Drinking Water Supply and Sanitation Government Departments Closing in 0 days TDR #33730456

Tube Well Work Div Sadulpur As Per Enclosed Tender Document

Issued by Government Departments · sadulpur, Rajasthan
Tender Value
1.20 Crore
Estimated cost
Bid Submission
13 Sep 2022
0 days left
EMD
2.40 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
sadulpur → Rajasthan
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tube Well Work Div Sadulpur As Per Enclosed Tender Document

BOQ

Name of Work:Annual rate contract for Construction and Commissioning of 200 MM Tube wells under Div Sadulpur dist. Churu With 2 Years Defect Liability Period
Sl. No. Item Description
1Construction of tube well from ground level & up to 100 mtr depth to accommodate housing and assembly pipe of following sizes in all type of alluvium strataunconsolidated formation such as pebbles, boulders etc. by percussion/rotary drilling method as per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended up to date) and technical specifications, with gravel as per IS:4097-1967 and it\"s packing as per IS: 2800 (Part I & II) 1979 as amended up to date (the work includes the cost of gravel & it\"s primary packing and packing during development, lowering of housing & strainer assembly pipes with supply and wrapping of coir-rope, wherever necessary for arresting fine sand particles and development work, but excluding the cost of housing and strainer pipe assembly). The work would be completed after obtaining sand free water.
2Nominal bore 200 mm dia.
3Add 15% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 100 mtr and up to 200 mtr, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr.
4Add 40% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 200 mtr, rate shall be applicable for only extra depth beyond 200 mtr .
5Construction of Tube Well from ground level and up to 100 mtr. depthto accommodate housing and assembly pipe in all type of alluvium strata, unconsolidated formation such as pebbles, boulders etc. by percussion/ rotary drilling methodas per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended up to date) and technical specifications for removal of overburden. The work includes the cost oflowering of casing pipe, but excludes the cost of casingpipe.
6Nominal bore 200 mm dia.
7Add 15% extra on above item(Item No 2.2.1 to 2.2.2) for drilling depth beyond 100 mtr, rate shall be applicable for only extra depth beyond 100 mtr .
8Construction of tube well after completion of drilling by rotary /percussion method & up to 100 mtr. depthin all type of rocks by DTH systemas per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended up to date) and technical specifications. The workshall be deemed completed only after obtaining sand free water. The bore well should have a throughout nominal size bore beyond casing pipe.
9Nominal bore 200 mm dia.
10Add 15% extra on above item (Item No 2.3.1 to 2.3.3) for drilling depth beyond 100 mtr and up to 200 mtr from ground level, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr.
11Add 30% extra on above item(Item No 2.3.1 to 2.3.3) for drilling depth beyond 200 mtr and from ground level, rate shall be applicable for only extra depth beyond 200 mtr .
12Add 15% extra on above item (Item No 2.3.1 to 2.3.3) for drilling, where strata is collapsible and lowering of casing pipe is required . The work includes lowering of casing pipe, but excluding the cost of casing pipe. The rate shall be applicable for stretch of collapsible strata only.
13Construction of Tube Well up to 100 mtr. depthin all type of rocks by DTH system & over burden to accommodate casing pipe of following sizes in all types of soils & over burden including lowering of casing pipes, (if required) excluding cost of casing pipes, as per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended up to date) and technical specifications. The work would be completed after obtaining sand free water. The tube well should have a through out bore as per nominal dia of casing pipe.
14Nominal bore 200 mm dia.
15Add 15% extra on above item (Item No 2.4.1 to 2.4.2) for drilling depth beyond 100 mtr and up to 200 mtr from ground level, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr.
16Add 30% extra on above item(Item No 2.4.1 to 2.4.2) for drilling depth beyond 200 mtr and from ground level, rate shall be applicable for only extra depth beyond 200 mtr .
17Add 15% extra on above item (Item No 2.4.1 to 2.4.4) for drilling, where strata is collapsible and lowering of casing pipe is required . The work includes lowering of casing pipe, but excluding the cost of casing pipe. The rate shall be applicable for stretch of collapsible strata only.
18Nominal bore 200 mm dia.
