Repair To Earthing, Lighting Protection In Domestic And Tech Area At Af Stn Nal Under Ge ( Af ) Nal As Described In Bill Of Quantities, bikaner-Rajasthan

Military Engineer Services-MES has published Repair To Earthing, Lighting Protection In Domestic And Tech Area At Af Stn Nal Under Ge ( Af ) Nal As Described In Bill Of Quantities. Submission Date for this Tender is 21-09-2022. Electrification Work Tenders in bikaner Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

33667830
Corrigendum : Repair To Earthing, Lighting Protection In Domestic And Tech Area At Af Stn Nal Under Ge ( Af ) Nal As Described In Bill Of Quantities
Open Tender
Indian
Rajasthan
bikaner
21-09-2022

Tender Details

Repair To Earthing, Lighting Protection In Domestic And Tech Area At Af Stn Nal Under Ge ( Af ) Nal As Described In Bill Of Quantities

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Sep-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-09-2022
2 19-Sep-2022 CORRIGENDUM 02 DATED 19 SEP 2022 Date 21-09-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 30000.0 /-
Tender Value
INR 15 Lakhs /-

BOQ Items

Name of Work: REPAIR TO EARTHING, LIGHTING PROTECTION IN DOMESTIC & TECH AREA AT AF STN NAL UNDER GE (AF) NAL
Sl. No. Item Description
1Supply and fixing as in repair Air termination, single pointed, copper rod 12mm dia and 300mm long including nuts, bolts and washers complete all as specified and directed.
2M&L as in repair Copper strip 20 mm x 3.15 mm with proceline insulator and fixing screws etc for roof conductors and down conductors above the ground all as specified and directed.
3M&L as in repair for making test point terminal block made of gun metal or phosphorus bronze size 75mmx75mmx25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed.
4S&F as in repair 20 mm x 3.00 mm copper strip as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe through wall /floor / roof or fixed to poles or any other indicated situation for loop earthing including proceline insulator with nuts and bolts etc. as required complete all as specified and directed. Note:- (i) Excavation & earth work shall be measured and paid for separately. (ii) Cutting holes in the wall and making good with cement plaster / mortar alongwith distemper / white wash is deemed to be included in the rate quoted. (iii) Insulators shall be measuared and paid for separately in the respective item.
5All as per description of serial item No. 4.00 here in before but galvanised iron strip of size 25mm x 4mm
6S&F as in repairs epoxy based insulator 40mm height for fixing GI strip/Copper stripon wall / ceiling / floor / poles etc. complete all as specified and directed.
7S&F as in repair HDPE pipe medium grade external dia 40mm, exclusive of boxes (junction / terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and directed.
8S&F as in repair galvanised steel tubes 40mm bore light grade with all fittings, laid in trenches / fixed to walls/poles with suitable clamps, nuts, bolts etc for passing of earth continuity conductor including necessary welding where required complete all as specified and directed.
9S&F as in repair galvanised steel tubes 20mm bore light grade with all fittings, laid in trenches / fixed to walls/poles with suitable clamps, nuts, bolts etc for watering arrangement complete all as specified and directed.
10S&F as in repair galvanised steel tubes 15mm bore medium grade with all fittings, laid in trenches / fixed to walls/poles with suitable clamps, nuts, bolts etc forcomplete all as specified and directed.
11S&F as in repair PVC Bib tap of dia 15 mm standard of PTMT any colour high pressure screwed for iron pipe and fixed (Minimum weight 90gms) complete all as specified and directed.
12Taking down / out existing copper / GI strip as earth continuity conductor fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles etc,incl straightening the twisted / bent up portion of strip and re-fixing in position complete all as specified and directed. Note:- Welding / soldering of earth continuity conductor where required shall be measured and paid for separately.
13M&Las in repair of earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly in ground in vertical position, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below ground level.The earth plate to be connetced with copper earthing strip of size 20 mmx3 mm m thick by means of brazing between copper strip and earth plate min 45 cm in vertical length and copper strip also to be joined by brazing only. The copper earthing stripto be protected by GI pipe 40 mm bore (medium grade) up to ground level and there after with40mm dia HDPE pipe up to test point. Earthing shallincludeprovision of funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth platefurther filled with60 cm thick Tibba sandand 2nd layer with30 cm of Magnesium sulphate powder (compact thickness ), 3rd layerwithtibba sand up to ground level. Earthing shall also include concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 Mtr , andas shown on electrical plate No. 3 ofMES Schedule Part-I complete to obtain less than 2 Ohm earth resistance value, complete all as specified and as directed .
14Supply and fixing as in repair PVC insulated multistranded copper conductor cable 10 sqmm single core 1100 volts grade including copper lugs/thimbles on both side fixed from common Earth point to neutral point at main switch / earth dolly including nuts, bolts, washers complete all as specified and directed.
15M&L for brazing of copperearth continuity conductor 32mmx6mm / 25mmx3mm including cleaning the conductor and replacement of nuts, bolts for better earthing and connectivety and fixing at its original position complete all as specified. Note: Contractor shall make arrangements of gas cylinder and T&P for brazing and cost is deemed to be included in the unit rate.
16Material and labour for maintenance of 120 Nos copper earthing scattered area as per list specified in particular specification clause 12.00 by pouring water on twice a month and adding salt solution on requiredintervals to maintain earth resistance less than 1 Ohm for a period of 09 months complete, submitting individual earth resitance results on 1st of every month, carrying out earth test of individual earth as and when demanded by MESwith in 08 hours and rectifying the defects within 24 hours if found earth resistance more than 1 Ohm, all as specified and directed. NOTE : (i) Testing of earthing will be done by 3 Pole Fall of potential method. (ii) Cost of tools and materilas required to perform the test is demed to be included in the rate quoted. (iii) Contractor will arrange water bowser for watering at his own end. (iv) Water shall be issued for filling from MES Pump House. (v) This item will not be operated in Monsoon period. (vi) Funnel, bucket for pouring of water shall be arranged by the contractor at his own soure.
17NotesContd/..... (vii) Each earth shall be tested on monthly basis. (viii) Particular earthing shall be maintained for a period of 7 months as per above description and while making payment on completion of 7 months. The whole process shall be considered as composite one unit for the particular earthing. (ix) Cost of Common salt is included in the unit quoted rate of this item. (x) Contractor shall submit user certificate duly signed by JE,Engineer-in-Charge and user for payment purpose.
18Supply and layingcommon salt in earthing pits filled around earthing electrodes complete all as specified and directed. Note:- (i) Excavation and earthwork shall be measured and paid for separaetly. (ii) This item shall be not be operated for earthings considered against item No. 16 here in before.
19Supply and layingcharcoal dust / breeze suitable for earthing complete all as specified and directed. Note:- (i) Excavation and earthwork shall be measured and paid for separaetly. (ii) This item shall be not be operated for earthings considered against item No. 16 here in before.
20Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 Mtr deep and getting out, forming bottom surfaces to required gradient complete all as specified and directed.
21Returning, filling in trenches including spreading leveling watering and well ramming in layers n.exc 25 cm thick complete all as specified and directed.
22Removal of surplus soil to a distance not exc. 50 metre and depositing where directed at a level not exc. 1.50mtr above the starting point complete all as specified and directed.
23Testing of existing seriviceable earthing located at diffierent locations after disconnecting from test point by using suitable earth tester, measuring the earth values in ohms and writing the values on earth chamber ln bold white colour letters not exc 2cm height on the black back ground such as tested on, due date of testing eg-EP No-01, ER-1.0 Ohms& Date of testing : DD/MM/YYYY and recording of test results in prescribed format all as directed by Engr-in-Charge. Note:- (i)the test results shall be kept on record duly signed by contractor, JE/EM and user concerned. (ii) This item shall be not be operated for earthings considered against item No. 16 here in before.
24M&L as in repair earth pit chamber, size 300mm x 300 mm (internal dimensions) and wall thickness 120mmwith PCC 1:3:6 type C-1 using 20mm graded stone aggregates including RCC cover 50mm thick in cement concrete 1:2:4 type B-1 reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways complete all as specified and directed.
25S&F as in repairs precast RCC earth pit cover, size 540mm x 540mm x 50mm in cement concrete 1:2:4 type B-1 duly reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways includinghandle complete all as directed.
26M&L painting earthing chambers with two coats of synthetic enamel paint in red / yellow colour and writingln bold black colour letters 1.5cm height "Chem Pit-1, Conventional Pit-5"complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail