Military Engineer Services-MES has published Special Repair For Replacement Of Cfl Light Fittings To Led Light In Testing Hall, Sub Guard Room, Main Guard Room, Airmen Billet And Mess Activity Room And P-90, 91 And P-92 Block Including Internal Wiring At No. 2 Afsb Mysore. Submission Date for this Tender is 31-08-2022. Electrification Work Tenders in bangalore Karnataka. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. |
2 | M&L for Point wiring with 1.5 sqmm, single core ,PVC insulated, unsheathedFRLS cable, 1100 volts grade, IS -694marked, with multi stranded copper conductor and earthcontinuity copper conductor cable of same size as in phase/neutral and connected to common earth dolly drawn through and including rigid PVC conduit of suitable size alongwith fittings and accessories, fixed /laid/concealed in walls/ceilings including cutting chases and making good to walls, floors etc, and alsoincl suitable sunken type pressed steel terminal box and suitable laminated sheet top cover for the following :- One light/Ceiling fan/ EF/Wall Fan controlled by one, one way switch |
3 | One light controlled by Two, Two way switch |
4 | One three pin socket outlet 5 Amp controlled by one, one way switch on independent board |
5 | All as per above but with 2.5 sqmm and 2.5 sqmm as earth conductor on independent board for 15 Amp Socket |
6 | All as per above but with 4 sqmm and 4 sqmm as earth conductor on independent board for 15 Amp Socket |
7 | Supply and Fix Modular switch 2 way 6A, 1 module |
8 | Supply and fix Modular switch 1 way 6A, 1 module |
9 | Supply and fix Modular switch 1 way 16A, 1 module |
10 | Supply and fix Modular Socket, 6A - 2/3 pin combined 2 module, |
11 | Supply and fix Modular 0 Socket 6A/16A - 2/3 pin combined 2 module, |
12 | S & F Modular Fan step regulator, 120W - 2 module |
13 | Supply and Fix Modular white cover Plate with Frame 01 Module |
14 | Supply and Fix Modular white cover Plate with Frame 02 Module |
15 | Supply and Fix Modular white cover Plate with Frame 03 Module |
16 | Supply and Fix Modular white cover Plate with Frame 04 Module |
17 | Supply and Fix Modular white cover Plate with Frame 06 Module |
18 | Supply and Fix Modular Metal Flush box 01/ 02 Module |
19 | Supply and Fix Modular Metal Flush box 3 Module |
20 | Supply and Fix Modular Metal Flush box 4 Module |
21 | Supply and Fix Modular Metal Flush box 6 Module |
22 | Supply and fix ceiling rose 3 Phase / PVC/ Polycarbonate, isolated body. |
23 | Supply and fixing LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. |
24 | Supply and fixing LED lights fitting 1x 10W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. |
25 | Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete. |
26 | Supply and Fix Single pole and neutral enclosure witha two pin and earth plug and socket complete with one single pole 20 Amp MCB |
27 | S&F in replacement SPN distribution boards protection class IP-43 single door suitable for mounting MCB with min 200 Amps rating bus bar SPN 08 way. |
28 | S&F in replacementdistribution boards protection class IP-43 single door suitable for mounting MCB with suitable rating bus bar TPN 4 way. |
29 | S&F in replacementdistribution boards protection class IP-43 doubble door suitable for mounting MCB with suitable rating bus bar TPN 12 way. |
30 | Supply and fixing 415V 10KA "B" curve miniature circuit breaker (MCB) of Four poles and current carrying capacity 63 Amp to 100Amps in the DB complete with connection testing and commissioning. |
31 | Supply and fixing 6 to 32 amp rating 240V, 10KA "B" curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning |
32 | All as per above but SPN 40 Amp |
33 | Removing of Ceiling Fan from site, Carrying to workshop, Cleaning, Greasing and Refixing at same location |
34 | Removing of ExhaustFan from site, Carrying to workshop, Cleaning, Greasing and Refixing at same location |
35 | Removing of Wall MountedFan from site, Carrying to workshop, Cleaning, Greasing and Refixing at same location |
36 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. |
37 | LED Bulb 10 Watts |
38 | Wiring for circuit/submain wiring alongwith earth wire with the followingsizes of FR is PVC insulated copper conductor, single core cable in surface/ recessed as required 2 x 10 Sqmm+ 1 x 10 Sqmm earth wire |
39 | Wiring for circuit/submain wiring alongwith earth wire with the following sizes of FR is PVC insulated copper conductor, single core cable in surface/ recessed as required 2 x 6 Sqmm+ 1 x 6 Sqmm earth wire |
40 | Wiring for circuit/submain wiring alongwith earth wire with the following sizes of FR is PVC insulated copper conductor, single core cable in surface/ recessed as required 2 x 4 Sqmm+ 1 x 4 Sqmm earth wire |
41 | Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion |