| 1 | Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient forlaying cables/pipes etc. including removing cable protection covers/ bricks complete all as specified and directed. Notes : (i) Excavation shall be made carefully in order to avoid damage of existing cables and brick protection.(ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations |
| 2 | M&L for Returning, filling in, including spreading leveling, watering and well ramming the excavated soil in layers not exceeding 25 cm thick complete all as specified and directed. |
| 3 | M&L for Removal of surplus excavated soil to a distance not exceeding 50 Mtr distance and depositing as directedat a level not exceeding 1.5 mtr above starting point complete all as specified and directed. |
| 4 | Material & labour for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches/ducts for cable protection complete all as specified and directed.(NOTE : Thickness after punning shall be measured for payment) |
| 5 | M&L for Un-reinforced precast concrete cable cover class LV type I, flat, size 250mm x 150mm x 40mm as proteciton to under ground cable laid dry flat adjoining each other complete all as specified and directed |
| 6 | Fixing / laying only old retrieved bricks of any description as obtained from dismantling of the cable complete all as specified and directed. |
| 7 | Disconnecting and taking out old unserviceable GI pipe and Supplying, laying & jointing GI water tubing, 80 mm bore, light grade as in sleeving etc laid in trenches / pole post etc, cutting and making necessaries arangement by means of wedling and jointing suitable for post of larntent/ street light fitting including PCC work complete all as specified and directed . Make of pipe TATA / Jindal / Swastik / Prakash / BSTor any other ISI marked make approved by GE.(Note : PCC work shall be measured and paid seperatly under Sch \"A\" relevent item) |
| 8 | Disconnecting and taking out old unserviceable GI pipe and Supplying, laying & jointing GI water tubing, 100 mm bore, light grade as in sleeving etc laid in trenches / pole post etc, cutting and making necessaries arangement by means of wedling and jointing suitable for post of larntent/ street light fitting including PCC work complete all as specified and directed . Make of pipe TATA / Jindal / Swastik / Prakash / BSTor any other ISI marked make approved by GE.(Note : PCC work shall be measured and paid seperatly under Sch \"A\" relevent item) |
| 9 | M&L for cement concrete 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in cills, steps, copings, holdfast and the like including weathering, slightly rounded or chamfered angles and throating as directed with and including necessary form work complete all as specified and directed. |
| 10 | Material & ,labourin replacement of UNSV Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed with and including two coataluminium paint over a coat ofred oxide primer complete all as specified and directed. |
| 11 | Disconnecting and taking out old existing unserviceable/ non- functional LT Cable and Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I)-1988 marked, screened, PVC sheathed, armoured electric power cable (heavy duty) with aluminum conductor for working voltage upto and including 1100 Volts, cross sectional area of under mentioned size of cables laid in trenches/fixed on pole/wall / passed through pipe complete all as specified and directed. Make:Havells/GLOSTER/Polycab) (NOTE: Earth work, sand cushioning, pipe, clamps for holding cables and brick protection shall be measured and paid separately ) |
| 12 | 25 Sqmm 3½ core. |
| 13 | 35 Sqmm 3½ core |
| 14 | 50 Sqmm 3½ core |
| 15 | 70 Sqmm 3½ core |
| 16 | 95 Sqmm 3½ core |
| 17 | 120 Sqmm 3½ core |
| 18 | 150 Sqmm 3½ core |
| 19 | 185 Sqmm 3½ core |
| 20 | 16 Sqmm 4 core |
| 21 | M & L for cutting chases in hard standing road/path/drain etc for passing cables/pipes etc. size of and removing the excavated materials and disposal at 50 metre distance and making good the cutting after the pipe and cables are laid with PCC 1:3:6 type C-1 using 20mm graded stone aggregates complete all as specified and directed. |
| 22 | Supply & fixing inreplacement pin type porcelain, vitreous, white, brown or green insulators, including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, 100mm height and 65mm dia suitable for working pressure upto and including 1100 volts LT line fixed on poles grade complete all as specified and directed |
| 23 | Supply and fixing inreplacement shackle type porcelain vitreous, white, brown or green insulator for working pressure 1100V of 115mm dia and 100mm high including galvanized mild steel strip 31 x 3mm, insulator bolts 14mm dia washer and nutfor LT lines fixed on poles. complete all as specified and directed. |
| 24 | S&F in replacement of UNSV aluminium conductor, steel reinforced (ACSR) of any size/description on LT poles/lines including stringing, tightening, binding to insulators with aluminium wire making and connecting jumpers, connections etc including connecting, commissioning and testing complete all as specified & directed. |
| 25 | S&F in replacement of UNSV MCCB, 630 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity Icu100% = 35/36 KA with adjustable thermal & magnetic setting, of Make : Legrand/Indo Asian/Schnieder/Havells Cat No-IHLLSECF0630 |
| 26 | S&F in replacement of UNSV MCCB, 400 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity Ics = 100% of Icu 35/36 kA with adjustable thermal & magnetic setting, of Make : Legrand/Indo Asian/Schnieder/Havells Cat No-IHLLSECF0400 |
| 27 | S&F in replacement of UNSV MCCB, 250 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity Icu = 35/36 kA with adjustable thermal & magnetic setting, ofMake : Legrand/Indo Asian/Schnieder / L&T / Havells Cat No-IHLLSECF0250 |
| 28 | S&F in replacement of UNSV MCCB, 200 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity Icu = 35/36 kA with adjustable thermal & magnetic setting, of Make : Legrand/Indo Asian/Schnieder / L&T / Havells Cat No-IHLLSECF0200 |
| 29 | S&F in replacement of UNSV MCCB, 160 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity Icu = 35/36 kA with adjustable thermal & magnetic setting, of Make : Legrand/Indo Asian/Schnieder / L&T / Havells Cat No-IHLLSECF0200 |
| 30 | S&F in replacement of UNSV MCCB, 100 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, ofMake : Legrand/Indo Asian/Schnieder / L&T |
| 31 | S&F in replacement of UNSV MCCB, 63 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, of Make : Legrand/Indo Asian/Schnieder / L&T |
| 32 | S&F in Replacement of UNSV of front operated ON Load type changeover switch 4 pole, 415 volts, 630 Amps with and including sheet enclosurecomplete all as specified and directed.Cat part No:IHCNFO0125 of make Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 33 | S&F inReplacement of UNSVof front operated ON Load type changeover switch 4 pole, 415 volts, 400 Amps without sheet enclosure complete all as specified and directed. Cat part No:IHCNFO0200 of make Havells orMake Indo Asian equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 34 | S&F inReplacement of UNSVof side operated OFF Load type changeover switch 4 pole, 415 volts, 630 Amps with and including sheet enclosurecomplete all as specified and directed.Cat part No:IHBFFE0630 ofmake Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 35 | S&F in Replacement of UNSVof side operated OFF Load type changeover switch 4 pole, 415 volts, 630 Amps with and including sheet enclosurecomplete all as specified and directed.Cat part No:IHBFFE0400 ofmake Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 36 | SS&F in Replacement of UNSVof side operated OFF Load type changeover switch 4 pole, 415 volts, 250 Amps with and including sheet enclosurecomplete all as specified and directed.Cat part No:IHBFFE0320 ofmake Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 37 | S&F in Replacement of UNSVof side operated OFF Load type changeover switch 4 pole, 415 volts, 200 Amps with and including sheet enclosurecomplete all as specified and directed. Cat part No:IHBFFE0320 ofmake Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 38 | S&F in repair and testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 160 Amps with and including sheet enclosurecomplete all as specified and directed. Cat part No:IHBFFE0320 ofmake Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 39 | S&F in Replacement of UNSV of side operated OFF Load type changeover switch 4 pole, 415 volts, 100 Amps with and including sheet enclosurecomplete all as specified and directed.Cat part No:IHBFFE0320 ofmake Havells or equivalent in Legrand/Indo Asian/Schnieder / L&T |
| 40 | Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP-56 class protection made of out & 2mm thick CRCA Sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire415 V, 50 Hzfactory fabricated in an approvedfactory having modernfabrication and comprising of following :-(Location - SO Block) (i) Incoming :-(a) MCCB, 400 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity , 35 KA with adjustable thermal magnetic setting, Qty – 01 Make:Legrand/Schnieder/Siemens/Havells)(b) Digital Ammeter 3 Phase AC0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases-R Y B of 3 Nos,(d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No.(e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size.(ii) Out Going :-(a) MCCB, 250 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 01 No.(Make: Legrand/Schneider/Siemens/Havells/C&S)(b) MCCB, 200 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 01 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (c) MCCB, 100 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 03 No. (Make: Legrand/Schneider/Siemens/Havells/C&S (d) On load Change over switch of cap 200 Amps, 4 pole, 415 Volts, AC supply,with sheet metal enclosure with adjustable thermal & fixed magnetic setting, Qty – 01 No.(Make: Legrand/Schneider/Siemens/Havells/C&S |
| 41 | Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire415 V, 50 Hzfactory fabricated in an approvedfactory having modernfabrication and comprising of following :-(Location - D5 Bldg) (i) Incoming :-(a) MCCB, 315 Amps, 4 pole, 415 Volts, AC supply, with suitable enclosure Qty – 01 Make:Legrand/Schnieder/Siemens/Havells)(b) Digital Ammeter 3 Phase AC0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases-R Y B of 3 Nos,(d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No.(e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size.(ii) Out Going :-(a) MCCB, 200 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 03 No.(Make: Legrand/Schneider/Siemens/Havells)(b) MCCB, 160 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 01 No.(Make: Legrand/Schneider/Siemens/HavellsNote : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost offixing ofthe panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(v)The bottom of panel shall have minimum 45cm height from existing ground / floor level. |
| 42 | Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire415 V, 50 Hzfactory fabricated in an approvedfactory having modernfabrication and comprising of following :-(Location - Security office) (i) Incoming :-(a) MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, with suitable enclosure Qty – 01 Make:Legrand/Schnieder/Siemens/Havells)(b) Digital Ammeter 3 Phase AC0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases-R Y B of 3 Nos,(d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No.(e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size. (ii) Out Going :-(a) MCCB, 160 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells) (b) MCCB, 100 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 03 No.(Make: Legrand/Schneider/Siemens/Havells(c) On load Change over switch of cap 100 Amps, 4 pole, 415 Volts, AC supply,with sheet metal enclosure with adjustable thermal & fixed magnetic setting, Qty – 01 No.(Make: Legrand/Schneider/Siemens/Havells/C&S Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost offixing ofthe panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(v)The bottom of panel shall have minimum 45cm height from existing ground / floor level. |
| 43 | Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame including power coating complete with locking arrangement mounted on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire415 V, 50 Hzfactory fabricated in an approvedfactory having modernfabrication and comprising of following :-(Location - F2/E1 Block) (i) Incoming :-(a) MCCB, 250 Amps, 4 pole, 415 Volts, AC supply,having breaking capacity , 35 KA with adjustable thermal magnetic setting, Qty – 01 Make:Legrand/Schnieder/Siemens/Havells)(b) Digital Ammeter 3 Phase AC0 – 200 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases-R Y B of 3 Nos,(d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No.(e) Bus-bar chamber having 3 nos insulated aluminium bus-bar of 600Amps rating and one No. bus bar of 300 Amps rating of suitable shape and size. (ii) Out Going :-(a) MCCB, 100 Amps, 3 pole, 415 Volts, AC supply,having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 04 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost offixing ofthe panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(v)The bottom of panel shall have minimum 45cm height from existing ground / floor level. |
| 44 | Dismantling, taking down and removing the old existing un serviceable non-functional / broken hinges of any description and in any position of existing feeder pillar boxes/panel boards/feeder pillar boxes etc and supplying and fixing new cold rolled 50 mm long medium weight mild steel butt hinges in position with necessary spot welding etc including making necessary adjustment for free and smooth movement of panel and locking arrangements complete all as specified and directed (Note :- Each hinge point shall be measured as one unit. ) |
| 45 | Supplying, Fixing, jointing and testing for provision of straight through joints, epoxy type with epoxy jointing materials, suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cablesall as specified and directed. MAKE : M.SEAL/DENSON/ MAHINDRA CHEMICALS/3M) :- |
| 46 | 50 Sqmm 3½ core |
| 47 | 70 Sqmm3½ core |
| 48 | 95 Sqmm 3½ core |
| 49 | 120 Sqmmto150 Sqmm 3½ core |
| 50 | 185 Sqmm 3½ core |
| 51 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to galvanized iron earth lead 32X 6 mm GI strip, (main earthing lead ) by means of galvanized bolts, nuts and washers all as shown in electrical plate No . 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel & wire mesh incl necessary excavation and earth work in any type of soil, and PCC (1: 3 : 6) type C-1 (using 20 mm graded black trap/ granite/ Basalt stone aggregate) for earth pitwith 40x40x6 mm mild steel angle iron frame for cover and 40 mm thick precastRCC cover in 1 : 2 : 4 type B1(using 20 mm graded black trap/granite/ basalt stone aggregate) with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle, completeall as specified & directed . |
| 52 | Material and labour in replacement of UNSV GI strip of size 32mm x 6mm for laying along the wall/roof on batten or burried in ground or drawn in conduit pipe or fixed to poles or any other situation as directed or as required GI strip of size 32mm x 6mm earth continuity conductor complete with all accessories such as porcelain insulators, saddles and fixing screw etc for conductor all as specified and directed. |
| 53 | Material and labour in replacement of UNSV GI strip of size 4mm dia galvansed iron or steel wire for laying along the wall/roof on batten or burried in ground or drawn in conduit pipe or fixed to poles or any other situation as directed or as required GI wire of size 4mm dia galvansed iron or steel wire earth continuity conductor complete with all accessories such as porcelain insulators, saddles and fixing screw etc for conductor all as specified and directed. |
| 54 | M&L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure all as specified and directed. |
| 55 | Disconnecting, dismantling, taking out & removing unserviceable MCCB box and Supplying and fixing of MCCB box of range 200 amp to 400 amp capacity completeall as specified and directed. |