| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 10-10-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 17-10-2022 |
| 2 | 30-09-2022 | CERTAIN CHANGES IN BOQ AND TENDER DOCUMENTS | BOQ | 10-10-2022 |
| Sl. No. | Item Description |
| 1 | Taking down carefully existing copper point wiring (light,fan, socket or power) complete including fixture and fittings such as switches, bellpushes, ceiling roses, pendents, regulators, sockets, light fitting, callbells etc removiing materials to store for keeping in safe custody or for taking credit(credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc. to match existing complete all as specified and directed |
| 2 | M & L forPoint wiring with multi-stranded copper conductor, single core FRLSH, PVC insulated and unsheathed cable, including PVC insulated unsheathed multistranded copper conductor single core FRLSH cable as earth continuity conductor to common earth and connected to earth dolly, GI terminal boxes, modular frame & cover plate (suitable for modular switch/sockets). |
| 3 | Comprising the followingOne light point controlled by one switch or one fan point controlled by one switch & fan regulator etc. with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid 20mm PVC medium duty concealed conduit complete all as specified and directed |
| 4 | All as per item No. 2.00 above but One Socket outlet 3 pin, 6 Amp, on the same board, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, complete all as specified and directed |
| 5 | All as per item No. 2.00 above but One Socket outlet 3 pin, 6 Amp, independent, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid 20mm PVC medium duty concealed conduit complete all as specified and directed |
| 6 | All as per item No. 2.00 above but One socket outlet 3 pin, 5/15 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid 20mm PVC medium duty concealed conduit complete all as specified and directed |
| 7 | All as per item No. 2.00 above but One Bell/Buzzer point controlled by one push button with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid 20mm PVC heavy duty concealed conduit complete all as specified and directed |
| 8 | All as per item No. 2.00 above but One light point controlled by two, 2 way switches with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid 20mm PVC medium duty concealed conduit complete all as specified and directed |
| 9 | S&F Switch modular type, single pole, one way, 6 Amp, one module, complete complete all as specified and directed |
| 10 | S&F Switch modular type, single pole, one way, 16 Amp,one module, complete complete all as specified and directed |
| 11 | S&F Switch modular type, single pole, two way, 6 Amp, one module, complete complete all as specified and directed |
| 12 | S&F Bell push switch, modular type, single pole, one way, 6 Amp, one module, complete complete all as specified and directed |
| 13 | S&F Socket outlet modular type, multipurpose, 2/3 pin, single pole one way, 6 Amp,two module, complete complete all as specified and directed |
| 14 | S&F Socket outlet modular type, multipurpose, 2/3 pin, single pole one way 6/16 Amp, two module, complete complete all as specified and directed |
| 15 | S&F Fan regulator, modular type, 5 step, high speed, two module complete complete all as specified and directed |
| 16 | M & L for point wiring for one light / fan point controlled by one switch with 1.5 Sqmm (nominal area) PVC insulated, unsheathed multi stranded copper conductor cable FR-LSH in existing conduit, and existing sunken boxes but including3 mm thick phenolic laminated sheet top cover for sunken boxes flush to surfacefor one light point/fan point, controlled by one switch and /or fan regulator including PVC insulated unsheathed 1.5 Sqmm copper conductor cable FR-LSH connected to common earth dolly complete all as specified and directed |
| 17 | AllaspersrlitemNo.16.00(here-in-before) but socket 3 pin, 5 Amp, 230 volt flush type onsame board |
| 18 | AllaspersrlitemNo.16.00(here-in-before) but for one socket point, out let, 3 pin, 5 Amp in independent board. |
| 19 | AllaspersrlitemNo. 16.00(here-in-before) but for call bell point. |
| 20 | AllaspersrlitemNo.16.00(here-in-before) but for one light point controlled by two, two way switch. |
| 21 | AllaspersrlitemNo. 16.00(here-in-before) but for 15 Amp socket out let by using 2.5 Sqmm PVC insulated unsheathed copper conductor cable FR-LSH multi strand on independent boardincluding provn of2.5 Sqmm unsheathed, multi strandedcopper conductor cable FR-LSH continues as earth wire connected to earth dolly etc complete all as specified and directed |
| 22 | S&F Switch piano, flush type, single pole, one way, 5 Ampcomplete all as specified and directed |
| 23 | S&F Switch piano, flush type, single pole, one way, 15 Ampcomplete all as specified and directed |
| 24 | S&F Switch piano, flush type, single pole, two way, 5 Ampcomplete all as specified and directed |
| 25 | S&F bell push 5/6 Amps 230 V ACcomplete all as specified and directed |
| 26 | S&F Socket outlet, 3 pin, 5Amp, flush typecomplete all as specified and directed |
| 27 | S&F Socket outlet, 2 in 1, 3 pin, 5 and 15 Amp flush type complete all as specified |
| 28 | S&F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd.complete all as specified and directed |
| 29 | S&F Ceiling rose, 3 terminal PVC/polycarbonate, suitable for 230 V, AC, 50 Hz supplycomplete all as specified and directed |
| 30 | S&F call bell, ding dong type, AC 230 Vcomplete all as specified and directed. |
| 31 | S&F wall mounted extruded Aluminium/polycarbonate LED batten fixture T8(G13 holder) 1.2 m, including one LED retrofit tube 20(±10%) watt, 1.2 m T8 6500K,efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor and inbuilt driver completecomplete including making connection complete all as specified and directed. |
| 32 | S&F LEDpanel light fitting, recessed mounted, square shaped of size (595x595x65) mm, 36(±10%)watts efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed. |
| 33 | S&F LED street light fitting 35 Watt, 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrossion resistant complete with IP 65/66 protection including fixing with GI/MS bracket made out of suitable size of light grade tube upto 1.2 mtr length bent to shape with 02 sets of MS clamps made out of minimum 3 mm MS flat iron with suitable bolt and nuts complete with making connection complete allas specified and directed |
| 34 | S&F Lamp holder PVC/polycarbonate type with back platecomplete all as specified and directed. |
| 35 | S&F in replacement sub main two single core PVC copper conductor unsheathed wiremulti stranded 6 sqmm along with earth wire 6.0 sqmm copper conductor single core wire connected by common earth in and including medium grade 20mm size concealed conduit complete complete all as specified and directed(Note :- two lengths of 6.0 sqmm cable and one length of 6.0 sqmm earth cable alongwith pvc concealed conduitwill be measured as one running length) |
| 36 | S&F in replacement sub main two single core PVC copper conductor unsheathed wiremulti stranded 6 sqmm along with earth wire 6.0 sqmm copper conductor single core wire connected by common earth inexisting surface/recessed PVC/steel conduit complete complete all as specified and directed(Note :- two lengths of 6.0 sqmm cable and one length of 6.0 sqmm earth cablewill be measured as one running length) |
| 37 | Supplying,laying, jointing & testing, in replacement underground XLPE insulated screen PVC bedded, GI steel strip or wire armoured heavy duty LT electric power cable cross sectional area 10 sqmm 2 core with aluminium conductor, 1100Volts grade, complete all as specified and directed |
| 38 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. N exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft / loose soilcomplete all as specified and directed |
| 39 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm.complete all as specified and directed |
| 40 | Removing excavated surplus soil to a distance n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed |
| 41 | M&L for Sand cushioning in trenches for cables including watering and consolidationcomplete all as specified and directed |
| 42 | M&L for Bricks protection with old size Sub classs B bricks for protection of PVC/XLPE UG cable in trenches with axis perpendicular to cable, laid dry and flat, joining each other with gap between adjacent bricks not exceeding 10mm complete all as specified and directed |
| 43 | M&L for providing cement concrete 1:2:4 type B-1 (20mm graded stone aggregate)in foundation, filling & mass concrete etc. Any work,including demolition of old cement concrete complete all as specified and directed |
| 44 | Supply, laying & testing 50mm bore \"light grade\" galvanised, with all fitting, unions,elbows etc and fixed complete to walls and ceilings or laid in floors including taking down old GI pipecomplete all as specified and directed |
| 45 | M & L for earthing with galvanized steel plate electrode 600 x 600 mm x 6 mm size directly burriedin ground vertically to earth pit not less than 2.25 meter deep below normal ground level with top edge of the earth plate not less than 1.5 m below normal ground level surrounded with coal dust and common salt filling in alternative layers of 15 cm thick eachconnected to and including GI earth wire 4 mm dia by means of nuts, bolts, check nuts & washers etc connecting to earthing test point, main switch board and including 15 mm dia GI pipe light grade for protection of earth lead from earth plate to distribution board and 20 mm dia GI pipe medium grade connected with funnel having wire mess for watering purpose including necessary excavation and earth work, PCC (1:2:4) type B-1 (using stone aggregates)for earthing pit, 10mm thick cast iron cover with angle iron frame all as specified and shown in electrical plate No 3 of SSR Part-I andtesting on completion including replacement of old unserviceable. |
| 46 | S&F in replacement sheet metal encloser single door 2 way SPN 240V ISI marked complete with neutral and earth link and bus bar complete made out of CRCA steel sheet Factory made including blanking plate for unused module complete all as specified and directed |
| 47 | S&F in replacement sheet metal encloser double door 8 way SPN 240V ISI marked complete with neutral and earth link and bus bar complete made out of CRCA steel sheet Factory made including blanking plate for unused module complete all as specified and directed |
| 48 | All as per item No. 47 above, but 04 way, TPN, 415 Vcomplete all as specified and directed. |
| 49 | S&F in replacement single pole and neutral enclosure 240V with a two pin and earth plug and socket complete with one single pole MCB 20Amp complete all as specified and directed |
| 50 | S&F in repair MCB 6-32 Amp, 240V, SP, 10 KA ‘C’ seriescomplete all as specified and directed |
| 51 | S&F in repair MCB 20-32 Amp, 240V, SPN, 10 KA ‘C’ series complete all as specified and directed |
| 52 | S&F in repair MCB, 40 to 100Amp,415V, TPN, 10 KA ‘C’ series complete all as specified and directed |
| 53 | S&F in repair MCCB , four pole, 415V, 63A, 16kAcomplete all as specified and directed |
| 54 | S&F in repair MCCB, four pole, 415V,100A, 16kAcomplete all as specified and directed |
| 55 | M&L for dismentaling and taking down complete solar water heater system of 1000/1100 LPD capacityinstalled at single/double/triple story bldgs,Refixing the same after carrying out following works:-(i) complete cleaning and de-scaling of inlet and out let connections, solar collectors, glasses, hot water tank, cold water tank, make up tank, fittings, fixtures & pipelines etc with suitable chemical agent.(ii) Complete servicing and maintenance (iii) Replacement of unsv spares as deemed necessary such as hot water tank, flat plate collectors, rubber gaskets, nuts, bolts, clamps, flanges etc., repair of minor leakages if any by carrying out minor welding/brazing.(iv)complete testing and to ensure proper functioning & maintaining minimum water temparature i.e.60°C.complete all as specified and directed.Note : (a) Cost of minor spares such as chemical agents, rubber gaskets, nuts, bolts, clamps, flanges etc and minor welding/brazing deemed to be included in the quoted rate.(b) The cost of hot water tank, flat plate collectors shall be paid in respective items from item No. 58 to 63. |
| 56 | All as per item No. 55 here-in-before but of capacity 500 LPDcomplete all as specified and directed |
| 57 | All as per item No. 55 here-in-before but of capacity 300/200/100 LPDcomplete all as specified and directed |
| 58 | Supply only hot water tank of capacity 1000 Ltrs without heat exchanger (Non pressurized) type,inner tank made of SS 304L with inlet, outlet & overflow arrangement & valves, duly insulated with glass wool/rockwool not less than 100mm thick layer & outer metallic body and including sacrificial anode, temperature guage & make-up tank etc. complete all as specified and directed. Note:- The fixing of tank shall be paid under item No. 55 here -in- before. |
| 59 | Supply only hot water tank of capacity 500 Ltrs without heat exchanger (Non pressurized) type, cylindricalshape, inner tank made of SS 304L with inlet, outlet & overflow arrangement & valves, duly insulated with glass wool/rockwool not less than 100mm thick layer & outer metallic body and including manufacturer recommended electrical backup(heating elements & thermostat), sacrificial anode, temperature guage & make-up tank etc. complete all as specified and directed. The electrical back-up system should be thermostatically controlled at 50°C complete all as specified and directed. Note:- The fixing of tank shall be paid under item No. 55 here -in- before |
| 60 | Supply only hot water tank of capacity 200/300 Ltrs without heat exchanger (Non pressurized) type,inner tank made of SS 304L with inlet, outlet & overflow arrangement & valves, duly insulated with glass wool/rockwool not less than 100mm thick layer & outer metallic body and including sacrificial anode, temperature guage & make-up tank etc. complete all as specified and directed.Note:- The fixing of tank shall be paid under item No. 55 here -in- before |
| 61 | Supply only hot water tank of capacity 100 Ltrs without heat exchanger (Non pressurized) type, cylindricalshape, inner tank made of SS 304L with inlet, outlet & overflow arrangement & valves, duly insulated with glass wool/rockwool not less than 100mm thick layer & outer metallic body and with manufacturer recommended electrical backup(heating elements & thermostat), sacrificial anode, temperature guage & make-up tank etc. complete all as specified and directed. The electrical back-up system should be thermostatically controlled at 50°C complete all as specfied. Note:- The fixing of tank shall be paid under item No. 55 here -in- before |
| 62 | Supply only hotwater tank of capacity 100 Ltrs without heat exchanger (Non pressurized) type,inner tank made of SS 304L with inlet, outlet & overflow arrangement & valves, duly insulated with glass wool/rockwool not less than 100mm thick layer & outer metallic body and including sacrificial anode, temperature guage & make-up tank etc. complete all as specified and directed. Note:- The fixing of tank shall be paid under item No. 55 here -in- before |
| 63 | Supply only flat plate collector ISI marked in the standard size of 1860mmx1240mmx100 mm (minimum dimensions) complete in all respects having fabricated aluminium sheet outer frame casing & back plate and toughened radiation glass having exellent solar transmittance, Heat absorbing unit shall be consisting of copper sheet ultrasonic/laser welded to specified nos of copper tubing grid, with selective black chrome or ultra selective sputtered coating, absorber plate must be encased in not less than 50mm resin bonded insulation & aluminum foil for barrier against out-gassing complete with end plates, collars and fixing arrangement with washer/rubber seals connection etc. complete all as specified and directed. Note:- The fixing of flat plate shall be paid under item No. 55 here -in- before |
| 64 | Supply & Installation in repair of1000 Ltrs capacity rotational moulded three layered white in colour, polyethylene water storage tanks (cylindrical, vertical with closed top) hoisted and fixed in position all as specified in SSR Part-I ofincluding inlet /outlet arrangements & other accessories (of approved make ) etc complete all as specified and directed |
| 65 | Supply & Installation in repair of500 Ltrs capacity rotational mouldedthree layered white in colour, polyethylene water storage tanks (cylindrical, vertical with closed top) hoisted and fixed in position all as specified in SSR Part-I ofincluding inlet /outlet arrangements & other accessories (of approved make ) etc complete all as specified and directed |
| 66 | Supply & Installation in repair 300 litresHDPEwater storage tanks Polytuf Three layered white in colour, rotational moulded polyethylene (cylindrical vertical with closed top) , hoisted and fixed in position including inlet /outlet arrangements & other accessories (of approved make ) etc complete all as specified and directed |
| 67 | Supply & Installation in repair 200 litresHDPEwater storage tanks Polytuf Three layered white in colour, rotational moulded polyethylene (cylindrical vertical with closed top) , hoisted and fixed in position including inlet /outlet arrangements & other accessories ( of approved make ) etc complete all as specified and directed |
| 68 | S&F in repair 15mm Ball valves high pressure of PTMT with epoxy coated Aluminium rod & highdensity plastic ball screwed for fixed complete all as specified and directed |
| 69 | S&F in repair 20mm Ball valves high pressure of PTMT with epoxy coated Aluminium rod & highdensity plastic ball screwed for fixed complete complete all as specified and directed |
| 70 | M&L in repair Iron/steel framed work for supporting structure of water tanks, collectors and similar work conforming to Fe-290 Gde-E-165inclusive of one primer coat, one under coat and one finishing coat of approved paint complete all as specified and directed. |
| 71 | Supply, laying & testing 15mm bore\"medium grade\" galvanised, with all fitting, unions, elbows etc and fixed complete to walls and ceilings or laid in floors including taking down old GI pipe complete all as specified and directed |
| 72 | Supply, laying & testing 20mm bore\"medium grade\" galvanised, with all fitting, unions, elbows etc and fixed complete to walls and ceilings or laid in floors including taking down old GI pipe complete all as specified and directed |
| 73 | Supply, laying & testing 25mm bore \"medium grade\" galvanised, with all fitting, unions, elbows etc and fixed complete to walls and ceilings or laid in floors including taking down old GI pipe complete all as specified and directed |
| 74 | Supply and fixing in repair of aluminium cladding with wire mesh and minimum 50mm thick glasswool of 48kg/m3 density for hot water 15mm GI tubing complete with fittings and fixing materials complete all as specified and directed |
| 75 | Supply and fixing in repair of aluminium cladding with wire mesh and minimum 50mm thick glasswool of 48kg/m3 density for hot water 20mm GI tubing complete with fittings and fixing materials complete all as specified and directed |
| 76 | S&F in replacement toughned radiation glass having exellent solar transmittance(minimum 90%), of minimum 4mm sizethick & of standard size as per existing arrangementof solar collector complete complete all as specified and directed |
| 77 | S&F in replacement rubber hose pipe minimum 50mm thick of size 15mm dia between hot water tank & collector complete all as specified and directed |
| 78 | S&F in replacement of temperature gauge range 0 to 100 °C as per existing size complete all as specified and directed |
| 79 | M&L in repair for size 15mm gun metal globe or gate valve with iron wheel head screwed both end for iron pipe complete all as specified and directed. |
| 80 | M&L in repair for size 20mm gun metal globe or gate valve with iron wheel head screwed both end for iron pipe complete all as specified and directed. |
| 81 | M&L in repair for size 25mm gun metal globe or gate valve with iron wheel head screwed both end for iron pipe complete all as specified and directed. |
| 82 | S&F in repair 15mm size,Bib taps cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixedcomplete all as specified and directed |
| 83 | S&F in repair 20mm size,Bib taps cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified |
| 84 | S&F in replacement heating element 5.0 KW 230V AC, 50 cycle, triangular / round type ISI marked complete with rubber gasketfor hot water tank electrical back up system complete all as specified & directed |
| 85 | S&F in replacement heating element 3.0 KW 230V AC, 50 cycle, triangular / round type ISI marked complete with rubber gasketfor hot water tank electrical back up system complete all as specified & directed |
| 86 | S&F in replacement thermostat ISI marked stem type 240 Volts, AC supply temp range at least 30 to 75 degree C for geyser/solar water heater system complete all as specified and directed |
| 87 | S&F in repair Switch modular type single pole, one way, 6 Amp, one module, complete complete all as specified and directed |
| 88 | S&F in repair Switch modular type single pole one way, 16 Amp,one module, complete complete all as specified and directed |
| 89 | S&F in repair Socket outlet modular type, multipurpose, 2/3 pin, single pole one way, 6 Amp,two module, complete complete all as specified and directed |
| 90 | S&F in repair Socket outlet modular type multipurpose 2/3 pin single pole one way 6/16 Amp, two module, complete complete all as specified and directed |
| 91 | S&F in repair Fan regulator, modular type, 5 step, high speed, two module complete complete all as specified and directed |
| 92 | S&F in repair wall mounted extruded Aluminium/polycarbonate LED batten fixture T8(G13 holder) 1.2 m, compatible with existing T8 retrofit tube complete including making connection complete all as specified and directed. |
| 93 | S&F in repair retrofit LED tubelight 20(±10%) watt compatible with existing batten fixture, 1.2 m T8 6500K,efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor and inbuilt driver complete all as specified and directed. |
| 94 | S&F in repair LED street light fitting 35 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrossion resistant complete with IP 65/66 protection including fixing with GI/MS bracket made out of suitable size of light grade tube upto 1.2 mtr length bent to shape with 02 sets of MS clamps made out of minimum 3 mm MS flat iron with suitable bolt and nuts complete with making connection complete allas specified and directed |
| 95 | S&F in repair LED flood light fitting sqaure shape 150 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp, bracket with impact and corrossion resistant complete with IP 65/66 protection with suitable bolt and nuts, fixing at any height upto 15m complete with making connection complete all as specified and directed |
| 96 | S&F in repair wall mounted LED batten fitting 10 (±10%) watt, 6500K,0.6m, efficacy not less than 90 lumen/watt , extruded Aluminium/polycarbonate, PC diffusor and inbuilt driver complete includign making connection complete all as specified and directed. |
| 97 | S&F in repair decorative wall light fixture made of polycarbonate suitable for retrofit 9W LED lamp(base B-22) complete with PC diffusor & including one 9W LED lamp(base B-22), 6500K, not less than 90 lumen/watt efficacy including making connection complete all as specified and directed. |
| 98 | S&F in repair surface mounted round shape 6 watt 220V AC surfce type with high efficiency PMMA diffusor soft glare free light complete with drivers, holders, LED lamps suitable for roof ceiling inlcluding making connection complete all specified and directed |
| 99 | S&F in repair LEDdownlighter/spot light fitting, recessed mounted, round shaped of ceiling cut outf90mm, 03watts efficacy not less than 90 lumen/watt, 6500K extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed. |
| 100 | S&F in repair LEDdownlighter/spot light fitting, recessed mounted, round shaped of ceiling cut outf160mm, 12watts efficacy not less than 90 lumen/watt, 6500K extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed. |
| 101 | S&F in repair LEDlandscape/bollard light fitting, round shaped of 0.6m pole size, 8/10watts, efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, IP65, PC diffusor, module and inbuilt driver complete including making connection & fixing of pole base with nut and bolt to PCC pedestal/coping complete all as specified and directed. |
| 102 | S&F in repair LEDpanel light fitting, recessed mounted, square shaped of size (595x595x65)mm, 36(±10%)watts efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed. |
| 103 | S&F in repair LEDpanel light fitting, surface mounted, square shaped of size (600x600x70) mm, 34(±10%)watts efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed. |
| 104 | S&F in repair LEDpanel light fitting, recessed mounted, rectangle shaped of size (1195x295x70) mm, 36(±10%)watts efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed. |
| 105 | S&F in repair post top lantern LED type 20 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistance complete with driver and lamp complete all as specified and directed |
| 106 | Taking down unsv ceiling fan/exhaust fan, sealing cable end dismentaing blades and removing fan and blades to E/M store complete all as specified and directed. |
| 107 | Hanging only ceiling fan and connecting up incluidng provision of cable from ceiling rose or connector to fan complete all as specified and directed.Note: Ceiling Fans shall be provided by the E/M store free for fixing only. |
| 108 | Fixing only exhaust fan and connecting up including provision of cable from ceiling rose/connector to fan complete all as specified and directed. Note: Exhaust fan shall be provided by the E/M store free for fixing only. |
| 109 | S&F in repair rigid non-metallic PVC conduit external dia 20mm in size exclusive of boxes(junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.complete all as specified and directed. |
| 110 | S&F in repair PVC junction boxes(1 to 4 way) complete all as specified and directed. |
| 111 | Supplying and fixing in replacement 1100volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 6sqmm complete all as specified |
| 112 | Supplying and fixing in replacement mild steel Make up tank5 Ltrs capacity synthetic painted with single coat of primer as per approved dimension matched with ground sample complete all as specified and directed. |
| 113 | Supplying and fixing in replacement PVC/PS/HDPE cable junction box of size 100mmx100mmx60mm complete with terminals 5 pole, IP 65 protectedcomplete all as specified and directed |
| 114 | Labour only for attending door to door, ARMAAN, & user complaints to carryout inspection, cleaning & normal servicing of solar water heating system at various location for faulty connections and making solar water heating system serviceable after testing complete all as specified and directed.Note: 1. Cost of minor spares such as rubber gaskets, nuts, bolts, clamps, flanges etc and minor welding/brazing deemed to be included in the quoted rate.2. Proper record & document to be maintained for each complaint/inspection duly signed by user, cost incurred on this deemed to be included in the quoted rate. |
| 115 | Supplying and fixed in replacement metal halide lamp 150w double ended complete all as specified and directed. |
| 116 | Supplying and fixed in replacement metal halide lamp 150w single ended threaded complete all as specified and directed. |
| 117 | Supplying and fixed in replacement LED 9watt 2pin, G24, 6500K, efficacy not less than 90 Lm/watt complete all as specified and directed. |
| 118 | Supplying and fixed in replacement LED 9watt landscape light fitting complete with die cast aluminium hoising, driver, IP 65, waterproof, with reflector, multicolor complete all as specified and directed. |
| 119 | Supplying and fixed in replacement LED 7watt bass B22, 6500K, efficacy not less than 90Lm/watt complete all as specified and directed. |
| 120 | Supplying and fixed in replacement halogen lamp 1000w double endedcomplete all as specified and directed. |
| 121 | Supplying and fixed in replacement 1000w halogen bipin T-11 lamp for stage lightening complete all as specified and directed. |
| 122 | Note:- Net contract sum shall be calculated after deduction of Sch. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy