Electrical Repairing And Maintenance Work At Govt. Non Residence Building Situated At H.Q. District Sawai Madhopur
Tender Value
1 Lakhs
Estimated cost
Bid Submission
21 Sep 2022
0 days left
EMD
2000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
madhopur → Rajasthan
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Electrical Repairing And Maintenance Work At Govt. Non Residence Building Situated At H.Q. District Sawai Madhopur
BOQ
| Sl. No. | Item Description |
| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point as per PWD specification for electrical Works with ISI marked 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade (IS:694)and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit & it\"s all accessories( J.B. , Bends etc.) , round tiles,18 SWG Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / lamp Holder/ 3 pin connector , screws etc, making connections,all as per pre approved by Engineer in charge, testing etc. complete as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessoriesrefer Chapter E - 04, E - 05 & E - 07 . For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 2 | Long point(up to 10 mtr..) |
| 3 | Wiring of 3/5 pin 6 amp. Light plug point as per PWD specification for electrical Works with ISI marked 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV grade (IS:694)and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit & it\"s all accessories( J.B. , Bends etc.) , round tiles, 18 SWG Hot Dipped Galvanized Modular Box with earth terminal, 6 A modularswitch, 3/ 5 pin 6 A modular socket, Modular face plate with grid plate, screws etc,all as per pre approved by Engineer in charge,making connections, testing etc. complete as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessoriesrefer Chapter E - 04, E - 05 & E - 07.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 4 | On board |
| 5 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) vergin material PVC conduit as per PWD specification for electrical Works along with its accessories (IS: 3419 ) as requiredinrecess includingcutting the wall, covering conduit and making good the same as required. All relative and latest acceptance tests reports by any NABL accredited lab for the conduit shall be submitted before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 6 | MMS ( IS:9537 P - III ) PVC conduit |
| 7 | 25 mm |
| 8 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.99% purity copper, class 5 stranding in acc. to IEC 60228 forlower watt loss , oxygen free ( <10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4,, in existingsurface or recessed PVC/ MS conduit/casing capping includingall as per pre approved by Engineer in charge,making connections, etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 9 | 1 x 1.5 sq.mm |
| 10 | 1 x 2.5 sq.mm |
| 11 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 12 | 4 x 10.0 sq.mm |
| 13 | 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. |
| 14 | Supplying and drawing FRLS PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.99% purity copper, class 5 stranding in acc. to IEC 60228. FRLS PVC insulation which provides better fire retardant properties then normal PVC & also emits Low Smoke in case of fire & usetype A insulation PVC, in existing conduit including , all as per pre approved by Engineer in charge,making connections, etc. as required.OEM Must have its own in house NABL lab setup for all testing facilities for wires.For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 15 | 2 x 1.5 sq.mm |
| 16 | Supply & drawing Wiring for sub mains as per PWD specification for electrical Works with ISI marked(IS:694), 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped includingall as per pre approved by Engineer in charge, making connections, as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires.For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 17 | 10.0 sq.mm |
| 18 | Providing & Fixing of ISI marked (IS:1258)6 ampbatten/angle lampholder as per PWD specification for electrical Works,made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 19 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 18 SWG with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 3/5 pin 16 amp. socket outlet (IS:1293) [ as per detailed in respective item in BSR] , making connection , testing , etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 20 | Providing & Fixing ofISI marked (IS:1293) 16 ampunbreakable 3 pin plug top with lamp indicator as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 21 | Providing & Fixing of 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C tripping characteristic as per type of load andsite requirement) 4KV impulse withstand voltage,as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductorline load reversibility, label holding facility , IP 20 contact protection and fitted withexisting distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A ratingincluding making connections, testing etc. as required.. OEM shall have submitNABL / CPRI / ERDA accrediated lab test reportsbefore execution & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 22 | Single pole MCB |
| 23 | 6 A to 32 A rating |
| 24 | Triple pole MCB |
| 25 | 40 A rating |
| 26 | Providing & Fixing of IK 09 rating recessed/surface mounting heavy duty Vertical type sheet steel 1.6 mm thick Distribution board as per PWD specificationfor electrical Works ISI marked conforming to IS-13032 & IS-8623 / conforming to IEC 61439-3 with provision of incomer suitable for MCCB and SP / TP MCB as outgoing ,phosphatised ,powder painted complete with insulated suitable ratingcopper bus bar , neutral link, earth link and din bar, masking sheet,including making internal DB terminations with copper lugs and with detachable gland plate, testing etc. as required complete in all respect.OEM shall have submitNABL / CPRI / ERDA accrediated lab test reportsbefore execution & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 27 | IP 43- Double door with Provision of Incomer MCCB 100 / 125/160 A Rating |
| 28 | 4 Way |
| 29 | S&F following sizesof ISI marked ( IS:14927 P - II ) UPVC casing capping as per PWD specification for electrical Works along with all accessorieslike coupler, inner, outer, elbow, square box, tee, end cap etc. on surfacewithscrews, expansionfasteners , All as per pre approved by Engineer in charge, making connections, testing etc. complete as required. For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 30 | 32 mm x 12 mm |
| 31 | Providing & Fixing of energy efficient direct fit (Retrofit) Polycarbonate /Extruded AlBase Housing & diffuser SMD Mid Power LED tube (with integral driver), on existing fixture. Power Consumption of18W / 20Wsystem lumen efficacy = 110 lm/Watt output, internal surge protection of 2.5 KV ,THD < 15% ,p.f.=0.95,CRI >80 , life time of minimum35000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. |
| 32 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 33 | 4\" ,18/ 20Watt LED Tube Without Batten ( Polycarbonate base) |
| 34 | Providing & Fixing of IP 20 boxmade outfrom 1.2mm thick CRCA sheet steel with depth of minimun 30 mm and finished with powder coating andsuitable for mounting LED tubeincludingside covers, holders , internal wiring to illuminate the single sided connection LED tube. ( Without tube).All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 35 | Suitable for 4\" LED Tube shape fixture 1 X 18/20 W |
| 36 | Providing & Fixing of IP40 LED Recessed / Surface Mounted, Round / Sqaure Non-Dimmable Back lit SMD Mid Power LED Downlight with die-cast aluminum housing & Heat Sink for heat dissipation with UV Stabilized non yellowish Diffuser with internal/ external BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% and in compliance to IEC standards. System Lumen efficacy of = 120 lm / watt, THD < 10 % ,p.f.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. |
| 37 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 38 | Surface Mounting |
| 39 | LED Downlight 18/20W |
| 40 | 4\" ,18/ 20Watt LED Tube Without Batten ( Polycarbonate base) |
| 41 | Providing & Fixing offollowing size mounting grid plates with cover plates as per PWD specification for electrical Works, made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 42 | 3 Module |
| 43 | 12 Module |
| 44 | Providing & Fixing offollowing size hot dip galvanized M.S. box of 18 SWG as per PWD specification for electrical Works, with earthing terminal in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 45 | 3 Module |
| 46 | 10 / 12 module |
| 47 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , minimum width of 1 module switch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 48 | 6 A one way switch |
| 49 | Providing & Fixing of modular type lockable feature socket duly ISI marked (IS :1293) as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , minimum width of 1 module switch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 50 | 6 A3 pin shuttered socket |
| 51 | 16 A6 pin shuttered socket |
| 52 | Providing & Fixing of modular type Step Fan regulator duly ISI marked (IS :11037) as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , minimum width of 1 module switch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 53 | 5 step fan regulator 100 watt 2 Module |
| 54 | Providing & Fixing of ISI marked (IS:2268-1994) single / multi tone electronic call bell as per PWD specification for electrical Works, including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 55 | Providing & Fixing of energy efficient /energy saving IP 20 LED direct retrofit Bulbin existing holder or fixture as required with system lumen efficacy =100 lm/Watt output ,pf 0.95 , CRI >70,minimum life time of minimum25000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. |
| 56 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 57 | 9 Watt |
| 58 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected byPVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack &ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 59 | Supply and Installation of unsheilded/ sheilded Information outlets made of high impact plastic body with ABS, FR Grade with provision for protection against dust in jack/ FP, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact punch termination on reliable copper tin plated Insulation displacement contact, Itcomplied with ANSI/TIA/EIA 568standard. In existing modular/MS Boxes along with necessory connections as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR. |
| 60 | Cat 6A, Sheilded Information Outlet |
| 61 | Labour charges for installation of submersible motor pump set including lowering/ delowering of pipes, cables, accessories etc. in tube-well/ open well complete including T&P, transportation of tripod, chain pulley block & any other material required for this purpose complete in all respect. |
| 62 | Delowering and Lowering |
| 63 | Rewinding of single phase/3phase submersible motor including all necessary material and of the same characteristics as original with required size of super enamelled wire \"E\" class insulation material and testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 64 | From7. 5 HP to 10.0 HP |
| 65 | Providing & Fixing of Fluorscent tube rod in existing fixtures as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 66 | Flourscent powder coated |
| 67 | 36/40 Watts |
| 68 | Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of = 120 lm/Watt ,THD < 10 % , p.f.=0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. |
| 69 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 70 | Suspended Mounting/Surface Moutning |
| 71 | 36W LED light fixture 2\"x2\" with acrylic / prismatic front cover. |
| 72 | Rewinding of Heavy duty Exhaust fan motor including all necessary material,The motor is to be wound taking no. of coils,turns and pitch as it was originally wound with required size super enamelled wire with \"E\" class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 73 | 300/ 380 mm sweep |
| 74 | Providing and Replacement ofball bearing of ceiling/ exhaust fanand refixing the same at suitable location as requiredand as per OEM recommendations. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 75 | P & F aluminiun blade for 20\"\" desert cooler fanas required. |
| 76 | Supplying and Laying ISI marked P.V.C. insulated submersible cable as per PWD specification for electrical Worksconfirming to IS:694 and as per IS 8130 : 2013 of 1.1 kV grade .Wire should be made from99.99% purity copper, class 5 stranding in acc. to IEC 60228 forlower watt loss , oxygen free ( <10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4 including making connection etc. as required.OEM Must have its own in house NABL lab setup for all testing facilities for wires. All as per pre approved by Engineer in charge, making connections.For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 77 | 4.0 Sq.mm 3 core flat / Round |
| 78 | Providing & Fixing of Ballast for existing FTL / CFL fixture as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 79 | High frequency electronic ballast 18/36 watts for FTL |
| 80 | Rewinding of ceiling fan motor (starting and running winding) including all necessary material. The motor is to be wound taking no. of coils, turns and pitch as it was originally wound with required size super enamelled wire with \"E\" class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. (New model ceiling fan) |
| 81 | 900/1200 mm sweep (New model ceiling fan) |
| 82 | Providing and Replacement ofball bearing of ceiling/ exhaust fanand refixing the same at suitable location as requiredand as per OEM recommendations. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 83 | S & F of capacitor of 230V/ 275V, 50Hz rating of plastic casing and terminals -Lugs or copper wire. |
| 84 | Running capacitor |
| 85 | 2.5/3.15 micro farad |
| 86 | 4.0 micro farad |
| 87 | P & Fof ISI marked vertical pump suitable for 20\" desert coolerincluding making connection testing etc. as required. |
| 88 | ISI marked vertical pump |
| 89 | Rewinding of motor of desert cooler fan with super enamelled copper wire, \"E \" class insulation material including removing,refixing,testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 90 | Labour Chargesfor fixing of desert cooler in windows including handling of cooler upto desired location, making electrical/water connections, testing etc. as required. |
| 91 | Ground floor |
| 92 | First floor |
| 93 | SITC of IP 40quick make and quick break4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings as per PWD specification for electrical Works, conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 800 V, provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections with lugs & spreaders,etc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 94 | With Thermal Magnetic release |
| 95 | 160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
AI Tender Summary
Tender Timeline
Sep 15, 2022
11:30 IST
Tender Published
Tender notice published.
CompletedSep 21, 2022
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedSep 23, 2022
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender