Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 23-09-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 30-09-2022 |
| 2 | 13-09-2022 | AMENDMENT | BOQ | 23-09-2022 |
| Sl. No. | Item Description |
| 1 | Excavation in trenches n.exc 1.5 Mtr wide and n,exc 1.5 Mtr in depth loose/soft soil and getting out for underground cable/erection of poles, stays etc complete all as specified and as directted by Engeer-in-Charge. |
| 2 | All as per Item No 1 here in before butbut exceeding 1.5 mtr deep but not exc 3.0 mtr deep. |
| 3 | M&L sand cushioning for cables with river washed sand and punning to provide required cover as per SSR part I complete all as specified and as directed by Engineer-in-Charge. |
| 4 | Supply and laying bricks common burnt clay sub classs \"B\" old size for cable protection. |
| 5 | All as per item Ser No 4 here in before but except bricks.Note: Old bricks retrieved from item No 20 here in after shall be used. |
| 6 | M&L PCC 1:4:8 type D2 using 40 mm graded mechanically crushed stone aggregate for mass filling in pole pit and foundation etc including provision of necessary from work to achieve fair finished surfaces complete all as specified and directed. |
| 7 | M&L PCC 1:3:6 type C2 using 40 mm graded crushed stone aggregate as in pole foundation, coping stay etc including provision of necessary form work to achieve fair finishes surfaces, complete all as specifiedand directed. |
| 8 | Returning, filling including spreading, levelling, watering and well ramming in layers not exc 25CM thick each layers complete all as specified and directed by Engineer-in-Charge. |
| 9 | Removal of excavated material n,exc50 Mtr away and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 10 | Supply and erection of PCC pole 9.0 mtr long in true vertical position 102x172 mmm at top 102x279 mm at bottom class-10 incl providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip including dismantling and taking down old PCC poles complete all as specified and directed by Engr-in-Charge. Note: (i) Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 11 | Supply and erection (in true vertical position) Steel tubular swaged poles complete with cast iron base plate, finial taper plug bolts, nuts & screws all as specified of type 410 SP-31 ( 9.0 mtr length)complete all as specified in IS 2713 (Part-II) 1980 including one coat of red oxide primer and two coats of aluminium paint to exposed surfaces incl providing of two coats of black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip and with black bituminus paint for embedded portion of pole including dismantling and taking down old Steel poles compete all as specified and directed by Engr-in-Charge. Note: (i) Earth work and PCC shall be measured and paid seperately.(ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 12 | Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as directed by Engr-in-Charge. |
| 13 | Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as directed by Engr-in-Charge. |
| 14 | Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-300 Sqmm complete all as directed by Engr-in-Charge. |
| 15 | Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.50 x 400 Sqmm complete all as directed by Engr-in-Charge. |
| 16 | Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4 x 25-50 Sqmm complete all as directed by Engr-in-Charge. Note: Earth work will be measured and paid seperately. |
| 17 | Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as directed by Engr-in-Charge. Note: Earth work will be measured and paid seperately. |
| 18 | Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-400 Sqmm complete all as directed by Engr-in-Charge. Note: Earth work will be measured and paid seperately. |
| 19 | M&Lfor drilling hole of any size manully as per site requirement, drilling for laying pipes under the road for crossing electrical cables complete all as per direction of Engr-in-Charge. Note: Pipe will be measured and paid for seperately. |
| 20 | Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, watt etc. |
| 21 | Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with cluminium conductor heavy duty 1100 volts grade 16 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall etc. Note: (i) Earth work, sand , bricks removing , returning filling Aluminium thimbles/lugs will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii)All equiments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost. |
| 22 | All as per item ser No 21 here in before but for 3.5 core 25 Sqmm |
| 23 | All as per item ser No 21 here in before but for 3.5 core 35 Sqmm |
| 24 | All as per item ser No 21 here in before but for 3.5 core 50 Sqmm |
| 25 | All as per item ser No 21 here in before but for 3.5 core 70 Sqmm |
| 26 | All as per item ser No 21 here in before but for 3.5 core 95 Sqmm |
| 27 | All as per item ser No 21 here in before but for 3.5 core120 Sqmm |
| 28 | All as per item ser No 21 here in before but for 3.5 core 150 Sqmm |
| 29 | All as per item ser No 21 here in before but for 3.5 core 185 Sqmm |
| 30 | All as per item ser No 21 here in before but for 3.5 core 240 Sqmm |
| 31 | All as per item ser No 21 here in before but for 3.5 core 300 Sqmm |
| 32 | Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, walls etc and locate the fault, rectify, the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminium conductor heavy duty 1100 volts including testing for any size complete as directed by Engr-in-charge (Excavation/earth work & sand cushioning, brick and joint shall be measured & paid for seprately). |
| 33 | Supply and fixing stay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv. Note: Excavation and earth work, PCC work will be measured and paid seperately only. |
| 34 | M & L in replacement cross arms, bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape & size as indicated including one primercoat, one under coat and one finishing coat of synthetic enamel paint including dismantling and taking down old material complete all as specified and directed. |
| 35 | M & L in replacement shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm complete all as specified and directed by Engineer-in-Charge. |
| 36 | M & L in replacement pin type insulator porcelain vitreous white or brown 1100 volts grade100 mm hight and 65 mm dia with GI spindle two washer and one GI nut complete all as specified and directed by Engineer-in-Charge. |
| 37 | M&L aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site including taking down old U/S (ACSR) conductor complete all as specified by Engr-in-charge. |
| 38 | M&L in replacement 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as directed by Engr-in-Charge. |
| 39 | Dismantling and taking down old u/s earthing, material and labour for new earthing complete with galvanized steel earth electrode plate of size 600x600x6mm thick burried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth strip of size 32x6 mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm TMT steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection & watering pipe, funnel, wire mesh, also including earth work, common salt, charcol dust complete all as specified and directed by Engr-in-charge. |
| 40 | Dismantling and taking down old u/s earthing, material for earthing complete with galvanized steel earth electrode plate of size 600x600x6mm thick burried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth wire of size 4mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm TMT steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection & watering pipe, funnel, wire mesh, also including earth work, common salt, charcol dust complete all as specified and directed by Engr-in-charge. |
| 41 | M&L in replacement GI tubing 50 mm bore light grade, on poles, on walls, under floors, road crossing as reqd at site complete all as directed by Engr-in-Charge. Note: Clamps, Nut bolts, saddle etc will be measured and paid seperately. |
| 42 | All as per Item No 41 here in before but 80 mm dia. |
| 43 | Supply and fixing in replacement MCCB TPN 630 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge. |
| 44 | Supply and fixing in replacement MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge. |
| 45 | Supply and fixing in replacement MCCB TPN 250 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge. |
| 46 | Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge. |
| 47 | Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 16/18 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge. |
| 48 | M&L for detecting fault in cable of any typewith fault locator equipment which is supply as per cable serviceable cable to cable.Note :-(a) The fault which is detected through cable fault locater will only be paid under this item.(b) Charges of Cable fault locator and DG set including transportation charges deemed to be included in the quoted rate.(c) Earth fault locator will be provided by the contractor for even single fault no delay on this account will be acceptable otherwise penality will leived Rs 500/- per day. (d) Necessary testing of cable after making joint shall be deemed to be including in the cost of relevent item.However necessary earth work cable cutting, joint making shall be paid under relevant item. |
| 49 | Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS completeas per direction of Engr-in-Charge. |
| 50 | Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 3 line as per IS completeas per direction of Engr-in-Charge. |
| 51 | Re-stretching existing/retrieved ACSR conductor on LT pole and building conductor on insulator properly using new binding wire/jumper wire complete allas directed at site by Engr-in-Charge.Note: (i) Each Run of line conductor shall be measured & paid for separetly. |
| 52 | Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 50 sqmm incl dismantling old thimbles of any type. |
| 53 | Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185sqmm incl dismantling old thimbles of any type. |
| 54 | Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400sqmm incl dismantling old thimbles of any type. |
| 55 | Material and labour for shifting heavy items / excavation / cleaning areas / cleaning site by providing crane/hydra/excavators/tractors/trolley etc as required at site complete, all as specified and directed. |
| 56 | Material & Labour for painting cleaning and repair of LT panel size upto 0.6 x 0.6 x0.6 mtr after cleaning of surface including removing rusted particles removing dust, tightening nut, bolts welding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide including stand complete all as directed.Note: (i) Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate.(ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. |
| 57 | Material & Labour for painting cleaning and repair of LT panel size upto 1.2 x 1.2 x0.6 mtr after cleaning of surface including removing rusted particles removing dust, tightening nut, bolts welding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide including stand complete all as directed.Note: (i) Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate. (ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. |
| 58 | Material & Labour for surface cleaning of steel tubular poles LT 9 mtrs long including removing rusted particles panting withtwo coats of synthetic enamelaluminium paint over a coat of red oxide including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl reparing and painting on coping with cement base white paint complete all as directed.Note: (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge.(ii) The quoted rates shall including the reparing of coping with cement / PCC. |
| 59 | Material & Labour, cement base paint for PCC pole 9 mtr long includingblack & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms bracing supports, clamps, eye hooks, security light bracket, clamp etc incl repairing and painting on coping with cement base white paint complete all as directed.Note: (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge.(ii) The quoted rates shall including the repairing of coping with cement / PCC. |
| 60 | M&L for spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge. |
| 61 | Supply and fixing in replacement on load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed by Engr-in-Charge. |
| 62 | Supply and installation in replacement of all in one integrated Solar street light 25 Watt compact, aesthetic eco friendly and modern integrated Solar Street in extruded aluminium housing with high efficiency mono crystaline silicon photo voltaic panel, high efficency SMD LED 6500K having secondary lens optic for street light distribution,high performance lithium battery, MPPT charge controller and intelligent control, module/sensor with higher reliability long service life including 50 mm bore GI pipe medium grade pole upto 4 mtr height for mounting of Solar Lights suitable for easy and quick instllation including PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) complete all as specified and directed. |
| 63 | Taking down old unsv switches and S & F Automatic street light control with infrared sensor based NATRURE SWITCH and VOLTAGE MONITORING SYSTEM (VMS) . Three phase loadof 8 KW for automatic switching of street lights.Nature switch operation should be based on Natural light Lux level . Required illuminance level for switching ON is < 30 Lux and for switching OFF < 10 Lux. The sensor should also have part night operation facility of min, 4 hrs to max 12 hrs, VMS should have adjustable over & under voltage trip level and protection against phase loss, Beutral loss & phase reverse incl power contractors (63Amos) and incoming-outgoing MCB rating of 63 Amps& main load circuit wiring (Copper) of minimum 16 sqmm.The sensor, VSM power contractor, MCBs incl connected items should be enclosed in a pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC junction box conforming to IP54. The circuit should also have provision for manual operation (i.e sensor & VMS by pass option)Model swadeep-02EC8kW1P-VMS or equivelent in Schneider/Havells/Legrand.Make(i) Nature switch : Kakatiya Energy Systems/Healer/Bajaj(ii)Power contractor - L&T / BCH/Schneider(iii)Voltage Controlling Device - L&T (IV) MCB- Hager/Schneider/L&T/Legrand, (v)Enclosure & circuit sheet - Sintex (shock proof , rust proof, termite proof, FR rade) (vi)Circuit wiring-Polycab/FinolexNote: (i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii)The sensor must have the warranty of min of 2 yers. (iii)The test certificate and warranty cirtificate must be provided by supplier.(iv)Cost of marking description on the box is incl quoted rate. |
| 64 | M&L Chemical spray (DC>2.26 having container 415 ml/300g for precision blended multipurpose product to prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanism clean etc complete all as specified and directed by Engr-in-Charge. |
| 65 | Dismantling and taking down old unsv LT Panel, Supply, Install, Testing and Commissioningoutdoor type cubical panel board of size 2.0 x1.5 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alloy ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, Copper bus bar of 630 A, tested at factory approved from CPRI, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-(i) Supply and fixing MCCB 630 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming)-01 Nos(ii) Supply and fixing MCCB 400 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos(iii) Supply and fixing MCCB 315 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos(iv) Supply and fixing MCCB 250 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos(v) Supply and fixing MCCB 200 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 03 Nos(vi) RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos(vii) Digital Ammeter of range 0-300 A, auxiliry voltage 230 volts with selector switch 01 Nos(viii) Digital Volt meter of range 0-500 A, auxiliry voltage 230 volts with selector switch 01 Nos(ix) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete. |
| 66 | Dismantling and taking down old unsv LT Panel and Sypply, Install, Test and Commissioningoutdoor type cubical panel board of size 1.2 x1.0 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alloy ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shell completly vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, Copper bus bar of 400 A, tested at factory approved from CPRI, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-(i) Supply and fixing MCCB 400 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming)-01 Nos(ii) Supply and fixing MCCB 250 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 04 Nos(iii) Supply and fixing MCCB 200 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos(iv) RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos(v) Digital Ammeter of range 0-300 A, auxiliry voltage 230 volts with selector switch 01 Nos(vi) Digital Volt meter of range 0-500 A, auxiliry voltage 230 volts with selector switch 01 Nos(vii) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete. |
| 67 | Dismantling and taking down old unsv LT Panel and Supply, Install, Testing and Commissioningoutdoor type cubical panel board of size 1.2 x1.0 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alloy ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completly vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl copper bus bar of 400 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-(i) Supply and fixing MCCB 400 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming)-01 Nos(ii) Supply and fixing MCCB 315 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos(iii) Supply and fixing MCCB 200 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos(iv) Supply and fixing MCCB 100 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos(v) RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos(vi) Digital Ammeter of range 0-300 A, auxiliry voltage 230 volts with selector switch 01 Nos(vii) Digital Volt meter of range 0-500 A, auxiliry voltage 230 volts with selector switch 01 Nos(viii) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete. (a) The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type insulated.(b) Cost of making description on the front door as per direction of Engr-inCharge is encl in quoted rate.(c) Cable will be entered in panels through gland. |
| 68 | Dismantling and taking down old unsv LT Panel and Supply, Install, Testing and Commissioningoutdoor type cubical panel board of size 1.2 x1.0 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alloy ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completly vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl copper bus bar of 400 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-(i) Supply and fixing MCCB 315 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming)-01 Nos(ii) Supply and fixing MCCB 100 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 04 Nos(iii) RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos(iv) Digital Ammeter of range 0-300 A, auxiliry voltage 230 volts with selector switch 01 Nos(v) Digital Volt meter of range 0-500 A, auxiliry voltage 230 volts with selector switch 01 Nos(vi) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete.(vii) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete.(a) The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.(b) Panel drawing shall be got approved before placing of order from Engr-in-Charge.(c) The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.(d)Cost of making description on the front door as per direction of Engr-in-Charge is encl in quoted rate. (e)Cable will be entered in panles through gland.(f) Cost of marking descreption on the front door as per direction of Engr-in-Charge |
| 69 | Dismantling and taking down old unsv LT Panel and Supply, Install, Testing and Commissioningoutdoor type cubical panel board of size 1.2 x 1.0x0.5M ,outer shell made out of 3.15 mm thick MS sheet and inner shell 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm above and 45 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alloy ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completly vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl Copper bus bar of 400 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-(i) Supply and fixing MCCB 400 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming)-01 Nos(ii) Supply and fixing MCCB 125 Amps, 415 volt 4 pole breaking capacity 25 KA,Adjustable type , ISI marked all. Outgoing) - 04 Nos(iii) RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos(iv) Digital Ammeter of range 0-500 A, auxiliry voltage 230 volts with selector switch 01 Nos(v) Digital Volt meter of range 0-500 A, auxiliry voltage 230 volts with selector switch 01 Nos(vi) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete.(a) The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.(b) Panel drawing shall be got approved before placing of order from Engr-in-Charge.(c) The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.(d) Cost of making description on the front door as per direction of Engr-in-Charge is encl in quoted rate.(e) Cable will be entered in panles through gland.(f) Cost of marking descreption on the front door as per direction of Engr-in-Charge. |
| 70 | Dismantling and taking downUNSV LED street/security/flood lights upto 200 watt after disconnection electric supply and to fix again after repairing of unsv AC/DC drivers incl proper connections all as directed by Engr-in-charge. Note: (i) Cost of repair and driver is incl in quoted rate.(ii) Ifrepair is not possible then replacement of street/security light will be measured and paid seperately under relevent items. |
| 71 | Dismantling and taking downUNSV LED street/security/flood lights upto 200 watt after disconnection electric supply and to fix again after repairing of unsv AC/DC drivers incl proper connections all as directed by Engr-in-charge. Note: (i) Cost of repair and driver is incl in quoted rate.(ii) Ifrepair is not possible then replacement of street/security light will be measured and paid seperately under relevent items. |
| 72 | Dismantling and taking down old unsv street/security lights and Material & labour for new LED street light fittings of 70 watt system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, TOP opening separe driver compartment with frame, IP 66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy>120lm/W and system efficacy 90 lm/w 240 volts AC, 50 Hz CRI>70% operating voltage range 160 V-270 V, power factor>0.95, working temperature range -20 degree C to 60 degree C, built in surge protection of more than 5kv with facility of power supply shall be removed without removing light fitting from pole, make proper connection, cutting, welding, drilling holes, nut bolts, washer complete all as direted by Engineer-in-charge. |
| 73 | Dismantling and taking down old unsv street/security lights and Material & labour for new LED street light fittings of 90 watt system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, TOP opening separare driver compartment with frame, IP 66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy>120lm/W and system efficacy 90 lm/w 240 volts AC, 50 Hz CRI>70% operating voltage range 160 V-270 V, power factor>0.95, working temperature range-20 degree C to 60 degree C, built in surge protection of more than 5kv with facility of power supply shall be removed without removing light fitting from pole, make proper connection, cutting, welding, drilling holes, nut bolts, washer complete all as direted by Engineer-in-charge. |
| 74 | Dismantling and taking down old unsv street/security lights and Material & labour for new LED street light fittings of100 watt system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, TOP opening separare driver compartment with frame, IP 66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy>120lm/W and system efficacy 90 lm/w 240 volts AC, 50 Hz CRI>70% operating voltage range 160 V-270 V, power factor>0.95, working temperature range -20 degree C to 60 degree C, built in surge protection of more than 5kv with facility of power supply shall be removed without removing light fitting from pole, make proper connection, cutting, welding, drilling holes, nut bolts, washer complete all as direted by Engineer-in-charge. |
| 75 | Dismantling and taking down old unsv street/security lights and Material & labour for new LED street light fittings of 200 watt system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, TOP opening separare driver compartment with frame, IP 66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy>120lm/W and system efficacy 90 lm/w 240 volts AC, 50 Hz CRI>70% operating voltage range 160 V-270 V, power factor>0.95, working temperature range -20 degree C to 60 degree C, built in surge protection of more than 5kv with facility of power supply shall be removed without removing light fitting from pole, making proper connection, cutting, welding, drilling holes, nut bolts, washer complete all as direted by Engineer-in-charge. |
| 76 | Supply and fix 1100 volt grade heavy duty cable PVC insulated aluminium stranded conductor PVC sheathed suspended by insulating hanger not more than 1 mtr apart including 4mm suspension, cable size 10 sqmm twin core multi strand conductor complete all as specified and directed. |
| 77 | Supply and fixor passing through pipe, 1100 volts grade heavy dutyPVC insulated flat twin core cable of size 4 sqmm nominal cross section with connection in sintex box flood light complete all as specified and directed by Engr-in-charge.Note: PVC pipe will be measured and paid seperately under relevent items. |
| 78 | Supply and fix rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. Note: PVC pipe will be clamp at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates. |
| 79 | M&L for fixing of new street light bracket made out of GI pipe medium grade 25 mm bore suitable to fit with LED street light approx length not less than 120cm bent to shape including new clamps made of MS flat of size 30x4 mm thick including cutting, welding holes, nut, bolts washers etc including two coat of aluminium paint over one coat of red oxide primer on MS work complete all as specified and as directed. |
| 80 | Note:-Amount of credit ofRs. 489560.00 for retrieved materials is mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy