| 1 | Total amount of Sch \"A\" Part-I(Building Work) Note 1 :- This schedule is not pre-priced by MES and the rate indicated as \"Rs. 0.00\" under column 5 signifies this fact only. |
| 2 | Design, prepare structural drawing, fabrication, supply, transportation and erection of prefabricated shelters (PEB Structure), single storied building(03 m clear height atwall edges and 3.325mclear height at ridge inthe centre) as per drawing No CWE/DIN/PREFAB/01/2019 dated 26 Nov 2019 including footings, floorings, sanitary blocks and fittings, water tanks, paintings, anchor bolt, base plate, all structural steel items, roofing and wall cladding with 50 mm thick polyurethane sandwich panel made of galvalume sheet, gutters, flashings, rainwater pipes. The design and drawing shall be vetted from any IITs/NITs/Government Engineering College, complete as per specifications given in tender documents as directed by GE. |
| 3 | NOTE: Schedule ‘A’ Part IIto VIII are Prepriced by MES the rate indicated under column 5 signifies this fact only. |
| 4 | Lump sum price worked out by the tenderer for Excavation and Earth works as listed in Schedule ‘A’ Part-II |
| 5 | Lump sum price worked out by the tenderer for Internal Electrification as listed in Schedule ‘A’ Part-III |
| 6 | Lump sum price worked out by the tenderer for Internal Water Supply as listed in Schedule ‘A’ Part-IV |
| 7 | Lump sum price worked out by the tenderer for Road, Path and Culvert as listed in Schedule ‘A’ Part-V |
| 8 | Lump sum price worked out by the tenderer for Sewage Disposal as listed in Schedule ‘A’ Part-VI |
| 9 | Lump sum price worked out by the tenderer for External Water Supply as listed in Schedule ‘A’ Part-VII |
| 10 | Lump sum price worked out by the tenderer for External Electrification as listed in Sch \"A\" Part VIII |
| 11 | SCH \"A PART IX(Miscellaneous B/R and E/M works)Note 1 :- This schedule is not pre-priced by MES and the rate indicated as \"Rs. 0.00\" under column 5 signifies this fact only. |
| 12 | Bringing approved earth from surfaces outside defence land including all cost such as royalty if any transportation, taxes, etc for area filling/forming embankment, earth required for the item shall be supplied by contractor from out side MOD land as approved by GE of any lead at own arrangement, as per para 3.6 of SSR2020-part II, complete all as specified and directed. |
| 13 | Supply and fixing BLDC base technology ceiling fan 1200 mm, RPM 370, Air delivery 220 CMM, 26 Watt, with remote control and white colour ceiling fan including fixing arrangement of any type including taking down of existing ceiling fans and deposited to MES store yard. Make : Havells- Efficiencia Neo, BLDC 5 star or equivalent make as given in Appx B all as specified and directed by Engineer-in-charge. |
| 14 | M & L for bracket made out of GI pipe 25 mm dia medium grade, 1.5 metre long bent to shape with MS flat iron clamps made out of 40 mm X 6 mm thick mild steel nuts, bolts complete all as directed by Engineer-in-charge including taking down old unserviceable. |
| 15 | S & F batten including tube light 9W, Polycarbonate housing LED, ofLED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 140 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 910, lumen efficacy of minimum 100 lumens per watt, integral electronic driver (SMPS based constant current output) with output short circuit protection, over voltage protection, surge voltage protection upto 2 KVs, CRI greater than 80%, THD less than 20%, CW available CCT of 4000K, power factor of minimum 0.95, life span of minimum 50000 working hours as per catalogue No. LUMILINEBS9WLED840SPCWH of Havells or equivalent of Make mentioned under Appendix \"B\" complete all as specified and as directed. |
| 16 | S & F LED street lights nominal power 25 Watt LED, of LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen efficacy of minimum 100 lumens per watt, lumen output of minimum 4500, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 70%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with epoxy powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hours as per catalogue No. ENDURAPEARLSL25WLED757SASYTOPC of Havells or equivalent of Make mentioned under Appendix \"B\" including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 complete all as specified and as directed. |
| 17 | S & F batten including tube light 20W, Polycarbonate housing LED ,ofLED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 140 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 1910, lumen efficacy of minimum 95 lumens per watt, integral electronic driver (SMPS based constant current output) with output short circuit protection, over voltage protection, surge voltage protection upto 2 KVs, CRI greater than 80%, THD less than 20%, CW available CCT of 4000K, power factor of minimum 0.95, life span of minimum 50000 working hours as per catalogue No. LUMILINEBS20WLED840SPCWH of Havells or equivalent of Make mentioned under Appendix \"B\" complete all as specified and as directed. |
| 18 | S & F vertical distribution board multi phase, double door, 4 way including MCCB (rated current(In): 63A, ultimate short circuit breaking capacity (Icu): 10 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, fixed thermal and fixed magnetic setting, four pole, suitable for 415 V, 50 Hz AC) as incoming and MCB (single pole (SP), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 6A to 32 A, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20) as outgoing complete all as specified and as directed. |
| 19 | S & F health faucet with jet spray, 1.5 metre long, cast copper alloy, nickel chromium plated finish, 15 mm bore, 100 mm long with 1.5 metre long stainless steel shower hose and mounting device attached to wall complete all as specified and as directed by Engineer-in-Charge. |
| 20 | M & L for construction of new valve chamber of size 900 mm X 900 mm X 900 mm including necessary earth work in any type of soil, PCC foundation M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate as in base concrete, brick work (one and half brick thick) in CM 1:6 with 20 mm thick cement plaster internally and externally in two coats of (12 mm and 8 mm) in cement mortar 1:4, 3 mm thick mild steel cover of structural steel of grade E165 as per IS 15911: 2010 riveted with angle iron (50 mm X 50 mm X 6 mm) frame of structural steel of grade E165 as per IS 15911: 2010, frame welded to base plate of size 150 mm X 12 mm and made of structural steel of grade E165 as per IS 15911: 2010, base plate fixed with 200 mm thick PCC coping in M15(Nominal Mix) using 20 mm nominal size graded crushed stone aggregate 50 mm X 50 mm X 6 mm mild steel washer, PCC benching 200 mm thick in M15(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate with necessary, welding, riveting, bolting including painting exposed steel surfaces with two coats of bituminous paint and embedded surfaces of steel with two coats of tar, finishing exposed faces of concrete surfaces and plaster surfaces with three coats of white wash as per drawing No. TD/EM/6 sheet Nos 1/2 & 2/2 of HQ CE Shillong Zone complete all as specified and as directed. |
| 21 | M & L for auguring under road, pavement, hard standing, railway lines by trenchless technology using latest boring technique and necessary machine for insertion of GI pipe of 50 mm and 40 mm nominal bore complete all as specified and as directed. |
| 22 | S & F LED flood lights nominal power 200 Watt LED, of LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 22000, lumen efficacy of minimum 110 lumens per watt, built-in, isolated electronic LED driver (SMPS based constant current supply) with lower THD, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 5 KVs, protection grade IP 65, CRI greater than 70%, beam angle of 50? clear, THD below or less than 10%, CW available CCT of 5700K ± 300K, power factor of minimum 0.95, integral high pressure die-cast aluminium housing with epoxy powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hours as per product code 169929 and catalogue reference BJFL 200W LED I of Bajaj or equivalent of Make mentioned under Appendix \"B\" with and including fixing at any height on building using 1.5 metre medium grade galvanized iron pipe bracket made of 32 mm nominal bore and necessary nuts, bolts, clamps and concreting and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 2.5 sqmm as per IS 694: 2010 complete all as specified and as directed. |