Provision Of Fire Escape Ladder And Water Hydrant At Af Stn Suratgarh

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 30-Aug-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-Sep-2022

BOQ

Name of Work : PROVISION OF FIRE ESCAPE LADDER AND WATER HYDRANT AT AF STN SURATGARH
Sl. No. Item Description
1SCHEDULE `A\" PART - I (Building Works) is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only.
2Construction ofpump house building on permanent specification complete all as specified and shown on drawings.
3Construction ofFire Exit Staircase on permanent specification complete all as specified and shown on drawings.
4Construction of Semi UG sump 100000 ltrs capacity on permanent specification complete all as specified and shown on drawings.
5NOTE: Schedule ‘A’ Part IIto VIII are under Ser No. 2.01to 2.07 are Prepriced by MES.
6Lump sum price worked out by the Contractor for “EXCAVATION AND EARTH WORKS” as listed in Schedule ‘A’Part II
7Lump sum price worked out by the Contractor for“INTERNAL ELECTRIFICATION WORKS ” as listed in Schedule ‘A’Part III
8Lump sum price worked out by the Contractor for“ PCC ROAD, PATH, HARDSTANDING AND PQC FOR FIRE FIGHTINGWORKS ” as listed in Schedule ‘A’Part IV
9Lump sum price worked out by the Contractor for “MILD STEEL DOOR IN SRE, FENCING AND GATE WORKS” as listed in Schedule ‘A’Part V
10Lump sum price worked out by the Contractor for“ EXTERNAL ELECTRIFICATION WORKS ” as listed in Schedule ‘A’Part VI
11Lump sum price worked out by the Contractor for \"FIRE FIGHTING WITH FIRE ALARM AND GAS SUPPRESSION WORKS” as listed in Schedule ‘A’Part VII
12Lump sum price worked out by the Contractor for “DEMOLITION AND DISMANTLING WORKS” as listed in Schedule ‘A’Part VIII
13SCHEDULE `A\" PART - X MISC ITEMSis not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only.
14INTERNAL ELECTRICFICATION
15S & F 40 WattLED tube light fitting industrial type prewired with all accessories Conf to Cat Pt NoMAGNUMGRANDILS40WLED857PC of Havells or equivalent of make Bajaj/Philips inlcuding connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable 3 core of size 0.50Sqmm.
16S&F LED Bulk Head luminaire comprises of pressure die cast housing, acrylic diffuser & frame, having IP65 protection, energy efficient 13.5 Watt, conf to cat pt No LHEXCGP7IN5W013 of Havells or equivalent of make Bajaj/Phillips complete with all accessories, internally pre wired and connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable 3 core of size 0.50Sqmm all as required at site or directed.
17S&F LED street light fitting made of pressure die cast alumn alloy housing, acrylic diffuser & frame, having IP65 protection, energy efficient 45 Watt,complete with all accessories, internally pre wired and connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable 3 core of size 0.50Sqmm and mounting brackey made of GI tubing medium grade 25mm dia, 1.2 mtr long, bent to shape all as required at site or directed.
18Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC illuminated double sided pictorial exit signs provided with appropriate direction arrow painted in green on whitewith an 3W LED Lamp including in-built rechargeable batteries, charger and Driver suitable for 90 minute operation and including accessories for surface/ recessed or ceiling suspended mounting, complete all as specified and directed.
19Supply, installation testing and commissioning pure sine wave invertor 825 VA, 230 volts, 50 Hz complete with 12 V 165 AH maint free lead acid battery, complete assy housed in weather proof polycarbonate enclouser all as required at site or directed. Make AMRON/Microtech/Exide/Luminious
20EXTERNAL ELECTRIC SUPPLY
21Supply, installation , testing and Commissiong of LT feeder pillar box,Kisokindoor type, compartmentlised having separate compartment for incomer, outgoing and APFC sytem, CPRI type tested, LT 440 Volts, 50 Hz , 3 Phase4 wire supply , floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 3.15 mm thick MS Sheet CRCA on angle iron 50X50X6mm frame of size suitable to incorporate following accessories with front and rear opening doors, handle type locking arrangementpowder coated internally and externally, shall have channel base of appropriate size and mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 typeC-2 , using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed, including earth work complete comprising of following :
22(i) Incoming-(a) MCCB 200 Amps 4 Pole, Breaking capacity -36KA-01 No.(b) Phase indicating lamps LED type RYB -01 Set (Set of three).(c) Multifunctional Digital meter 01 Nos suitable to measure all electrical parameters with built in selector switch and-01 No and appropriate rating resin die cast CTs-03 Nos.(ii) Bus Bar- Electrolytic high conductivity aluminium bus bar of capacity 1.5 times the MCCB rating-04 Nos.(iii) Outgoing-(a) MCCB 4 pole 160Amps, 36KA-01 Nos.(b) MCCB 4 pole 100Amps, 36KA-02 Nos.All accessories prewired with suitable sizecopper conductor cable or strip as required or recommended by manufacturer
23FIRE FIGHTING AND FIRE ALARM
24Supply ,Installation,testing & commissioning ofelectrical driven main fire pump (As per CFEES recommended) suitable for auto operation & manual operation (both) including pressure switch consisting of following complete in all respect as reqd (plant room,flooded suction) comprising of the following:-(a)Horizontal type ,single stage ,centrifugal end suction,pump of cast iron body and bronze impeller with stainless steel shaft to ensure a minimum pressure of 5.5 Kg/sqcm at the highest and farthest outlet,at specified flow of 2850 LPM at 70 Mtr head (44.33WHP) running at 1450 RPM complete with mechanical seal pressure guage with GMcock on delivery side of pump including 50 M by pass arrangement (with 50 mm valve and upto 5 m heavy grade pipe )for periodical testing of working pump set conforming toIS-12469:1988. (b) Suitable HP,Squirral cage induction motor TEFC type 1450 RPM Synchronized speed suitable for operation on 415 Volt,3 Phase 50 Hz AC supply with IP 55 class of protrection for enclosure,horizontal foot mounted type with class F insulation confirming to IS-325-1978.
25(c) Common base frame for mounting pump and motor fabricated of mild steel channel as per manufacturer\"s recommendation with heavy duty anti vibration pads and painting of base frame in approved colour.(d)Suitable mechanical seal with mounting arrangement.(e) Suitable cement concrete foundation duly plastered with anti vibration pads including in cost,(f)Coupling and coupling guard for direct coupling of pump and motor. (g) Drain pipe with valve (50mm dia)(h)PVC insulated copper conductor of 1100 Volt grade ,3 core of suitable size from panel to electric motor.
26All as per Serial item 6.01 & 6.02 here-in-before but for LPM 2280 and WHP 35.46
27Supply ,Installation,testing & commissioning of Diesel driven main fire pump (As per CFEES recommended) suitable for auto operation & manual operation (both) including pressure switch consisting of following complete in all respect as reqd (plant room,flooded suction) comprising of the following:-(a)Horizontal type ,single stage ,centrifugal end suction,pump of cast iron body and bronze impeller with stainless steel shaft to ensure a minimum pressure of 5.5 Kg/sqcm at the highest and farthest outlet,at specified flow of 2850 LPM at 70 Mtr head (44.33WHP) running at 1800 RPM complete with mechanical seal pressure guage with GMcock on delivery side of pump including 50 M by pass arrangement (with 50 mm valve and upto 5 m heavy grade pipe )for periodical testing of working pump set conforming toIS-12469:1988.(b) Water cooled diesel engine of suitableBHP at 1450 RPM for the above pump complete with standard accessories and suitable cooling system (c ) Common base frame for mounting pump and motor fabricated of mild steel channel as per manufacturer\"s recommendation with heavy duty anti vibration pads and painting of base frame in approved colour.
28(d)Suitable mechanical seal with mounting arrangement. (e) Suitable cement concrete foundation duly plastered with anti vibration pads including in cost,(f)Coupling and coupling guard for direct coupling of pump and motor. (g) 3 hrs running capacity fuel storage tank fabricated from 16 SWG thick MS plate tank shall be provided with inlet,outlet,overflow,vent,drain connections,fitting connection,locking arrangement and level indicator.Tank shall be mounted on suitable steel structure (painted with 2 coats synthetic enamel paint over a coat of red oxide primer).Tank shall be provided with epoxy coat from inside and two coat of synthetic enamel paint outside over two coats of red oxide primer. (h)12 volts 180 AH lead acid battery, as per manufactrer recommendations,with boost/Trickle changer for starting the engine
29(j) provision of suitable logic control AMF /Automatic panel for starting the Engine automatically in the event of pressure drop beyond set limit on mains failure or failure of electric driven pump to start including pressure switch and suitable wiring between engine ,pressure switch and control panel complete with DC ammeter,DC voltmetre,indication lamp,push botton,hooter lock out ,timers,interlocking relays,fuel level indicators as reqd.
30All as per Serial item 6.04 & 6.06 here-in-before but for LPM 2280 and WHP 35.46
31Supply ,Installation,testing & commissioning ofelectrical driven Pressurisation pump (Jockey pump) (As per CFEES recommended) suitable for auto operation & manual operation (both) including pressure switch consisting of following complete in all respect as reqd (plant room,flooded suction) comprising of the following:- (a)Horizontal type ,single stage ,centrifugal end suction,pump of cast iron body and bronze impeller with stainless steel shaftwith flow 180 LPM at 90 Mtr head (3.6WHP) running at 1450 RPM complete with mechanical seal pressure guage with GMcock on delivery side of pump including 50 M by pass arrangement (with 50 mm valve and upto 5 m heavy grade pipe )for periodical testing of working pump set conforming toIS-12469:1988. (b) Suitable HP,Squirral cage induction motor TEFC type 1450 RPM Synchronized speed suitable for operation on 415 Volt,3 Phase 50 Hz AC supply with IP 55 class of protrection for enclosure,horizontal foot mounted type with class F insulation confirming to IS-325-1978.
32(c) Common base frame for mounting pump and motor fabricated of mild steel channel as per manufacturer\"s recommendation with heavy duty anti vibration pads and painting of base frame in approved colour.(d)Suitable mechanical seal with mounting arrangement. (e) Suitable cement concrete foundation duly plastered with anti vibration pads including in cost. (f)Coupling and coupling guard for direct coupling of pump and motor. (g) Drain pipe with valve (50mm dia)(h)PVC insulated copper conductor of 1100 Volt grade, 3 core of suitable size from panel to electric motor.
33Supply, laying, jointing and testing ductile iron DI pipe of 80mm dia including rubber gasket spigot & socket ends centrifugally cast type K-9 ISI marked in any length laid in trenches as required at site complete all as specified and directed.
34Supply, laying, jointing and testing ductile iron DI pipe of 100mm dia including rubber gasket spigot & socket ends centrifugally cast type K-9 ISI marked in any length laid in trenches as required at site complete all as specified and directed.
35Supply, erection, commisioning and testing of 80mm bore CI Sluice Valves , conforming to IS:14846. The valves shall be flanged having solid wedge gate valve, IS&Y Type, hand wheel with open-close indications etc all conforming to IS:780 but of nominal pressure rating of PN 1.6 as per TAC approved.
36Supply, erection, commisioning and testing of 100mm bore CI Sluice Valves , conforming to IS:14846. The valves shall be flanged having solid wedge gate valve, OS&Y Type, hand wheel with open-close indications etc all conforming to IS:780 but of nominal pressure rating of PN 1.6 as per TAC approved.
37Supply and fixingof CI foot valve of size 150mm dia flanged ends with swing type operation with rubber seat conforming to IS :4038 and all accessories including suitable nuts, bolts, washers etc, complete all as specified and directed.
38Supply and fixingof CI foot valve of size 250mm dia flanged ends with swing type operation with rubber seat conforming to IS :4038 and all accessories including suitable nuts, bolts, washers etc, complete all as specified and directed.
39Supply and fixingof CI foot valve of size 80mm dia flanged ends with swing type operation with rubber seat conforming to IS :4038 and all accessories including suitable nuts, bolts, washers etc, complete all as specified and directed.
40Supplying, fixing, testing and commissioning of double flanged flexicon rubber expansion joint 65mm dia (suitable for system pressure) of standard length as per manufacturer specifications including rubber gaskets, flanges, nuts, bolts and washers etc. of following sizes, complete all as specified and directed.
41Ditto but 80mm
42Ditto but 100mm
43Ditto but 150mm
44Ditto but 250mm
45Supplying, fixing, testing and commissioning of150mm dia C.IY Strainer (screwed / flanged) with stainless steel fin wire mesh perforated sheet basket with necessary flange / uionons nuts, bolts and washers etc., complete all as specified and directed.
46Ditto but 250mm
47Ditto but 80mm
48Supply, erection, commissioning and testing of C.I. Body 4 way fire Draw-off connection 150 mm dia with Gun metal coupling complete with in built check valve, 1 No. 150 mm dia sluice valve, 150 mm dia flanged outlet and matching flanges, nuts, bolt & washer.(Approved Make). 150 mm complete all as specified and directed.
49Supply, erection, commisioning and testing of Leg supported Mild steel Air vessel 250MM dia x 1.5m high adequate size to take care of pressure surges during operation of the system and venting of entrapped air in the system shall be complete with 20MM air relief valve, pressure gauge with isolation cock , 20MM drain valve and shutt off valve at the inlet.(closed with pipe caps on either end).complete all as specified and directed
50Supply and fix fire hydrant landing valve type A (single head outlet) gunmetalof 80 mm dialanding valve with 63 mm dia female outlet complete and 80 mm inlet with rubber blank cap and chain as per IS 5290-1983 ,suitable for brigade hose of 63 mm with couplings concorming to IS 903 complete all as specified and directed . Yard Hydrant
51Supply and fix fire hydrant landing valve type A (double head outlet) gunmetalof 80 mm dialanding valve with 63 mm dia female outlet complete and 80 mm inlet with rubber blank cap and chain as per IS 5290-1983 ,suitable for brigade hose of 63 mm with couplings concorming to IS 903 complete all as specified and directed. Yard Hydrant
52Supply, erection and installation of Fire Hose Cabinet to be mounted externally near the Hydrant Post fabricated from 16 SWG MSSteel of appox size 800 mm x 600 mm x 250 mm with a canopy , door with 4 mm glass encased in heavy grade rubber beading, a key box in built in the box, suitable to accomodate one hydrant valve, one branch nozzle and two 30 mtrs hose, weather proof, Finished with P.O. fire red color, mounted on suitable angle iron legs for free standing at a height as required or directed. ( Sample to be approved prior to entire supply)
53Supply, erection and installation of Fire Hose Cabinet to be mounted internally on walls Post fabricated from 16 SWG MSSteel of appox size 800 mm x 600 mm x 250 mm, door with 4 mm glass encased in heavy grade rubber beading, a key box in built in the box, suitable to accomodate one hydrant valve, one branch nozzle and two 15 mtrs hose, weather proof, Finished with P.O. fire red color, suitablemounting arrangement at a height as required or directed. ( Sample to be approved prior to entire supply).
54Supply ,fixing, testing and commissioning of63mm dia 15 mtr longControlled perclating rubbberised fabric hose conforming toIS 8423 (type \"A\") including gun metal male and female instantaneous coupling,bound and rivetted to hose pipe with 1.5 mm dia copper wire complete in all respects ,hose BSI marked ,conforming to IS 636 type II andcomplete male female coupling conforming to IS 903 complete all as specified and directed.
55Supply ,fixing, testing and commissioning of63mm dia 30 mtr longControlled perclating rubbberised fabric hose conforming toIS 8423 (type \"A\") including gun metal male and female instantaneous coupling,bound and rivetted to hose pipe with 1.5 mm dia copper wire complete in all respects ,hose BSI marked ,conforming to IS 636 type II andcomplete male female coupling conforming to IS 903 complete all as specified and directed.
56Supply ,fixing,testing and commissioning of wall mounting swinging type First aid firehose reel with drum,hanging bracket,30 mtr long and20mm dia high pressure hose reel as per IS 444 with gunmetal shut off nozzle having 5mm dia orifice. The hose reel shall be conforming to IS 884-1985.Rate shall includingfor 25 mm dia MS pipe connection from riser to hose reel sockets,nipples,elbows and ball valve (25mm dia). Drum shall be fixed on adjoining wall through anchor fasteners/cement concrete book or MS stand as per site requirement and the rate for fixing/hanging items in the rates quoted(for internal hydrant and one each an either side of stage)complete all as specified and directed.
57Providing supply, erection and commisioning of Gun metal, short type, instantaneous pattern Branch pipe to suit fire hose delivery coupling of 63 mm size complete with G M nozzle of 20 mm nominal size conforming to IS 8090, complete all as specified and directed.
58Supplying and fixing following size electrically operated water flow switches (Vane type) including tamper switch and accessories, complete with tap off socket arrangement as required, with potential free contact with 2 Nos. NONC, complete all as specified and directed.
59Supplying and fixing 50 mm dia inspectors test assembly with built in test valve, sight glass, sectional drain valve, union with corrosion resistant orifice, complete all as specified and directed.
60Supplying, fixing, testing & commissioning of25 mm dia auto air vent valve (PN-16) on top of each sprinkler riser with ball valve, flanged inlet connection etc, complete all as specified and directed.
61Supplying & fixing dial type (100 mm) pressure gauge with isolation ball valve suitable for working pressure of 250 PSI.Cost shall be inclusive of Supplying any short pieces, nipples, elbows etc, complete all as specified and directed.
62Supply and fixing M.S. puddle flanges fabricated from 750 mm long pipe pieces madeup ofR.C.C. water tanks wall / slab. The entire fitting shall be hot dipped galvanised (Flanges shall confirm to BS10 Table E) of 80 mm dia (Screwed ends MS plate 6 mm thick; 100 mm x 100 mm plus dia of pipe), completeall as specified and directed.
63Supply and fixing M.S. puddle flanges fabricated from 750 mm long pipe pieces madeup ofR.C.C. water tanks wall / slab. The entire fitting shall be hot dipped galvanised (Flanges shall confirm to BS10 Table E) of 100 mm dia (Flanged ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe), completeall as specified and directed.
64Supply and fixing M.S. puddle flanges fabricated from 750 mm long pipe pieces madeup ofR.C.C. water tanks wall / slab. The entire fitting shall be hot dipped galvanised (Flanges shall confirm to BS10 Table E) of 150 mm dia (Flanged ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe), completeall as specified and directed.
65Supply, installation, testing and commissioning 3 phase and neutral, 415 volts indoor type factory made free standing, floor mounting, dust and vermin proof cubical type, LT feeder pillar box fabricated from 2 mm thick (minimum) CRCA sheet with anti corrosive coating and finally epoxy powder coating of lint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos ofaluminimumbusbar 400 amp including suitable aluminium earth strips conforming to IS and all as specified with supply and to accommodate the MCCBs and metering equipment :-INCOMING(i) MCCB 4 Pole 160 amp 50 Hz, 415 V with reputring capacity 35 KA with microprocessor based release - 01 No (ii)Multifunctional meter Digitalflush type with in built selector switch - 01 No(iii)LED INDICATORS Red, Yellow and Blue -INCOMING AND EACH OUTGOING (iv) CTs of ratio 160/5 having accuracy class 1 and VA burden 15 VA:- 3 Nos OUTGOING(A) Main pump(i) MCCB 3 Pole 100amp 50Hz,415 Hz with electronic release - 01 No( Main pump) (ii) Fully automatic star delta starter100HP, in open execution comprising air break contactors, over load protection relays, single phase protector, time delay relay, auxiliary contacts for auto functioning, selector switch for auto/manual mode etc duly prewired all as required and directed.iii) Push button for manual ON/OFF of the Pump.
66iv) LED Indicators for ON/OFF v) Virtual serial port driver(VSPD) 01 nos(B) Jockey pump(i) MCCB 3 Pole 40amp 50Hz,415 Hz with electronic release - 01 No( Jockey pump) ii) DOL starter 10HP in open execution comprising air break contactor, over load protection relays, single phase protector, time delay relay, auxiliary contacts for auto functioning, selector switch for auto/manual mode etc duly prewired all as required and directed.iii) Push button for manual ON/OFF of the Pump.iv) LED Indicators for ON/OFF v) Virtual serial port driver(VSPD) 01 nos(C) Diesel engine driven Fire pumpi) Battery charger 10A 01 nosii) Control circuit for auto operation of the pump.iii) Push button for manual ON/OFF of the Pump.iv) LED Indicators for ON/OFF v) DC hooter 12v 01 Nosall accessories prewired with suitable size copper conductor cables, wiring from panel to pumps/control switches etc within plant room, MCBs for protection of relays/contactor coils/measuring instrumentsall as required to make the system functional on auto/manual mode completeall as specified and directed.
67M&L forearthing with steelearth plate electrode ofsize 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate,40mm dia GI tubing light grade protection pipe upto test point, 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate and filling of vegetable soil to the remaining 10%,removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I completeall as specified and directed.
68Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 250 mm dia suitable for 0.4 Mpa working pressure, completeall as specified and directed.
69Supplyinstallation testing and commissioning of modular dry powder typefire extigusher 2 kgs ceiling suspended capacble of covering 3 mtr dia when installed at 3.7 mtr hight complete all as specified and as directed.
70Providing supply, erection and installation of Dry Chemical Powder Fire Extinguisher ( ABC Type ) 9 Kgs capacity completewith chromium plated gun metal union(cap), fitted with braided hose and opennozzle with initial charge of DryChemical Powder and gas cartridgeThe extinguisher is internally coated with Lead Tin by electrolitic Process and externally coated with lead tin with Fire red Paint and cylinder bearing No.(IS:15683:2006) and the gascartridge bearing with ISI certitifcation mark, completeall as specified and directed.
71Providing supply, erection and installation of carbon-di-oxide 4.5 Kgs capacity fire extinguisher, made of mild steel with chromium plated gun metal union (cap), fitted with braided hose The extinguisher is internally coated with Lead Tin by electrolitic Process and externally coated with lead tin with Fire red Paint and cylinder bearing No. IS:15683 and the gascartridge bearing with IS certitifcation mark, completeall as specified and directed.
72Providing supply, erection and installation of CLEAN AGENT TYPE fire extinguishers, 4.0 kg capacity conforming to IS:15683 with extinguishing agent: FE 36 (HFC-236fa) and enviromentally save with ZERO ODP, wall bracket handle fitted with high pressure flexible discharge hose with ISI certitifcation mark, completeall as specified and directed.
73Providing supply, erection and installation ofMECHANICAL FOAM TYPE fire extinguishers, 9 Ltrs capacity conforming to IS:13386 with extinguishing agent: water+AFFF and propelling Nitrogen gas, wall bracket handle fitted with high pressure flexible discharge hose with discharge throw of 2 - 5 Mtrs.,with ISI certitifcation mark, completeall as specified and directed.
74Providing supply, erection and installation oftrolley mounted MECHANICAL FOAM TYPE fire extinguishers, 45Ltrs capacity conforming to IS:13386 with extinguishing agent: water+AFFF and propelling Nitrogen gas, wall bracket handle fitted with high pressure flexible discharge hose with discharge throw of 2 - 5 Mtrs.,with ISI certitifcation mark, completeall as specified and directed.
75Providing supply, erection and installation of Dry Chemical Powder Fire Extinguisher ( ABC Type ) 6 Kgs capacity completewith chromium plated gun metal union(cap), fitted with braided hose and opennozzle with initial charge of Dry Chemical Powder and gas cartridgeThe extinguisher is internally coated with Lead Tin by electrolitic Process and externally coated with lead tin with Fire red Paint and cylinder bearing No.(IS:15683:2006) and the gascartridge bearing with ISI certitifcation mark, completeall as specified and directed.
76Supply installation testing and commissioning of self contained mobile foam(as per fire norms) for rapid deployement of foam extingushing agent to fire in chemical spills of capacity 100 cum where (in most cases)proves ineffective in quenching hydro carbon liquid based fires in petroleum, chemical and other similer industries. This compact ready for action equipment consist of foam tank inductor branch pipe and fire hose box (double door)(900mmx600mmx500mm)16 guage suitable for 02 Nos 15 m Hose along with male and female coupling for ready to plug in to a suitable water supply as required to complete the system and the following details are required as under(i)Working pressure 7 Kg/cm2 to 10 Kg/cm2(II) Max allowable back pressure 65% of inlet pressure(III)Hydrraulic test pressure 25 KGf/cm2 for 5 minutes(IV)Inductor 3% or 6 % fixed type(V)inlet/outlet variable type 63 mm instataneous male GM/SS coupling(V)Dip tube:SS304(VII)Pickup tube :PVC brided flexible house complette
77Material and Labour for Cutting/Taping ofCI/DI/MS pipe of bore size 80/100mm in position for reducing to required length for insertion of new tees, branches etc including necessary welding or any other work complete all specified and as directed.
78Material and labour for DI specials such as tees, bends of any sizeand radius, tapers, collars, tail pieces, caps and plugs etc.
79Construction of valves pit chamber having internal dismention 90 cm x 60 cm x 60 cm (internal height) using PCC (1:4:8)40 mm graded stone aggregate for foundation 15 cms thick, 23 cm thickwall in CM (1:4) 10 mm thick rendering all around the brick work with 1:6 cement mortar PCC (1:2:4) type B1 coping with 20mm graded aggregate for grouting MS frame including 8mm thick MStop sheet cover with locking arrangement, MS frame made out of 40 x 40 x 6 mm thick angle iron including painting of steel surface with two coats of synthetic enamel paint over a coat of red oxide primers finishing coal including necessary excavation in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 mtrs all as directed
80Supply and fixing MS pipe header as per IS 3589, 250 mm dia size min 6 mm thick 4 mtr length with flanged ends closed with dead plates not less than 20 mm thick fixed with nuts bolts and washer and rubber gasket and including provision of following incoming and outgoing connections of MS pipe, Heavy duty, Class C, of length 300 mm with flanged ends with two coats of synthetic enamel paint over one coat of red oxide primer all as specified.(a)200/150/100/65 mm dia incoming - 03 No.(b) 150/100 mm dia outgoing - 02 NoNote : (i) CI Sluice valve/Butterfly valves shall be measured seperately under respective items.(ii) Cost of any other size branch as incoming or outgoing if needed at site shall be included in the quoted rate.(iii) Cost of the brick work required to support the header is included in the quoted rate.