19Deepening of existing tube well by DTH system beyond existing depth up to 100 mtr. and above in all type of rocks including flushing of tube well and obtaining sand free water.
20Nominal bore 150 mm dia.
21Nominal bore 200 mm dia.
22Testing verticality of tube well by plumbing system and yield test and draw down test by pumping system as per IS : 2800 (Part – II) – 1979 or as per amended up to date.
23Supplying & PackingP-gravel suitable for slot size/mesh size as suggested in IS 2800 (Part-1) 1991 or as per amended up to date.
24Development of tube well having depth up to 250 mtr as per IS: 11189- 1985 and IS: 2800 (Part- I)- 1991 (both amended up to date) using suitable methods to give sand free water for required yield of the gravel packed tube well.
25Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to dateoffollowing sizes
26200 mm dia NB (Thickness of pipe 5.4mm & mass of tube 28.46 Kg/m)
27Labour charges for making slots on blank pipes made of ERW MS black pipe ISI marked of following sizes, the slotting should be as per IS:8110-1985.
28200 mm dia nominal bore of 5.4mm thickness
29Providing & laying ISI marked GI Pipe Light duty ( “A” class) as perIS: 1239for casing pipe for submersible cable external work 40 mm dia complete in all respect.
30Supply & Installation of 3 phase ISI marked submersible motor pump set ofthree star or better rating of BEEand as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect.
31Up to 5.5 KW (7.5 HP) & head up to 120 mtr.
32Up to 5.5 KW (7.5 HP) & head above 120 mtr.
337.5 KW (10 HP) & head up to 120 mtr.
347.5 KW (10 HP) & head above 120 mtr.
359.3 KW (12.5 HP) & head up to 120 mtr.
369.3KW (12.5 HP) & head above 120 mtr.
3711 KW (15 HP) & head up to 120 mtr.
3811 KW (15 HP) & head above 120 mtr.
3913 KW (17.5 HP) & head up to 120 mtr.
4013 KW (17.5 HP) & head above 120 mtr.
4115 KW (20 HP) and above, head up to 120 mtr.
4215 KW (20 HP) and above, head above 120 mtr.
43Supply and Fixing of Electric feeder panel (having projected canopy)for submersible pump set Single phase up to 5 HP, comprising of DOL Starter, MCB, Indicating Light, Ammeter, Volt meter, connection plate, condensers of approved make and the panel enclosure should be made out from 18 gauge M.S. Sheet with powder coating. Panel size Height 600 mm Width 500 mm depth 250 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The operation of panel should be suitable for on 240 Volt AC Supply.
44Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB, DOL starter, overload relay, ampere meter, volt meter, phase preventer,phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 300mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level.The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply.
45Up to 5.00 HP
46Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply.
47Above 5 HP and up to 10 HP
48Above 10 HP and up to 15 HP
49Above 15 HP and up to 20 HP
50Above 20 HP and up to 30 HP
51Supply & Fixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc.
523 core 4.0 Sq.mm
533 core 6.0 Sq.mm
543 core 10.0 Sq.mm
553 core 16.0 Sq.mm
56Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size.
5710.0 Sq.mm, 4 core
5816.0 Sq.mm, 4 core
5925.0 Sq.mm, 3.5 core
6035.0 Sq.mm, 3.5 core
61Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required.
62Supply & Fixing M S clamp set of 50x6 mm flat from iron with nuts and bolts etc. for holding the riser pipe assembly of submersible pump set.
63Supply & Fixing tube well coverof MS sheet 8mm thick at top & 5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm long & two GI flanges at both ends in 80mm sizes passing through a hole in the centre of MS sheet. A 25 mm socket with end plug shall also be welded over top plate. A GI nipple having outside thread of size 1/2\" (for installation pressure gauge) shall be provided & welded with 80mm GI nipple near top plate nipple shall be provided with end plug.
64200 mm dia
65Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B\" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect.
6650 mm dia
6765 mm dia
6880mm dia
69Providing & Lowering in tube well ISI marked HDPE pipe as per IS 4984:1995 or amended up to date in PE 80 grade and class PN 10 of following dia. including HDPE/GI fittings and PVC rope confirming to IS 5175:1992 or amended up to date, along with clamping of submersible cable etc. complete in all respect.
7050 mm dia
7163 mm dia
7275 mm dia
73Providing, installing, testing and commissioning of double flanged bulk flow meter with removable mechanism, of class B conforming to ISO 4064/1 or amended up to date of approved make including cost of all material andlabouras per specifications with GI Box (sheet 16 SWG) suitable with locking arrangement of following dia.
7450 mm dia
7565 mm dia
7680 mm dia
77Providing & Fixing pump safety cage as per specifications or as directed by Engineer in charge.
78Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes
7965 mm dia
8080 mm dia
81Proving and Fixing 32 mm dia Full way valve or wheel valve as per IS:778 or amended up to date of approved make, on pump delivery pipe.
82Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover.
83Providing, lowering, laying and jointing in trenches, standard lengths HDPEISI marked Pipes as per IS-4984: 1995 (amended up to date)with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe byelectro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work) .Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply may be in coil or straight length in 6 M/12 M.
84HDPE PE-80PN-6
8575 mm dia
8690 mm dia
87110 mm dia
88Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil
89Dismantling of cement concrete pavement for pipe line line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work.
90Dismantling of flexible pavement for pipe line line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks per technical specification and scope of work.
91Bituminous courses
92Granular courses
93Providing and laying in position cement concrete M10 grade nominal mix 1:3:6 (1 Cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size) in base course complete including all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work.
94Providing and laying in position cement concrete in specified grade over prepared base course complete including finishing, curing, all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work.
95M20 grade Nominal Mix1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size).
96Plain cement concrete pavementof M-30 Grade
97Removing& Re-fixing of Precast concrete interlocking blocks for laying of pipe line by manual method, stacking of serviceable & non serviceable material separately, disposal of dismantled material lead up to 50 mtr. The C.C. interlocking paving blocks be laid on average 25 mm thick bed of coarse sand and the joints to be filled with fine sand. Laying procedure on compacted sub base as defined. Complete job is to be executed as per the directions of Engineer in charge. The rates to be inclusive of fixing of minimum 70 percent reusable precast concrete interlockingblock and cost of required new precast concrete interlocking block against damaged, including alllead and lift as per Technical specifications.(Interlocking blockmanufactured by fully computerized automatic stationery hydraulic vibro pressed machine & full computerized automatic batching plant of class A-1 as per BS:6717-2001. Tensile splitting strength and breaking load as per BS: 6717-2001Colour: Grey cement natural colour. Variation in Dimension : Less than 1.6 mm Variation in thickness: Less than 3.2 mm)
9860 mm thick.
9980 mm thick.
100100 mm thick
101Horizontal directional drilling (by trenchless technology) of suitable dia hole minimum 1.0 mtr below natural ground level in all type of soil under CC/BT roads and pulling HDPE pipes of dia up to 110 mm, which are available in the form of a coilincluding excavation, shoring/ strutting, preparation, maintain the thrust and including, road dismantling, excavation and refilling of drive pit and exit pit, restoration of road cut as per technical specification and scope of work.Excluding cost of pipe line.Note: Trenchless laying shall be done only for laying of pipe line (rising main) and road crossing of distribution pipe line under CC/BT roads.
102Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves) , Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work.
103Manually Operated Resilient Seated Sluice Valves of Class PN 1.6
10480 mm dia
105100 mm dia
106125 mm dia
107150 mm dia

AI Tender Summary

OUR REF NO 33730456
AUTHORITY Government Departments
TENDER VALUE 1.20 Crore
LAST DATE 13-09-2022
Authority
Authority Name Public Health Engineering Department
Work Description Tube Well Work Div Sadulpur As Per Enclosed Tender Document
Basic Detail
Tender No 21/2022-23
Bidding Type Tender
Location
City sadulpur
State Rajasthan
Key Dates
Publish Date 30 Aug 2022
Submission Date 13 Sep 2022
Open Date 14 Sep 2022
Finance
Tender Value 1.20 Crore
Tender Fee 1000
EMD 2.40 Lakhs
Exemption Not Available
Document List
e779984b-91e8-4a03-9ea9-8864d5bc26af.html
BOQ_522029.xls
TD_24.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 30, 2022
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 13, 2022
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Sep 14, 2022

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

e779984b-91e8-4a03-9ea9-8864d5bc26af.html

xls

BOQ_522029.xls

pdf

TD_24.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders