| 1 | SITC 500 DG Set with AMF PanelSupply, installation Commesioning of silent type DG set 500 KVA 3 Phase 415 Volt,Diesel Engine Liquid Cooled, electric start developing required B.H.P. at 1500 rpm suitable for alternator output at 0.8PF. The Diesel Engine should be capable of providing 10 % overload, alternator mounted on common base frame complete with inbuilt fuel tank, Residential silencer, sound proof (Acoustic) enclosure 18 gaugeas per CPCB rules. specifications, battery with leads, first fill of lub oil & Coolant, safeties,on a common Base frame along with other accessories including foundation Make:- Caterpillar, Cummins/ Sudhir, Kirloskar, Greaves. (As per specification on DNIT Page No. 26-30) |
| 2 | SITC Commissioning of Transformer 500 KVASupply, installation Commesioning of Transformer 500 KVA IS 1180 level -1,ONAN type cooling, 3 phase, frequency 50 Hz, Voltage HV/LV 11/0.433KV, On load tap changer includingRCC foundation Make:- Kirloskar, Cromption, ABB, Sudhir.(As per specification on DNIT page No. 31) |
| 3 | Electrical Work (AS per specification on DNIT page No. 32-37)Supply & erection of Vacuum Circuit Breaker (VCB) attached with existing panel including all types of works , 11 KV cubical panel of Crompton Greaves make 11KV 800A 26.3kA Indoor Air Insulated OG VCB Panel with Aluminium Bus Bar, OC/EF Relay, CT, PT, Necessary indications Complete in all respects makeCrompton Greaves only. |
| 4 | Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-Overall size 300sq.mm (3½ Core) Unarmoured (Loose) CSR 34.10 A XXXI (1340.00 + 25% = Rs.1675.00) |
| 5 | Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-Overall size 300sq.mm (3½ Core) Unarmoured (Loose) CSR 34.10 D XXXI ( 1029.00 + 25% = Rs.1286.25) |
| 6 | Supply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanized steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be laid 1.50 meter below ground level including excavation, sand cushioning, covering with sand & First class bricks and back filling the trench etc., of the required size HT Cable Overall size 50sq.mm (3Core) 34.36 A II (799 + 10% = 878.90) |
| 7 | Supply and erectionof Heat shrinkable cable end termination/ Straight through joint kit for 11 KVA /6.6 KV (E) XLPE Cables as approved & desired by Enginer in chargeHeat Shrinkable End Termination for cable size 50-95 sq. mm, 3Core (Outdoor Type)34.36 C VI (2457+ 40 % = 3439.80) |
| 8 | Supply and erection of XLPE/ PVC insulated PVC sheathed (10 core) unarmoured copper conductor cable (ISI marked) confirm to IS:7098 (PART-I), 1988 loose in the existing trench or pipe with suitable size of copper thimbles/ lugs complete in all respect as desired by the Engineer-in-charge Overall size 1.5sq.mm (10 Core) 34.09 XIV a (173 + 30% = Rs.224.90) |
| 9 | Supply and erection of XLPE/ PVC insulated PVC sheathed (10 core) unarmoured copper conductor cable (ISI marked) confirm to IS:7098 (PART-I), 1988 loose in the existing trench or pipe with suitable size of copper thimbles/ lugs complete in all respect as desired by the Engineer-in-charge Overall size 2.5sq.mm (10 Core) 34.09 XIV b (258 + 30% = Rs. 335.40) |
| 10 | Civil WorkEarth work in excavation in foundations trenches etc. in all kinds of soil where Pick-Jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear fromthe edge of excavation and subsequent filling around masonry in 15 cm, layers with compaction including disposal of all surplus soil as directed within lead of 30 metres. |
| 11 | Cement concrete 1:8:16 with 40 mm gauge brick ballast mixing by mechanical means using concrete mixer volumetric type |
| 12 | Reinforced cement concrete M-20 mechanically batch mixed using batch typeconcrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth. |
| 13 | Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering) |
| 14 | Cold twisted detormed (Ribbed/ Tor steel) Bars (Fe 500 grade as per IS 1786-2008) , for R.C.C works, where not including in the complete rate of RCC including bending and binding placing in position complete |
| 15 | Structural steel work in angles, tees, flats, riveted, including cutting, fixing all gusset plates, bolts, nuts, rivets etc. with hoisting and erecting in position. Size 50X50X6 mmSize 50X50X5mm |
| 16 | Supply, fixing in position, testing and commissioning of the following Below ground/Over ground MS class ‘C’ pipes of following diameter cut to required lengths and installed with all welded joints, complete with the necessary fittings like elbows, tees and reducers, sockets etc. excluding valves for Chilled / Hot water lines but including insulation as per specifications.100 mm dia MS pipes |