81Supply and fixing MS pipe header as per IS 3589, 250 mm dia size min 6 mm thick 4 mtr length with flanged ends closed with dead plates not less than 20 mm thick fixed with nuts bolts and washer and rubber gasket and including provision of following incoming and outgoing connections of MS pipe, Heavy duty, Class C, of length 300 mm with flanged ends with two coats of synthetic enamel paint over one coat of red oxide primer all as specified.(a)200/150/100/65 mm dia incoming - 03 No.(b) 150/100 mm dia outgoing - 01 NoNote : (i) CI Sluice valve/Butterfly valves shall be measured seperately under respective items.(ii) Cost of any other size branch as incoming or outgoing if needed at site shall be included in the quoted rate.(iii) Cost of the brick work required to support the header is included in the quoted rate.
82Supply,Fixing, Testing & Commissioning ofCP Bronze/GM Sprinklersas per IS:9972,comprises of15 mm dia conventional pattern,68 degree C,quatzoid bulb type pendent/upright sprinklers ,UL/FM listed/approved
83Supply, Installation,Testing and Commissioning of Mild steel black pipe Class \"C\" conforming toIS:1239 for pipes upto 150 mm dia and IS:3589-1991 for pipes above 150 mm dia. including cutting, screwing, welding etc. complete with forged steel / butt welded fittings viz. tees, bends, elbows, flanges, reducers, clamps / hangers etc. including cutting holes and chases in brick or RCC walls/slabs and making good the same complete including painting of pipes, fittings & steel work with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade. Refer technical specifications for details.
8480 mm Dia
8565 mm Dia
8632 mm Dia
8725 mm Dia
88Supply, Installation,Testing and Commissioning of Cost Iron Butterfly valve as per IS:13095,with SS disc, shaft, seating rings, internal fasrening with matching flange,nuts, bolts & washers etc. complete (PN 1.6) of following sizesas per site requirement. For details, refer tender specifications.
8980 mm Dia
9065 mm Dia
9150 mm Dia (butterfly or Ball Valve)
9220 mm Dia (ball valve)
93Providing and fixing in position 100 mm dial type (Glycerene filled Industrial / rugged application type) pressure gauges with isolating valve of approved makes, fitted in the pipeline via socket connection (NO direct weld allowed) in both the scales (meters & British units) with required fittings (PN - 16).
94Supply, installation, testing and commissioning of fire signage of photo luminescent on aluminium sheet of 1.0 mm (± 10%) containing lumigen-III as base chemical, covered with U/V stabilized coating size 450 x 200. (All supports shall be approved by EIC /consultant and shall be weather protected)
95Fire signs
96General signs
97Supplying and fixing approved make 25mm dia. Automatic air release valve.
98Supplying, erecting & commissioning Fire Hose cabinet comprising of internal hydrant.Two keys in recess type compartment for break glass,19mm dia. Reinforced hose reel 15m length as per IS 5132 fitted with 6.35mm dia nozzle and shut off valve (IS 884 - 1969) . The hose reel shall be recessed swing typewith reel drum.The hose shall be provided with coupling as per detailed specifications.The Frame shall comprise of suitable size and made of 16 guage \"MS sheet to house the above accessories. The cabinet shall be firmly fixed to the wall with expansion bolts. The cabinet shall be powder coated both internally and externally. The door shall be provided with suitable locking arrangement as per standards.The quote shall include fixing the cabinet to the wall & making good to the wallNOTE: Contractor shall include in his rate for providing level controller, cabling from level controller/pressure switch to panel etc. complete as required to operate the system automatic/manual. Pump shall be protected against running
99Supply, installation, testing & commissioning of analog addressable Fire Alarm Control Panel (FAC), 2 loop (NFS 3030D) with battery charger and with the battery back up for 8 hours normal operation and one hour alarm operation.The FACP shall eb expandable upto 10 loop.the FACP shall include a full featured operator interface control and annuciation panel that shall include a bcklit 640- character liquid crystal display, and a QWERTY style alphanumeric kaypad for the feiled programming and control of the fire alarm system.System shoudl support upto 159 detectors and 159 modules in one Loop.the panel shall be UL listed and FM approved and comply UL 864, 9th Edition requirement.The enclosure shall also be UL listed.The quoted rate shall include supply of necessary software and harware for programming the panel with all necessary licence. (20% take extra). 2 Loop Panel(NFS3030D).
100Network Repeater Panel with 6 inch or 640-characters; The LCD shall Display all,events / Each 2Detectors, devices status of complete systems in the networked, The NRP shall be equipped with QWERTY Keypad. Mounting options include an enunciator’s box, and blank modules are required for mounting Complete as required as per technical specification.
101Supply, installation, testing and commissioning of Wall/ Ceiling mounted type FS24X, is a multi-spectrum Quad. Band Triple IR (IR/IR/IRNis) fire/flame detector designed to,meet the exact needs of hangar applications, delivering excellent sensitivity and nuisance alarm rejection. Its large monitoring range of greater than 60 m /200 ft on \"Very Sensitive\" setting for the detection of a 0.1 f1\"12/1 ft2 n-Heptane reference fire, allows FS24X to deliver the greatest volumetric coverage of all available multi-spectrum IR detectors . In addition, this device also offers a much larger cone of vision than comparable Quad Band IR/Vis solutions (90° full 100% ± 45° from _on axis/110° full 100% ± 55° from on axis). including mounting bracket, power Supply unit. Complete as required as per.technical specification.
102Supply, Installation, Testing & Commissioning of Intelligent and electronically addressable Duct Detector (high velocity) with the hard addressing feature, with housing, sampling tubes,LED and bypass switch for testing complete as per specification.(DNR)
103Supply, Installation, Testing.& Commissioning of Intelligent and electronically addressable, fixed temperature (57°C) thermostat type heat detector with mounting base, LED, fixed temperature setting as per specification. (For Kitchen ) completeall as specified and directed.
104Supply, lnstallation, Testing & Commissioning ofDual Action Addressable Manual Pullstation with ,Address Switch to programme the modules which monitors and reports contact status..Complete as required as per technical specification.(NBG-12Lx), completeall as specified and directed.
105Supply, lnstallation, Testing & Commissioning of Fault Isolator Module, which should not ocupy any address in the loop, should be capable of monitoring shorted loop circuit and automatically restore, communications when shorted conditions are corrected, complete as required as per technical specification.(lso-X), completeall as specified and directed.
106Supply,installing,testing and commissioningof 2c x1.5sq.mm,PVC insulatedFRLS Armoured copper cable for SLC Loop & Power Supply, confirming to ISstandards and specifications complete as required as per technical specification.
107Supply, installing testing and commissioning of 4c x 2.5 sq. mm, PVC insulated FRLS Armoured copper cable for SLC Loop1 & Power Supply, confirming to IS standards and specifications complete as required as per technical specification.
108Supply, installation, Testing & commissioning of PESO Each 2 251433.00 502866.00 MR Approved and UL listed 180 L SEAMLESS CYLINDER (designed as per. IS 7285 part 2) with PESO approved valve, PESO approved & UL Listed OEM factory filled with 3M Novec 1230 suppression liquid, pressurized to 70 bar with Contracted Pressure !3uage @ 65 Deg C (for Room- 01, 1w+1S)
109Supply, installation; Testing & commissioning of PESO Approved and UL listed 34 L SEAMLESS CYLINDERVJ (designed . as per IS 7285 part 2) with PESO approved J valve, PESO approved & UL Listed OEM factory filled with 3M Novec 1230 suppression liquid, pressurized to 70 bar with Contracted Pressure Guage @ 65 Deg C (for Room- 02, 1 W +1S)Note:-All cylinders are furnished :With a name plate that provides the following information that is specifc to that container:(i) Assembly number(ii) Weight information(iii) Agent weight(iv) Gross weight(v) Installation Instructions(vi) All cylinder finished with red colour.
110M & L NOVEC 1230 AGENT PER 1 KG
111M & L for 180 Litre cylinder wall mounting braket having epoxy power coated to mount the cylinder in vertical position. Each cylinder shall have 2 bracket complete all as specified and directed.
112M & L for 34,45,60 & 80 litre 267ø container bracket having expoxy powder coated to mount the cylinder in vertical \" position. Each cylinder having 2 bracket complete all as specified and directed.
113M & L for Male adaptor (1/4\"\" BSPT x 1/4\" BSPP)complete all as specified and directed.
114M & L for Male elbow (1/4\" NPT x 1/4\" BSPP)complete all as specified and directed.
115M & L for DN1/4\" PTFE flexible actuation hose x 710mmcomplete all as specified and directed.
116M & L for Male pilot hose connector ( 1/4\" BSPP x 1/4\" BSPP)complete all as specified and directed.
117M. & L for removabletype Electrical actuator - standard(bridge rectifier) c/w placement switch (TLX)Electrical actuator shall have following specification.(i) Body: Mild Steel or Dull Nickel(ii) Swivel nut: Brass(iii) Actuation pin: Stainless Steel(iv) Actuation type: Latching(v) Reset requirements: Manually by reset tool(vi) Nominal voltage: 24 V DC(vii) Back EMF Protection: Bridge rectifier
118M& L for Local manual actuator having manual release Each 4valve of bras body.(i) The manual actuator device shall be used for opening the container at zone selection point for discharge manually.(ii) The manual discharge actuator shall be of the electrical/pneumatic actuation type and shall be supervised at the AUTOMATIC FIRE SUPPRESSION SYSTEM GAS RELEASE PANEL.
119M & L for Discharge pressure switch - standard (UL/FM). The pressure switch is activated by pressure from the agentduring discharge and can be used to signal to a control panel that the system has actually discharged. The pressure switch latches on operation and has a reset button. Pressure Switch shall have following specification. (i)\"Housing: Die cast Aluminium(ii) Pressure Connection: Nickel Plated Brass(iii) Connection: 1/4\" NPT Female(iv) Conduit Thread: 1/2\" NPT Female(v) Installation Environment: non-corrosive I indoor(vi) IP Rating: IP65(vii) DC Switch Rating: 1A 24v de
120M & L for 50 mm discharge hose of Durable reinforced synthetic rubber construction shall be suitable to withstand atsystem pressure having minimum length of 500 mm complete all as specified and directed..
121M & L for 25 mm discharge hose of Durable reinforcedsynthetic rubber construction shall be suitable to waithstand at system pressure having minimum length of 500 mm.
122M & L for 50 mm manifold check valve complete all as specified and directed.
123M & L for 25 mm manifold check valve complete all as specified and directed.
124M & L for Brass nozzle - 50mm 360 degree NPT - India complete all as specified and directed.
125M & L for Brass nozzle - 15 mm 360 degree NPT - India complete all as specified and directed.
126M & L for System Warning Sign - SAPPHIRE PLUS complete all as specified and directed.
127M & L for Agent Discharge Warning Sign - SAPPHIREPlus complete all as specified and directed.
128Supply & Installation of Manifold (Sch 80; ASTM A106 Gr B)with mounting and all accessories complete all as specified and directed.
129Supply. & Installation of Conventional Gas release panel withbatterybackup(120 minslocallysupplied withall interconnections) complete all as specified and directed.
130Supply & Laying of NOVEC Piping as required, Sch 40 ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold, position & support the Manifold and Piping properly. Approx qty. Indicated in the boq.Vendor should submit pipe network calculation for final quantity of pipe complete all as specified and directed.
131Supply & Laying of 2 C x 1.5 Sq.mm stranded copperconductor, XLPE insulated, extruded PVC inner sheathed overall armored flame retardant low smoke (FRLS} outer shelted type 1.1 KV grade cable. Cable should quote with GI saddle spacers, Glands, Junction Boxes (wherever required}, terminals, Ferruling complete. (Cable colour should be RED}complete all as specified and directed.
132Supply & Installation of Abort switch complete all as specified and directed.
133Supply & Installation of Emergency Actuation Switch complete all as specified and directed.
134Note:- The testing of complete . system, room integrity system incld. Pressure testing of piping with nitrogen as per NFPA 2001 & Flushing with Nitrogen shall be carried out in presence of rep. of accepting officer. contractor rep, E-in­ Charge, rep of user ancl J T AC company . The rates are deemed to include this aspect and all material and T&P required for testing shall be provided by contractor. The cost of pressure testing of piping with nitrogen will be measured and paid in relevant item of BOQ
135Supply ,install,testing ,commissioning of pressurising system for staircase and lift well in SRE bldg by providing Tube axial flow fans , suitable for three phase operation at 1450 RPM, Long case tube axial flow fans complete with all accessories, suitable for wall mounted /Floor Mounted/ ceiling suspended installation. The fan shall be supplied with suitable 3PH/4P motor at 1450 RPM, and shall be selected for 40 mm static pressure 011/G) , (F Class motor insulation) All fan with fire retardant Canvas connection, bird screen and Gravity dampers. Fans capacity as per below mentioned. These fans to be supplied with Electrical starter panel (IP54) and all interconnecting cables (FRLS-ZH) and all accessories, and shall be integrated with Fire alarm panel. The unit of following CFM will serve as supply of fresh air to the pressurization zone.
13618000 CFM Staircase/Lobby Pressurization (SP 40)
13710000 CFM Lift Well Pressurization (SP 40)
138Supply, fabrication, installation, balancing and commissioning of sitefabricatedGSSsheetmetalrectangularducting22SWG/ 0.711mm as per IS-655 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved all as specifed and directed.
139Supplying, installing, testing and balancing of aluminium supply airsq.m 8 grills without VCD/return air grills of various sizes. Each grill shall be with fixed horizontal front bar at Zero/15 Deg deflection through the collar and registerall as specifed and directed.
140Fire damper with Actuator (Pressurzation system)Supplying, Fixing, testing and commissioning of fire dampers(along with required integration) in MUA supply air duct/main branch and in Pressurization fan main ducting where required (refer tender drawing for location details) of required sizes i/c control wiring, The damper shall be motorized and spring return so as to close the damper in no signal or in event of power failure automatically and open the same in case of signal received. The spring return action shall be inbuilt mechanism and not externally mounted. Scope includes safe mounting and all accessories, and inetgration with MUA power panel and fire panel, as needed all as specifed and directed.
141Electric actuator with necessary linkage to actuate fire damperscomplete with required wiring (fire survival) and associated aq::essories. Note: Fire dampers shall be supplied with sensors/actuators/control etc duly .factory fitted and tested at manufacturers works and certificate to this effect produced along with delivery of fire damper. In case of fire damper installed with MUA, the damper shall also be closed in the event of fire signal, but opens when the fan of that respective zone is switched ON, completing the action qucikly, as required and as per Electric Actuator.• I Electric actuator with necessary linkage to actuate fire damperscomplete with required wiring (fire survival) • and associated accessories. Note: Fire dampers shall be supplied with sensors/actuators/control etc duly .factory fitted and tested at manufacturers works and certificate to this effect produced along with delivery of fire damper.In case of fire damper installed with MUA, the damper shall also be closed in the event of fire signal, but opens when the fan of that respective zone is switched ON, completing the action qucikly, as required and as per Electric Actuator
142Fire Damper with actuator.Note : (i) Contractor shall get the detailed design and shop drawings made ( for stair case and lift well pressurising system) from any one of the TAC company naming, Effisense Consulting, NewDelhi/S&T,NewDelhi/VPAEnterprises;and submit to Accepting officer for final approvals through proper channel before procurement of materials(ii) The testing of complete system as per NFPA 2001/NBC 2016 shall be carried out in presence of rep of accepting officer, contractor rep, rep of user and above mentioned TAC company. The rates are deemed to include this aspect and all material and T&P required for testing shall be provided by contractor.
143Demolition of cement concrete (PQC) (Rigid/Flexible Pavement) by PQC cutting machine of any depth exc 15cm thickness but above ground floors specifically provided for complete.Note:-Nothing extra shall be paid for removing ofdemolished material from siteto a out side of MOD land fromthe starting point complete all as specified and as directed
144Providing 400 micron polythene film as per IS-2508 laid over sand layer including all necessary cutting, overlaps not less than 300mm and wastagecomplete all as specified and as directed.Note:- Sand layer measured and paid separately.
145Supply only non circular polyster fiber as secondary reinforcement with circumcircle diameter 30-35 micron design for melting point 240-260 degree celcius and having of 1.34 to 1.4 recron @ 1 kg/Cum of concrete complete all as specified and directed.
146Forming 25mm wideExpansion joint using pre-formed filler board and filled with polyurethane joint filling sealant using mechanical means upto full depth(depth minimum above the back up rod dia 32 mm) with minimum performance guarantee of 10 years and minimum Movement Accommodation Factor (MAF) + or - 30% conforming to the requirement of BS:5212, BS-4252 and EN-141875-2003 for Hydrolysis/water resistance test including two coats of primer and providing 10 mm dia,approved quality closed cell polythene back up rod complete all as specified and shown on drawings..Note: (i) Edges of joints shall be rounded up by mechanical means at the time of final cutting. (2) Initial cutting shall be carried out within 24-36 hours of casting. (3) Final cutting, rounding of edges, use and waste of back up rodto avoid deposition of foregion materials in the joint upto final filling of jointsshall be carried out after 28 days . (4) Applying masking tape on the edges of joint to prevent accidental slippage of sealant on top surfaces and to give a neat finish to the sealant and removing the masking tape after sealant is applied as required.
147Forming 8mm wide x 25 mm deep construction joint using diamond cutter and filled with polyurethane joint filling sealant using mechanical means upto min depth of 10mm (depth minimum above the back up rod dia 10 mm) with minimum performance guarantee of 10 years and minimum Movement Accommodation Factor (MAF) + or - 30% conforming to the requirement of BS:5212, BS-4252 and EN-141875-2003 for Hydrolysis/water resistance test including two coats of primer and providing 10 mm dia,approved quality closed cell polythene back up rod complete all as specified and shown on drawings..Note: (i) Edges of joints shall be rounded up by mechanical means at the time of final cutting. (2) Initial cutting shall be carried out within 24-36 hours of casting. (3) Final cutting, rounding of edges, use and waste of back up rodto avoid deposition of foregion materials in the joint upto final filling of jointsshall be carried out after 28 days . (4) Applying masking tape on the edges of joint to prevent accidental slippage of sealant on top surfaces and to give a neat finish to the sealant and removing the masking tape after sealant is applied as required.
148Forming 6 x 110 mm wide contraction (dummy) joint using diamond cutter & filled with polyurethane joint filling sealant using mechanical means upto minimum depth 10mm (depth minimum above the back up rod 8 mm dia with minimum performance guarantee of 10 years and minimum Movement Accommodation Factor (MAF) + or - 30% conforming to the requirement of BS:5212, BS-4252 and EN-141875-2003 for Hydrolysis/water resistance test including two coats of primer and providing10mm dia approved quality closed cell polythene back up rodcomplete all as specified and shown on drawings. .Note: (i) Edges of joints shall be rounded up by mechanical means at the time of final cutting. (2) Initial cutting shall be carried out within 24-36 hours of casting. (3) Final cutting, rounding of edges, use and waste of back up rodto avoid deposition of foregion materials in the joint upto final filling of jointsshall be carried out after 28 days. (4) Applying masking tape on the edges of joint to prevent accidental slippage of sealant on top surfaces and to give a neat finish to the sealant and removing the masking tape after sealant is applied as required.
149M&L for coloured designer Chequered cement concrete tiles 300X3000X25mm thick, set, jointed and pointed in neat cement slurry in floors with grey cement and pigments complete all as specified and as directed.
150Demolition of DLC and WMMof any specification and thickness in existing Pavement complete all as specified and directed.Note:-Notheing extra shall be paid for removing ofdemolished material from siteto a out side of MOD land fromthe starting point complete all as specified and as directed
151Material and labour for wet mix macadam (WMM) of 150mm thick (compacted thickness) in two layers each layer 75 mm thick compacted separately with coarse aggregates of grading as per MORTH specifications & IRC by using mechanical paver, rolled and consolidated to required gradient and camber complete with plate vibrator to achive void free compaction complete all as specified and directed.NOTE:- Three layer of 10 Sqm shall be measured as a single unit.
152M&L for dry lean concrete (DLC) of grade M-15 (Design Mix) 150 mm thick with minimum cement content 250 kg per Cum as in sub base course, laid, spreading with mechanical paver and rolled with 8 to 10 tonne power road roller, made up to true surfaces including binding with screening grade \"A\" and consolidated to required gradient and camber complete all as spcified and directed. Note :- No price adjusment of cement shall be made in the variation in quantity if excess cement used/approved in the work as result of design mix.
153M & L for forming 8mm wide x 25mm deep construction joint using diamond cutter and filled with joint polyurethane joint fillinf sealent using mechanical means upto minimum depth 10mm (depth minimum above the10mm dia backup rod) with minimum performance guarantee of 10 years and minimum movement accommodation factor (MAF) + 30% conferming to BS: 5212, BS: 4252 and EN-141875-2003 for hydrolysis/water resistance test incl two coats of primer and providing 10mm dia approvedquality closed cell polythane backup rod complete all as specified and directed.
154M & L for forming 25mm wide expansionjoint using pre-formed filler board and filled with polyurethane joint fillinf sealent using mechanical means upto minimum upto full depth (depth minimum above the 32mm dia backup rod) with minimum performance guarantee of 10 years and minimum movement accommodation factor (MAF) + 30% conferming to BS: 5212, BS: 4252 and EN-141875-2003 for hydrolysis/water resistance test incl two coats of primer and providing 10mm dia approvedquality closed cell polythane backup rod complete all as specified and directed.
155M & L for forming 06mm wide x 110mm deep constraction (Dummy)joint using diamond cutter and filled with polyurethane joint filling sealent using mechanical means upto minimum depth 10mm (depth minimum above the 08mm dia backup rod) with minimum performance guarantee of 10 years and minimum movement accommodation factor (MAF) + 30% conferming to BS: 5212, BS: 4252 and EN-141875-2003 for hydrolysis/water resistance test incl two coats of primer and providing 10mm dia approvedquality closed cell polythane backup rod complete all as specified and directed.
156NOTE FOR ITEM NO 9.01 to 9.03: (i) Edge ojoints shall be rounded up by mechanical means at the time of final cutting. (ii) Initial cutting shall be carried out with in 24-36 Hrs of casting. (iii) Final cutting, rounded of edges, use and waste of backup rod to avoid deposition of foregion materials in the joints up to final filling of joints shall be carried out after 28 days. (iv) Applying masking tape on edgeses of joint to prevent accidental slippage of sealent on the top surfaces and to give a neat finish to the sealent and removing the masking tape after sealent is applied and as required.
157M&L for 400 micron polythene film as per IS- 2508 laid over sand layer incl all necessary cutting, overlaps not less than 300mm complete all as spcified and directed.
158Supply only non-circular polyester fiber as secondary reinforcement with circumcirle diameter 30-35 micron design for melting point 240-260 degree celsius and having of 1.34 to 1.4 recron @ 1kg/cum of concrete complete all as specified and directed.
159M & L fixed in repair for110mm diahigh density PVC pipe complete all as specified and directed.
160S & Ffire resistant door frame of section 143 x 57 mm having built in rebate made out of 16 SWG G.I Sheet (Zinc coating not less than 120 gm/sqm) duly filled with vermiculite based concrete mix, suitable for mounting 120 minutes fire rated door shutters. The frame is fitted with intumescing fire seal strip of size 10x4 mm (minimum) all-round the frame and fixing with dash fastener of approved size and make, applying a coat of approved brand fire resistant primer etc including 50 mm thick glazed fire resistant door shutters of 120 minutes fire rating conforming to IS:3614 (Part II) tested and certifed as per laboratory approved by Engineer-in Charge with suitable mounting on door frame, consisting of vertical styles lock rail, top rail, 100 mm wide bottom rail 200 mm wide, made out of 16 SWG G.I Sheet (zinc coating not less than 120 gm/m2) duly filled FR Insulation material and fixing with necessary stainless steel ball bearing hinges as approved including a coat of approved fire resistant primer etc with suitable buidling Hardware like sash Lock :OML-11A-F 45/85 & OML-11A-F 55/72 Pivot/Hinge, 100 mm SS Butt Hinge: OZ-SS-BHF 4x3x3, Door Closer NSK-680, Kick plate, Consealed Flush Boly, Door Seal, Door Stopper, Push Handle etc Complete all as specified and directed.
161Demolition of cement concrete (PQC) (Rigid/flexible pavement) by PQC cutting machine with diamond cutter upto 350 mm depth above ground floors including removal of demolished material from out side of MoD land, complete all as specified and directed.

AI Tender Summary

OUR REF NO 33489721
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 3.57 Crore
LAST DATE 06-09-2022
Authority
Authority Name Military Engineer Services
Work Description Provision Of Fire Escape Ladder And Water Hydrant At Af Stn Suratgarh
Basic Detail
Tender No CEWAC/SUR/T-03/2022-23
Bidding Type Tender
Location
City suratgarh
State Rajasthan
Key Dates
Publish Date 30 Aug 2022
Submission Date 06 Sep 2022
Open Date 13 Sep 2022
Finance
Tender Value 3.57 Crore
Tender Fee 2000
EMD 4.32 Lakhs
Exemption Not Available
Document List
959e4768-76ca-4ab3-abf2-e5bdb4848290.html
Binder1.pdf
BOQ_609053.xls
T-03SURATGARH_KM_C250i220.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 30, 2022
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 06, 2022
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Sep 06, 2022
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Sep 13, 2022

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

959e4768-76ca-4ab3-abf2-e5bdb4848290.html

pdf

Binder1.pdf

xls

BOQ_609053.xls

pdf

T-03SURATGARH_KM_C250i220.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders