm (50mm2) i/c jumpering etc. Complete
495Erection of Stay Set LT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
496Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
497Dismantling of old conductor i/c rolling of conductor , De-stringing& lifting ofall dismantled material from site of work to concerned divisional store ( per Km single wire)
498Reconductoring of LT Lines -3 phase 4 wire with 50 Sq. mm Rabbit conductor
499Erection of steel tubular pole 9mtr long (Single pole) for LT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms and Shackle Insulators, Filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
500Laying, stringing , sagging& binding with Insulator of ACSR rabbit conductor of size6/1/3.35 mm (50mm2) i/c jumpering etc. Complete
501Laying, stringing , sagging& binding with Insulator of ACSR rabbit conductor of size6/1/4.72 mm (100mm2) i/c jumpering etc. Complete
502Erection of Stay Set LT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
503Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
504Dismantling of old conductor i/c rolling of conductor , De-stringing& lifting ofall dismantled material from site of work to concerned divisional store (per Km single wire)
505Cabling of LT line with AB Cable
506Laying, Installtion of Suspension & Tension assembly etc., Sagging of LT AB Cable of size: 3 X 95 sqmm, jointing and termination kits etc. complete
507Erection of steel tubular pole 9mtr long (Single pole) for LT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms & AB cable fitting, filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
508Erection of Stay Set LT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
509Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
510Erection of LT Distibution box complete
511Erection of IPC
512Erection of PVC 3.5 Core 16 sqmm
513LT ,ABCable3x185 Sq. mm {additional 1% sagging & wastage)
514Laying, Installtion of Suspension & Tension assembly etc., Sagging of LT AB Cable of size:3x185 Sq. mm, jointing and termination kits etc. complete
515Erection of steel tubular pole 9mtr long (Single pole) for LT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms & AB cable fitting, filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
516Erection of Stay Set LT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
517Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
518Erection of LT Distibution box complete
519Erection of IPC
520Erection of PVC 3.5 Core 16 sqmm
521HT ,ABCable3x95+70 Sq. mm {additional 1% sagging & wastage)
522Laying, Installationof Suspension & Tension assembly etc., Sagging of 11 kV HT ,ABCable3x95+70 Sq. mm, jointing and termination kits etc. complete
523Laying, InstalHTion of Suspension & Tension assembly etc., Sagging of 22 kV HT ,ABCable3x95+70 Sq. mm, jointing and termination kits etc. complete
524Erection of steel tubular pole 9mtr long for HT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms & AB cable fitting, filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
525Erection of Stay Set HT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
526Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
527HT XLPECable3x120 Sq. mm {additional 1% sagging & wastage)
528Laying, installationof Suspension & Tension assembly etc., Sagging of HT XLPECable3x120 Sq. mm, jointing and termination kits etc. complete
529Erection of steel tubular pole 9mtr long for HT Line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms & XLPEcable fitting, filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
530Erection of Stay Set HT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
531Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
532Erection of Steel Ropefor holding of XLPE Cable 3x120 sqmmalongwithfixing clampsand allied material.
533HT AB Cable on poles [Size: (3x120 +95 Sq, mm ){additional 1% sagging & wastage)
534Laying, Installation of Suspension & Tension assembly etc., Sagging of 11 kV HT ,ABCable (3x120 +95Sq. mm), jointing and termination kits etc. complete
535Erection of steel tubular pole 9mtr long for HT line viz digging of pit, Drilling of holes in X-arms, Erection of pole, Erection of X-arms & AB cable fitting, filling of pit & ramming , painting of pole & filling of concrete in RCC muffcomplete (Punching of the poles is stricitly not allowed)
536Erection of Stay Set HT (Digging of pit, fixing of stay rod, filling of pit , nozzeling & tighting)
537Erection of Earthing set (Digging of pit, fixing of GI wire to the earth system & filling of pit)
538CIVIL WORKS
539Construction ofFoundation for 6.30MVA Sub-Station,33/11KV Power transformer, Baffle wall ,R.S. Joist foundation,VCB foundation, CT/PT, oil sump, Cable trenches, Screening and spreading stone shingle on PCC and Foundation & fencing for 250 to 630KVA DTRs. etc.
540Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil.
541Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge.:-Hard rock (blasting prohibited)
542Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:3:6 (1 Cement : 3 coarse sand): 6 graded stone aggregate 40 mm nominal size)
543Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand) : 8 graded stone aggregate 40 mm nominal size)
544Centering and shuttering including strutting, propping etc. and removal of form for:
545Foundations, footings, bases of columns, etc. for mass concrete.
546Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
547Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level 1:1.5:3 (1 cement : 1.5 coarse sand): 3 graded stone aggregate 20 mm nominal size)
548Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement 1:1.5:3 (1 cement : 1.5 coarse sand) : 3 graded stone aggregate 20 mm nominal size)
549Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more.
550Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
551Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm.
552Supplying, filling, spreading & leveling gravels of approved size in required thickness, for all leads & lifts, all complete as per direction of Engineer-incharge.
553Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:1½:3 (1 Cement: 1½ coarse sand) : 3 graded stone aggregate 20 mm nominal size)
554Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia 4 mm
555Providing and fixing ISI marked M.S. pressed butt hinges bright finished with necessary screws etc. complete :100x58x1.90 mm
556Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete :250x16 mm
557Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes for weep holes in fire protection wall complete in all respect.75 mm diameter.
558Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:- 1:5:10 (1 cement : 5 coarse sand: 10 graded stone aggregate 40 mm nominal size)
559Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail