Indian Institute Of Science Education And Research-IISER has published Supply, Installation, Testing And Commissioning Of 22.0 Tr Capacity Vrf Unit At Dcs Instrument Room ( W024 ) . Submission Date for this Tender is 04-10-2022. Air Conditioner Tenders in kolkata West Bengal. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 27-Sep-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 04-10-2022 |
Sl. No. | Item Description |
1 | Supply, Installation, Testing and commissioning of following capacityall Inverter based control VRFtype air-conditioning comprising of Rotary/scroll compressors in single /multiple configuration. The outdoor unit shall be designed to workon variable refrigerant circulation depending on the actual load sensing. The variable capacity compressors shall be of inverter control. The condenser fins shall be coated with anti corrosive material for longer life. The unit shall have oil arrestor to prevent oil migration, Suction accumulator shall be provided to balance variable refrigerant circulation. The unit shall be capable of cooling as well as Heating ( Heat pump ). The unit shallalso meet CPCB norms on noise and Air pollution levels etc., as required. (i) The system shall operate with only two pipes i.e., suction and liquid line that can be connected to multiple indoor units. The intelligent microprocessor based control system shall maintain the communication between indoor and outdoor units to operate the compressors in most efficient way and to keep the equal running time for constant speed compressors. The unit shall work with only R 410A refrigerant gasand suitable for 3 phase, 380 V+ /- 10%, 50 Hz AC power supply. (ii) The prices should include lifting, shifting and positioning of outdoor units. The unit shall be factory charged gas and oil required for first charge should be included in the individual price quoted below. Makes - LG/ Samsung/ Daikin/ Toshiba / Mitsubishi electric / Hitachi/ Midea / Carrier Midea |
2 | ODU- 14 HP(CKT 1) |
3 | INDOOR UNITS ( EVAPORATIVE UNIT): Supply, Installation, Testing and Commissioning of indoor units complete with blower, compact cooling coil, electronic expansion valve, multi speed fan motor, dynamically balanced blowers, air filter of efficiency 80% down to 20 microns, insulated drain pan & drain pump ( drain pump not required in Hi wall). Cassette units to have provision for Fresh Air Intake & decorative panel. Indoor units should have wireless / corded Remote Controller as a standard accessory. (Hi walls /Cassette to have wireless remotes and ductable units - ceiling suspended unit above false ceiling to have corded remorts and if Wireless then remote unit shall be along with IR receiver Kit including 3 x 1.5 Sq mm round flexible copper cable (up to 3.0 meters) including connection, etc as required). The Scope shall include necessary batteries and the unit shall be suitable for operation on single phase AC supply. 4-Way Cassette type Indoor Units with Cordless Remotes. |
4 | Cassette Capacity : 4 TR |
5 | Cassette Capacity : 2 TR |
6 | Supply,Installation,TestingandCommissioningofrefrigerant flow distribution y branches/ REFNUTS complete with nitrile rubber insulation in the suction & liquid lines for various sizes of copper refrigerant piping. |
7 | Copper Refrigerant Piping with Nitrile Rubber Insulation for VRF/VRV Units |
8 | Rigid PVC Drain Piping with Nitrile Rubber Insulation |
9 | Communication Cabling between Outdoor Unit & Indoor Units |
10 | Outdoor Unit Stand with Anti Vibration Pads (rate can be provided after site inspection) |
11 | Pressure testing, vaccumising and supply and charging of additional gas because of pipe length as required. |
12 | ELECTRICAL WORK: Supply and fixing of electrical panel:Panel made of CRCA of 2mm thickness, double door, floor mounted, front hinge opening, indoor type, locking arrangement, rubber lining, epoxy polyester powder coating ,IP 54 Protection, Bus bar made of ETP copper bar suitable for 200 A Pre wired. R-Y-B phase indicator lamp, Two sided panel earthing provision, separate compartment for Incoming and outgoing, brass compression gland, PVC insulated 1.1 KV grade copper conductor,pin or ring type aluminium sockets for cabling. 1. Incomer- 1 no. 200 A MCCB, 4 Pole, 415 Volt, 3 ph, 50 Hz, C curve, thermal magnetic release. 2. Out comer-3 nos. 63A 4P MCB,C curve and 6 nos. 20A DP MCB, C curve MCB and MCCB (Makes: L&T/ Siemens/ ABB/ Havells/ Schneider) |
13 | Supply and fixing of one numberPVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required (clamped with 1mm thick saddle) (Make : Havells/Finolex/Polycab etc.) |
14 | 3.5 Core 35.0 Sq.mm. Armoured Aluminium Cable |
15 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
16 | 3½ X 35 sq. mm (32mm) |