Military Engineer Services-MES has published Repair / Maintenance Of Ac Plants / Cooling Towers, Window / Split Type Ac, Voltage Stabilizer Of Capacity 5 To 7.5 Kva In Certain Different Locations Under Ge ( Utilities ) Udhampur.. Submission Date for this Tender is 10-10-2022. Voltage Stabiliser Tenders in udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 23-Sep-2022 | BOQ REVISED | BOQ | 03-10-2022 |
2 | 03-Oct-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 10-10-2022 |
Sl. No. | Item Description |
1 | Taking out old existing unserviceablemetal plug socket and supply and fix new metal plug and socket board complete enclosurewith single pole & neutral and earth plug with MCB SP 32/40 Amps, 220 Volts completesuitable for window/ Split type complete all as specified and directed by Engr-in-Charge. |
2 | Taking out old existing unserviceable DB two Way and MCB SPN 40 Amps and Supply and fix Sheet Metal Enclosure with DBs single pole and neutral 2 Way, 240 volts bywith one SPN MCB of capacity 40 Amps complete all as specified and directed by Engr-in-Charge. |
3 | Taking out old existing unserviceable front show grill and supply and fixnew front show grill for LG/Voltas /Sidwal/Godrejwindow type AC 1.5 Toncomplete all as specified and directed by Engr-in-Charge. |
4 | Taking out old existingunserviceablereversible type inner unit of split type AC of capacity 1.5/2.0 Ton and supply and fix new inner unit of split typeAC of capacity 1.5 /2.0Ton as existing shape, size and make complete all as specified and directed by Engr-in- Charge. Make : Godrej/ Carrier/ Bluestar, Voltas/Hitachi/LG. |
5 | Taking out old existingunserviceable reversible type outer unit of split typeAC of capacity 1.5/2.0 Ton and supply and fix new outer unit of split typeAC of capacity 1.5 /2.0Ton existing shape and size with out compressor complete all as specified and directed by Engr-in-Charge. Make : Godrej/Carrier/Bluestar, Voltas/Hitachi/LG. |
6 | Disconnecting from electrical system carrying to workshop & back to store/site after repair dismantling the voltage stabilizer of capacity 7.5KVA,5KVA,2KVA,1KVA,0.5KVA thoroughly checking,cleaning all parts by brushing and assembling after repalcement of required burnt unserviceable parts / componenets, testing and comminssioning complete after necessary repair / replacement of components as below:- |
7 | Rewinding of main coil (primary/secondary) with super enameled copper wire of existing size including varnishing and insulation material of capacity 7.5KVA. |
8 | All as per ser item No.06.01 here-in-before but of capacity 5KVA. |
9 | All as per ser item No.06.01 here - in-before but of capacity 2KVA. |
10 | All as per ser item No.06.01 here-in-before but of capacity 1KVA. |
11 | All as per ser item No.06.01 here-in-before but of capacity 0.5KVA. |
12 | Replacement of unserviceable relay for 7.5KVA & 5KVA,30amp 24volts DC. |
13 | Replacement of unserviceable Step down transformer 24 volts 2Amp for 7.5 KVA & 5KVA. |
14 | Replacement of unserviceable circuit plate with connection wire. |
15 | Replacement of unserviceable relay for 0.5KVA, 1KVA & 2KVA,16amp 24volts DC. |
16 | Replacement of unserviceable Voltmeter 0- 300V, AC 75 Sqm. |
17 | Replacement of unserviceable Ampre meter 0- 30Amp, AC 75 Sqm. |
18 | Replacement of unserviceable push switch. |
19 | Replacement of unserviceable time delay circuit. |
20 | Replacement of unserviceable connector switch 30amp 220volts AC. |
21 | Replacement of unserviceable 3pin socket 5Amps,240volts. |
22 | Replacement of unserviceable 3pin socket 15Amps,240volts. |
23 | Water tap internal threaded /external threaded suitable for water cooler complete all as specified and directed by Engr-in-Charge. |
24 | Taking out old existingunserviceablecooling coil and supply and fix new cooling coil of existing shape and sizesuitable for 1.5/2 Ton Split/Window type ACcomplete all as specified and directed by Engr-in-Charge. |
25 | Taking out old existingunserviceablecondensing coil and supply and fix new condensercoil of existing shape and sizesuitable for 1.5/2Ton Split/Window type AC complete all as specified and directed by Engr-in- Charge. |
26 | Repair/replacement of PCB for LG /Voltas/Loyed/Hitachi/Godrejwindow/Split type AC 1.5 ton / 2Ton capacity complete all as directed by Engr-in- Charge. |
27 | Repair/replacement of inverter technologyPCB complete with indoor /outdoor unit and sensorfor LG /Voltas/Hitachi/Carrier/Daiken split type AC 1.5ton/2Ton cap complete all as directed by Engr-in-Charge. |
28 | Taking out old existingunserviceable coilSenser andsupply and fix newcoil senser of existing shape and sizesuitable for 1.5/2 Ton Split Type ACcompleteall as specified and directed by Engr-in- Charge. |
29 | Taking out old existingunserviceableheating Senser andsupply and fix newheating senser of existing shape and sizesuitable for 1.5/2 Ton Split Type ACcompleteall as specified and directed by Engr-in-Charge. |
30 | Taking out old unserviceableblower and supply and fix new blower(plastic body)of 1.5/2.0 Ton Split/Window type AC (as per sample approved by GE) complete all as specified and directed by Engr-in-Charge. |
31 | Supply and topping up of refrigerant gas R-22 in Split air conditioner of capacity 1.5/ 2TR complete all as specified and directed by Engr-in-Charge. |
32 | Supply and topping up of refrigerant gas R-410 in Split air conditioner of capacity 1.5/ 2TR complete all as specified and directed by Engr-in-Charge. |
33 | Supply and topping up of refrigerant gas R-600 in Referigerator complete all as specified and directed by Engr-in-Charge. |
34 | Supply and topping up of refrigerant gas R-134 in Water Cooler and Referigerator complete all as specified and directed by Engr-in-Charge. |
35 | L -Shape thimble brass (in replacement)in pk(50Nos in one pkt) complete all as specified and directed by Engr-in-Charge. |
36 | Thimble brass(50Nos in one pkt) ( in replacement ) suitable for all type of AC,Watercooler, Referigerator,Deep freezer in pkt complete all as specified and directed by Engr-in-Charge. |
37 | Old unserviceable Reverse cycle valve for window type AC/ Split Type AC of capacity 1.5 Ton /2.0 Ton (in replacement)including welding, brazing complete all as specified and directed by Engr-in-Charge. |
38 | Flexible drain pipe for Window type/Split Type AC of any capacity complete all as specified and directed by Engr-in-Charge. |
39 | Taking out old existingunserviceable swing motor and supply and fix new swing motor 0.3HP, 220 volts complete with Louvers, base ,clamps, nuts, bolts of size/shape suitable for 1.5/2.0 Ton Splt/window type AC of capacity 1.5 Ton complete all as specified and directed by Engr-in-Charge. Make:- LG/Voltas/Hitachi/Godrej. |
40 | Taking out old existingunserviceable compressor andsupply and fix newhermetic/Rotary sealed unit compressor and making connection to suction and discharge pipe(after disconnecting of sealed unit).New sealed unit compressor should be of same make, capacity as perlatest new model of same manufacturer with same specifications conforming to original compressor including rechargingwith refrigerant F-22 , Hydrocarbon Gas, replacement of copper tubing of existing size for suction and discharge and replacing parts with gas brazing and carryout leakage, testing with the help of halide torch, soap solution, vacuum pump and rebuilding of standard 800 PSI discharge pressure after creating vacuum with the help of vacuum pump and testing after installation in the system all as directed by Engr-in-charge for the following sealed units pertaining to window type ACs/ Split complete all as specified and directed by Engr-in-Charge. Type ACs:- (a) Sealed unit (Compressor Rotary Type) Suitable for capacity 1.5 Ton Window type/spllit type ACs. Make-LG/Godrej/Hitachi/universal. |
41 | All as per serial item No. 40.00 here-in-before but of capacity 2.2 ton for walk in cold room. |
42 | Taking out old existingunserviceable inverter and supply and fix new inverter model sealed unit compressor and making connection to suction and discharge pipe(after disconnecting of sealed unit).New sealed unit compressor should be of same make, capacity as perlatest new model of same manufacturer with same specifications conforming to original compressor including rechargingwith refrigerant R-32/410 , Hydrocarbon Gas, replacement of copper tubing of existing size for suction and discharge and replacing parts with gas brazing and carryout leakage testing with the help of halide torch, soap solution, vacuum pump and rebuilding of standard 800 PSI discharge pressure after creating vacuum with the help of vacuum pump and testing after installation in the system all as directed by Engr-in-charge for the following sealed units pertaining to window type ACs/ Split complete all as specified and directed by Engr-in-Charge. Type ACs:- (a) Sealed unit (Compressor inverter model ) Suitable for capacity 1.5 Ton Window type/spllit type ACs. Make-LG/Daiken /Hitachi/Carrier/ Voltas. |
43 | Taking out old existingunserviceable compressor and supply and fix newhermetic/Rotary sealed unit compressor and making connection to suction and discharge pipe(after disconnecting of sealed unit).New sealed unit compressor should be of same make, capacity as perlatest new model of same manufacturer with same specifications conforming to original compressor including rechargingwith refrigerant F-22 , Hydrocarbon Gas, replacement of copper tubing of existing size for suction and discharge and replacing parts with gas brazing and carryout leakage testing with the help of halide torch, soap solution, vacuum pump and rebuilding of standard 800 PSI discharge pressure after creating vacuum with the help of vacuum pump and testing after installation in the system all as directed by Engr-in-charge for the following sealed units pertaining to window type ACs/ Split complete all as specified and directed by Engr-in-Charge. Type ACs:- (a) Sealed unit (Compressor Rotary Type) Suitable for capacity 2Ton Window type/spllit type ACs. Make-LG/Godrej/Hitachi/universal |
44 | Taking out old existingunserviceable inverter and supply and fix newinverter model sealed unit compressor and making connection to suction and discharge pipe(after disconnecting of sealed unit).New sealed unit compressor should be of same make, capacity as perlatest new model of same manufacturer with same specifications conforming to original compressor including rechargingwith refrigerant R-32/410 , Hydrocarbon Gas, replacement of copper tubing of existing size for suction and discharge and replacing parts with gas brazing and carryout leakage testing with the help of halide torch, soap solution, vacuum pump and rebuilding of standard 800 PSI discharge pressure after creating vacuum with the help of vacuum pump and testing after installation in the system all as directed by Engr-in-charge for the following sealed units pertaining to window type ACs/ Split complete all as specified and directed by Engr-in-Charge. Type ACs:- (a) Sealed unit (inverter model) Suitable for capacity 2Ton Window type/spllit type ACs. Make -LG/Carrier/Hitachi/diaken/ Voltas. |
45 | Taking out old existingunserviceable compressor and supply and fix new hermitically /Rotary sealed unit compressor and making connection of suction and discharge pipe(after disconnecting of sealed unit).New sealed unit compressor should be of same make, capacity as per existing unitoflatest new model of same manufacture with same specification conforming to original compressor including rechargingwith refrigerant gas F-22/R-134A,R-600, Hydrocarbon Gas, replacement of copper tubing of existing size for suction and discharge and changing parts with gas brazing and leakage testing with the help of halide torch, soap solution, vacuum pump and rebuilding of standard 800 PSI discharge pressure after creating vacuum with the help of vacuum pump and testing after installation in the system all as directed by Engr-in-charge for the following sealed units pertaining to Water coolers, refrigerator and deep freezers:- Make – Godrej / Blue Star /Voltas |
46 | All as per serial item No 44.00 here-in-before but of capacity 40/80 Ltr. |
47 | All as per serial item No 44.00 here-in-before but of capacity 60/120 Ltr. |
48 | All as per serial item No 44.00 here-in-before but of capacity 150/180 Ltr. |
49 | All as per serial item No 44.00 here-in-before but for Refrigerator of capacity 165/170 Ltr. |
50 | All as per serial item No 44.00 here-in-before but for Refrigerator of capacity270 to 290 Ltr. |
51 | All as per serial item No 44.00 here-in-before but for Refrigerator of capacity 310 Ltr. |
52 | All as per serial item No 44.00 here-in-before but for Deep Freezers of capacity 320 Ltr. |
53 | Supply, fix and testing(in replacement) of complete new Fan Motor of same model and type, single phase 230V complete with base and clamps, nuts, bolts main lead as required etc against burnt defective motor of following capacity/Models as under:- |
54 | Fan motor1/16 HP single shaft for water cooler complete all as specified and directed by Engr-in-Charge. Make: Air master/Crompton. |
55 | Fan motor1/20 HP single shaft for water cooler as per the original make of complete fan motor. Make: Air master /Crompton. |
56 | Fan Motor 1/35HP single shaft for water cooler Make: Air master/Crompton |
57 | Fan Motor 1/70HP single shaft for water cooler side holder, bushes with main lead. Make: Air master/Crompton |
58 | Supply and fix (in replacement) of Fan motor with fan suitable (in replacement) for LG double door 286ltr / 310 Ltr refrigerators complete all as specified and directed by Engr-in-Charge. |
59 | Fan motor(in replacement) of 165/170 Litre Refrigerator and supplyand fix new fan motorof existing make, shape and sizecomplete all as specified and directed by Engr-in-Charge. |
60 | All as per serial item No 47.00 here-in-before but suitablefor single door Refrigerator of capacity 310 litrecomplete all as specified and directed by Engr-in- Charge . |
61 | Taking out old unserviceableCondensing coil for 165/170 to 310 Litre Referigeratorand supplyand fixnew condenser coilof existing make shape and size complete all asdirected by Engr-in-Charge. |
62 | Supply, fix andtesting (in replacement) ofFan Motor of same model and type, single phase 230V complete with base and clamps, nuts and bolts of suitable size etc. against burnt/ defective motorof capacity 1/8 HP double shaft for 1.5 /2.0 Tonwindow type AC including base, frame, side clamps complete all as specified and directed by Engr-in-Charge. Make: Air master/ Crompton. |
63 | All as per serial item No 50.00 here-in-before butBlower Fan Motorsingle shaft for Split type AC complete with base, clamps, side holders, rubber bushes etc. |
64 | All as per serial item No 50.00 here-in-before but Fan motor 1/7 HP for cooling coil of Split Type AC as per the original make of split type AC complete with base, frame, clamps, side holders, rubber bushes with main lead suitable for Voltas/ LG. Make: Air master/Crompton. |
65 | Taking out old existing unserviceable Starting Capacitor of capacity 50+6 mfd and supply and fixnew Multi purpose Running Capacitor of capacity 50+6mfd for window /split type AC complete all as specified and directed by Engr-in- Charge. |
66 | Taking out old existing unserviceable Starting Capacitor of capacity 120+150 mfd and supply & fixnew Multi purpose startingCapacitor of capacity 120/150 mfd for window/split AC complete all as specified and directed by Engr-in-Charge. |
67 | Taking out old existing unserviceable Starting Capacitor of capacity 40+80 mfd and supply and fixnew Multi purpose startingCapacitor of capacity 40/80 mfd for water cooler complete all as specified and directed by Engr-in- Charge. |
68 | Taking out old existing unserviceable Starting Capacitor of capacity 40+60 mfd and supply and fixnew Multi purpose startingCapacitor of capacity 40/60 mfd for water coolercomplete all as specified and directed by Engr-in- Charge. |
69 | Taking out old existing unserviceable Starting Capacitor of capacity 80/100mfd and supply and fixnew Multi purpose Running Capacitor of capacity 80/100 mfd for water coolercomplete all as specified and directed by Engr-in-Charge. |
70 | Taking out old existing unserviceable Multi purpose running Capacitor of capacity 45+5 mfd and supply and fixnew Multi purpose running Capacitor of capacity 45+5 mfd for window /split type AC complete all as specified and directed by Engr-in-Charge. |
71 | Taking out old existing unserviceable Multi purpose running Capacitor of capacity 36+6 mfd andsupply and fixnew Multi purpose running Capacitor of capacity 36+6 mfd for window /split type AC complete all as specified and directed by Engr-in-Charge. |
72 | Taking out old existing unserviceable Multi purpose running Capacitor of capacity 10 mfd and supply and fixnew Multi purpose running Capacitor of capacity 10 mfd for water cooler complete all as specified and directed by Engr-in- Charge. |
73 | Taking out old existing unserviceable Multi purpose running Capacitor of capacity 4 mfd and supply and fixnew Multi purpose running Capacitor of capacity 4 mfd for water cooler complete all as specified and directed by Engr-in-Charge. |
74 | Taking out old existing unserviceable Multi purpose running Capacitor of capacity 20 Mfd and supply and fixnew Multi purpose running Capacitor of capacity 20 mfd for water cooler complete all as specified and directed by Engr-in-Charge. |
75 | Taking out old existing unserviceable thermostateand supply and fix new thermostate for water coolerof any capacitycomplete all as specified and directed by Engr-in-Charge. |
76 | Taking out old existing unserviceable Fan Blade and supply and fixnew Fan Blade of 1.5/2ton window type ACof any capacitycomplete all as specified and directed by Engr-in-Charge. |
77 | Taking out old existing unserviceable Fan Blade and supply and fixnew Fan Blade of 1.5/2 ton split type ACof any capacitycomplete all as specified and directed by Engr-in-Charge. |
78 | Repair/replacement of water pump motor of desert cooler including electric connection and testing for better performance complete all as directed by Engr-in-Charge. |
79 | Replacement of "T" junction for desert cooler for watering the three side of the desert cooler with nozzels complete all as specified and directed by Engr-in-Charge. |
80 | Replacement of Khas khas set for the doors of desert coolers complete all as directed by Engr-in-Charge. |
81 | Servicing window/split type air conditioner 1.5 TR capacities of any make by opening the indoor/ outdoor unit ,cleaning the air filter,condenserincluding complete body of the unit with brush and air blower, washing with cleaning detergent & fresh water ,greasing fan motor ,rectification of loose electric connections andreplacement of u/s knobs of electrical items complete all as directedby the Engr-in-Charge. |
82 | Disconnecting and taking down unserviceable overload/PTC relay for water cooler ,Deep freezer and referigerator and supply and fix new over load relay/PTC relay and testing for water cooler ,Deep freezer and referigeratorsatisfactory performance commissioning complete all as specified and directed by Engr-in-Charge. |
83 | Disconnecting and taking down unserviceable thermostat from split type ACand supply and fix new thermostat for split type AC 1.5/ 2.0 Ton cap AC and testing the same for satisfactory performance complete all as specified and directed by Engr-in-Charge. |
84 | Pressure testing and rectifying leakage in the system of window/splitair conditioner up to1.5/2 TR capacity including testing forsatisfactory performance, commissioning complete all as specified and directed by Engr-in-Charge. |
85 | Copper tubing (in replacement) of existing size for suction and discharge and replacing parts with gas brazing and carryout leakagetesting with the help of halide torch, soap solution, vacuum pump and rebuilding of standard 800 PSI discharge pressure after creating vacuum with the help of vacuum pump complete all as specified and directed by Engr-in-Charge. |
86 | Cleaning of coils of Window/Split by using alkaline based coil cleaner (Non Acid based) including taking down filters, spraying the diluted alkaline based coil cleaner, leaving it for five minutes and then flushing with running water. Fixing back the filters. Testing & re-commissioning etc complete all as specified and directed by Engr-in-Charge. Make: C-Shine |
87 | Taking out old existing unserviceable Fan motor 4x4 and supply and fixnew Fan motor 4x4 for water coolerof any capacitycomplete all as specified and directed by Engr-in-Charge. |
88 | Sub main wiring with four single core PVC insulated(inreplacement) , unsheathed copper conductor cable, 1100volts grade of size 4.0 sqmm, FRLS in and including concealed PVC conduit, heavy duty, ISI marked,of dia 25mm and thickness not less than 2mm with all accessories such as bends, Tees, elbows, reducer socket, bell mouth,tube ends etc including cutting chases, pinning in masonry walling & making good to facing by pointing / plastering in cement mortar 1:3 to ends or edges for concealed wiring including 4.00 sqmm PVC insulated copper conductor cable as earth lead to connecting to the earth dolly complete all as specified and directed by Engr-in-Charge. Note :- Two run of wire and single run of earth wire 1RM of PVC conduit shall be measured as one unit. |
89 | Taking out old existing unserviceable diacharge valveand supply and fixnew discharge valve of 1.5/2 ton split type ACof any capacitycomplete all as specified and directed by Engr-in- Charge. |
90 | Taking out old existing unserviceable suctionvalveand supply and fixnew suction valve of 1.5/2 ton split type ACof any capacitycomplete all as specified and directed by Engr –in- charge. |
91 | Taking out old existing unserviceable bush and supply and fixnew bush of 1.5/2 ton split type AC.of any capacity make LG/ Voltas complete all as specified and directed by Engr-in- Charge. |
92 | Taking out old existing unserviceable capillary and supply and fixnew capillary of 1.5/2 ton split type /window type AC.of any capacity complete all as specified and directed by Engr-in- Charge. |
93 | Taking out old existing unserviceable dead Nut and supply and fixnew dead nut of 1.5/2 ton split type /window type AC.of any capacity complete all as specified and directed by Engr-in- Charge. |
94 | Taking out old existing unserviceable NRVand supply and fixNRV of 1.5/2 ton split type /window type AC.of any capacity complete all as specified and directed by Engr-in- Charge. |
95 | Old unserviceable remote control unit (in replacement) Suitable for 1.5 / 2.0Ton split type ACworking on both ( Hot & Cool) complete all as specified and directed by Engr-in- Charge. |
96 | Sub main wiring with two single core PVC insulated unsheathed copper conductor cable 1100 volts grade 6.0 Sq mm size HRFR in and including concealed PVC conduit heavy duty ISI marked 25mm dia non metallic with all accessories such as bends, Tees, elbows, reducer socket, bell mouth, tube ends etc. including cutting chases, pinning in masonry walling & making good to facing by pointing/plastering in cement mortar 1:3 to ends or edges for concealed wiring including4.0 Sq mm PVC insulated copper conductor cable as earth lead to connecting to the earth dolly complete all as specified anddirected by Engr-in-Charge. Note :Two run of wire and single run of earth wire and 1 RM of PVC conduit shall be measured as one unit |
97 | Repair of Deep frezeer of capacity 320ltr by dismatiling the whole condensing as well as cooling coil and finding the leakage /damage portion. Rectify the leakage and damaged parts and vaccume leakage the whole system. Then charging the refrigerent Gas and confroming no leakage . Then reassembling the same deep freezer by provinding proper insulation material at the disturbed area complete all as specified and directed by Engr-in-Charge. |
98 | Repair /repalcement of broken /water leakage from connection of water cooler of capacity 40/80Ltr to 150/150Ltrs capcity by dismatiling the front sheet of thewater cooler tank, removing the thermocol sheet and doing necessary cutting /welding /brazing work to stop the leakage and make good the damaged portion and fixing of tap connection and reassembling the front sheet including providing the thermocol as a thermal insulation to the water coolers and testing the coolers for no leakage as complete all as specified and directed by Engr- in-Charge. |
99 | Taking out & re-fixing after repair to roof/building at same location / other location including shifting where required, of split /window/casttee type AC by making hole, drilling , cutting on wall and necessary gas pipe connection , electric connections and insulations complete all as specified and directed by Engr-in-Charge. Note:- All items including gas, copper pipe and electric cable if required will be measured and paid separately under relevent items of contract. |
100 | Flexible drain pipe for Water Cooler of any capacity any size complete all as specified and directed by Engr-in-Charge. |
101 | Taking out old existing unserviceable NRV spare parts from air curtain such as Air Curtain motor, Air curtain door sensor, Air curtain blower, blower wheels replacement with new and fix of any capacity or size complete all as specified and directed by Engr-in- Charge. |
102 | Flexible conduit pipe size 40mm complete all as specified and directed by Engr-in-Charge. |
103 | Taking out old existing unserviceable foam insulationand supply and fixnew foam insulation of 1.5 / 2 ton split type /window type AC.of any capacitycomplete all as specified and directed by Engr-in-Charge. |
104 | New indoor unit of splitAC (in replacement) of capacity 2.0ton with compatible for existing out door unitfrom authorized dealers of company complete all as specified anddirected by Engr-in-Charge. Make:- Voltas/LG. |
105 | New outdoor unit w/o compressor (in replacement) ofsplitACof capacity 2.0 ton with compatible for existing indoor door unitfrom authorized dealers of company complete all as specified and directed by Engr-in-Charge. Make:- Voltas/ LG |
106 | Electronic control Board (PCB) (in replacement ) of Existing Make duly ISI marked for window type AC 1.0/1.5/2.0 Ton capacity complete all as specified and directed by Engr-in-Charge. |
107 | Taking out old existingunsv heating Sensorsupply and fix newheating sensorof existing shape and sizesuitable for 1.5/2 Ton Split Type ACcompleteall as specified and directed by Engr-in-Charge. |
108 | Taking out old existing unserviceable Starting Capacitor of capacity 80/100mfd supply and fixnew Multi-purpose Running Capacitor of capacity 80/100 mfd for water coolercomplete all as specified and directed by Engr-in-Charge. |
109 | All as per serial item No. 96.00 here-in-before but of size 36/6 for water cooler. |
110 | Blower motor of Split type AC 1.5/2.0 Ton (in replacement) of existing make & modelcomplete all as specified and directed by Engr-in-Charge. |
111 | Copper tube (in replacement) of 1.5 /2.0 Ton split AC 1/4 complete all as specified and directed by Engr-in-Charge. |
112 | Copper tube( in replacement) 1.5 /2.00 Ton split AC 1/2 complete all as specified and directed by Engr-in-Charge. |
113 | Carry out Servicing, Oiling, Greasing and Cleaning of water cooler of capacity 40/80 Ltr from authorised rep or service engineer from the manufacturer with high pressure pump, checking of defects/ leaking and adjusting setting to work and testing complete all as specified & directed by Engr-in-Charge. |
114 | Detection/rectification of leakage of gas in the system and gas charging in the system with appropriate quantity of gas including testing for smooth functioning of water cooler of capacity 40/80 Ltr complete all as specified and directed by Engr-in-Charge. |
115 | Starting relay and overload relay (in replacement ) ofsuitable for existing size and make water cooler complete all as specified anddirected by Engr-in-Charge. Make: Epcos/Asian. |
116 | Fan blade of condenser motor (in replacement) of any make and capacity of water cooler /AC /Ref or deep freezer complete all as specified and directed by Engr-in-Charge. |
117 | Carry out Servicing, Oiling, Greasing and Cleaning of Deep freezer of capacity 300/320 ltr from authorised rep or service engineer from the manufacturer with high pressure pump, checking of defects/ leaking and adjusting setting to work and testing complete all as specified and directed by Engr-in-Charge. |
118 | Gas charging in deep freezer any make and capacity including testing of leakage complete all as specified anddirected by Engr-in-Charge. |
119 | Repair , servicing and maintenance, refrigerator of any capacity including replacement of following UNSV Partscomplete all as specified and directed by Engr-in-Charge. |
120 | Repair/ replacement ofnewsealed compressorofsuitable forRefrigerator ofsingle phase, 230 Volt, 50 Hzof Refrigerator / Deep Freezer of any Size in and including refrigerant gas filling up to required levelcomplete all as specified and directed by Engr-in-Charge. |
121 | Thermostat switch for refrigerator any make & capacity complete all as specified and directed by Engr-in-Charge. |
122 | Sub main wiring with 2 Run of 4 Sqmm cable and one run of 2.5 sqmmPVC insulated, unsheathed FR cable of multi-stranded copper conductors 1100 volt grade IS- 694 marked drawn through and including non-metallic PVC conduit pipe medium grade ISI marked (not less than 20 mm dia) along with fittings and accessories concealed on wall and surface on ceiling complete all as specified and directed by Engr-in- Charge. |
123 | MCB distribution board single pole and neutral 8 way factory (in replacement) made sheet steel, phosphates, powder painted with 100 Amps rated busbar, 240 volts, neutral link, earth bar and Din rail double door complete including taking down/dismantling of old unserviceable one complete all as specified and directed by Engr-in-Charge. |
124 | Repairing /Servicing and rewinding of motor 3 phase 400-440 volt complete disconnecting the electric supply removing of pully and fan and opening of both end covers taking out Bearings and rotor checking of air gap, checking of rotor field winding, replacement of bearings, greasing fo bearings including rewiring with superior quality copper winding wire insulating material, vanishing binding of winding etc complete all as directed by Engr -in-Charge reassembling, replacing rusted nut, bolts, washers, checking and adjusting the alignment, connecting electric connection completed all as specified and directed by Engr-in-Charge:- |
125 | Electric motor 3 phase 40 HP of AC Plant. |
126 | Electric motor 3 phase 15 HP of AC Plant. |
127 | Electric motor 3 phase 10 HP of AC Plant. |
128 | Electric motor 3 phase 5 HP of AC Plant. |
129 | Electric motor 3 phase 3 HP of AC Plant. |
130 | Repairing/ servicingof water pump including removing of old gland packing, gland bolt and fixing of new gland packing , gland bolt, cleaning of impeller/Replacement of impeller complete all as specified anddirected by Engr-in-Charge:- |
131 | Monoblock pumping set 10 HP. |
132 | Monoblock pumping set 7.5 HP. |
133 | Monoblock pumping set 5.0 HP. |
134 | Descaling of condenser after opening of both end cover, circulation of descaling solution forcibly using pump for circulating decaling solution and rubbingmanually using nylon brush of size 1/4,3/8,1/2,5/8 inch descaling rod etc without damaging copper tubing and re-fixing of side cover using new gasket of rubber insulation sheet of 3mm thick and replacement of rusted nuts bolts etc complete all as specifiedand directed by Engr-in-Charge :- |
135 | 47.5 TR cap Condenser. |
136 | 7.5 TR cap Condenser. |
137 | 5 TR cap Condenser. |
138 | Descaling and flushing of cooling coil complete with chemical, bends and cleaning complete all as specified and directed for the following:- |
139 | 47.5 TR Capacity Plant. |
140 | 7.5 TR Capacity Plant. |
141 | 5 TR Capacity Plant. |
142 | Repairing serving of cooling coil tower of AC plat FRP Type by dismantling ad taking out the one comb PVC files complete ad PV Nozzles the PVC files by suitable descaling solution including bruising and cleaning complete with cleaning solution and water replacing the defective PVC flange along with rubber gasket and rusted bolts nuts and washer etc cleaningthe water sump ad XMP wire mesh with suitable cleaning solution re-assembling the same including replacing the defective water filter flanges of pipe joints etc and testing complete all as specifiedand directed (PVC Files will be measured ad paid separatelyfor the following:- |
143 | 15 TR Capacity plant installed at 37 AMSD A/C Plant. |
144 | 95 TR Capacity plant installed at OT ICU. |
145 | Serving of compressor unit by draining out the used compressor oil,opening both side cover head covers and taking out the defective oil filtercleaning the sump by using suitable cleaning solution replacing the defective oil filter element checking of solution and discharge valve adjust them and re-fixing the side covers head covers including replacing the suitable gasketcompleteand re-filling of new compressor oil to the required level, removing the pull checking the serviceability of shaft seal ass, replacement of shaft assly and re-fixingthe pull including replacing the defective gas filter and testingcomplete all as specifiedand directedby Engr-in-Charge. Note:- Oil filter element gas filter and shaft seal will be measured and paid for separately. |
146 | Compressor model JS43F 50B 47.5 TR Capacity. |
147 | Compressor model JS43F 50B 7.5/5 TR Capacity. |
148 | Supply and replacement of following items complete all as specified and directive by Engr-in-Charge:- |
149 | Different pressure control switch Type MP-55. Make: Indfos/ Danfos. |
150 | Low pressure cut out control switch MP-I. Make: Idofos / dafos. |
151 | Pressure cut out cotrol switch MP-5. Make: INDFOS/DANFOS. |
152 | Oil pressurecut out off switch MP-15 Make: INDFOS/DANFOS. |
153 | Hand shut off valve of size 1/4 x ¼. |
154 | Solenoid control valve suitable for central AC Plant upto 95 TR Cap. |
155 | Condenser safety valvefor central AC plant upto95 TR. |
156 | 110 Amp,3pole, 415 Volts, 50 Hz Power contactor (MNX110) auxiliary contact 2 NO + 2 NC, (in replacement ) of coil voltage 440 Volts, complete all as specified and directed by Engr-in-Charge. Make: Model No CS94137 of L&T/Schineider / Havells. |
157 | 32 Amp,3pole, 415 Volts, 50 Hz Power contactor (MNX32) auxiliary contact 2 NO + 2 NC (in replacement) of coil voltage 440 Volts, complete all as specified and directed by Engr-in-Charge. Make: Model No CS 94111 L&T/Schineider/Havells. |
158 | Comprehensive maintenance and replacing complete control wiring of AC Plant/ AHU control panel with single core FRLS PVC insulated, unsheathed, Multi stranded copper conductor of suitable size but not less than 2.5 sqmm, including all necessary addition and alteration in panel, thimble, mounting bracket, and coding for indication of cable complete all as specified an directed by Engr-in-Charge. |
159 | MCCB Three pole 415 Volt 50 Hz 160 Amps wit breaking capacity 25 KA type DT. Make: L &T/ABB/SCHNEIDER/ SIMESE. |
160 | MCCB Three pole 415 Volt 50 200 Amps with breaking capacity 25 KA type Make:L&T/ABB/SCHNEIDER/ SIMESE. |
161 | Over load relays MK 1 Type relays range 44 to 75 Amps Make: L&T/Autoix/MDS/SIMEMS OR Equivalent. |
162 | Over load relays MK 1 Type relays range 14 to 23 Amps Make: L&T/Autoix/MDS/SIMEMS OR Equivalent. |
163 | AC Amps meter 0 to 30 Amps direct reaching type. Make : AE/PL/L&T/Standard. |
164 | AC Ampsmeter 0 to 100 Amps Make:AE/PL/L&T/Standard. |
165 | AC Voltmeter electronic digital type 0 to 500 V as per sample. Make:AE/PL/L&T/Standard. |
166 | Electronic timer switch 240/415 volt 50 Hz for 30 to 60 seconds Make:GIC/L&T. |
167 | Single phase preventer suitable for 415 volt 50 Hz 3 phase as per existingtype. Make: L&T /Siemes. |
168 | Taking out the defective thermostatic expansion valve and supply and fix thermostatic expansion valve suitable for the following :- |
169 | Central AC Plant 95 TR. Make:ALCO/IFOS. |
170 | Central AC Plant 15 TR Capacity. Make: ALCO/IDFOSS. |
171 | HEPA filter 10 to 20 microns static wove both side DPE mesh in aluminium frame efficiency 90% of sizes as per site requirement complete all as specified and directed by Engr-in-Charge. |
172 | Factor made performance HEPA filters of 99 micro down to 5 micro of standard sizewith multiple pockets & self supporting filters bags with MS/GI anodised aluminium frame suitable for central AC Plant including replacement of bolts & nuts & taking down unserviceable complete all as specified and directed by Engr-in-Charge. |
173 | Supply and fix V Belt of following sizes:- |
174 | V-Belt B-64. |
175 | V-Belt B-80. |
176 | V-Belt B-86. |
177 | V-Belt B-124. |
178 | Supply only compressor oil I sealed container manufactured by Hindustan Petroleum limited as per site requirement or equivalent complete all as directed by Engr-in-Charge. |
179 | Provide skilled technician for attendingofanybreakdown of AC Plant of capacity 47.5 TR/ 7.5 TR whenever required round the clock ,rectify the fault and restart the plant within three hour after receipt of complaint of any nature i.e. Compressor, Condenser,Cooling tower , AHU, control panel etc complete all as specified and directed by Engr-in-Charge. Note -(i) The cost ofreplaced spare parts will be paid and measured separately.(ii)If complaint is not attended by contractor with in five hour the penalty of Rs 500 / per hourto be imposed and amount of penalty will be deducted from RAR. (iii) The cost of transportation (to and fro) for all kind of necessary equipment / T&P shall be arranged/brought by contractor to complete the job at site or at E/M yard and no extra cost shall be paid to the contractor to this effect. (iv) Complaint shall be lodged by telephonically ,so contractor to specifythe telephone no who willreceive the complaint round the clock. |
180 | Thermal insulation to chillier pipe lie with one coat of bituminous paint polish sheet fiberglass wool thickness of the souled be 50 mm wire meshand cover with POP/White cement with paintingto match the existing complete all as specified and directed by Engr-in-Charge. |
181 | Disconnecting and isolating the compressor of Accel Make SMC 6- 100 Model from the existing AC system by putting plates to suction and discharge valve opening of the compressor removing of internal parts cleaning of the oil partsthoroughly replacement of the following parts including trust washers, mirror parts like nuts , bolts etc including polishing to the crank shaft resembling back all the serviceable parts after complete overhauling removing of the plates of the compressor including testing commissioning complete all as directed by Engr-in-Charge. Note : Spare parts & consumable will be measured & paid separately charging of compressor oil will be measured & paid separately. |
182 | Supply & fix the following spares forAccel Make SMC-6-100 Model Compressor includingtaking down oldunserviceable spare parts complete all as specified and directed by Engr-in-Charge. |
183 | Mainbearing pump and seal end. |
184 | Cylinder liner. |
185 | Piston. |
186 | Piston ring. |
187 | Suction Strainer. |
188 | SV Reeds. |
189 | Discharge valve assembly. |
190 | CR Bearing. |
191 | Gasket Set. |
192 | Crank Shaft for suitable size. |
193 | O ringSet. |
194 | Rocker arm frame. |
195 | Oil pump gear. |
196 | Connecting Rod. |
197 | Valve springs. |
198 | Serving of air Handling Unit of capacity 90 TR by opening of both side cover taking out the Frsh air filter cleaning the External & Internal surface of AHU, Primary air filter, wire mesh filter, Tumble Blower fan and re-fixing the side covers head covers after painting & necessary welding including replacing the suitable gasketcomplete all as specifiedand directive by Engr- in-Charge. Note:Necessary Nut, Bolts, washers, pickings are included in quoted rate. |
199 | Serving of air Handling Unit of capacity 15 TR by opening of both side cover taking out the Fresh air filter cleaning the External & Internal surface of AHU, Primary air filter, wire mesh filter, Tumble Blower fan and re-fixing the side covers head covers after painting & necessary welding including replacing the suitable gasketcomplete all as specifiedand directed by Engr- in-Charge. Note: Necessary Nut, Bolts, washers, pickings are included in quoted rate. |
200 | Shaft seal assembly of a make of compressor including removing of the unserviceable shaft seal assembly as testing all as specified and directed by Engr-in-Charge. |
201 | Dismantling of unserviceable Sprinkler carefully & supply & fix new Sprinkler made out from aluminium die casting suitable for upto 100 TR Capacity cooling tower etc complet all as specified and directed Engr- in-Charge. |
202 | Taking out of old unserviceable butterfly valve form existing pipe lie & supply and fixing new butterfly valve of size 100mm made out of mild steel including necessary modification of existing pipe lie & replacement of flangeswith new bolts & nuts etc complete replacement of flanges with new bolt and nuts includingall connected works complete all as specified and directed by Engr-in-Charge. Make:-Advance /Audco/Kirloskar/ Neta. |
203 | Water pressure gauge 0 to 10 KG 2/4 dia suitable for condenser chillier water lie including removing old unserviceable pressure gauge etc complete all as specified and directed by Engr-in-Charge. |
204 | Taking out old existing unserviceable DB two Way and MCB SPN 40 Amps and Supply and fix Sheet Metal Enclosure with DBs single pole and neutral 2 Way, 240 volts with one SPN MCB of capacity 40 Amps complete all as specified and directed by Engr-in- Charge. |
205 | MCB SPN (in replacement) upto 63 Amps, 10 KA,240V, 50Hz, "C" Series complete all as specified and directed by Engr-in-Charge. |
206 | 5 KW Fined strip heating element for AHU of ductable air conditioning plant with complete accessories complete all as specified and directed by Engr-in-Charge. |
207 | Supply, laying, connectingand testing of PVC sheathed copper conductor cableof 6 sqmm3 core laying on ground/cable duct/on wall along with suitable support on cable duct / on wall complete all as specified and directed by Engr-in-Charge. Make:- Bajaj/Havelles |
208 | Supply, laying, connecting and testing of PVC Sheathed copper conductor cableof 35 sqmmSingle core laying on ground/cable duct/on wall along with suitable support on cable duct / on wall complete all as specified and directed by Engr-in-Charge. Make:- Bajaj/Havelles |
209 | PVC sheathed Twin core (in replacement) Aluminium conductor cable 6 sqmm complete all as specified and directed by Engr-in-Charge. |
210 | PVC sheathed Twin core (in replacement) Aluminium conductor cable 4 sqmm complete all as specified and directed by Engr-in-Charge. |