| 1 | Supply of ISI marked aluminium conductorXLPE insulated cable as per IS 7098, armoured, served, sheathed1100 volts grade. 70 sqmm 3 1/2 core |
| 2 | Supplying and making end terminationwith brass compression glands of following sizes of 1.1. kv grade multicore aluminium conductor PVC insulated and PVC sheathed3½ X 70 sq. mm |
| 3 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.Above 35 sq. mm and upto 95 sq. mm |
| 4 | Supplying and laying of following sizeDWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming toIS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench including sand cushioning and protective covering etc., complete as required.75 mm dia for road cross |
| 5 | Supply, installation, testing and commissioning ofsub main control L.T cubicle type totally enclosedwall mounttype, dust, damp and vermin proof L.T danger notice plate, connection of incoming and outgoing cables with thimbles, stove enameled painted and having following incoming/ outgoing MCCB , meters, indicators and doublebus bar arrangements complete as required. a) 2no.160 Amp. 4pole25KA b)1no 160 Amp 4P Change Over manualc) 4 no 63A TPN 10 KA C- curve MCBd)3no.40-63 A , 10 KA C-curve Double pole MCB.e) 0-500volt volt meter (digital)f) 1 set 160Amp busbar 4 strip heavy duty aluminum multi connection basbar out goining.g) Phase selector switches. |
| 6 | Supplying and fixing 6 A to 32 A rating, 240/415 V, 10 kA, “C”-curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 7 | Single pole |
| 8 | Double pole |
| 9 | Supplying and fixing 40 - 63 A rating, 240/415 V,“C”-curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. Double pole |
| 10 | Supplying and fixing 40 - 63 A rating, 240/415 V,“C”-curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. TPN with Enclosure |
| 11 | Providing and fixing of 12 way Double door distribution Board (PDB, LDB/UDB) |
| 12 | Wiring for circuit (raw power)/ submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed in class heavy duty PVC conduit as required Note :Rates of Suitable PVC conduitincluded in above description for the following items |
| 13 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 14 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 15 | 2 x 10 sq.mm + 1 x 10 sq.mm earth wirefor Sub main |
| 16 | 4 x 10 sq.mm + 2 x 10 sq.mm earth wire for Sub main wiring |
| 17 | Providing and fixing of Heating points using 4 sq.mmPVC insulated copper wire of FRLSthrough 1” 2mm heavy duty PVC conduitand providing and fixing of 6/16 Amp. of Modular Switch, socket recessed in wall covered with modular sheet/ MS boxof required size including providing and fixing of 4mm² PVC insulated copper wire as earth wire, point taken up to D.B. duly tested and commissioned, complete point in all aspects note: all items included like Conduit, wire, MS box, switches etc. |
| 18 | Providing and fixing of Lighting point wiring with 1.5 mm2 PVC insulated copper wire of FRLS through heavy duty PVC conduit pipe with all necessary accessories including providing and fixing of ceiling rosewithround junction plate 5Amp switches of recessed in wall using Modular switches, plate & MS box of required size, point taken upto D.B. duly tested and commissioned,etc. note: all items included like Conduit, MS junction box, wire, box, switches etc. |
| 19 | Providing and fixing of fan point wiring with 1.5 sq. mm PVC insulated copper wire of FRLSthrough heavy duty PVC conduitwith all necessary accessories including providing and fixing of ceiling rosewithround junction plate 5Amp switches of recessed in wall using Modular plate & MS boxof required size, point taken upto D.B. duly tested and commissioned,etc.note: all items included like Conduit, Junction box, wire, box, switches etc. |
| 20 | Providing and fixing of 15 surface LEDslim230V , complete in all respects. With 2kv surge protection commercial type |
| 21 | Providing, fixing of T520W LEDslim230V , complete in all respects. With 2kv surge protection. |
| 22 | Providing and fixing of 12”x12” Metalictype exhaust fan complete with all accessories includindg Frame etc . |
| 23 | Providing and fixing of 48 inches Sweep energy efficient ceiling fanof approved sample at site including wiring the down rods of standard length (30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc including Fan Junction MS box as required. |
| 24 | Providing and fixing of Fan down rods upto 3ft long |
| 25 | Providing and fixing of Fan dimmer electronicregulator Including MS box and Modular Plate 5Ampere 3 pin type. |
| 26 | Supply of advance maintenance free Chemical Gel Earthing of Dual Pipe Technology (GI) of 3 mtrs long 80 mm dia of outer shell (MS) with the 50 mm dia of inner shell (MS) of 80-100 microns galvanized CHEMRODE filled with highly conducting metallic compounds with the permenant sealings at both the ends with the lead terminal of 50x10mm size at the top. The electrode shall be duly tested and certified by CPRI (Central Power Research Institute), Govt of India for a peak short circuit withstanding capacity of 60 KA. including Supply/ fixing of environment friendly rust proof heavy duty weather proof polyplastic earth pit chamber. |
| 27 | Supplying and laying 25 mm x 5 mm G.I. strip at 0.50m. below ground level as strip earth electrode, including soldering etc. as required. |
| 28 | sypplying of 1000 mm wide, 2000mm length,1.1kV grade, antiskid rubber mat, As per IS 15652-2006 and of reputed make to be spread in front ofthe415 V switchgear panels / DBs etc. |
| 29 | Supplying, fixing of Automatic fire fighting ball “TECHIDEAS” ELIDE FIREor equivalent ABC typeextinguishing ball, automatic fire extinguishing technology.AUTOMATIC fire fighting ball Size (Diameter.) 6 inches. or 152 mm. (ELB01)WEIGHT (Kg.) 1.3 Kg. +/- 0.2 Kg.COVERAGE AREA 4 sq. meter radius 360 degreeInstallation ambient temperature -40 C° up to +85 C°Service life of automatic fire surveillance (years) 5 yearsOperating time (sec.) 3-5 secondsOperating temperature 280 C° or touching the flame etc.including Providing, fixing of suitable holding stand for same |
| 30 | Note. The quoted percentage (%age) should preferably be in fractional form in order to minimize concurrence of similar quoted rates |