| 1 | Supply, installation, commissioning and testing of outdoor type, 440 Volts, AC, LT, APFC panel of60 KVAr capacity, factory fabricated, made out of 3.15mm CRCA sheet, CPRI approved, duly wiring with copper flexible wire of suitable ratingfor power control , Panel shall be dully powder coated with 8tanks sheet treatment ( De-greasing, water rinsing, de-rusting, water rinsing, Activation- phosphating, water rinsing, (Passivation thickness of powder coating shall not be less than 80 microns)in and including the following :(A) Incoming : (i) MCCB, 415 volts, 4 pole, 160 Amps, 25 kA with rotary Handle Mechanism - 01 No (ii) Digital Ammeter with built - in - selector switch Aux Supply 230 Volts, AC - 01 No (iii) Digital Voltmeter with built in selector switch Aux Supply 230 Volts, AC-01 No(iv) LED indication lamp 230 Volts, AC 22.5mm dia RYB-03 Nos (v) MCB 2 Amp, Single Pole-03 Nos (vi) Microprocessor APFC relay with single CT sensing 12 stages auxilary supply 230volts, AC - 01 No (vii) Aluminium busbar 25x10mm, TPN - 01 Set(viii)Auto/Manual Switch - 01 No |
| 2 | (B)Outgoing :- (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 01 No (ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 01 No (iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 06 No(iv) MCB Triple pole 63 Amps, 10 kA, \"C\" series - 01 No (v) MCB Triple pole 32 Amps, 10 kA, \"C\" series - 01 No(vi) MCB Triple pole 16 Amps, 10 kA, \"C\" series - 06 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 01 No(viii) Capacitor duty contactor 3 pole 10 KVAr - 01 No(ix) Capacitor duty contactor 3 pole 05 KVAr - 06 No(x) 22.5mm dia Push Button ON/OFF-08 set(xi) 22.5 mm dia LED Red - 08 Nos(xii) 22.5mm dia LED Green-08 Nos(xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT(xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel(xv )All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper typeMake : MCCBs/MCB/LED/PB/Capacitor/Contactor/APFC : L&T/Siemens/SchneiderMake (APFC Panel) : Tricolite/ Mc Layers/Asian Switchgear)Notes :(i) GA drawing for APFC panel shall be got approved from the Accepting Officer before manufacturing of APFC panels (ii) Pre dispatch inspection shall be arranged for routine test at manufacturer\"s workshop by the contractor(iii)Test report for powder coating shall be provided with panels(iv) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process(v) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be demmed to be included in unitrate quoted against this item. |
| 3 | Supply, installation, commissioning and testing of outdoor type, 440 Volts, AC, LT, APFC panel of95 KVAr capacity, factory fabricated, made out of 3.15mm CRCA sheet, CPRI approved, duly wiring with copper flexible wire of suitable ratingfor power control , Panel shall be dully powder coated with 8tanks sheet treatment ( De-greasing, water rinsing, de-rusting, water rinsing, Activation- phosphating, water rinsing, (Passivation thickness of powder coating shall not be less than 80 microns)in and including the following :-(A) Incoming :(i) MCCB, 415 volts, 4 pole, 250 Amps, 36 kA with rotary Handle Mechanism - 01 No(ii) Digital Ammeter with built - in - selector switch Aux Supply 230 Volts, AC - 01 No (iii) Digital Voltmeter with built in selector switch Aux Supply 230 Volts, AC-01 No (iv) LED indication lamp 230 Volts, AC 22.5mm dia RYB -03 Nos(v) MCB 2 Amp, Single Pole-03 Nos (vi) Microprocessor APFC relay with single CT sensing 12 stages auxilary supply 230volts, AC - 01 No(vii) Aluminium busbar 25x10mm, TPN - 01 Set (viii)Auto/Manual Switch - 01 No(B)Outgoing :-(i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos(ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 02 Nos(iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 07 Nos(iv) MCB Triple pole 63 Amps, 10 kA, \"C\" series - 02 Nos(v) MCB Triple pole 32 Amps, 10 kA, \"C\" series - 02 Nos |
| 4 | (vi) MCB Triple pole 16 Amps, 10 kA, \"C\" series - 07 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos(viii) Capacitor duty contactor 3 pole 10 KVAr - 02 Nos (ix) Capacitor duty contactor 3 pole 05 KVAr - 07 Nos (x) 22.5mm dia Push Button ON/OFF-11 set(xi) 22.5 mm dia LED Red - 11Nos (xii) 22.5mm dia LED Green-11 Nos(xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT(xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel (xv )All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type Make : MCCBs/MCB/LED/PB/Capacitor/Contactor/APFC : L&T/Siemens/Schneider Make (APFC Panel) : Tricolite/ Mc Layers/Asian Switchgear)Notes :(i) GA drawing for APFC panel shall be got approved from the Accepting Officer before manufacturing of APFC panels (ii) Pre dispatch inspection shall be arranged for routine test at manufacturer\"s workshopby the contractor (iii)Test report for powder coating shall be provided with panels(iv) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process(v) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be demmed to be included in unitrate quoted gainst this item.(vi) One 20 KVAr capacitor shall be fixed type (Connected directly )and others shall be controlled through APFC relay |
| 5 | Supply, installation, commissioning and testing of outdoor type, 440volts, AC, LT, APFC panel of110 KVAr capacity, factory fabricated, made out of 3.15mm CRCA sheet, CPRI approved, duly wiring with copper flexible wire of suitable ratingfor power control , Panel shall be dully powder coated with 8tanks sheet treatment ( De-greasing, water rinsing, de-rusting, water rinsing, Activation- phosphating, water rinsing, (Passivation thickness of powder coating shall not be less than 80 microns)in and including the following :- (A) Incoming :- (i) MCCB, 415 volts, 4 pole, 315 Amps, 36 kA with rotary Handle Mechanism - 01 No(ii) Digital Ammeter with built - in - selector switch Aux Supply 230 Volts, AC - 01 No(iii) Digital Voltmeter with built in selector switch Aux Supply 230 Volts, AC-01 No (iv) LED indication lamp 230 Volts, AC 22.5mm dia RYB-03 No (v) MCB 2 Amp, Single Pole-03 No (vi) Microprocessor APFC relay with single CT sensing 16 stages auxilary supply 230volts, AC - 01 No(vii) Aluminium busbar 25x10mm, TPN - 01 Set (viii)Auto/Manual Switch - 01 No (B)Outgoing :-(i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos(ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 03 Nos(iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 08 Nos (iv) MCB Triple pole 63 Amps, 10 kA, \"C\" series - 02 Nos(v) MCB Triple pole 32 Amps, 10 kA, \"C\" series - 03 Nos(vi) MCB Triple pole 16 Amps, 10 kA, \"C\" series - 08 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos |
| 6 | (viii) Capacitor duty contactor 3 pole 10 KVAr - 03 Nos(ix) Capacitor duty contactor 3 pole 05 KVAr - 08Nos (x) 22.5mm dia Push Button ON/OFF-13 set (xi) 22.5 mm dia LED Red - 13Nos (xii) 22.5mm dia LED Green-13 Nos(xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT (xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel(xv )All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type Make : MCCBs/MCB/LED/PB/Capacitor/Contactor/APFC : L&T/Siemens/Schneider Make (APFC Panel) Tricolite/ Mc Layers/Asian Switchgear)(Notes :(i) GA drawing for APFC panel shall be got approved from the Accepting Officer before manufacturing of APFC panels (ii) Pre dispatch inspection shall be arranged for routine test at manufacturer\"s workshop by the contractor (iii)Test report for powder coating shall be provided with panels(iv) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process (v) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be demmed to be included in unitrate quoted against this item. (vi) One 20 KVAr capacitor shall be fixed type (Connected directly )and others shall be controlled through APFC relay |
| 7 | Supply, installation, commissioning and testing of outdoor type, 440volts, AC, LT, APFC panel of112.5 KVAr capacity, factory fabricated, made out of 3.15mm CRCA sheet, CPRI approved, duly wiring with copper flexible wire of suitable ratingfor power control , Panel shall be dully powder coated with 8tanks sheet treatment ( De-greasing, water rinsing, de-rusting, water rinsing, Activation- phosphating, water rinsing, (Passivation thickness of powder coating shall not be less than 80 microns)in and including the following :- (A) Incoming :- (i) MCCB, 415 volts, 4 pole, 315 Amps, 36 kA with rotary Handle Mechanism - 01 No(ii) Digital Ammeter with built - in - selector switch Aux Supply 230 Volts, AC - 01 No(iii) Digital Voltmeter with built in selector switch Aux Supply 230 Volts, AC-01 No(iv) LED indication lamp 230 Volts, AC 22.5mm dia RYB-03 Nos(v) MCB 2 Amp, Single Pole-03 Nos (vi) Microprocessor APFC relay with single CT sensing 16 stages auxilary supply 230volts, AC - 01 No(vii) Aluminium busbar 25x10mm, TPN - 01 Set (viii)Auto/Manual Switch - 01 No (B)Outgoing :- (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos(ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 03 Nos (iii) Capacitor 7.5 KVAr ultra heavy duty 440V cylindrical - 01 No(iv) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 07 Nos(v) MCB Triple pole 63 Amps, 10 kA, \"C\" series - 02 Nos |
| 8 | (vi) MCB Triple pole 32 Amps, 10 kA, \"C\" sries - 03 Nos(vii) MCB Triple pole 16 Amps, 10 kA, \"C\" sries - 08 Nos(viii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos(ix) Capacitor duty contactor 3 pole 10 KVAr - 03 Nos(x) Capacitor duty contactor 3 pole 7.5 KVAr - 01 No(xi) Capacitor duty contactor 3 pole 05 KVAr - 07 Nos(xii) 22.5mm dia Push Button ON/OFF-13 set(xiii) 22.5 mm dia LED Red - 13Nos(xiv) 22.5mm dia LED Green-13 Nos (xv) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT (xvi) Sensing CT as per site load condition shall be provided alongwith APFC Panel (xvii )All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper typeMake : MCCBs/MCB/LED/PB/Capacitor/Contactor/APFC : L&T/Siemens/Schneider Make (APFC Panel) Tricolite/ Mc Layers/Asian Switchgear)(Notes :(i) GA drawing for APFC panel shall be got approved from the Accepting Officer before manufacturing of APFC panels (ii) Pre dispatch inspection shall be arranged for routine test at manufacturer\"s workshop by the contractor(iii)Test report for powder coating shall be provided with panels(iv) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process (v) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be demmed to be included in unit quoted rates.(vi) One 20 KVAr capacitor shall be fixed type (Connected directly )and others shall be controlled through APFC relay |
| 9 | Supply, installation, commissioning and testing of outdoor type, 440 Volts, AC, LT, APFC panel of130 KVAr capacity, factory fabricated, made out of 3.15mm CRCA sheet, CPRI approved, duly wiring with copper flexible wire of suitable ratingfor power control , Panel shall be dully powder coated with 8tanks sheet treatment ( De-greasing, water rinsing, de-rusting, water rinsing, Activation- phosphating, water rinsing, (Passivation thickness of powder coating shall not be less than 80 microns)in and including the following :-(A) Incoming :-(i) MCCB, 415 volts, 4 pole, 315 Amps, 36 kA with rotary Handle Mechanism - 01 No (ii) Digital Ammeter with built - in - selector switch Aux Supply 230 Volts, AC - 01 No(iii) Digital Voltmeter with built in selector switch Aux Supply 230 Volts, AC-01 No (iv) LED indication lamp 230 Volts, AC 22.5mm dia RYB-03 Nos(v) MCB 2 Amp, Single Pole-03 Nos (vi) Microprocessor APFC relay with single CT sensing 16 stages auxilary supply 230volts, AC - 01 No (vii) Aluminium busbar 25x10mm, TPN - 01 Set(viii)Auto/Manual Switch - 01 No (B)Outgoing :- (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos(ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 05 Nos (iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 08 Nos (iv) MCB Triple pole 63 Amps, 10 kA, \"C\" series - 02 Nos(v) MCB Triple pole 32 Amps, 10 kA, \"C\" series - 05 Nos (vi) MCB Triple pole 16 Amps, 10 kA, \"C\" series - 08 Nos(vii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos(viii) Capacitor duty contactor 3 pole 10 KVAr - 05 Nos |
| 10 | (ix) Capacitor duty contactor 3 pole 05 KVAr - 08 Nos (x) 22.5mm dia Push Button ON/OFF-15 set (xi) 22.5 mm dia LED Red - 15 Nos(xii) 22.5mm dia LED Green-15 Nos(xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT (xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel(xv )All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type Make : MCCBs/MCB/LED/PB/Capacitor/Contactor/APFC : L&T/Siemens/SchneiderMake (APFC Panel) : Tricolite/ Mc Layers/Asian Switchgear)(Notes : (i) GA drawing for APFC panel shall be got approved from the Accepting Officer before manufacturing of APFC panels(ii) Pre dispatch inspection shall be arranged for routine test at manufacturer\"s workshopby the contractor(iii)Test report for powder coating shall be provided with panels(iv) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process (v) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be demmed to be included in unit rate quoted against this item .(vi) One 20 KVAr capacitor shall be fixed type (Connected directly )and others shall be controlled through APFC relay |
| 11 | Supply, installation, commissioning and testing of outdoor type, 440 Volts, AC, LT, APFC panel of135 KVAr capacity, factory fabricated, made out of 3.15mm CRCA sheet, CPRI approved, duly wiring with copper flexible wire of suitable ratingfor power control , Panel shall be dully powder coated with 8tanks sheet treatment ( De-greasing, water rinsing, de-rusting, water rinsing, Activation- phosphating, water rinsing, (Passivation thickness of powder coating shall not be less than 80 microns)in and including the following :-(A) Incoming :-(i) MCCB, 415 volts, 4 pole, 320 Amps, 36 kA with rotary Handle Mechanism - 01 No (ii) Digital Ammeter with built - in - selector switch Aux Supply 230 Volts, AC - 01 No (iii) Digital Voltmeter with built in selector switch Aux Supply 230 Volts, AC-01 No(iv) LED indication lamp 230 Volts, AC 22.5mm dia RYB-03 Nos(v) MCB 2 Amp, Single Pole-03 Nos(vi) Microprocessor APFC relay with single CT sensing 16 stages auxilary supply 230volts, AC - 01 No(vii) Aluminium busbar 25x10mm, TPN - 01 Set (viii)Auto/Manual Switch - 01 No (B)Outgoing :- (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos (ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 05 Nos(iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 09 Nos |
| 12 | (iv) MCB Triple pole 63 Amps, 10 kA, \"C\" series - 02 Nos(v) MCB Triple pole 32 Amps, 10 kA, \"C\" series - 05 Nos (vi) MCB Triple pole 16 Amps, 10 kA, \"C\" series - 09 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos(viii) Capacitor duty contactor 3 pole 10 KVAr - 05 Nos(ix) Capacitor duty contactor 3 pole 05 KVAr - 09Nos (x) 22.5mm dia Push Button ON/OFF-16 set (xi) 22.5 mm dia LED Red - 16Nos(xii) 22.5mm dia LED Green-16 Nos (xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT(xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel(xv )All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type Make : MCCBs/MCB/LED/PB/Capacitor/Contactor/APFC : L&T/Siemens/SchneiderMake (APFC Panel) Tricolite/ Mc Layers/Asian Switchgear) (Notes :(i) GA drawing for APFC panel shall be got approved from the Accepting Officer before manufacturing of APFC panels (ii) Pre dispatch inspection shall be arranged for routine test at manufacturer\"s workshopby the contractor(iii)Test report for powder coating shall be provided with panels (iv) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process(v) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be demmed to be included in unitrate quoted against this item. (vi) One 20 KVAr capacitor shall be fixed type (Connected directly )and others shall be controlled through APFC relay |
| 13 | Supply, installation, commissioning and testing of outdoor type, 440 Volts, AC, LT, APFC panel of200 KVAr capacity, factory fabricated, made out of 3.15mm CRCA sheet, CPRI approved, duly wiring with copper flexible wire of suitable ratingfor power control , Panel shall be dully powder coated with 8tanks sheet treatment ( De-greasing, water rinsing, de-rusting, water rinsing, Activation- phosphating, water rinsing, (Passivation thickness of powder coating shall not be less than 80 microns)in and including the following :-(A) Incoming :-(i) MCCB, 415 volts, 4 pole, 630 Amps, 50 kA with rotary Handle Mechanism - 01 No (ii) Digital Ammeter with built - in - selector switch Aux Supply 230 Volts, AC - 01 No(iii) Digital Voltmeter with built in selector switch Aux Supply 230 Volts, AC-01 No(iv) LED indication lamp 230 Volts, AC 22.5mm dia RYB-03 Nos(v) MCB 2 Amp, Single Pole-03 Nos (vi) Microprocessor APFC relay with single CT sensing 16 stages auxilary supply 230volts, AC - 01 No(vii) Aluminium busbar 25x10mm, TPN - 01 Set(viii)Auto/Manual Switch - 01 No (B)Outgoing :-(i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 06 Nos(ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 06 Nos (iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 04 Nos (iv) MCB Triple pole 63 Amps, 10 kA, \"C\" series - 06 Nos |
| 14 | (v) MCB Triple pole 32 Amps, 10 kA, \"C\" series - 06 Nos(vi) MCB Triple pole 16 Amps, 10 kA, \"C\" series - 04 Nos(vii) Capacitor duty contactor 3 pole 20 KVAr - 06 Nos (viii) Capacitor duty contactor 3 pole 10 KVAr - 06 Nos(ix) Capacitor duty contactor 3 pole 05 KVAr - 04 Nos (x) 22.5mm dia Push Button ON/OFF-16 set (xi) 22.5 mm dia LED Red - 16Nos (xii) 22.5mm dia LED Green-16 Nos (xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT (xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel(xv )All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper typeMake : MCCBs/MCB/LED/PB/Capacitor/Contactor/APFC : L&T/Siemens/Schneider Make (APFC Panel) Tricolite/ Mc Layers/Asian Switchgear) (Notes : (i) GA drawing for APFC panel shall be got approved from the Accepting Officer before manufacturing of APFC panels(ii) Pre dispatch inspection shall be arranged for routine test at manufacturer\"s workshopby the contractor(iii)Test report for powder coating shall be provided with panels (iv) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process (v) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform,The cost of all above shall be demmed to be included in unitrate quoted against this item. (vi) One 20 KVAr capacitor shall be fixed type (Connected directly )and others shall be controlled through APFC relay |
| 15 | Material and labour for providingPlain Cement Concrete(PCC) in (1:4:8) type D-2 using 40 mm graded crushed stone aggregate as in foundation, filling and mass concrete etccomplete all as specified and directed . |
| 16 | Material and labour for providingPlain Cement Concrete(PCC) in ( 1:2:4) type B-1 using 20 mm graded crushed stone aggregatefor coping of poles including necessary form work for fairfinishedsurface complete all as specified and directed . |
| 17 | Material and labourfor40 mmgradedbroken stone aggregatefor laying and spreading around APFC panels,11 KV four pole and around the transformer ,complete all as specified and directed . |
| 18 | S&Fearth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthling etc. as required,32x6mmgalvanised iron strip, including taking down old unserviceable earth continuity conductor complete all as specified and directed . |
| 19 | Disconnecting, dismantling, taking down existing capacitor bank of any type and size complete all as specified and directed |
| 20 | Supply and laying or fixing or passing in trenches/ on pole/ through pipes,1100 volts grade XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor of cross section area 70 sqmm, 3.5 coreand testing on completionincluding taking out old unserviceable cable complete all as directed.( Note : Excavation and earthwork, sand cushioning and cable protection will be measured and paid for separately against relevant items of this BOQ.) |
| 21 | Supply and laying or fixing or passing in trenches/ on pole/ through pipes,1100 volts grade XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor of cross section area 240 sqmm, 3.5 coreand testing on completion including taking out old unserviceable cable complete all as directed.( Note : Excavation and earthwork, sand cushioning and cable protection will be measured and paid for separately against relevant items of this BOQ.) |
| 22 | M&L for earthingcomplete, in replacement, with galvanised steel earthpipe 3000 mm long, 50mm bore, medium grade,directly burried in the ground (earth pit not less than 2.25M deep below ground level) with top edge of earth plate not less than 1.50M deep below normal ground level, connected to galvanised iron strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 40mm bore GI pipe light grade including necessary fittings for protection of earthing strip, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be given 12mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge8 mesh per linear including50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS TMTbar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 2 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS/ GI bolts & washers as required and connection from earth test point to earth electrode with same GI earth strip alongwith protection pipe and testing on completion complete all as specified and directed.Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rates as quoted by the contractor. |
| 23 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, for laying of pipe, cable etc or n. exc.10 Sqm on plan and n. exc. 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and directed. |
| 24 | Returning, filling in excavated approved soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed. |
| 25 | Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point including spreading complete all as specified and directed. |
| 26 | Supply and spreading clean and dry fine sand free from sharp materials (unwashed) laying in trenches around the cable for cushioning in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. ( Note : Punned thickness shall be measured. ) |
| 27 | Supply and laying brick covering with width equal to length of brick as mechanical protection to cable with well burnt sub class ‘B’ bricks laid dry, flat, complete all as specified and directed by Engr in charge. |
| 28 | Supplying and fixing/ laying of 50mm bore dia GI pipe light grade in trenches/ under roads/ along pole/ wall including all fittings, ISI marked as required for cable protectionincluding dismantling of old unserviceable GI pipe completeall as specified and directed. |
| 29 | Supplying and fixing/ laying of 80mm bore dia GI pipe light grade in trenches/ under roads/ along pole/ wall including all fittings, ISI marked as required for cable protectionincluding dismantling of old unserviceable GI pipe completeall as specified and directed. |
| 30 | Supply and fixing MCCB, adjustable thermal and fixed magnetic setting type,4 pole 200 Amps rupturing capacity 25 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed |
| 31 | Supply and fixing MCCB, adjustable thermal and fixed magnetic setting type,4 pole 250 Amps rupturing capacity 36 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed |
| 32 | Supply and fixing MCCB, adjustable thermal and fixed magnetic setting type,4 pole 400 Amps rupturing capacity 50 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed |
| 33 | Supply and fixing MCCB, adjustable thermal and fixed magnetic setting type,4 pole 630 Amps rupturing capacity 50 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed |
| 34 | Schedule of credit amount of Rs. 1,07,020.00to be deducted during AOC |