Bids for The Work of construction of cluster & Intermediate pumping stations along with switchyards and associated civil, EMI works, construction of CWR, OHSR’s of different capacity along with associated works, Rising Main pipeline, Distribution Main Pi
Tender Overview
Project Description
Bids for The Work of construction of cluster & Intermediate pumping stations along with switchyards and associated civil, EMI works, construction of CWR, OHSR’s of different capacity along with associated works, Rising Main pipeline, Distribution Main Pipeline from OHSRs to VTCs, Pipeline network of village Distribution, Providing Functional Household Connections in villages and their other habitations, testing , commissioning and trial run of whole system and all related civil works on Single Point Responsibility basis contract including Operation & Maintenance (upto VTC) for Ten years after one year defect liability period to be carried out under Jal Jeevan Mission (JJM) of Package – IVth (Baswa & Sikrai) of Isarda Dausa Water supply Project, District Dausa”.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 17-Aug-2022 | DATE EXTEND 1 | Date | 12-Sep-2022 |
| 2 | 30-Aug-2022 | CORRIGENDUM-I | Technical Bid | 12-Sep-2022 |
| 3 | 09-Sep-2022 | CORRIGENDUM-II DATE EXTEND | Date | 26-Sep-2022 |
| 4 | 25-Sep-2022 | CORRIGENDUM-III | Date | 11-Oct-2022 |
BOQ
| Sl. No. | Item Description |
| 1 | Part-01: Providing, Laying and Jointing of DI K-7/ K-9, HDPE Pipe Line for Rising, Distribution and VDS |
| 2 | Providing, lowering, laying in· trenches, aligning, fixing in position and jointing DuctileIron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000(amended uptodate), withinternal cement mortar lining, suitable for potable water with rubber ring (EPDM) . joints as per IS: 5382-1985 including all taxes (Central and local), transportation andfreightcharges, inspection charges,loading/ unloading charges, including cost of labour and material, specials (Tee, bendetc.)satisfactory hydraulic testing, disinfection etc.complete as per technical specificationsand direction of Engineer-in-charge. (excludingearth work).Note :Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurementof the item and shall not be paid separately |
| 3 | 100 mm |
| 4 | 150 mm |
| 5 | 200 mm |
| 6 | 250 mm |
| 7 | 300 mm |
| 8 | Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended upto date) withnecessaryjointingmateriallikemechanicalconnectors, i.e.thread/insertjoint/quickreleasecouplerjoint/compression fitting joint or flanged joint and specials jointing pipe by butt fusion/ electrofusionweldingmethod,includingalltaxes,transportation andfreight charges, inspectioncharges, loading/unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer in-charge of following class and diameter. (excluding earth work). Note:Providingandfixingofallrequisitespecialsasperdrawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply of pipe shall be in straight length in 6/12 M. |
| 9 | HDPE PE-80 PN 6 |
| 10 | 75 mm |
| 11 | 90 mm |
| 12 | 110 mm |
| 13 | 125 mm |
| 14 | 140 mm |
| 15 | 160 mm |
| 16 | 180 mm |
| 17 | 200 mm |
| 18 | 225 mm |
| 19 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means intrenchesofrequiredwidthandgradientforlayingandjointingofpipeline including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to1.5Mtr.includingtakingouttheexcavatedsoil,andthenreturningthesoilas required in layers not exceeding 20cm in depth including consolidating each deposited layerby ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil |
| 20 | In all type of soil |
| 21 | In soft Rock |
| 22 | In Hard Rock ( Blasting prohibited) |
| 23 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 24 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 25 | 80 mm |
| 26 | 100 mm |
| 27 | 150 mm |
| 28 | 200 mm |
| 29 | 250 mm |
| 30 | 300 mm |
| 31 | Providing,lowering, aligning,fixingin positionin pipeline,CID/FSluicevalvesstraight and pocket less body passage of approved make of following Pressure rating & dia complete, confirfing to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200Stem - SS 304 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS, Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside,Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steelInsersion rubber of black EPDM 6mm thick . Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 32 | Manually Operated CI Sluice valve of Class PN-1.0 |
| 33 | 80 mm HW |
| 34 | 100 mm HW |
| 35 | 125 mm HW |
| 36 | 150 mm HW |
| 37 | 200 mm HW |
| 38 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, DI Body Flanged End Tamper proof Kinetic Air Valve of approved makes of following pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammended up to date) Body, High pressure cover , Low pressure cover, Cowl and Joint support ring - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball : AISI 304 stainless Steel, Seat ring & Gasket - EPDM/NBR ,HP Orifice & HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & cover inside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will have a screen to prevent Tamper of float, with DI metal seated D/F Non rising stem Sluice Valves as per (IS: 14846 amended upto date) PN 1.6 ratings Valves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 39 | Class PN 1.0 |
| 40 | 40mm |
| 41 | 50 mm |
| 42 | Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI Double ActingKinetic Air Valvewith isolatingSluiceValveofapproved makesfor following pressure rating & dia complete, confirming to IS: 14845-2000 (amended upto date) and of following specifications: Body , Cover and Cowl - Grey Cast Iron asperIS:210-FG200,Float-StainlessSteelAISI304/IS:3444, FloatGuide- HBT1.HP Orifice-HTB2/ SS,Bodyseatring- Leadedtinbronze/SS .Sealring and face ring - EPDM/NBR ,Ends flanged according to IS 6418,Fastners - CS, Epoxy paint inside outside of food grade safe for drinking water ,Valves including all mateial, labour,testingandcommissioningasperTechnicalSpecificationsandasper direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work.50 mm |
| 43 | Providing,lowering,aligning,fixing inpositionandJointing inpipe line,CI single Air ValveFlanged/ Screwed type of approved makes for following pressure rating &diacomplete,confirmingtoIS:14845-2000(amended uptodate)andof following specifications: Body , Cover and Cowl - Grey Cast Iron as per IS:210- FG 200 ,Float - Stainless Steel AISI 304 / IS: 3444 ,Float Guide- HBT1,Body seat ring - Leadedtinbronze/SS,Sealringandfacering-EPDM/NBR,Endsflanged accordingtoIS6418orscrewedScrewedtypeshallhaveextcrnalpipethreads conforming to IS 554Fastners - CS Epoxy paint inside outside of food grade safe for drinking water ,Valves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 44 | 25 mm |
| 45 | 50 mm |
| 46 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 47 | EFM 100 mm |
| 48 | EFM 150 mm |
| 49 | EFM 200 mm |
| 50 | SITC of Bulk Flow Meter with removable mechanism class \"B\" confirming to ISO:4064:2005/ IS: 2373 of approved make of following dia sized pipelines and specifications complete: Media : Water (Clear ), Temp. 50 deg., Pr. rating: PN16, Protection type: IP- 68, Body Material : IS-210 Gr. FG-200, Accuracy Class :Class B (±2 % @ Nominal flow rate), Magnetic Drive, Dry Dial, Epoxy powder coated, Pulse out put option, Anti-magnetic protection including all materials and making connection with existing pipeline requiredfor Bulk Flow Meter including cutting the existing pipeline etc. complete in all respect as per technical specification and as per direction of Engineer In Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work |
| 51 | BFM 80 mm |
| 52 | BFM 100 mm |
| 53 | BFM 150 mm |
| 54 | BFM 200 mm |
| 55 | Providing, lowering, aligning and fixing in position DI D/F Diaphragm type Pressure Reducing / Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body & Bonet - Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or ASTM A 536, Diaphragm and Resilient seal disc - Flexible, non-wicking nylon fabric reinforced synthetic elastomer -Buna-N / EPDM (FDA / WRAS approved), Body Seat Ring - Cast stainless steel ASTM- A 351 GR. CF8M / AISI- 316, raised, replaceable inline & onsite Stem - Stainless Steel, AISI-316, raised, replaceable inline & onsite Spring & Bearing bush- Stainless Steel, AISI-316 ,Disc guide, disc retainer & diaphragm washer - Stainless Steel, AISI-304/ 316/Bronze ,Seal- EPDM/ NBR ,Pilot Body- Stainless Steel, AISI-304/ CF8 or Brass Tubing - Stainless Steel, AISI-304 / Copper ,Solenoid Valve- Stainless Steel, AISI-316 ,Throttling plug - Stainless Steel, AISI 304, Nut- Bolts - SS Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5, Class 150 and Class 300/ EN-1092-2. nsersion rubber of black EPDM 6mm thick Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning as per Technical Specification & as per direction of Engineer-In- Charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 56 | 100 mm |
| 57 | 150 mm |
| 58 | 200 mm |
| 59 | Providing, lowering, aligning & fixing in position DI D/F Plunger Type Flow Control Valve of approved make of following Pressure rating & dia complete and of following specifications: Body- Ductile cast iron of grade GGG40/GGG50 as perDIN 1693 or EN-JS 1030, Plunger/ Piston - Stainless steel AISI- 304/ Gr 1.4301, Piston Guides- Bronze Welded Overlay / SS Shaft/Crank/Spindle- Stainless steel AISI- 420/ Gr 1.4021 Body Seat Ring- Stainless steel AISI- 316/304/ Bronze IS:318- LTB2 ,Seal ( O- ring / Quad ring)- EPDM/ NBR, Bearing Bush - Bronze IS:318- LTB2,Slotted cylinder / Strainer / Diffuser- AISI- 420/ 304,Nut- Bolts - SS, Face to Face- as per ANSI B 16.1/ EN 558-1 and Flange ends should be as per ANSI B-16.5,Class 150 and Class 300/ EN-1092-2. Insersion rubber of black EPDM 6mm thick ,Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied both inside and outside . Suitable support structure as per directN 1.6 ratings Valves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work.r direction of Engineer-in-charge. |
| 60 | Plunger Type Flow Control Valve |
| 61 | 100 mm |
| 62 | 150 mm |
| 63 | 200 mm |
| 64 | Providing,lowering,laying,aligning, fixinginpositionandjointingCI dismantling joint(SuitableforSluicevalvesetc.)asperISspecifications complete of the following sizes including alljointingmaterial, cost of all labour, testing and commissioning Technical Specifications and as per direction of Engineer. Class PN 1.0 |
| 65 | 80 mm |
| 66 | 100 mm |
| 67 | 150 mm |
| 68 | 200 mm |
| 69 | 250 mm |
| 70 | 300 mm |
| 71 | Construction of Air valve Pillars as per approved design & drawing and specifications given in Tender Document. |
| 72 | Construction of RCC valve chamber for Valves different Size of Pipes including earthwork excavation, 100mm PCC M10 (1:3:6 (1 Cement: 3 coarse sand : 6 graded stone aggregate 20mm nominal size) as leveling course, RCC M20 grade (1:1½:3 (1 Cement : 1½ coarse sand : 3 graded stone aggregate 20mm nominal size) for base slab, side wall & \"AA\" class LoadingFerro-Cement drain covers, including cost of steel reinforcement not less than 80kg per cum CC, form work,proper curing of concrete work complete in all respect as per standard specifications and drawings and as directed by Engineer.Sluice Valves Chamber |
| 73 | 100 mm |
| 74 | 150 mm |
| 75 | 200 mm |
| 76 | 250 mm |
| 77 | 300 mm |
| 78 | Junction valve chamber: |
| 79 | Junction Valve Chamber |
| 80 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (if required ) excluding the cost of centering, shuttering and reinforcement for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. M20 grade Nominal Mix / Design Mix |
| 81 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor five level. (\"Original producers\" who manufacture billet directly from ironores and roll the bilets to produce steel conforming to IS:1786)-Hot rolled deformed bars |
| 82 | Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings,strap beam, raft , bases of columns etc. |
| 83 | SupplylayingandpushingofMScasingpipeofspecifiedthicknessapprovedby concerned department authority by trenchless method adopting any suitable technologybelowgroundatrequireddepthunderrunningtrafficconditionasper Highway/Railwaystandardincludingcarryingoutsurveyworkatthejobsitefor determining underground cable trenches like telephone, cable, water & sanitary lines and resistivity test for finding the soil strata using necessary equipments for completion of works, mobilizing of machineries and specialized crewat thejob site complete in all respect, including excavation of driven pit and exit pit (up to 3 meter depth) with proper protection at these sites with shoring sheets and ISMB. Providing MScuttingedgesforfrontshieldandconstructingthrustbedatdesignatedlevel. Necessarydewateringandprovidingconcretefoundationatthebaseofthedriven pit, PVC/Rubber saddle as per the requirement of Highway/Railway authority, crane for handing of pipe and any other machinery, tools, and tackles required, construction of temporary works as per design, drawing and method as per approved byauthority specification and the direction of the Engineer.Applycorrosion,resistant,protectiononinsideandoutsideofcasingpipe asper technical specification. |
| 84 | National Highway CrossingBaswa |
| 85 | Casing pipe 300 mm, Carrier Pipe 150 mm, 7 No |
| 86 | Casing pipe 400 mm, Carrier Pipe 200 mm,1 No |
| 87 | Casing pipe 500 mm, Carrier Pipe 250 mm,1 No |
| 88 | Highway Crossing Baswa |
| 89 | Casing pipe 300 mm, Carrier Pipe 100 mm,18 No |
| 90 | Casing pipe 300 mm, Carrier Pipe 150 mm, 28 No |
| 91 | Casing pipe 400 mm, Carrier Pipe 200 mm,20 No |
| 92 | Casing pipe 500 mm, Carrier Pipe 250 mm,18 No |
| 93 | Casing pipe 600 mm, Carrier Pipe 300 mm,6 No |
| 94 | Railway CrossingBaswa |
| 95 | Casing pipe 300 mm, Carrier Pipe 150 mm,2 No |
| 96 | Casing pipe 400 mm, Carrier Pipe 200 mm, 2 No |
| 97 | National Highway CrossingSikrai |
| 98 | Casing pipe 300 mm, Carrier Pipe 100 mm, 2 No |
| 99 | Casing pipe 300 mm, Carrier Pipe 1500 mm,2 No |
| 100 | Casing pipe 500 mm, Carrier Pipe 250 mm,3 No |
| 101 | Highway Crossing sikrai |
| 102 | Casing pipe 300 mm, Carrier Pipe 100 mm,16 No |
| 103 | Casing pipe 300 mm, Carrier Pipe 150 mm, 20 No |
| 104 | Casing pipe 400 mm, Carrier Pipe 200 mm,13 No |
| 105 | Casing pipe 500 mm, Carrier Pipe 250 mm,20 No |
| 106 | Casing pipe 600 mm, Carrier Pipe 300 mm,2 No |
| 107 | SURGE PROTECTION SYSTEM. |
| 108 | Providing, lowering, laying, alingning, fixing in position in pipe line Air Cussion Valvesas per IS:14845 of following dia (including jointing and jointing material), including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer etc,complete in all respect |
| 109 | M.S. Fabricated Self Acting Air Cushion Valves suitable for pr. rating , PN-1.6 |
| 110 | 25 mm |
| 111 | 50 mm |
| 112 | 80 mm |
| 113 | Providing, lowering, laying, alingning, fixing in position in pipe line Zero Velocity Valves of as per IS:14845 of following dia (including jointing and jointing material), including all material,labour, testing and commissioning as per Technical Specifications and as per direction of Engineer etc,complete in all respect. |
| 114 | M.S. Fabricated Plain End Self actuating consists of Spring Loaded Closing Disc for stopping reverse flow Zero Velocity Valve with By-Pass arrangement |
| 115 | 100 mm |
| 116 | 150 mm |
| 117 | 200 mm |
| 118 | Dismantlingofcementconcretepavementforpipelinelineandchambersby mechanical means using pneumatictools, cuttingthe peripheraledge byCCcutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurementfordismantledtrenchtobemade asperstandardtrenchwidth specifiedintenderdocumentandnoextrapaymentshallbemadebemadefor trenchwidthmorethanspecified,re-handlingofmaterial/earthtocompletethe tasks as per technical specification and scope of work. |
| 119 | Dismantling of flexible pavement for pipe line line and chambers by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks per technical specification and scope of work. |
| 120 | Providing and laying in position cement concrete in specified grade over prepared base course complete including finishing, curing, all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be made as per standard trench width specified in tender document and no extra payment shall be made for trench width more than specified, complete work as per technical specification and scope of work.CC 1:1.5:3 |
| 121 | Construction of village Transfer chambers (VTC) |
| 122 | Type A for Intermediate villages |
| 123 | Type B for endVillages |
| 124 | Providingandlayinginpositioncementconcreteinspecifiedgradeoverprepared basecoursecompleteincludingfinishing,curing,allmaterial,labour,machinery, lighting,guardingforroadrestorationworkintrenchesofpipelineandchamber work. Measurement for CC work to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work. |
| 125 | M20 grade Nominal Mix1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size). |
| 126 | ProvidingHouseholdTapConnection aspertechnicalspecification andapproved drawing and as per relevant IS code (amended up to date) from HDPE pipe line up to consumer meter/premises by using electro fusion saddlepiece(Completejob).Thisjobincludesdigging out suitable size of pits and trench for laying service line in all kinds of soil;depositingandrefillingofpit&jhiriwithwatering&ramming /compacting in layers and disposal of surplus excavated soil as directed with in a lead of 100 meter ; providing & fixing of all fitting dulyapprovedinaccordancewith specificationforpotablewater including electrofusion saddle piece, gunmetal ferrule 4.0 mm , GM Full-wayValve(IS:778Mark)orwheelvalveandspecials,below ground level 20 mm nominal dia MDPE pipe PE80 PN 16 as per ISO 4427 / 20 mm nominaldia PPR-C (Three layered) pipePN16 SDR 7.4 (IS:15801:2008)(ISImark)forandabovegroundlevelusing20mm diaPPR-Cpipe withstandardPPRfittings/15mmdiaGIpipes with fittings in the premises for fixing a tap / meterbox (excluding) ,including accessories with flushing, cleaning, disinfecting and testing ofpipelinecompleterequiredformakingofserviceconnection completeinallrespectincludinglabourcharges.Theserviceline should be laid at least 45 cm below ground level.Note:Roadcutandrestorationisnotpartofthisitemandpaid seperately. |
| 127 | Forconnectionwith20mmdiaMDPE/PPR-Cpipelengthupto05 mtr. |
| 128 | P& F Bib cock (IS : 8931 mark), superior quality of approvedmake , brss 400 gm, 15 mm nominal bore. |
| 129 | Roadcuttingforhouseholdserviceconnectioninminimumtrench widthwhereeverroadcrossingisrequired.Roadcuttingofcement concrete,WBM, Black top etc. of all thickness shall be doneby using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CC M-30 grade as per specification and direction of Engineer in charge.. |
| 130 | Add extra over item no 1.21 & 1.22 for providing20 mm PE80 PN 16 as per ISO 4427 MDPE pipe including excavation, providing, laying & jointing of service line above 5.00 mtr. |
| 131 | Horizontal directional drilling (by trenchless technology) of suitable dia hole minimum 1.0 mtr below natural ground level in all type of soil under CC/BT roads and pulling HDPE pipes of dia up to 110 mm, which are available in the form of a coil including excavation, shoring/ strutting, preparation, maintain the thrust and including, road dismantling,excavation and refilling of drive pit and exit pit, restoration of road cut as per technical specification and scope of work. Excluding cost of pipe line. Note: Trenchless laying shall be done only for laying of pipe line (rising main) and road crossing of distribution pipe line under CC/BT roads |
| 132 | Part-02:Provision for Construction of OHSRs including Boundary wall |
| 133 | ConstructionandcommissioningofRCCINTZEtypeOverHeadServiceReservoirof followingcapacityandstagingaspertheScopeofworkandTechnicalspecifications, consisting of the following main activities: -a)Topographicsurvey,preparationofsitecontourplan,conductingSBCtest andits approval from departmentbefore construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction.b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc.c)OHSRshallbeprovidedwithadequateplinthprotectionallaroundthestructureina width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR.The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil.d) Providing and applying two coats of food grade epoxy paint on the inside surface on the top dome, edge beam and 600 mm height of the vertical wall.e)Conducting successfully hydro test and water tightness test as per I.S. code.f) Providingandapplyingthreecoatsofanti-carbonationpaintonthetopsurfaceof the Top Dome.g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc..h)ProvidingandfixingSS-304ventilator,SS304manholeframeandcoverandSS-304 ladder from top dome/Slab to bottom dome/Slab inside container.i) Providing and fixing of MS section ladder from the last landing to balcony having railing all around it and MS ladder with safety cage from balcony to top dome/slab.j) Providing and fixing water level indicator (float type).k)Providingandfixingofhandrailingallaroundthebalcony,topdomeandstaircase consisting of 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm angle iron vertical post at a maximum spacing of 1500mm centres.l) All MS parts to be painted with two coats of the enamelpaint overthe primercoat of red oxide.m)Providingandfixingof150mmwidePVCwaterbarfortheconstructionjointsinthe container (vertical wall & cone wall).n) ProvidingoneAluminium portableladderofappropriatelengthto accessfirstlanding (3.5 to 4.5m above GL) from ground.o) Lighting arrestorconsisting ofproviding andfixing of2 Nos. of chemical earthing and connecting it to the conical cover of SS ventilator with two separate GI strips of 50mmX3mm.p) CI/DI puddle collar shall be fixed in the bottom dome/ slab for connecting inlet, outlet, overflow and washout pipe of the reservoir.q) Painting the name of the scheme and other details on the reservoir, and any other work relatedtostructureasperthedirectionsofEngineer-in-Charge,TechnicalSpecification and Scope of Work.r)Inlet,outlet,overflow,washoutpipesandvalvesarenotincludedinthiswork, provision for the same shall be taken separately. |
| 134 | 100 KL |
| 135 | 150 KL |
| 136 | 200 KL |
| 137 | 250 KL |
| 138 | 300 KL |
| 139 | 450 KL |
| 140 | Construction and commissioning of RCC flat slab Over Head Service Reservoir offollowing capacity and staging including all material and labour charges as per the Scopeof work and Technical Specification, consisting of the following main activities: -a) Topographic survey, preparation of site contour plan, conducting SBC test and itsapproval from department before construction. Submission and approval of concrete mixdesign and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection allaround the structure including all material, labour, shuttering, scaffolding etc.c) OHSR shall be provided with adequate plinth protection all around the structure in awidth starting from edge of structure at GL and extending at least up to 1.0m beyond theedge of outer most projection of OHSR. The plinth protection shall consist of 150mm thickPCC in M-15 grade concrete laid over 150mm thick layer of compacted soil. d) Providing and applying two coats of food grade epoxy paint on the inside surface roofslab, and 600 mm height of the vertical wall.e) Successfully hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the top surface of theroof slab.g) Providing and applying three coats of cement-based paint on the external surface of thecontainer, balcony, cone wall, columns & beams etc.h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304ladder from top Slab to bottom Slab inside container. i) Providing and fixing of MS section ladder from the last landing to balcony and MS ladderwith safety cage from balcony to top slab. |
| 141 | j) Providing and fixing water level indicator (float type).k) Providing and fixing of hand railing all around the balcony, roof and staircase, consistingof 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm angle ironvertical post at a maximum spacing of 1500mm centres.l) All MS parts to be painted with two coats of the enamel paint over the primer coat ofred oxide.m) Providing and fixing of 150mm wide PVC water bar for the construction joints in thecontainer (vertical wall & cone wall).n) Providing one Aluminium portable ladder of appropriate length to access first landing(3.5 to 4.5m above GL) from ground.o) Lighting arrestor consisting of providing and fixing of 2 Nos. of chemical earthing andconnecting it to the conical cover of SS ventilator with two separate GI strips of50mmX3mmp) CI/DI puddle collar shall be fixed in the bottom/slab for connecting inlet, outlet,overflow and washout pipe of the reservoir.q) Painting the name of the scheme and other details on the reservoir, and any other workrelated to structure as per the directions of Engineer-in- Charge, Technical Specificationand Scope of Work.r) Inlet, outlet, overflow, washout pipes and valves are not included in this work,provision for the same shall be taken separately. |
| 142 | Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-III & STAGING 15 M |
| 143 | 50 KL |
| 144 | ProvidingandfixingdoubleflangedISImarkedDI ClassK-9pipesasperIS:8329-2000 (amended up to date), asvertical pipes for RCC Reservoirs including specials required such asduckfootbend,bend,teeetc.providingandfixingclampsatevery3mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testingetc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope of work. (Size in MM)Inlet, Outlet, Overflow & Washout |
| 145 | 100 MM |
| 146 | 150 MM |
| 147 | 200 MM |
| 148 | 250 MM |
| 149 | 300 MM |
| 150 | 350 MM |
| 151 | 400 MM |
| 152 | 450 MM |
| 153 | 500 MM |
| 154 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. ( FOR INLET -2, AND WASHOUT-1) |
| 155 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 156 | 100 MM |
| 157 | 150 MM |
| 158 | 200 MM |
| 159 | 250 MM |
| 160 | 300 MM |
| 161 | 350 MM |
| 162 | 400 MM |
| 163 | 450 MM |
| 164 | 500 MM |
| 165 | Providing,lowering,laying,aligning, fixinginpositionandjointingCI dismantling joint(SuitableforSluicevalvesetc.)asperISspecifications complete of the following sizes including alljointingmaterial, cost of all labour, testing and commissioning Technical Specifications and as per direction of Engineer. Class PN 1.0 |
| 166 | 100 MM |
| 167 | 150 MM |
| 168 | 200 MM |
| 169 | 250 MM |
| 170 | 300 MM |
| 171 | 350 MM |
| 172 | 400 MM |
| 173 | 450 MM |
| 174 | 500 MM |
| 175 | Providing, laying and fixing float valve system of following dia of C.I. with internal parts of auxiliary valve of copper float ball, gunmetal ball cap, brass lever, brass split pin, gunmetal piston & piston cap, washer of nitrile rubber with gunmetal body including all material, labour, hydraulic testing and commissioning as per Technical Specifications and as per direction of Engineer. |
| 176 | 150MM |
| 177 | 200MM |
| 178 | Construction of RCC valve chamber for Valves different Size of Pipes including earthwork excavation, 100mm PCC M10 (1:3:6 (1 Cement: 3 coarse sand : 6 graded stone aggregate 20mm nominal size) as leveling course, RCC M20 grade (1:1½:3 (1 Cement : 1½ coarse sand : 3 graded stone aggregate 20mm nominal size) for base slab, side wall & \"AA\" class LoadingFerro-Cement drain covers, including cost of steel reinforcement not less than 80kg per cum CC, form work,proper curing of concrete work complete in all respect as per standard specifications and drawings and as directed by Engineer.Sluice Valves Chamber |
| 179 | (Chamber Size= 1.45 X 1.45 X 1.60 M ) for pipe size 100 mm to 250 mm |
| 180 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 181 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 182 | Part-03:Provision for Construction of CWR |
| 183 | Construction of Clear water reservoir, as per specification including providing and fixing, inlet , outlet, washout and over flow pipes,providing andinstallation of valves on Inlet, outlet Washout and over flow pipes, puddle collars , duck foot bends,pipesinterconnecting pipes andtheir inter connection with incoming and out going mains including all speciails float wall,water indicator, pilant protaction works, color washing, slogan writing,finising testing and commissioning complete as per specificationsfor Rectangular type CWRs |
| 184 | Pichupara CWR |
| 185 | Sodala CWR (Sekhpura) |
| 186 | Kolana CWR |
| 187 | Bandikui CWR |
| 188 | Kolwa CWR |
| 189 | Gurha CWR (Nagwas) |
| 190 | MotukaCWR (Bhadadi Meena) |
| 191 | Kankarwas CWR (Mahukhera) |
| 192 | Rajahera CWR |
| 193 | Sikrai CWR |
| 194 | Torda CWR (Bairawanda) |
| 195 | JheejhunCWR |
| 196 | Providing, installation, testing and commissioning of submersible monoblock pump set conforming to IS 8034 and 2 pole motor operating at syncronised speed of speed 3000 RPM, with water proof winding. Pump shall be suitable for various delivery head and discharge with stainless steel shaft. Motor suitable for working on 415 V ± 10%, 3 Ph, 50 Hz AC and with water lubricated bearing to accept entire hydraulic thrust. Supply, with cable guard, thrust carbon/fiber bearing to withstand entire hydraulic thrust. The pump set shall be suitable for direct coupling, with suitable suction strainer. Pump should have suitable discharge out let as per manufacturer\"s design. Antithrust stream lined non return valve shall be provided with the pump and minimum 6 m submersible copper conductor cable in single / double run and 2 pairs of suitable size erection clamp 10 mm thick shall be provided with each pump etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power the directions of Engineer-in- Charge, Technical Specification |
| 197 | 7.5 KW (10 HP) |
| 198 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 199 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with 50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 200 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 201 | Part-04: A-Provision for Construction of Pichhupara Kalan Pump house |
| 202 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Daleri Head worknear proposed 2250 KL CWR (For Installation of 3W+3S Pumps & 2 pumps for future) |
| 203 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 204 | Somara OHSR route23.93 LPS / 55 m head/25 KW |
| 205 | Sumel kalan OHSR route14.42 LPS / 75m head/20 KW |
| 206 | Keratpura OHSR route 19.55 LPS /75 m head/30 KW |
| 207 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 208 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 209 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 210 | 125 MM |
| 211 | 200 MM |
| 212 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 213 | Motorized Sluice Valves with Electric Actuator and integral starter of Class PN 1.6 |
| 214 | 150 MM |
| 215 | 200 MM |
| 216 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 217 | 125 MM |
| 218 | 200 MM |
| 219 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 220 | 125 MM |
| 221 | 200 MM |
| 222 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 223 | 125 MM |
| 224 | 150 MM |
| 225 | 200 MM |
| 226 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 227 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 228 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 229 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 230 | 50 mm |
| 231 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 232 | - 1.0 to +1.0 kg/cm² |
| 233 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 234 | 150 mm |
| 235 | 200 mm |
| 236 | Water meter chamber: |
| 237 | 150 mm |
| 238 | 200 mm |
| 239 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 240 | 250KVA |
| 241 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 242 | 11KV HT Panel (drowout type) |
| 243 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 244 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 245 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 246 | 110VDC |
| 247 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 248 | 25 A + 25 A |
| 249 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 250 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 251 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 252 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 253 | 50mm x 6mm copper strip |
| 254 | 50mm x 6mm G.I. Strip |
| 255 | 32mm x6mm G.I. Strip |
| 256 | 25mm x 6mm G.I. Strip |
| 257 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 258 | 3 core 95.0 Sq.mm |
| 259 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 260 | Indoor |
| 261 | 3 core 70/95 Sq.mm |
| 262 | Outdoor |
| 263 | 3 core 70/95 Sq.mm |
| 264 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 265 | 300 SQMM,3.5 core |
| 266 | 35 SQMM, 3 CORE |
| 267 | 4.0 Sq.mm x 3 Core |
| 268 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 269 | Hot Dipped Galvanized |
| 270 | 450mm x 50mm x 2.0mm |
| 271 | 600mm x 50mm x 2.0mm |
| 272 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 273 | Hot Dipped Galvanized |
| 274 | 100mm x 50mm x 1.6mm |
| 275 | 150mm x 50mm x 1.6mm |
| 276 | 300mm x 50mm x 1.6mm |
| 277 | 450mm x 50mm x 2.0mm |
| 278 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 279 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 280 | 400 A MCCB Incomer (Fixed type )with metering CTs, multi fuction meter compatible to scada, Ampermeter with SS, Voltmeter with SS, IndicatingLamps,ControlFuse,wiringetc.completeinallrespect. Size:900(W)X600(H)X1000(D) |
| 281 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 282 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 283 | 200AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)600(H)X1000(D) |
| 284 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 285 | 30KW |
| 286 | 433V APFC Panel( 90KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 287 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 288 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 289 | Local Push Button Station |
| 290 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 291 | 7 Mtr. |
| 292 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 293 | Single arm overhang |
| 294 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 295 | LED street light fixture 80-90 watt |
| 296 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 297 | 1 X 250 Watt |
| 298 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 299 | 250 Watt |
| 300 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 301 | 20 Mtr Hm (in 2 section) |
| 302 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 303 | 1 X 250/ 150 Watt |
| 304 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 305 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 306 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 307 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 308 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 309 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 310 | 374 m3/hr capacity |
| 311 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 312 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 313 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 314 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 315 | Discharge 36 cum/hr and head 11 to 15 M |
| 316 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 317 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 318 | Part-04: B-Provision for Construction of Kolwa Pump house |
| 319 | Civil work such as construction of pump House. |
| 320 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Head worknear proposed 2250 KL CWR (For Installation of 3W+3S Pumps & 2 pumps for future) |
| 321 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 322 | Dhanwar OHSR route13.71 LPS / 60 m head/15 KW |
| 323 | Manota OHSR route22.35 LPS / 50m head/25 KW |
| 324 | Durki OHSR route 17.37 LPS /50 m head/20 KW |
| 325 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 326 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 327 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 328 | 125 MM |
| 329 | 200 MM |
| 330 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 331 | 150 MM |
| 332 | 200 MM |
| 333 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 334 | 125 MM |
| 335 | 200 MM |
| 336 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 337 | 125 MM |
| 338 | 200 MM |
| 339 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 340 | 125 MM |
| 341 | 150 MM |
| 342 | 200 MM |
| 343 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 344 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 345 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 346 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 347 | 50 mm |
| 348 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 349 | - 1.0 to +1.0 kg/cm² |
| 350 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 351 | 150 mm |
| 352 | 200 mm |
| 353 | Water meter chamber: |
| 354 | 150 mm |
| 355 | 200 mm |
| 356 | Electric equipment and accessories |
| 357 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 358 | 200KVA |
| 359 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 360 | 11KV HT Panel (drowout type) |
| 361 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 362 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 363 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 364 | 110VDC |
| 365 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 366 | 25 A + 25 A |
| 367 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 368 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 369 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 370 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 371 | 50mm x 6mm copper strip |
| 372 | 50mm x 6mm G.I. Strip |
| 373 | 32mm x6mm G.I. Strip |
| 374 | 25mm x 6mm G.I. Strip |
| 375 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 376 | 3 core 95.0 Sq.mm |
| 377 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 378 | Indoor |
| 379 | 3 core 70/95 Sq.mm |
| 380 | Outdoor |
| 381 | 3 core 70/95 Sq.mm |
| 382 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 383 | 300 SQMM,3.5 core |
| 384 | 35 SQMM, 3 CORE |
| 385 | 25 SQMM, 3 CORE |
| 386 | 16 SQMM, 3 CORE |
| 387 | 4.0 Sq.mm x 3 Core |
| 388 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 389 | Hot Dipped Galvanized |
| 390 | 450mm x 50mm x 2.0mm |
| 391 | 600mm x 50mm x 2.0mm |
| 392 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,crossmembersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 393 | Hot Dipped Galvanized |
| 394 | 100mm x 50mm x 1.6mm |
| 395 | 150mm x 50mm x 1.6mm |
| 396 | 300mm x 50mm x 1.6mm |
| 397 | 450mm x 50mm x 2.0mm |
| 398 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 399 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 400 | 400 A MCCB Incomer (Fixed type )with metering CTs, multi fuction meter compatible to scada, Ampermeter with SS, Voltmeter with SS, IndicatingLamps,ControlFuse,wiringetc.completeinallrespect. Size:900(W)X600(H)X1000(D) |
| 401 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 402 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 403 | 160AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)600(H)X1000(D) |
| 404 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 405 | 30KW |
| 406 | 22KW |
| 407 | S&FofStardeltaStarterwithMCB,MainandAuxContactor,O/L Relay,L/RSelectorSwitch,3Indicatinglamps,Start-StopPush Button,ControlMCBwithpanelwithallaccessorieswithfollowing rating |
| 408 | 15KW |
| 409 | 433V APFC Panel( 60KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 410 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 411 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 412 | Local Push Button Station |
| 413 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 414 | 7 Mtr. |
| 415 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 416 | Single arm overhang |
| 417 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 418 | LED street light fixture 80-90 watt |
| 419 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 420 | 1 X 250 Watt |
| 421 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 422 | 250 Watt |
| 423 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 424 | 20 Mtr Hm (in 2 section) |
| 425 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 426 | 1 X 250/ 150 Watt |
| 427 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 428 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 429 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 430 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 431 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 432 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 433 | 374 m3/hr capacity |
| 434 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 435 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 436 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 437 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 438 | Discharge 36 cum/hr and head 11 to 15 M |
| 439 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 440 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 441 | Part-04: C-Provision for Construction of Motuka Pump house (Bhadadi Meena) |
| 442 | Civil work such as construction of pump House. |
| 443 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement. |
| 444 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 445 | Bijupara OHSR route17.64 LPS / 55 m head/20 KW |
| 446 | Badiya Kalan OHSR route14.24 LPS / 50m head/15 KW |
| 447 | Punderpara OHSR route 12.37 LPS /45 m head/15 KW |
| 448 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 449 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 450 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 451 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 452 | 125 MM |
| 453 | 200 MM |
| 454 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 455 | 150 MM |
| 456 | 200 MM |
| 457 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 458 | 125 MM |
| 459 | 200 MM |
| 460 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 461 | 125 MM |
| 462 | 200 MM |
| 463 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 464 | 125 MM |
| 465 | 150 MM |
| 466 | 200 MM |
| 467 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 468 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 469 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 470 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 471 | 50 mm |
| 472 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 473 | - 1.0 to +1.0 kg/cm² |
| 474 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 475 | 150 mm |
| 476 | 200 mm |
| 477 | Water meter chamber: |
| 478 | 150 mm |
| 479 | 200 mm |
| 480 | Electric equipment and accessories |
| 481 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 482 | 200KVA |
| 483 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 484 | 11KV HT Panel (drowout type) |
| 485 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 486 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 487 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 488 | 110VDC |
| 489 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 490 | 25 A + 25 A |
| 491 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 492 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 493 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 494 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 495 | 50mm x 6mm copper strip |
| 496 | 50mm x 6mm G.I. Strip |
| 497 | 32mm x6mm G.I. Strip |
| 498 | 25mm x 6mm G.I. Strip |
| 499 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 500 | 3 core 95.0 Sq.mm |
| 501 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 502 | Indoor |
| 503 | 3 core 70/95 Sq.mm |
| 504 | Outdoor |
| 505 | 3 core 70/95 Sq.mm |
| 506 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 507 | 300 SQMM,3.5 core |
| 508 | 25 SQMM, 3 CORE |
| 509 | 16 SQMM, 3 CORE |
| 510 | 4.0 Sq.mm x 3 Core |
| 511 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 512 | Hot Dipped Galvanized |
| 513 | 450mm x 50mm x 2.0mm |
| 514 | 600mm x 50mm x 2.0mm |
| 515 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 516 | Hot Dipped Galvanized |
| 517 | 100mm x 50mm x 1.6mm |
| 518 | 150mm x 50mm x 1.6mm |
| 519 | 300mm x 50mm x 1.6mm |
| 520 | 450mm x 50mm x 2.0mm |
| 521 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 522 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 523 | 400 A MCCB Incomer (Fixed type )with metering CTs, multi fuction meter compatible to scada, Ampermeter with SS, Voltmeter with SS, IndicatingLamps,ControlFuse,wiringetc.completeinallrespect. Size:900(W)X600(H)X1000(D) |
| 524 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 525 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 526 | 160AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)600(H)X1000(D) |
| 527 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 528 | 22KW |
| 529 | S&FofStardeltaStarterwithMCB,MainandAuxContactor,O/L Relay,L/RSelectorSwitch,3Indicatinglamps,Start-StopPush Button,ControlMCBwithpanelwithallaccessorieswithfollowing rating |
| 530 | 15KW |
| 531 | 433V APFC Panel( 60KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 532 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 533 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 534 | Local Push Button Station |
| 535 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 536 | 7 Mtr. |
| 537 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 538 | Single arm overhang |
| 539 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 540 | LED street light fixture 80-90 watt |
| 541 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 542 | 1 X 250 Watt |
| 543 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 544 | 250 Watt |
| 545 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 546 | 20 Mtr Hm (in 2 section) |
| 547 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 548 | 1 X 250/ 150 Watt |
| 549 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 550 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 551 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 552 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 553 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 554 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work.374 m3/hr capacity |
| 555 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 556 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 557 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 558 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 559 | Discharge 36 cum/hr and head 11 to 15 M |
| 560 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 561 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 562 | Part-04: D-Provision for Construction of Sodala Pump house (Sekhpura) |
| 563 | Civil work such as construction of pump House. |
| 564 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Abaneri worknear proposed 3250 KL CWR (For Installation of 4W+4S Pumps & 2 pumps for future) |
| 565 | Mechanical Equipment & Accessories |
| 566 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 567 | Centrifugal horizontal split casing pumps & motor all other accessories of following duty conditions |
| 568 | Rampura Gujran OHSR route16.39 LPS / 50 m head/15 KW |
| 569 | Annatwara OHSR route19.56 LPS /45 m head/20 KW |
| 570 | Ralawata OHSR route 19.22 LPS / 65 m head/25 KW |
| 571 | Matuka OHSR route44.25 LPS / 25 m head/25 KW |
| 572 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 573 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 574 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 575 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 576 | 150 MM |
| 577 | 200 MM |
| 578 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 579 | Motorized Sluice Valves with Electric Actuator and integral starter of Class PN 1.6 |
| 580 | 150 MM |
| 581 | 200 MM |
| 582 | 250 MM |
| 583 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 584 | Class PN 1.6, Motorised Operated |
| 585 | 150 MM |
| 586 | 200 MM |
| 587 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 588 | Class PN 1.6 |
| 589 | 150 MM |
| 590 | 200 MM |
| 591 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 592 | 150 MM |
| 593 | 200 MM |
| 594 | 250 MM |
| 595 | Electric Overhead Travelling (EOT) Crane |
| 596 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 597 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 598 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 599 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 600 | Class PN 1.6 |
| 601 | 50 mm |
| 602 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 603 | - 1.0 to +1.0 kg/cm² |
| 604 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 605 | 150 mm |
| 606 | 200 mm |
| 607 | Water meter chamber: |
| 608 | 150 mm |
| 609 | 200 mm |
| 610 | Electric equipment and accessories |
| 611 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 612 | 250KVA |
| 613 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 614 | 11KV HT Panel (drowout type) |
| 615 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 616 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 617 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 618 | 110VDC |
| 619 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 620 | 25 A + 25 A |
| 621 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 622 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 623 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 624 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 625 | 50mm x 6mm copper strip |
| 626 | 50mm x 6mm G.I. Strip |
| 627 | 32mm x6mm G.I. Strip |
| 628 | 25mm x 6mm G.I. Strip |
| 629 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 630 | 3 core 95.0 Sq.mm |
| 631 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 632 | Indoor |
| 633 | 3 core 70/95 Sq.mm |
| 634 | Outdoor |
| 635 | 3 core 70/95 Sq.mm |
| 636 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 637 | 300 SQMM,3.5 core |
| 638 | 35 SQMM, 3 CORE |
| 639 | 25 SQMM, 3 CORE |
| 640 | 16 SQMM, 3 CORE |
| 641 | 4.0 Sq.mm x 3 Core |
| 642 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 643 | Hot Dipped Galvanized |
| 644 | 450mm x 50mm x 2.0mm |
| 645 | 600mm x 50mm x 2.0mm |
| 646 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 647 | Hot Dipped Galvanized |
| 648 | 100mm x 50mm x 1.6mm |
| 649 | 150mm x 50mm x 1.6mm |
| 650 | 300mm x 50mm x 1.6mm |
| 651 | 450mm x 50mm x 2.0mm |
| 652 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 653 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 654 | 400 A MCCB Incomer (Fixed type )with metering CTs, multi fuction meter compatible to scada, Ampermeter with SS, Voltmeter with SS, IndicatingLamps,ControlFuse,wiringetc.completeinallrespect. Size:900(W)X600(H)X1000(D) |
| 655 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 656 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 657 | 200AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)600(H)X1000(D) |
| 658 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 659 | 30KW |
| 660 | 22KW |
| 661 | S&FofStardeltaStarterwithMCB,MainandAuxContactor,O/L Relay,L/RSelectorSwitch,3Indicatinglamps,Start-StopPush Button,ControlMCBwithpanelwithallaccessorieswithfollowing rating |
| 662 | 15KW |
| 663 | 433V APFC Panel( 90KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 664 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 665 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 666 | Local Push Button Station |
| 667 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 668 | 7 Mtr. |
| 669 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 670 | Single arm overhang |
| 671 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 672 | LED street light fixture 80-90 watt |
| 673 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 674 | 1 X 250 Watt |
| 675 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 676 | 250 Watt |
| 677 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 678 | 20 Mtr Hm (in 2 section) |
| 679 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 680 | 1 X 250/ 150 Watt |
| 681 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 682 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 683 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 684 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 685 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 686 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 687 | 529 m3/hr capacity |
| 688 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 689 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 690 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 691 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 692 | Discharge 36 cum/hr and head 11 to 15 M |
| 693 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 694 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 695 | Part-04: E-Provision for Construction of Kankarwas Pump house (Mahukhera) |
| 696 | Civil work such as construction of pump House. |
| 697 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Abaneri worknear proposed 3250 KL CWR (For Installation of 4W+4S Pumps & 2 pumps for future) |
| 698 | Mechanical Equipment & Accessories |
| 699 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 700 | Centrifugal horizontal split casing pumps & motor all other accessories of following duty conditions |
| 701 | Balahera OHSR route18.84 LPS / 60 m head/25 KW |
| 702 | Mau kalan OHSR route10.54 LPS / 55 m head/15 KW |
| 703 | Bawari Kalan OHSR route14.11 LPS /70 m head/20KW |
| 704 | Golara Mod OHSR route22.33 LPS / 70 m head/30 KW |
| 705 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 706 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 707 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 708 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 709 | 150 MM |
| 710 | 200 MM |
| 711 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 712 | Motorized Sluice Valves with Electric Actuator and integral starter of Class PN 1.6 |
| 713 | 150 MM |
| 714 | 200 MM |
| 715 | 250 MM |
| 716 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 717 | Class PN 1.6, Motorised Operated |
| 718 | 150 MM |
| 719 | 200 MM |
| 720 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 721 | Class PN 1.6 |
| 722 | 150 MM |
| 723 | 200 MM |
| 724 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 725 | 150 MM |
| 726 | 200 MM |
| 727 | 250 MM |
| 728 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 729 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 730 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 731 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 732 | Class PN 1.6 |
| 733 | 50 mm |
| 734 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 735 | - 1.0 to +1.0 kg/cm² |
| 736 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 737 | 150 mm |
| 738 | 200 mm |
| 739 | Water meter chamber: |
| 740 | 150 mm |
| 741 | 200 mm |
| 742 | Electric equipment and accessories |
| 743 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 744 | 250KVA |
| 745 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 746 | 11KV HT Panel (drowout type) |
| 747 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 748 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 749 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 750 | 110VDC |
| 751 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 752 | 25 A + 25 A |
| 753 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 754 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 755 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 756 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 757 | 50mm x 6mm copper strip |
| 758 | 50mm x 6mm G.I. Strip |
| 759 | 32mm x6mm G.I. Strip |
| 760 | 25mm x 6mm G.I. Strip |
| 761 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 762 | 3 core 95.0 Sq.mm |
| 763 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 764 | Indoor |
| 765 | 3 core 70/95 Sq.mm |
| 766 | Outdoor |
| 767 | 3 core 70/95 Sq.mm |
| 768 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 769 | 300 SQMM,3.5 core |
| 770 | 35 SQMM, 3 CORE |
| 771 | 25 SQMM, 3 CORE |
| 772 | 16 SQMM, 3 CORE |
| 773 | 4.0 Sq.mm x 3 Core |
| 774 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 775 | Hot Dipped Galvanized |
| 776 | 450mm x 50mm x 2.0mm |
| 777 | 600mm x 50mm x 2.0mm |
| 778 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 779 | Hot Dipped Galvanized |
| 780 | 100mm x 50mm x 1.6mm |
| 781 | 150mm x 50mm x 1.6mm |
| 782 | 300mm x 50mm x 1.6mm |
| 783 | 450mm x 50mm x 2.0mm |
| 784 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 785 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 786 | 400 A MCCB Incomer (Fixed type )with metering CTs, multi fuction meter compatible to scada, Ampermeter with SS, Voltmeter with SS, IndicatingLamps,ControlFuse,wiringetc.completeinallrespect. Size:900(W)X600(H)X1000(D) |
| 787 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 788 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 789 | 200AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)600(H)X1000(D) |
| 790 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 791 | 30KW |
| 792 | 22KW |
| 793 | S&FofStardeltaStarterwithMCB,MainandAuxContactor,O/L Relay,L/RSelectorSwitch,3Indicatinglamps,Start-StopPush Button,ControlMCBwithpanelwithallaccessorieswithfollowing rating |
| 794 | 15KW |
| 795 | 433V APFC Panel( 90KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 796 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 797 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 798 | Local Push Button Station |
| 799 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 800 | 7 Mtr. |
| 801 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 802 | Single arm overhang |
| 803 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 804 | LED street light fixture 80-90 watt |
| 805 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 806 | 1 X 250 Watt |
| 807 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 808 | 250 Watt |
| 809 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 810 | 20 Mtr Hm (in 2 section) |
| 811 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 812 | 1 X 250/ 150 Watt |
| 813 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 814 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 815 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 816 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 817 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 818 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 819 | 529 m3/hr capacity |
| 820 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 821 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 822 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 823 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 824 | Discharge 36 cum/hr and head 11 to 15 M |
| 825 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 826 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 827 | Part-04: F-Provision for Construction of Gurha Pump house (Nagwas) |
| 828 | Civil work such as construction of pump House. |
| 829 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Nangwas Head worknear proposed 2250 KL CWR (For Installation of 3W+3S Pumps & 2 pumps for future) |
| 830 | Mechanical Equipment & Accessories |
| 831 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 832 | Centrifugal horizontal split casing pumps & motor all other accessories of following duty conditions |
| 833 | Tihara OHSR route20.49 LPS /80 m head/30 KW |
| 834 | MurliOHSR route29.23 LPS / 50m head/30 KW |
| 835 | Siddha Bada Ka Guwada OHSR route 8.33 LPS /80 m head/15 KW |
| 836 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 837 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 838 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 839 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 840 | 125 MM |
| 841 | 150 MM |
| 842 | 200 MM |
| 843 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 844 | Motorized Sluice Valves with Electric Actuator and integral starter of Class PN 1.6 |
| 845 | 150 MM |
| 846 | 200 MM |
| 847 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 848 | Class PN 1.6, Motorised Operated |
| 849 | 125 MM |
| 850 | 150 MM |
| 851 | 200 MM |
| 852 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 853 | Class PN 1.6 |
| 854 | 125 MM |
| 855 | 150 MM |
| 856 | 200 MM |
| 857 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 858 | 125 MM |
| 859 | 150 MM |
| 860 | 200 MM |
| 861 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 862 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 863 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 864 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 865 | Class PN 1.6 |
| 866 | 50 mm |
| 867 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 868 | - 1.0 to +1.0 kg/cm² |
| 869 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 870 | 150 mm |
| 871 | 200 mm |
| 872 | Water meter chamber: |
| 873 | 150 mm |
| 874 | 200 mm |
| 875 | Electric equipment and accessories |
| 876 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 877 | 250KVA |
| 878 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 879 | 11KV HT Panel (drowout type) |
| 880 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 881 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 882 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 883 | 110VDC |
| 884 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 885 | 25 A + 25 A |
| 886 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 887 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 888 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 889 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 890 | 50mm x 6mm copper strip |
| 891 | 50mm x 6mm G.I. Strip |
| 892 | 32mm x6mm G.I. Strip |
| 893 | 25mm x 6mm G.I. Strip |
| 894 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 895 | 3 core 95.0 Sq.mm |
| 896 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 897 | Indoor |
| 898 | 3 core 70/95 Sq.mm |
| 899 | Outdoor |
| 900 | 3 core 70/95 Sq.mm |
| 901 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 902 | 300 SQMM,3.5 core |
| 903 | 35 SQMM, 3 CORE |
| 904 | 16 SQMM, 3 CORE |
| 905 | 4.0 Sq.mm x 3 Core |
| 906 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 907 | Hot Dipped Galvanized |
| 908 | 450mm x 50mm x 2.0mm |
| 909 | 600mm x 50mm x 2.0mm |
| 910 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 911 | Hot Dipped Galvanized |
| 912 | 100mm x 50mm x 1.6mm |
| 913 | 150mm x 50mm x 1.6mm |
| 914 | 300mm x 50mm x 1.6mm |
| 915 | 450mm x 50mm x 2.0mm |
| 916 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 917 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 918 | 400 A MCCB Incomer (Fixed type )with metering CTs, multi fuction meter compatible to scada, Ampermeter with SS, Voltmeter with SS, IndicatingLamps,ControlFuse,wiringetc.completeinallrespect. Size:900(W)X600(H)X1000(D) |
| 919 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 920 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 921 | 200AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)600(H)X1000(D) |
| 922 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 923 | 30KW |
| 924 | S&FofStardeltaStarterwithMCB,MainandAuxContactor,O/L Relay,L/RSelectorSwitch,3Indicatinglamps,Start-StopPush Button,ControlMCBwithpanelwithallaccessorieswithfollowing rating |
| 925 | 15KW |
| 926 | 433V APFC Panel( 90KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 927 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 928 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 929 | Local Push Button Station |
| 930 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 931 | 7 Mtr. |
| 932 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 933 | Single arm overhang |
| 934 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 935 | LED street light fixture 80-90 watt |
| 936 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 937 | 1 X 250 Watt |
| 938 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 939 | 250 Watt |
| 940 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 941 | 20 Mtr Hm (in 2 section) |
| 942 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 943 | 1 X 250/ 150 Watt |
| 944 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 945 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 946 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 947 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 948 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 949 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 950 | 351 m3/hr capacity |
| 951 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 952 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 953 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 954 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 955 | Discharge 36 cum/hr and head 11 to 15 M |
| 956 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 957 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 958 | Part-04: G-Provision for Construction of Kolana Pump house |
| 959 | Civil work such as construction of pump House. |
| 960 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Kolana Head worknear proposed 2250 KL CWR (For Installation of 2W+2S Pumps & 2 pumps for future) |
| 961 | Mechanical Equipment & Accessories |
| 962 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 963 | Centrifugal horizontal split casing pumps & motor all other accessories of following duty conditions |
| 964 | Saylawas Kalan OHSR route 33.63 LPS /60 m head/40 KW |
| 965 | Sabarawali OHSR route49.44 LPS /75m head/70 KW |
| 966 | Jaisinghpura OHSR route27.02 LPS /80m head/40 KW |
| 967 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 968 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 969 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 970 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 971 | 200 MM |
| 972 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 973 | Motorized Sluice Valves with Electric Actuator and integral starter of Class PN 1.6 |
| 974 | 200 MM |
| 975 | 250 MM |
| 976 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 977 | Class PN 1.6, Motorised Operated |
| 978 | 200 MM |
| 979 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 980 | Class PN 1.6 |
| 981 | 200 MM |
| 982 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 983 | 200 MM |
| 984 | 250 MM |
| 985 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 986 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 987 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 988 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 989 | Class PN 1.6 |
| 990 | 50 mm |
| 991 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 992 | - 1.0 to +1.0 kg/cm² |
| 993 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 994 | 200 mm |
| 995 | Water meter chamber: |
| 996 | 200 mm |
| 997 | Electric equipment and accessories |
| 998 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 999 | 400KVA |
| 1000 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 1001 | 11KV HT Panel (drowout type) |
| 1002 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 1003 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 1004 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 1005 | 110VDC |
| 1006 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 1007 | 25 A + 25 A |
| 1008 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1009 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1010 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 1011 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 1012 | 50mm x 6mm copper strip |
| 1013 | 50mm x 6mm G.I. Strip |
| 1014 | 32mm x6mm G.I. Strip |
| 1015 | 25mm x 6mm G.I. Strip |
| 1016 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 1017 | 3 core 95.0 Sq.mm |
| 1018 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 1019 | Indoor |
| 1020 | 3 core 70/95 Sq.mm |
| 1021 | Outdoor |
| 1022 | 3 core 70/95 Sq.mm |
| 1023 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 1024 | 300 SQMM,3.5 core |
| 1025 | 95 SQMM, 3 CORE |
| 1026 | 50 SQMM, 3 CORE |
| 1027 | 4.0 Sq.mm x 3 Core |
| 1028 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 1029 | Hot Dipped Galvanized |
| 1030 | 450mm x 50mm x 2.0mm |
| 1031 | 600mm x 50mm x 2.0mm |
| 1032 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 1033 | Hot Dipped Galvanized |
| 1034 | 100mm x 50mm x 1.6mm |
| 1035 | 150mm x 50mm x 1.6mm |
| 1036 | 300mm x 50mm x 1.6mm |
| 1037 | 450mm x 50mm x 2.0mm |
| 1038 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 1039 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 1040 | Incommerfeeder(drowouttype)fortransformer630A/800A,50KA, ACB3pole,AlBusBars,DigitalMultifunctionmetercompatableto SCADA,metering,ProtectionCT\"s,IDMT3-O/C&1-E/F,indicating lamps,controlfuse,wiringetc.completeinallrespectofthesize appxo 900(D)X.2400(H)X1000(D) |
| 1041 | Bus Coupler Feeder (drowout type ), 630/800 A ACB, 50KA, 3 Pole withoutreleasewithAlBusBars,IndicatingLamps,ControlFuses andwiringetc.completeinallrespect.Size:900(W)x2400(H)x 1000 (D) |
| 1042 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1043 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1044 | 400AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)X900(H)X1000(D) |
| 1045 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 1046 | 45KW |
| 1047 | 75KW |
| 1048 | 433V APFC Panel( 150KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1049 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1050 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 1051 | Local Push Button Station |
| 1052 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 1053 | 7 Mtr. |
| 1054 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 1055 | Single arm overhang |
| 1056 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 1057 | LED street light fixture 80-90 watt |
| 1058 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 1059 | 1 X 250 Watt |
| 1060 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 1061 | 250 Watt |
| 1062 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 1063 | 20 Mtr Hm (in 2 section) |
| 1064 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 1065 | 1 X 250/ 150 Watt |
| 1066 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 1067 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 1068 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 1069 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 1070 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 1071 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 1072 | 349 m3/hr capacity |
| 1073 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 1074 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 1075 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 1076 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 1077 | Discharge 36 cum/hr and head 11 to 15 M |
| 1078 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 1079 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 1080 | Part-04: H-Provision for Construction of Rajahera Pump house |
| 1081 | Civil work such as construction of pump House. |
| 1082 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Rajahera Head worknear proposed 2750 KL CWR (For Installation of 3W+3S Pumps & 2 pumps for future) |
| 1083 | Mechanical Equipment & Accessories |
| 1084 | Providing,installation,testingandcommissioning ofSubmergedCentrifugal Pump sets with motor 4 pole sychronised speed of 1500 rpm ( water immersed, dryairfilled,class\"F\"insulatedTEWCmotorintegrallymountedonvolute casing pump sets for drinking water ) 3 phase, +/- 3%, 415 volt +/- 10%, along with suitable foundation/ installation device and with 10 mtr cable, material of construction of impeller SS, casing (volute) CI, wearing ring SS, etc. completein allrespectasper specification,scopeofworkanddirectionofEngineerin Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 1085 | Centrifugal horizontal split casing pumps & motor all other accessories of following duty conditions |
| 1086 | Kankarwas OHSR route65.81LPS /30 m head/40 KW |
| 1087 | Jeel ki Dhani OHSR route 29.15 LPS / 75m head/40 KW |
| 1088 | Noorpur OHSR route 12.86 LPS /45 m head/15 KW |
| 1089 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 1090 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 1091 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1092 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 1093 | 150 MM |
| 1094 | 200 MM |
| 1095 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1096 | Motorized Sluice Valves with Electric Actuator and integral starter of Class PN 1.6 |
| 1097 | 200 MM |
| 1098 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) short bodypattern type double eccentric Butterflyvalvesof approvedmakeoffollowingclass&diacompleteconfirmingtoBSEN593/BS 5155/ IS 13095/1991 amended up todate andof following specifications: Body, disc and end cover of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequentrevisions,FacetofacedimensionsasperDIN3202F4/IS13095 DrilledasperIS:1538.ElectrostaticEpoxyPowder(EP-P)/FusionBondedEpoxy (Non-Toxic &suitable for drinking water) coated withminimum thickness of 250 micron applied on both body and disc inside and outside. Disc seal ring of EPDM/ Neoprene(foodgradequality)anddiscsealretainingringofSS/CS.ShaftofSS- AISI- 304/316 & shaft bearings-bronze/ PTET or Teflon with EPDM/NBR \"O \"ring seal,Nut-BoltconfirmingtoIS:1363andIS:1367(Galvenisedsteel)Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along withpipelineasperTechnicalSpecification&asperdirectionofEngineer-in- charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1099 | Class PN 1.6, Motorised Operated |
| 1100 | 150 MM |
| 1101 | 200 MM |
| 1102 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1103 | Class PN 1.6 |
| 1104 | 150 MM |
| 1105 | 200 MM |
| 1106 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 1107 | 150 MM |
| 1108 | 200 MM |
| 1109 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 1110 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 1111 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 1112 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1113 | Class PN 1.6 |
| 1114 | 50 mm |
| 1115 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 1116 | - 1.0 to +1.0 kg/cm² |
| 1117 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 1118 | 150 mm |
| 1119 | 200 mm |
| 1120 | Water meter chamber: |
| 1121 | 150 mm |
| 1122 | 200 mm |
| 1123 | Electric equipment and accessories |
| 1124 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 1125 | 250KVA |
| 1126 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 1127 | 11KV HT Panel (drowout type) |
| 1128 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 1129 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 1130 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 1131 | 110VDC |
| 1132 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 1133 | 25 A + 25 A |
| 1134 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1135 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1136 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 1137 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 1138 | 50mm x 6mm copper strip |
| 1139 | 50mm x 6mm G.I. Strip |
| 1140 | 32mm x6mm G.I. Strip |
| 1141 | 25mm x 6mm G.I. Strip |
| 1142 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 1143 | 3 core 95.0 Sq.mm |
| 1144 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 1145 | Indoor |
| 1146 | 3 core 70/95 Sq.mm |
| 1147 | Outdoor |
| 1148 | 3 core 70/95 Sq.mm |
| 1149 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 1150 | 300 SQMM,3.5 core |
| 1151 | 50 SQMM, 3 CORE |
| 1152 | 16 SQMM, 3 CORE |
| 1153 | 4.0 Sq.mm x 3 Core |
| 1154 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 1155 | Hot Dipped Galvanized |
| 1156 | 450mm x 50mm x 2.0mm |
| 1157 | 600mm x 50mm x 2.0mm |
| 1158 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 1159 | Hot Dipped Galvanized |
| 1160 | 100mm x 50mm x 1.6mm |
| 1161 | 150mm x 50mm x 1.6mm |
| 1162 | 300mm x 50mm x 1.6mm |
| 1163 | 450mm x 50mm x 2.0mm |
| 1164 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 1165 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 1166 | 400 A MCCB Incomer (Fixed type )with metering CTs, multi fuction meter compatible to scada, Ampermeter with SS, Voltmeter with SS, IndicatingLamps,ControlFuse,wiringetc.completeinallrespect. Size:900(W)X600(H)X1000(D) |
| 1167 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1168 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1169 | 200AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)600(H)X1000(D) |
| 1170 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 1171 | 45KW |
| 1172 | S&FofStardeltaStarterwithMCB,MainandAuxContactor,O/L Relay,L/RSelectorSwitch,3Indicatinglamps,Start-StopPush Button,ControlMCBwithpanelwithallaccessorieswithfollowing rating |
| 1173 | 15KW |
| 1174 | 433V APFC Panel( 90KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1175 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1176 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 1177 | Local Push Button Station |
| 1178 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 1179 | 7 Mtr. |
| 1180 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 1181 | Single arm overhang |
| 1182 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 1183 | LED street light fixture 80-90 watt |
| 1184 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 1185 | 1 X 250 Watt |
| 1186 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 1187 | 250 Watt |
| 1188 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 1189 | 20 Mtr Hm (in 2 section) |
| 1190 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 1191 | 1 X 250/ 150 Watt |
| 1192 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 1193 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 1194 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 1195 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 1196 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 1197 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 1198 | 455 m3/hr capacity |
| 1199 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 1200 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 1201 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 1202 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 1203 | Discharge 36 cum/hr and head 11 to 15 M |
| 1204 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 1205 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 1206 | Part-04: I-Provision for Construction of SikraiPump house |
| 1207 | Civil work such as construction of pump House. |
| 1208 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Sikrai worknear proposed 3750 KL CWR (For Installation of 4W+4S Pumps & 2 pumps for future) |
| 1209 | Mechanical Equipment & Accessories |
| 1210 | Providing and fixingat site with necessary packing,Horizontal Centrifugal Split Casting pumps with 4 poleinduction motor operating at syncronised speed of speed 1500 RPM as per IS 12615: 2011 or amended up to date , CI casing and casingring,SS316impeller,SS410Shaftandshaftsleeve,couplingguard, common base plate, foundation bolts, Cement concrete foundation etc. completewithallrespectasperthespecificationandscopeofworkand direction of Engineer in Charge of following range of duty conditions.Note: Duty condition of required pump shall also be mentioned in BoQ. |
| 1211 | Sikrai Doongar OHSR route45.11 LPS /75 m head/65 KW |
| 1212 | Bhalpur OHSR route28.67 LPS / 55 m head/30 KW |
| 1213 | Goojar Seemla OHSR route23.51 LPS / 45 m head/20 KW |
| 1214 | Peepalki OHSR route41.72 LPS / 60 m head/50 KW |
| 1215 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 1216 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 1217 | Providing, lowering, aligning, fixing in position in pipe line at work site, DID/F Resilientseated(softseated)SluiceValves(GateValves), Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxypowder(EP-P)/Fusionbondepoxy(Non-Toxic-suitablefor drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS:1367 (Galvanisedsteel)Insersionrubberofblack EPDM6mm thick. Suitable supportstructureasperdirectionsofEIC,Sluicevalves includingall jointing& jointingmaterial,labour,testing and commissioning along with pipe line as per Technical Specifications and as perdirectionofEngineer-in-charge.Note:Ratesareexclusiveoftail piece/ dismantling joints and earth work. Manually operated class PN 1.6 For Suction side |
| 1218 | 200 MM |
| 1219 | 250 MM |
| 1220 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1221 | 150 MM |
| 1222 | 200 MM |
| 1223 | 250 MM |
| 1224 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1225 | 150 MM |
| 1226 | 200 MM |
| 1227 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 1228 | 150 MM |
| 1229 | 200 MM |
| 1230 | 250 MM |
| 1231 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 1232 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 1233 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 1234 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1235 | 50 mm |
| 1236 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 1237 | - 1.0 to +1.0 kg/cm² |
| 1238 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 1239 | 150 mm |
| 1240 | 200 mm |
| 1241 | Water meter chamber: |
| 1242 | 150 mm |
| 1243 | 200 mm |
| 1244 | Electric equipment and accessories |
| 1245 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 1246 | 400KVA |
| 1247 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 1248 | 11KV HT Panel (drowout type) |
| 1249 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 1250 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 1251 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 1252 | 110VDC |
| 1253 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 1254 | 25 A + 25 A |
| 1255 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1256 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1257 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 1258 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 1259 | 50mm x 6mm copper strip |
| 1260 | 50mm x 6mm G.I. Strip |
| 1261 | 32mm x6mm G.I. Strip |
| 1262 | 25mm x 6mm G.I. Strip |
| 1263 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 1264 | 3 core 95.0 Sq.mm |
| 1265 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 1266 | Indoor |
| 1267 | 3 core 70/95 Sq.mm |
| 1268 | Outdoor |
| 1269 | 3 core 70/95 Sq.mm |
| 1270 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 1271 | 300 SQMM,3.5 core |
| 1272 | 185 SQMM,3.5 core |
| 1273 | 35 SQMM, 3 CORE |
| 1274 | 25 SQMM, 3 CORE |
| 1275 | 50 SQMM, 3 CORE |
| 1276 | 120 SQMM, 3 CORE |
| 1277 | 4.0 Sq.mm x 3 Core |
| 1278 | Heavy Duty double compressed Lugs,Double Compression Brass Cable Gland with Nickel Plated, Cable Tie , Cable Tags, GI Nut- Bolts-Washers, Anchor Fastners,required hardware & accessories for various sizes as per requirements. |
| 1279 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 1280 | Hot Dipped Galvanized |
| 1281 | 450mm x 50mm x 2.0mm |
| 1282 | 600mm x 50mm x 2.0mm |
| 1283 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 1284 | Hot Dipped Galvanized |
| 1285 | 100mm x 50mm x 1.6mm |
| 1286 | 150mm x 50mm x 1.6mm |
| 1287 | 300mm x 50mm x 1.6mm |
| 1288 | 450mm x 50mm x 2.0mm |
| 1289 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 1290 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 1291 | Incommerfeeder(drowouttype)fortransformer630A/800A,50KA, ACB3pole,AlBusBars,DigitalMultifunctionmetercompatableto SCADA,metering,ProtectionCT\"s,IDMT3-O/C&1-E/F,indicating lamps,controlfuse,wiringetc.completeinallrespectofthesize appxo 900(D)X.2400(H)X1000(D) |
| 1292 | Bus Coupler Feeder (drowout type ), 630/800 A ACB, 50KA, 3 Pole withoutreleasewithAlBusBars,IndicatingLamps,ControlFusesandwiringetc.completeinallrespect.Size:900(W)x2400(H)x 1000 (D) |
| 1293 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1294 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1295 | 250AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)600(H)X1000(D) |
| 1296 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 1297 | 22KW |
| 1298 | 30KW |
| 1299 | 55KW |
| 1300 | 75KW |
| 1301 | 433V APFC Panel( 110KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1302 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1303 | 433VIndoor LT Switchgear Panel for CHLORINATION DEFUSION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1304 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 1305 | Local Push Button Station |
| 1306 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 1307 | 7 Mtr. |
| 1308 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 1309 | Single arm overhang |
| 1310 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 1311 | LED street light fixture 80-90 watt |
| 1312 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 1313 | 1 X 250 Watt |
| 1314 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 1315 | 250 Watt |
| 1316 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 1317 | 20 Mtr Hm (in 2 section) |
| 1318 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 1319 | 1 X 250/ 150 Watt |
| 1320 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 1321 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 1322 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 1323 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 1324 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 1325 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 1326 | 587 m3/hr capacity |
| 1327 | Campus development works |
| 1328 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 1329 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with 50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 1330 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 1331 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 1332 | Discharge 36 cum/hr and head 11 to 15 M |
| 1333 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 1334 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 1335 | Particulars |
| 1336 | Civil work such as construction of pump House. |
| 1337 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Torda Head worknear proposed 3000 KL CWR (For Installation of 3W+3S Pumps & 2 pumps for future) |
| 1338 | Mechanical Equipment & Accessories |
| 1339 | Providing and fixingat site with necessary packing,Horizontal Centrifugal Split Casting pumps with 4 poleinduction motor operating at syncronised speed of speed 1500 RPM as per IS 12615: 2011 or amended up to date , CI casing and casingring,SS316impeller,SS410Shaftandshaftsleeve,couplingguard, common base plate, foundation bolts, Cement concrete foundation etc. completewithallrespectasperthespecificationandscopeofworkand direction of Engineer in Charge of following range of duty conditions.Note: Duty condition of required pump shall also be mentioned in BoQ. |
| 1340 | Shekhpura OHSR route33.88 LPS / 55 m head/35 KW |
| 1341 | Moroli OHSR route39.60 LPS / 75m head/55 KW |
| 1342 | Bairawanda OHSR route43.35 LPS /70 m head/60 KW |
| 1343 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 1344 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 1345 | Providing, lowering, aligning, fixing in position in pipe line at work site, DID/F Resilientseated(softseated)SluiceValves(GateValves), Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxypowder(EP-P)/Fusionbondepoxy(Non-Toxic-suitablefor drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS:1367 (Galvanisedsteel)Insersionrubberofblack EPDM6mm thick. Suitable supportstructureasperdirectionsofEIC,Sluicevalves includingall jointing& jointingmaterial,labour,testing and commissioning along with pipe line as per Technical Specifications and as perdirectionofEngineer-in-charge.Note:Ratesareexclusiveoftail piece/ dismantling joints and earth work. Manually operated class PN 1.6 For Suction side |
| 1346 | 200 MM |
| 1347 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1348 | 200 MM |
| 1349 | 250 MM |
| 1350 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1351 | 200 MM |
| 1352 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 1353 | 200 MM |
| 1354 | 250 MM |
| 1355 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 1356 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 1357 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 1358 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1359 | 50 mm |
| 1360 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 1361 | - 1.0 to +1.0 kg/cm² |
| 1362 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 1363 | 150 mm |
| 1364 | 200 mm |
| 1365 | Water meter chamber: |
| 1366 | 150 mm |
| 1367 | 200 mm |
| 1368 | Electric equipment and accessories |
| 1369 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 1370 | 400KVA |
| 1371 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 1372 | 11KV HT Panel (drowout type) |
| 1373 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 1374 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 1375 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 1376 | 110VDC |
| 1377 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 1378 | 25 A + 25 A |
| 1379 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1380 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1381 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 1382 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 1383 | 50mm x 6mm copper strip |
| 1384 | 50mm x 6mm G.I. Strip |
| 1385 | 32mm x6mm G.I. Strip |
| 1386 | 25mm x 6mm G.I. Strip |
| 1387 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 1388 | 3 core 95.0 Sq.mm |
| 1389 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 1390 | Indoor |
| 1391 | 3 core 70/95 Sq.mm |
| 1392 | Outdoor |
| 1393 | 3 core 70/95 Sq.mm |
| 1394 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 1395 | 300 SQMM,3.5 core |
| 1396 | 185 SQMM,3.5 core |
| 1397 | 35 SQMM, 3 CORE |
| 1398 | 50 SQMM, 3 CORE |
| 1399 | 120 SQMM, 3 CORE |
| 1400 | 4.0 Sq.mm x 3 Core |
| 1401 | Heavy Duty double compressed Lugs,Double Compression Brass Cable Gland with Nickel Plated, Cable Tie , Cable Tags, GI Nut- Bolts-Washers, Anchor Fastners,required hardware & accessories for various sizes as per requirements. |
| 1402 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 1403 | 450mm x 50mm x 2.0mm |
| 1404 | 600mm x 50mm x 2.0mm |
| 1405 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 1406 | 100mm x 50mm x 1.6mm |
| 1407 | 150mm x 50mm x 1.6mm |
| 1408 | 300mm x 50mm x 1.6mm |
| 1409 | 450mm x 50mm x 2.0mm |
| 1410 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 1411 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 1412 | Incommerfeeder(drowouttype)fortransformer630A/800A,50KA, ACB3pole,AlBusBars,DigitalMultifunctionmetercompatableto SCADA,metering,ProtectionCT\"s,IDMT3-O/C&1-E/F,indicating lamps,controlfuse,wiringetc.completeinallrespectofthesize appxo 900(D)X.2400(H)X1000(D) |
| 1413 | Bus Coupler Feeder (drowout type ), 630/800 A ACB, 50KA, 3 Pole withoutreleasewithAlBusBars,IndicatingLamps,ControlFusesandwiringetc.completeinallrespect.Size:900(W)x2400(H)x 1000 (D) |
| 1414 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1415 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1416 | 250AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)600(H)X1000(D) |
| 1417 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 1418 | 37KW |
| 1419 | 55KW |
| 1420 | 75KW |
| 1421 | 433V APFC Panel( 120KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1422 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1423 | 433VIndoor LT Switchgear Panel for CHLORINATION DEFUSION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1424 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 1425 | Local Push Button Station |
| 1426 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 1427 | 7 Mtr. |
| 1428 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 1429 | Single arm overhang |
| 1430 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 1431 | LED street light fixture 80-90 watt |
| 1432 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 1433 | 1 X 250 Watt |
| 1434 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 1435 | 250 Watt |
| 1436 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 1437 | 20 Mtr Hm (in 2 section) |
| 1438 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 1439 | 1 X 250/ 150 Watt |
| 1440 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 1441 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 1442 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 1443 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 1444 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 1445 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 1446 | 493 m3/hr capacity |
| 1447 | Campus development works |
| 1448 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 1449 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with 50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 1450 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 1451 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 1452 | Discharge 36 cum/hr and head 11 to 15 M |
| 1453 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 1454 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 1455 | Particulars |
| 1456 | Civil work such as construction of pump House. |
| 1457 | ConstructionofPumphouseofrequiredsizesuitableforinstallationof maximum 4 no. monoblock pump sets as per approved GA drawing, scope ofworkandtechnicalspecificationcompleteworkinallrespect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement.At Jheejhun worknear proposed 4500 KL CWR (For Installation of 6W+6S Pumps & 2 pumps for future) |
| 1458 | Mechanical Equipment & Accessories |
| 1459 | BawanparaOHSR route49.37 LPS / 40 m head/40 KW |
| 1460 | Dhaliko OHSR route 27.04 LPS /50 m head/25 KW |
| 1461 | Peelwa Kalan OHSR route11.27 LPS / 40 m head/10 KW |
| 1462 | Jahangirpura OHSR route 18.78 LPS / 70 m head/25 KW |
| 1463 | Sarundla OHSR route44.22 LPS / 55 m head/45 KW |
| 1464 | Bhaogarh OHSR route25 LPS / 65 m head/30 KW |
| 1465 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depthsintrenchescompleteincluding alltaxes,material, labour, inside lining, outside coating, testingandcommissioning alongwith pipelineaspertechnicalspecifications anddirection of Engineer in-charge. |
| 1466 | MS pipespecialsupto600 mmdia (withminimum5.0 mmthickness sheet). For Common Header, Suction, Delivery etc. |
| 1467 | Providing, lowering, aligning, fixing in position in pipe line at work site, DID/F Resilientseated(softseated)SluiceValves(GateValves), Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxypowder(EP-P)/Fusionbondepoxy(Non-Toxic-suitablefor drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS:1367 (Galvanisedsteel)Insersionrubberofblack EPDM6mm thick. Suitable supportstructureasperdirectionsofEIC,Sluicevalves includingall jointing& jointingmaterial,labour,testing and commissioning along with pipe line as per Technical Specifications and as perdirectionofEngineer-in-charge.Note:Ratesareexclusiveoftail piece/ dismantling joints and earth work. Manually operated class PN 1.6 For Suction side |
| 1468 | 200 MM |
| 1469 | Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirfingtoBS-EN-1171/AWWAC-509andoffollowing specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202 F4, Stem/ spindle of SS (AISI 316 or equivalent) Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1470 | 200 MM |
| 1471 | 250 MM |
| 1472 | Providing,lowering,aligning,fixinginpositioninpipeline,DI doubleflanged resilient seated Dual plate check valave of approved make of following Pressure rating & dia complete,as per API: 594/ API: 598 and of following specifications: Body & Bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12asperIS1865orequivalentgradeasperIS:3896-part2-1985and subsequent revisions, Disc / plates - SG-400/12 or CF-8M,Face to face dimensions as per API: 594 , Flanges Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / FusionBondedEpoxy(Non-Toxic&suitablefordrinkingwater)coatedwith minimum thickness of 250 micron applied on body and cover inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring ofSS/CS.ShaftofSS-AISI-304/410,HingeSSAISI316/304,Spring SSAISI 316/304,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \"O \"ring seal, Nut-Bolt confirmingtoIS:1363andIS:1367(galvenisedsteel), Insersionrubberofblack EPDM6mmthick.Suitable supportstructureasperdirectionsofEIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 1473 | 200 MM |
| 1474 | Providing, installation, testing and commissioning of following Stain less steel AISI 304 Expansion bellows of 10/16 bar rating with tie rods as per technical specificationsandlayoutdrawingsincludingjointingmateriallikenuts,bolts, rubber gaskets etc. complete in all respect as per technical specification and as per direction of Engineer. |
| 1475 | 200 MM |
| 1476 | 250 MM |
| 1477 | Structural steel work in single section fixed with or without connecting plate including cutting, hoisting ( height upto 10 m), fixing in position and applying a priming coat of approved steel primer all complete. |
| 1478 | Supplying, erecting, testing & commissioning of Electrically Operated Travelling Crane (EOT) .Main girder & End Carriage fabricated from Rollled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineer. |
| 1479 | 3 MT Capacity(Span 9 M and Lift 6 M) |
| 1480 | Providing,lowering,aligning,fixinginpositionandJointinginpipeline,DIBody FlangedEndTamperproof KineticAirValveofapprovedmakesoffollowing pressure rating and dia and as per following specifications: Governing standard - AWWA C512/ IS:14845:2000(ammendeduptodate) Body,Highpressurecover , Lowpressurecover,Cowland Jointsupportring-Ductilecastironofgrade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865, Float- LP ball & HP ball:AISI304stainlessSteel,Seatring&Gasket-EPDM/NBR,HPOrifice&HP orifice plug : Bronze/ SS ,Bush: Bronze ,Flanges as per IS/ BS, Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body & coverinside and outside fastners - CS/ Galvenised steel, Outlet of big orifice will haveascreentopreventTamperoffloat, withDImetalseatedD/FNonrising stemSluiceValvesasper(IS:14846amended uptodate)PN1.6ratingsValves including all mateial, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. |
| 1481 | 50 mm |
| 1482 | Providing, installation, testing and commissioning of glycerin filled Pressure gauge of following ranges with isolation valve and tap off pipe complete in all respect as per technical specification and as per direction of Engineer. |
| 1483 | - 1.0 to +1.0 kg/cm² |
| 1484 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of followingdiaandspecificationscomplete:Media:Water(Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/MeterTube:SS304, Electrode:SSAISI316L/ HastelloyC276/ Tantalum,Lining Material : HardRubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completelysealed(leakproof)constructionasperrequirementofIEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertorEnclosure:DieCastAluminium,PowerSupply:80-240VAC- 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) andIP67fortransmitter/convertor,includingSurgeArrester,ifrequired, andallmaterialsrequiredformakingconnectionwithexistingpipeline includingcuttingtheexistingpipelineetc.completeinallrespectasper technical specification and as per direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 1485 | 200 mm |
| 1486 | Water meter chamber: |
| 1487 | 200 mm |
| 1488 | Electric equipment and accessories |
| 1489 | Supply, Installation, Testing and commissioning of copper wound ISI markedTransformer11/0.433KV,ThreePhase,50Hz,DYN11, ONANtype,Standardaccessorieslike,conservator,Silicagel breather, radiator, fins, HT & LT cable end boxes or Bus Duct flange, Liftinglugs,Bi-directionalPlain/FlangedRollers,Earthing terminal,Air relaese plug.Off load tap changer (+5% to -10% in stepsof2.5%),winding/Topoiltemperatureriseof45°C/40°C,ISImarked drain valves, Dial type temperature gauge, first fill oil, Epoxy basedpaintetchavingmax.totallossesasperenergyefficiency level-2atbasicInsulationlevelconformingtoIS2026(Part-Ito Part - II), latest ammended and IS 1180 Part-I : 2014 BEE star level -IasperGovt.ofIndia,MinistryofpowernotificationDated16th Dec.,2016.Transformersdescribedasaboveandasperthe following continuous rating |
| 1490 | 400KVA |
| 1491 | GI Structure for 11KV Incoming Power Supply Arrangement ,11 KV Lightning Arretors, 11KV Isolaror with Earth Switch,11KV DO Fuse Set of 100A,Outdoor CT/PT metering Set provided by JVVNL/Discom at Campus, 1500mm height Chain Link Fencing along with MS Gate 3M*3M, 50*6mm Angle Post, Barbid wire of three layersrequired hardware & accessories as per requirements, technical specifications and as directed by Engineer in charge. |
| 1492 | 11KV HT Panel (drowout type) |
| 1493 | Supply,Installation,TestingandCommissiongofindoortypefloor mountedmetalclad,11KVIncomerVCBpanelupto630A equippedwithfollowingswitchgearsandaccessoriesdesigned& testedasperlateststandardi.e.IEC62271-200,suitableforSTC 25KA/3andIACA-FLRfor25kA/1sec.MakeofHTPanel,Vaccum Interrupter and VCB should be of same make. 11KV/110VoltsPTClass0.5accuracyand100VAburdenwith1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeter andprotectionfuses/MCBforHTmeteringupto12KVonincomer, Ammeter,analogtype,selectorswitchesforammeters, MicroprocessorbasednumericalrelaywithO/L,E/FandS/C protection, Set of dual core dual ratio 3CTs of suitable ratio with sec 1 of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection, Multifunction Meter. |
| 1494 | Supply,Installation,TestingandCommissionofindoortypefloor mountedmetalclad,11KVOutgoingVCBpanelUPTO630Aequippedwithfollowingswitchgearsandaccessoriesdesigned&testedasperlateststandardi.e.IEC62271-200,suitableforSTC25KA/3andIACA-FLRfor25kA/1sec.MakeofPanel,Vaccum Interrupter and VCB should be of same make.11KV/110VoltsPTClass0.5accuracyand100VAburdenwith 1No. Voltmeter (0-12 KV), analog type, selector switch for voltmeterandprotectionfuses/MCBforHTmeteringupto11KV,Ammeter, analog type, selector switches forammeters, Microprocessor based numericalrelaywithO/L,E/FandS/Cprotection,Setofdualcoredualratio3CTsofsuitablerationwithsec1of15VAburdenandaccuracyClass–0.5formeteringandclass5P10forprotection, Multifunction Meter Outgoing upto 630 A VCB |
| 1495 | SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries , MS / Teakwood battery stand , interconnect wiring etc as required complete in all respect of rating: |
| 1496 | 110VDC |
| 1497 | SITCofFCBC ( Floatcumboostcharger)suitable for415V +/-10%,50 Hz , 1-? / 3 -? Input &24/ 48/110 VDC OutputNatural Cooled, freestandinginSheetSteelenclosure,SCRcontrolled,regulation +/-1% , Efficiency > 75% on FLAC/ DC Instruments, Selector Switch ,BuiltinDCDistributionBoard(6NoMCB),indication,controlasrequired of following rating: |
| 1498 | 25 A + 25 A |
| 1499 | Earthing Schedule Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1500 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 40 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1501 | GI Pipe, Class B, 40mm Dai with thickness of 3.610mm as per IS 1239 for the complete earthing system |
| 1502 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 1503 | 50mm x 6mm copper strip |
| 1504 | 50mm x 6mm G.I. Strip |
| 1505 | 32mm x6mm G.I. Strip |
| 1506 | 25mm x 6mm G.I. Strip |
| 1507 | Providing&LayingXLPEinsulatedIS:7098/II/85of approvedmakeH.T.cableforworkingvoltage11 K.V.Un-EarthedwithStrandedCompactedCircular AluminiumConductor,ConductorScreenedwith ExtrudedSemi-conductingcompound,XLPEInsulated, InsulationScreenedwithextrudedsemi-conductingcompoundincombinationwithCopperTape,coreslaid up,innersheathofThermoplastictape,galvanisedflat steel strip armoured and overall Extruded PVC Type ST-2OuterSheathedcabledirectingroundincluding excavationof30cmx100cmsizetrench,25cmlayerof riversand, second Class bricks covering, refilling earth, compactionofearth,makingnecessaryconnection testing etc.as required of size. |
| 1508 | 3 core 95.0 Sq.mm |
| 1509 | Providing&makingheatshrinkabletypeindoor/outdoor/straight throughterminations/jointkitofapprovedmakesuitableforXLPEinsulated11KVcable,withrequiredcomponents,preprationof cable ends,testing etc. as required of following sizes . |
| 1510 | Indoor |
| 1511 | 3 core 70/95 Sq.mm |
| 1512 | Outdoor |
| 1513 | 3 core 70/95 Sq.mm |
| 1514 | Providing & Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection,Complete as per technical specifications and as directed by Engineer in charge. |
| 1515 | 300 SQMM,3.5 core |
| 1516 | 185 SQMM,3.5 core |
| 1517 | 35 SQMM, 3 CORE |
| 1518 | 50 SQMM, 3 CORE |
| 1519 | 16 SQMM, 3 CORE |
| 1520 | 4.0 Sq.mm x 3 Core |
| 1521 | Heavy Duty double compressed Lugs,Double Compression Brass Cable Gland with Nickel Plated, Cable Tie , Cable Tags, GI Nut- Bolts-Washers, Anchor Fastners,required hardware & accessories for various sizes as per requirements. |
| 1522 | Supply,Fabricating&installingfollowingsizesofladdertypecable trays with rungs at span of 250 mm including horizontal and vertical bends,reducerstees,crossmembersandotheraccessoriesas requiredand dulysuspended from the ceiling/wall withsuspenders and including painting as required. |
| 1523 | Hot Dipped Galvanized |
| 1524 | 450mm x 50mm x 2.0mm |
| 1525 | 600mm x 50mm x 2.0mm |
| 1526 | Supply,Fabricating&installingfollowingsizesofperforatedcable traysincludinghorizontalandverticalbends,reducerstees,cross membersandotheraccessoriesasrequiredanddulysuspended from the ceiling withsuspenders and including painting as required. |
| 1527 | Hot Dipped Galvanized |
| 1528 | 100mm x 50mm x 1.6mm |
| 1529 | 150mm x 50mm x 1.6mm |
| 1530 | 300mm x 50mm x 1.6mm |
| 1531 | 450mm x 50mm x 2.0mm |
| 1532 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR as per latest IS 1562 :2006., 33 KV, 3 mm thick with proof voltage 36 KV / 3 min. and Break DownVoltage 65 KV |
| 1533 | 415 V LT PanelSITCoffloormountedPMCC(Indoor,DustproffIP-4Xfront operatedwith2mmthicksheetmetalcompartmentalised)withall accessibleparts,headshrinkablesleeves,SMC/DMCbusbar supports, padlocking facility on outgoing feeders etc. |
| 1534 | Incommerfeeder(drowouttype)fortransformer630A/800A,50KA, ACB3pole,AlBusBars,DigitalMultifunctionmetercompatableto SCADA,metering,ProtectionCT\"s,IDMT3-O/C&1-E/F,indicating lamps,controlfuse,wiringetc.completeinallrespectofthesize appxo 900(D)X.2400(H)X1000(D) |
| 1535 | Bus Coupler Feeder (drowout type ), 630/800 A ACB, 50KA, 3 Pole withoutreleasewithAlBusBars,IndicatingLamps,ControlFusesandwiringetc.completeinallrespect.Size:900(W)x2400(H)x 1000 (D) |
| 1536 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1537 | MCCB up to 100A(Fixed type ) as outgoing CT\"s, Ampermeter with SS,VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 600(W)300(H)X1000(D) |
| 1538 | 400AMCCB(Fixedtype)asoutgoingCT\"s,AmpermeterwithSS, VoltmeterwithSS,IndicatingLamps,ControlFuse,wiringetc. complete in all respect.Size: 900(W)X900(H)X1000(D |
| 1539 | SITCofSoftStarterswithpanelsuppliedbymanufacturer conforming to applicable standards with logic inputs & outputs, relay outputsandanalogueoutputs,pluginI/Oconnections,displayof electricalparameters,stateofload&operatingtime,RS485serial link for connections to Modbus. |
| 1540 | 30KW |
| 1541 | 45KW |
| 1542 | S&FofStardeltaStarterwithMCB,MainandAuxContactor,O/L Relay,L/RSelectorSwitch,3Indicatinglamps,Start-StopPush Button,ControlMCBwithpanelwithallaccessorieswithfollowing rating |
| 1543 | 11KW |
| 1544 | 433V APFC Panel( 150KVAR) in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor APFC Panel switchesgear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based APFC 8/12 Stage relays, APFC Duty Contactors, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1545 | 433VIndoor LT Switchgear Panel for POST CHLORINATION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1546 | 433VIndoor LT Switchgear Panel for CHLORINATION DEFUSION SYSTEM in cubicle made of CRCA sheet steel of minimum 2.5/2.0/1.6 mm thickness, comply with latest IS/ IEC, totally enclosed Operational on 3 Phase 415 voltages, 50Hz, neutrally grounded, IP 4X, The cubicle panel shall be vermin proof and dust-tight and shall be of compartmentalized type construction, nine tank pre-treatment process before powder coating, Paint Shade – Grey RAL 7032, gasket material- neoprene, AC/DC/CT wiring – 1.5/2.5sqmm PVC insulated multi strand Copper flexible wire, Heat shrinkable Colour coded PVC bus bar sleeves, cable entry Incoming – bottom and outgoing – Bottom as per requirement. The switchgears and control gears complete with all necessary supporting framework, nuts and bolts, Aluminum Bus Bar. The Indoor PCC panel switches gear (Air circuit breakers, MCCB, CTs, etc) and control gear (Microprocessor based relays, auxiliary contacts, Space heater and lighting, Digital A & V meters with Selector Switch, Phase Indications, Hooter, plug socket etc.) shall be mounted on the same panel Complete as per technical specifications and as directed by Engineer in charge. |
| 1547 | SITC of LocalPush Buttonstation fabricated with 16SWG CRCA sheet,paintedwithpolysterPowdercoatedfinishafterchemical treatmentwithFolliwngitemsandaccessories:- iShroudedTypepushbuttonwith2NOContactselementfor Start/forward-reverse. iiLockableMushroomheadtypepushbuutonwith2NCContact element. iii2.5Sqmmclipontypeterminalsasrequriedwith20%spares. iv 1.5 Sqmm PVC insulated felxible copper wire with lugs & ferrules as requried. |
| 1548 | Local Push Button Station |
| 1549 | SupplyanderectionofOctagonalpoleoffollowing lengthand dimensionas per table-3 withbaseplateon thecementconcretefoundationofM-15/M-20grade (1:1.5:3)withthehelpofanchorboltsofgrade6.8(IS 1367PIII).ThepoleshallbemadeofS-355JOgrade steelsheet,foldedlengthwisetoobtainedOctagonal shape,havingsinglelongitudinalseamweldandhot dippedgalvanisedinternally&externallyinaccordance withIS2629.Thepoleshallhaveaweatherproofflush doorandlockingarrangements.Thecompletework shallbesupervisedandcertifiedbythemanufacturers forsatisfactorysupply,erection,testingand commissioning. |
| 1550 | 7 Mtr. |
| 1551 | Supply,ErectionandFixingofhotdippedgalvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the poles |
| 1552 | Single arm overhang |
| 1553 | P/FIP-65/IP-66protectedstreetlightluminarieson bracket / Arm.Fixturemadefrompowdercoated singlepiecepressurediecastaluminumhousingwith heat dissipation fins on housing with high power LEDs . Diffuser/glasscoverforensuringIP-65protectionfor lampandcontrolgearcompartment,systemlumen outputof100lum/watthighpowerLED.Integrated drivershallbehighefficiencyhavingefficiencymore than 85 % and in compliance to IEC standards. System lifeof50000burninghourswith70%ofinitiallumens maintained. Fixture shall be in CE compliance. IP-65 protected LED street light luminaries |
| 1554 | LED street light fixture 80-90 watt |
| 1555 | P&FIP-65protectedintegralfloodlightluminaire suitableforHPSV/Metalhalidelampcomprisingof powdercoateddiecastaluminiumhousing, electrochemicallybrightenedandanodizedstippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral controlgearboxhavingcopperballast,capacitor, electronicignitorprewiredwithpvcinsulatedcopper conductoruptoterminalblockincludingmaking connection testing etc. |
| 1556 | 1 X 250 Watt |
| 1557 | P&FHighpressuresodiumvapour/Highpressure mercuryvapour/Metalhalide/Halogenlampas required. HPSV tubular lamp normal output. |
| 1558 | 250 Watt |
| 1559 | Supply, erection testing and commissioning of high mast lightingsystem(asperCP3-TRT/1996ofILE,UK) consistingoftotallyhotdipgalvanisedbysingledipped method high mast, lantern carriage suitable for up to 12 nosluminaries,mastheadassembly,twonosaviation obstruction neon lights, double drum type self sustaining winch,integralpowertool(winchmotorwithcontrol circuit) hot dipped galvanised heavy duty pipe lightening finial,suitableropesandCCfoundationofM-15grade complete as required. The mast is constructed from mild steelplates(asperBS-EN10025)cutandfoldedto form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised andcertifiedbythemanufacturersforsatisfactory supply,erection,testingandcommissioningofhigh mast.withallaccessories,whichalsoincludsinternal electricalcableandpanelwithfoundation. |
| 1560 | 20 Mtr Hm (in 2 section) |
| 1561 | P&FIP-65protectedmultitapballaststreetlight luminaireon bracketsuitableforHPSVLAMP, madeoutfrompowdercoatedsinglepiecediecast aluminiumhousing,electrochemicallybrightenedand anodized POToptics aluminium reflector, heat resistant andtoughenedglasscoverandaccessorieslikemulti tapcopperballast,electronicignitor,capacitor,holder prewireduptoterminalblocketc.asrequiredincluding makingconnectiontestingetc. |
| 1562 | 1 X 250/ 150 Watt |
| 1563 | SITC of Air Cooled split Air conditioners (wall mounted @ 2.0 ton) complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (EP foam pipe section) upto 10 Mtr (IDUto ODU), copper power cable upto 10 Mtr (IDU to ODU), R- 22 Refrigerant suitablefor 400/230V +10% of 50 Hz 1 /3 AC supply capable of performing COOLING, DEHUMIDIFICATION, AIR CIRCULATION, FILTERATION & VENTILATION of following capacity with resprocating/ rotary/ scroll compressor as specified. Energy Rating -5 Star. |
| 1564 | Providing and fixing in position lightening arrester set complete with 600mm x 600mm x 6mm thick G.I. earthing plate embedded below ground in earthling pit at 3.5 metre depth, G.I. strip of size 25mmx5mm thick from earthing plate to top of Over head tank, G.I. Finial made of GI bar 25mm dia and 2m long fixed on top of Building and connected to GI strip. The earthling set shall comply of IS:3043 complete in all respect as per specification and the direction of the Engineer. |
| 1565 | From3.3KWto7.5KWDOLStarterFeederwithMCB,Mainand AuxContactor,O/LRelay,L/RSelectorSwitch,3Indicating lamps,Start-StopPushButton,ControlMCB(Size:600(W)x400 (H) x 600 (D) |
| 1566 | SITC ofDGSet complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame&coupledthroughaflexiblecouplingorclose coupled.AlternatorshallbeselfregulatedwithstandardAlternator Protection( Over voltage, over speed & under voltage). Engine shall haveresidentialsilencer,upto10Mexhaustpiping,electronic/ Mechanical governor, Manual & electric Start, Batteries, Fueltank( with Stand)& piping, control panel (16 G) with MCCB (4P; 25 KA),Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engineinstrumentspanel,AVMandwithWeatherproof,powder coatedAccousticenclosureforDGsetforsoundattenuationfabricatedfrom1.6mmCRCAsheetsteel(structure)withsidewall fabricatedfrom1.6mmCRCAsheetandfilledwithfoamasper CPCBnormslatestamendments&IS8183.Thedoorsare fabricated from 1.6 mm CRCA sheet packed with accoustic material, floorofMSchequrredplate5.0mmthick,Alldoors/openingare sealed with neoprene/ EPDN gaskets. The enclosure has built in fuel tank,residentialsilencer(isolatedfrommainDGchamber)with protectionandtrippingofDGsetagainsttemperatureofmorethan 50°C.AllcontrolsforoperationofDGsetarefromoutsidethe enclosurewithDGcontrolpanelhavingmicroprocessorbased genset monitoring andcontrol systemmccbAmmeter, voltmeter, Pf meter,frequencymeter,KWHmeter,Ind.Lampsetc.mounted inside enclosure , visible and accessible from outside. The enclosure shouldbesuitableforfollowingcapacityDGsetsandalternator. Noiselevelislessthan75db(A)atadistanceof1Mtrs.duly certifiedbyauthorizedagency.Completeinallrespectoffollowing capacity : 62.5 KVA at 0.8 pf 415V 50Hz 3-Ø ( Radiator cooled and turbo charged) |
| 1567 | Supply,installation,testingandcommissioningof MNREapprovedGridtied SolarPanelswithinverter, meter,cable etc.suitable forRooftop installation as well as Utility Scale Solar Power Projects with 25 years of Linear Generation warranty.WorkincludesdesigningofsolarpanelareaandMSframeand foundationonground/roofofPumphouseorCWR,showingarrangementof panelinavailablespace,installationof PVmoduleonMSframeasper approved design and drawings. Mountingstructure shall be suitably designed to withstand wind velocity up to 150km/hr.Grid Tie Transformer less inverters, Multiple independent MPPTs, Peak efficiencyof>98%.ConnectuptomultiplestringsPVarrays,Easy&fast connection, Built-in string-level monitoring, IP65 protection level, Wi-Fi / internet based remote monitoring with 5 years warranty.All cabling up to panel and metre, earthing etc. required accessories and taxes are inclusive. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge.Note:Thereshallbe 5year servicewarranty forpanel, inverter,meter, cable etc. andsuitable provision shall be included in tender document. |
| 1568 | Providing, installation, testing and commissioning of Electro-chlorinator capable of producing active chlorine (in house generation) in the form of sodium hypochlorite solution by electrolysis of common salt with crystal solution tank of suitable capacity for brine solution complete with automatic metering cum dosing facility for disinfection of supplied water including supply and installation of dosing pumps of suitable duty points, supply of storage tank of suitable capacity for storage of hypochlorite solutionincluding packing, loading, unloading, transportation laying of inlet and outlet pipe lines and all required electric work. |
| 1569 | 742 m3/hr capacity |
| 1570 | Campus development works |
| 1571 | Construction of boundary wall of Brick/ stone masonary as per enclosed GA drawing,scopeofworkandtechnicalspecificationscompleteworkinall respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonary in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4.Superstructurework:StonemasonaryinCM:1:6,W-300,height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonary and cement mortar plaster 20 mm thick on brick masonary in CM 1:6.6. Expansion joint shall be on every 30 mtr.7.OntopofwallthereshallbeCCCoping75mmthick(1:2:4)shallbe provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. |
| 1572 | Providing 120cm. high fencing with angle iron posts 50x50x6mm. placed at every 3 Mtr. apart 30cm. in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner & every tenth posts to be strutted with 50x50x6mm angle iron provided with four horizontal lines and two diagonals of black barbed wire between two posts fitted and fixed with G.I. staple including earth work in excavation etc. complete. |
| 1573 | Providingandfixingsteel,gate,gratingandgrillsmadeofangles,tees, squarebars,flatsorblackpipewithholdfastandfitting completeas per design and drawing including cutting welding and fabrication with priming coat of red oxide and two coat of enamel paints. |
| 1574 | Supply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck FootBend, with Guide wire SS 304 etc. complete with all respect as per specification |
| 1575 | Discharge 36 cum/hr and head 11 to 15 M |
| 1576 | Providing and fixing with bracket/ supports etc wall/floor mounted fire extinguishers as per details below: |
| 1577 | ISI marked 10 kg capacity Dry Powder fire xtinguisher with high pressure discharge hose, squeeze gripe nozzle 120 gms carbon dioxide cartridge, gun metal cap with initial charge of dry power.Both extinguisher and dry power to be ISI marked. |
| 1578 | Provision of Construction of Civil Building : Baswa |
| 1579 | Electrician (each at every pump house) 8 nos, Plinth Area @ 85Sqm each |
| 1580 | Fitter(each at every pump house)8 nos, Plinth Area @ 85Sqm each |
| 1581 | Pump Driver(each at every pump house)8 nos, Plinth Area @ 85Sqm each |
| 1582 | Store Shed(each at every pump house)8 nos, Plinth Area @ 70Sqm each |
| 1583 | DG Shed (each at every pump house)8 nos, Plinth Area @30 Sqm each |
| 1584 | Provision of Construction of Civil Building : Sikrai |
| 1585 | Electrician (each at every pump house) 3 nos, Plinth Area @ 85Sqm each |
| 1586 | Fitter(each at every pump house)3 nos, Plinth Area @ 85Sqm each |
| 1587 | Pump Driver(each at every pump house)3 nos, Plinth Area @ 85Sqm each |
| 1588 | Store Shed(each at every pump house)3 nos, Plinth Area @ 70Sqm each |
| 1589 | DG Shed (each at every pump house)3 nos, Plinth Area @30 Sqm each |
| 1590 | Drainage Work and Horticulture at each pump house: |
| 1591 | Providing and fixing of reinforced Ferro-Cement drain covers designed for \"A\" & \"AA\" class loading duly marked on cover with adequate steelreinforcement having thickness 75mm to 150mm anti corrosive bitumen painted M.S. plate , Rim and M.S. lifting hooks, Admixtures likeplasticizer, bond improving compound, shrinkage, resistance compound, abrasion resistant complete as per approved design etc. |
| 1592 | For Class - \"A\" loading |
| 1593 | Span 300 to 450 mm Standard size 600x800mm |
| 1594 | Earth work in excavation in foundation trenches or drains including dressing of sides and ramming of bottoms, lift up to 1.5 Mtr. including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed within a lead of 50 meter. All kinds of soil. |
| 1595 | Brick masonry with F.P.S. bricks of class designation 75 in foundation and plinth with bricks |
| 1596 | Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 1597 | Providing and Laying Reinforced cement concrete pipe NP4/ prestrssed concrete pipe for culverts including jointing ends and fixing collar with cement mortar 1:2 complete as per clause 1000 & 2900 of MoRT&H specification including all material, labour form work, machinery. |
| 1598 | 200 mm internal diameter |
| 1599 | Cutting of trees, including cutting of trunks, branches and removal of stumps, roots, stacking of serviceable material with all lifts and up to a lead of 1000 mtrs and earth filling in the depression/pit to required compaction as per MoRT&H specification clause 201. (Measurment of girth to be done at height of 1 m above ground level) |
| 1600 | Girth from 300 mm to 600 mm |
| 1601 | Clearing Grass and Removal of Rubbish (Maximum 150mm) by manual means and disposal at a lead of 50 metres as per MoRT&H specification clause 201. |
| 1602 | Supply of dry manure including loading unloading, transportation & stacking at site. |
| 1603 | Farm yard manure (organic) |
| 1604 | Compost |
| 1605 | Goat dungmanure |
| 1606 | Supply & Stacking good earth at site complete including loading unloading & transporation etc. |
| 1607 | Supply of insecticides & pesticides at store in dust/liquid form complete |
| 1608 | Methly Prathion 2% |
| 1609 | Supply of different varities of tree/ shrubs/climbers according to height and age of the plant at site including loading/unloading & transportation etc. complete: |
| 1610 | Different flowing plants 900 mm to 1500 mm (Rs 50 to Rs 150) |
| 1611 | Different varrities of shrubs 600 mm to 900 mm (Rs 25 to Rs 160) |
| 1612 | Different varrities of climbers 900 mm to 1500 mm (Rs 48 to Rs 144) |
| 1613 | Laying of lawns including ploughing leveling breaking of clods manuring and removal of stones etc. (cost of manure or extra good earth to be paid separately )maintenance of lawn foe 30 days or more till the grass forms a thick lawns free from weeds and fit for moving in the duration of planting if lawn die some where the contractor will replant it at his own cost |
| 1614 | In rows 7.5 Cms. apart in either direction |
| 1615 | Renovating lawns including weeding cheeping the grass forking the ground top dressing with manure . Mixing tthe same with forked soil watering maintaining the lawn for 30 days for till the grass grass forms a thick lawns free from weeds and fit for moving in the duration of planting if lawn die some where the contractor will replant it at his own cost |
| 1616 | Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended upto date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by electro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee,bend etc.), satisfactory hydraulic testing, disinfection etc.complete as per technical specifications and direction of Engineer-in-charge of following class and diameter.(excluding earth work) . Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately. Supply may be in coil or straight length in 6 M/12 M. |
| 1617 | HDPE PE-100 PN-6 |
| 1618 | 75 mm dia |
| 1619 | P & F G.I. Pipes (External Work) with G.I. fittings excluding union (IS : 1239 Mark) including trenching & refilling earth etc. |
| 1620 | 15mm dia nominal bore \"B Class\" |
| 1621 | Construction of Campus Development, campus light, Road at each pump house |
| 1622 | Providing and laying in position cement concrete M10 grade nominal mix 1:3:6 (1 Cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size) in base course complete including all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work. |
| 1623 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (if required ) excluding the cost of centering, shuttering and reinforcement for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. M20 grade Nominal Mix / Design Mix |
| 1624 | M20 grade Nominal Mix1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mmnominal size). |
| 1625 | S & F cement concrete pre cast Kerb or Dand up to 60 cm length over 20 mm thick base of cement mortar1:4 including jointing earth work, pointing & jointing with cement mortar 1:4 of size Including cost of M- 20 Mix Dand/ Kerb Complete |
| 1626 | 20x20 cm |
| 1627 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting (height upto 10 m) ,fixing in position and applying a priming coat of approved steel primer all complete: |
| 1628 | Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mmdiameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead and including a coat of approved steel primerand two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/ vertical or curved surfaces) excluding the cost of purlins, rafters and trusses and including cutting to size and shape whenever required |
| 1629 | 1.00 mm thick with zinc coating not less than 275 gm/m2 |
| 1630 | Supply and erection of hot dipped galvanised steel swaged tubular pole /GI Conical Pole conforming to IS: 2713-1980 (part I to II) with galvanised base plate of size 400mm x 400mm x 7mm in position including excavation of the pit and filling the same with C.C. of M- 10/M-20 grade (1:3:6)/ grade(1:1.5:3) from base plate to 50cm above ground level, with the help of steel frame not less than 40 cm dia up to 114.3mm outer dia and 50 cm beyond 114.3mm outer dia around the pole. Duly finished with cement plaster, earthing terminals , cable entry, GI cable sleeve complete as required. The pole shall be galvanised using ISI mark tube for structural purpose. |
| 1631 | 7/7.5 Mtr. |
| 1632 | Add for supply and fixing of hot dipped galvanised Overhang of following size over the existing poles |
| 1633 | 76.1mm OD x 3.25mm thickness |
| 1634 | P/ F IP-65/ IP-66 protected street light luminaries on existing bracket. Fixture made from powder coated single piece pressure die cast aluminum housing with heat dissipation fins on housing with high power LEDs . Diffuser / glass cover for ensuring IP-65 protection for lamp and control gear compartment, system lumen output of 100 lum/watt high power LED. Integrated driver shall be high efficiency having efficiency more than 85 % and in compliance to IEC standards. System life of 50000 burning hours with 70 % of initial lumens maintained. Fixture shall be in CE compliance. |
| 1635 | LED street light fixture 60 Watt |
| 1636 | Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 1637 | 10.0 Sq.mm, 4 core |
| 1638 | Construction of RWH for Roof Area 200 Sqm at each pumphouse |
| 1639 | Earth work in excavation in foundation trenches or drains including dressing of sides and ramming of bottoms, lift up to 1.5 Mtr. including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed within a lead of 50 meter. All kinds of soil. |
| 1640 | Providing and laying in position cement concrete including curing compaction etc. of specified grade excluding the cost of centering and shuttering =All up to plinth leve |
| 1641 | 1:4:8 (1Cement :4 Course Sand :8 Graded stone aggregate 40 mm nominal size |
| 1642 | Brick masonry with F.P.S. bricks of class designation 75 infoundation and plinth with bricks I 1:6 cement Martar |
| 1643 | 1:2:4 (1Cement :2 Course Sand 4 Graded stone aggregate 20 mm nominal size |
| 1644 | Centering and shuttering with plywood or steel sheets including strutting, propping, bracing both ways and removal of formwork for foundations in basements rafts, footings, strap beams, bases of columns , etc. up to plinth level. |
| 1645 | Walls (any thickness) including attached pilasters,buttressesplinthandstring course. Add extra for shuttering in circular work (in respective centering and shuttering items) |
| 1646 | Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands , coping, bed plates, anchor blocks, sills, chhajjas lintel, beam etc. |
| 1647 | Providing and laying in position specified grade ofcement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers (as required ) excluding the cost of centering, shuttering and reinforcementfor Walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc.M20 grade Nominal Mix / Design Mix |
| 1648 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor three level. |
| 1649 | Thermo Mechanically treated bars |
| 1650 | Dry sinking of well true & vertical in all types of soil including sand, silt, clay, mixed upto 25% with gravel and river bed stones upto size 300 mm in any direction complete as per drawing and technical specification (depth from level of placing of cutting edge & internal dia,to be taken for measurement) rate includes all percentage of pebbles, boulders and river bed stones. (depth to be measured from ground level) |
| 1651 | Supply and installation of ISI marked India Mark II Hand pump set complete with cylinder & 15 connecting rods. |
| 1652 | Half brick masonry in foundation & plinth using bricks of designation 75 with nominal hoop rainforsed (2 Nos. 6mm MS bar) at every fourth course in for hoop rainforcement |
| 1653 | Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 1654 | Plaster on new surface on walls in cement sand mortar 1:4 including raking of joints etc. complete fine finish: |
| 1655 | 25 mm thick. |
| 1656 | Construction oftubewell up to 100m depth and above to accomodate housing and assembly pipe in all types of alluvium strata by rotay drilling method with \"code of practice for construction and testing of tubewells (IS:2800 (Part-II) : 1991 and IS:2800 (Part-II) :1979 both amended up to date) with supply of bail plug if necessary.The work will not include cost of housing pipe and strainer pipe assembly cost, gravel and development work. Work would be deemedcompleted only after obtaining sound free water during pumping. |
| 1657 | 250 mm |
| 1658 | Supply & lowering air line of 25mm dia, G.I. pipe \"B\" class having perforation 3 to 5mm size all arrow of G.I. pipe in Zig-Zag fashion & making air vent at top including the cost of Tee-Nipples, Elbow, Socket etc. |
| 1659 | Supply and lowering vent air pipe 63mm dia rigid PVC pipe(IS 4985) mark class II (4kg per cm2 ) with required all necessary fittings including perforation of 3 to 5 mm size all around the pipe at a distance of 180 to 220mm in zig zag fashion and making air vent at top complete as per direction of Engineer incharge. |
| 1660 | Supply & lying River-gravels of following sizes in recharge shaft, filter pit after screening & washing from kachha shift without deduction of voids |
| 1661 | Size 9 to 12 mm |
| 1662 | Size 3 to 5 mm |
| 1663 | Supply & laying of clean, clear sharp river sand of size 1 to 2mm coarse, without deduction of voids. |
| 1664 | P&F rigid PVC Pipe (IS:4985 mark) class II/ (4 Kg. /Cm2.) approved quality /makeincluding joining the pipe with solvent cement rubber ring and lubricant. |
| 1665 | 110 MM |
| 1666 | 160 MM |
| 1667 | P&F rigid PVC pipe fittings (IS: 4985 mark) of approved quality /make including joining the pipe with solvent cement rubber ring and lubricant: |
| 1668 | Cuppler |
| 1669 | 110 MM |
| 1670 | 160 MM |
| 1671 | Tee MM |
| 1672 | 110 MM |
| 1673 | 160 MM |
| 1674 | Bend |
| 1675 | 110 MM |
| 1676 | 160 MM |
| 1677 | Pipe Clip |
| 1678 | 110 MM |
| 1679 | Extra for supplying and fixing of 560 mm dia Ductile Iron manhole frame & cover, Hinged Type, Heavy Duty with test load of 400 KN, class D-400 as per BS EN 124, in place of RCC/ SFRC manhole frame & cover (ED/EHD) in manhole. |
| 1680 | Providing and fixing of reinforced Ferro-Cement drain covers designed for \"AA\" class loading duly marked on cover with adequate steel reinforcement having thickness 75mm to 150mm anti corrosive bitumen painted M.S. plate , Rim and M.S. lifting hooks, Admixtures like plasticizer, bond improving compound, shrinkage, resistance compound, abrasion resistant complete as per approved design etc. Standard Size 2100x500mm (150mm thick) for span 1201 to 1500mm |
| 1681 | Steel work |
| 1682 | For 11 RWH (SAY RS.) |
| 1683 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR PICHUPURA CWR |
| 1684 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1685 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1686 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1687 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1688 | 2KVA |
| 1689 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1690 | 1 SQMM, 24 Core |
| 1691 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1692 | 1 SQMM, 1 Pair |
| 1693 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1694 | 4C x 2.5 sq.mm |
| 1695 | 4C x 1.5 sq.mm |
| 1696 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1697 | 0-5M |
| 1698 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1699 | 1/2\" M (NPT) |
| 1700 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR KOLWA CWR |
| 1701 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1702 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1703 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1704 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1705 | 2KVA |
| 1706 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1707 | 1 SQMM, 24 Core |
| 1708 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1709 | 1 SQMM, 1 Pair |
| 1710 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1711 | 4C x 2.5 sq.mm |
| 1712 | 4C x 1.5 sq.mm |
| 1713 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1714 | 0-5M |
| 1715 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1716 | 1/2\" M (NPT) |
| 1717 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR SODALA CWR |
| 1718 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1719 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1720 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1721 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1722 | 2KVA |
| 1723 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1724 | 1 SQMM, 24 Core |
| 1725 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1726 | 1 SQMM, 1 Pair |
| 1727 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1728 | 4C x 2.5 sq.mm |
| 1729 | 4C x 1.5 sq.mm |
| 1730 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1731 | 0-5M |
| 1732 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1733 | 1/2\" M (NPT) |
| 1734 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR MOTUKA CWR |
| 1735 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1736 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1737 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1738 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1739 | 2KVA |
| 1740 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1741 | 1 SQMM, 24 Core |
| 1742 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1743 | 1 SQMM, 1 Pair |
| 1744 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1745 | 4C x 2.5 sq.mm |
| 1746 | 4C x 1.5 sq.mm |
| 1747 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1748 | 0-5M |
| 1749 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1750 | 1/2\" M (NPT) |
| 1751 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR KOLANA CWR |
| 1752 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1753 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1754 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1755 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1756 | 2KVA |
| 1757 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1758 | 1 SQMM, 24 Core |
| 1759 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1760 | 1 SQMM, 1 Pair |
| 1761 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1762 | 4C x 2.5 sq.mm |
| 1763 | 4C x 1.5 sq.mm |
| 1764 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1765 | 0-5M |
| 1766 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1767 | 1/2\" M (NPT) |
| 1768 | PROVISION OF AUTOMATION & PLC - SCADA WORK FORGURHA CWR |
| 1769 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1770 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1771 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1772 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1773 | 2KVA |
| 1774 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1775 | 1 SQMM, 24 Core |
| 1776 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1777 | 1 SQMM, 1 Pair |
| 1778 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1779 | 4C x 2.5 sq.mm |
| 1780 | 4C x 1.5 sq.mm |
| 1781 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1782 | 0-5M |
| 1783 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1784 | 1/2\" M (NPT) |
| 1785 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR RAJAHERA CWR |
| 1786 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1787 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1788 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1789 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1790 | 2KVA |
| 1791 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1792 | 1 SQMM, 24 Core |
| 1793 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1794 | 1 SQMM, 1 Pair |
| 1795 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1796 | 4C x 2.5 sq.mm |
| 1797 | 4C x 1.5 sq.mm |
| 1798 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1799 | 0-5M |
| 1800 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1801 | 1/2\" M (NPT) |
| 1802 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR KANKARWAS CWR |
| 1803 | Design,manufacture,supply,installation,testingand commissioning of indoor type PLC panel of size approx. 1100 mm X 700 mm X 2100mm (LBH) , fabricated out of min.2mmthickCRCAsheetcompletewithlatest configurationPC,necessaryprogrammingforSCADAsoftware and comprising of all accessories not limited to the following: DI –92 num DO – 92 num AI –16 num AO – 8 num MCB 10A DP – 1 num MCB4ADP – 2 num MCBSP2A – 8 num MCB 1A DP – 15 num 24 VDC Power Supply 10A – 1 num Push Buttons – 30 num Selector Switch - 15 num Control Relays – 200 num Annunciatorwith24WindowsNOtoNCType MicroprocessorBased,WindowSize75*42mm, 110VAC, with Electronic Hooter – 1 num Control Transformer – 1 num Emergency PB – 1 num Panel Cooling Fan – 1 num Panel Light with Door Switch – 1 num Control Indication Lamp – 30 num Wiring + TB etc – 1 lot Hardware – 1 lot |
| 1804 | HIM Display, Colour, 12\" having Ethernet Port, USB Port ect. |
| 1805 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1806 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1807 | 2KVA |
| 1808 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1809 | 1 SQMM, 24 Core |
| 1810 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1811 | 1 SQMM, 1 Pair |
| 1812 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1813 | 4C x 2.5 sq.mm |
| 1814 | 4C x 1.5 sq.mm |
| 1815 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1816 | 0-5M |
| 1817 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1818 | 1/2\" M (NPT) |
| 1819 | PROVISION OF AUTOMATION & PLC - SCADA WORK FORBandhikui CWR |
| 1820 | PRE-WIRED RTU Panel Compact RTU for variable power supply using batteries, rechargeable batteries, solar or 10.8 V DC to 28.8 V DC with integrated UMTS modem; connection to control center via Tele Control Basic, DNP3, IEC60870-5-104 and required communication protocols, on-board I/O (8 DI, 4 DQ, 4 AI), configuration and diagnostics per web interface, RJ45 port, mobile communications antenna (GSM/UMTS), Mini SIM card, with adapter Micro SIM card, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3, Open VPN-Client. |
| 1821 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1822 | 0-5M |
| 1823 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1824 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required.25mm x 3mm GI strip |
| 1825 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. (1 Pair * 0.75SQMM) |
| 1826 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR ESR @ 99 NOS |
| 1827 | PRE-WIRED RTU Panel Compact RTU for variable power supply using batteries, rechargeable batteries, solar or 10.8 V DC to 28.8 V DC with integrated UMTS modem; connection to control center via Tele Control Basic, DNP3, IEC60870-5-104 and required communication protocols, on-board I/O (8 DI, 4 DQ, 4 AI), configuration and diagnostics per web interface, RJ45 port, mobile communications antenna (GSM/UMTS), Mini SIM card, with adapter Micro SIM card, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3, Open VPN-Client. |
| 1828 | Application , Programming and Troubleshooting software for Compact RTUs FOR EACH PUMP HOUSE (CPS & IPS) |
| 1829 | Supply, installation, testing and commissioning ofMNRE approved off GridSolar Panelswith 25 years of Linear Generation warranty, Work includes designing of solar panel area and MS fabricated structure 120 micron hot dip galvanized iron , showing arrangement of panel in available space and installation ofPV module on frame structure such that minimum height of lower edge of panel shall be 4.0 mtr from ground level to safeguard against damage and theft as per indicative drawing enclosed with the bid document. The foundation of structure shall be in RCC. Mountingstructure shall be suitably designedto withstand wind velocity up to 150km/hr. The work shall be executed as perdetailedtechnical specifications, approved drawing and direction of Engineer in Charge. Note: There shall be 5 year service warranty for solar panel and mounting structureandsuitable provision shall be included in tender document. |
| 1830 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1831 | 0-5M |
| 1832 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1833 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required.25mm x 3mm GI strip |
| 1834 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. (1 Pair * 0.75SQMM) |
| 1835 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR VTC @229 NOS |
| 1836 | Supply of GSM /GPRSbased data transmitter for Bulk Flowmeter (woltman Pulse Output only ), Battery Powered -7.4V,battery life 3-5 Years,(1 no Data transmit in aday),4-20mA From Pressure RS485 Display-16*2 LCD,Encloser-165*120*65 mm,ABS Protection-IP65,Operating tempreature -55 Deg. C |
| 1837 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR SIKRAI CWR |
| 1838 | Design, manufacture, supply, installation, testing and commissioning of indoor type PLC Control Panel of size approx. 1800 mm (H) X 900 mm (L) X 500mm (B), fabricated out of min.2mmthickCRCAsheetcompletewithlatest PC configurations, Required Accessories & Hardware’s, necessaryprogrammingsoftware for HMI & SCADA and comprising of all accessories not limited to the following:- The proposed IOs are have 20% spares for the future. DI – 94DO – 58AI – 18AO – 2 Ethernet Switch 8 Port Managed , Routers, M2M Gateway, Control MCB 16A DP 6nos, 24 VDC Power Supply 4.5A, 3way Selector Switch for Auto/Manual/ local Remote, Control Relays,Indication Lamps for 24VDC & 220AC supply, Test push buttons, Annunciatorwith24WindowsNOtoNCTypeMicroprocessorBased withWindowSize75*42mm, 110VAC control supply, Electronic Hooter , Control Transformer,Panel Cooling Fan & Filters 2nos, Panel Light with Door Switch 1no, Power Socket 2nos , Control & Power wiring, Fuse TBs, suitable for monitoring of Motors & Valves status, Flow, Level, Pressure data, 11KV Switchyard & Transformers Data, Energy Data, Post Chlorination & diffusion system dataect. The all Pump House Data shall be communicated with MCC Bagri SCADA system. |
| 1839 | HIM Display, Colour, 15\" having Ethernet Port, USB Port ect. |
| 1840 | Operator & Engg. StationPC includes,Corei5processor,8GB DDR-3RAM,2TBSSD,DVDRWDrive,RS-232/485Ports,1ParallelPort,4nos.USBPort,2x EthernetCards,Keyboard,opticalmouse,32\"\"LED monitor, Latest Original window, MS Office, Anti Virus ect.Make - HP/DELL/ LENOVA |
| 1841 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1842 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1843 | 2KVA |
| 1844 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1845 | 1 SQMM, 24 Core |
| 1846 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1847 | 1 SQMM, 1 Pair |
| 1848 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1849 | 4C x 2.5 sq.mm |
| 1850 | 4C x 1.5 sq.mm |
| 1851 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1852 | 0-5M |
| 1853 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1854 | 1/2\" M (NPT) |
| 1855 | PROVISION OF AUTOMATION & PLC - SCADA WORK FORJHEEJHUN CWR |
| 1856 | Design, manufacture, supply, installation, testing and commissioning of indoor type PLC Control Panel of size approx. 1800 mm (H) X 900 mm (L) X 500mm (B), fabricated out of min.2mmthickCRCAsheetcompletewithlatest PC configurations, Required Accessories & Hardware’s, necessaryprogrammingsoftware for HMI & SCADA and comprising of all accessories not limited to the following:- The proposed IOs are have 20% spares for the future. DI – 110DO – 58AI – 18AO – 2 Ethernet Switch 8 Port Managed , Routers, M2M Gateway, Control MCB 16A DP 6nos, 24 VDC Power Supply 4.5A, 3way Selector Switch for Auto/Manual/ local Remote, Control Relays,Indication Lamps for 24VDC & 220AC supply, Test push buttons, Annunciatorwith24WindowsNOtoNCTypeMicroprocessorBased withWindowSize75*42mm, 110VAC control supply, Electronic Hooter , Control Transformer,Panel Cooling Fan & Filters 2nos, Panel Light with Door Switch 1no, Power Socket 2nos , Control & Power wiring, Fuse TBs, suitable for monitoring of Motors & Valves status, Flow, Level, Pressure data, 11KV Switchyard & Transformers Data, Energy Data, Post Chlorination & diffusion system dataect. The all Pump House Data shall be communicated with MCC Bagri SCADA system. |
| 1857 | HIM Display, Colour, 15\" having Ethernet Port, USB Port ect. |
| 1858 | Operator & Engg. StationPC includes,Corei5processor,8GB DDR-3RAM,2TBSSD,DVDRWDrive,RS-232/485Ports,1ParallelPort,4nos.USBPort,2x EthernetCards,Keyboard,opticalmouse,32\"\"LED monitor, Latest Original window, MS Office, Anti Virus ect.Make - HP/DELL/ LENOVA |
| 1859 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1860 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1861 | 2KVA |
| 1862 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1863 | 1 SQMM, 24 Core |
| 1864 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1865 | 1 SQMM, 1 Pair |
| 1866 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1867 | 4C x 2.5 sq.mm |
| 1868 | 4C x 1.5 sq.mm |
| 1869 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1870 | 0-5M |
| 1871 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1872 | 1/2\" M (NPT) |
| 1873 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR TORDA CWR |
| 1874 | Design, manufacture, supply, installation, testing and commissioning of indoor type PLC Control Panel of size approx. 1800 mm (H) X 900 mm (L) X 500mm (B), fabricated out of min.2mmthickCRCAsheetcompletewithlatest PC configurations, Required Accessories & Hardware’s, necessaryprogrammingsoftware for HMI & SCADA and comprising of all accessories not limited to the following:- The proposed IOs are have 20% spares for the future. DI – 94DO – 58AI – 18AO – 2 Ethernet Switch 8 Port Managed , Routers, M2M Gateway, Control MCB 16A DP 6nos, 24 VDC Power Supply 4.5A, 3way Selector Switch for Auto/Manual/ local Remote, Control Relays,Indication Lamps for 24VDC & 220AC supply, Test push buttons, Annunciatorwith24WindowsNOtoNCTypeMicroprocessorBased withWindowSize75*42mm, 110VAC control supply, Electronic Hooter , Control Transformer,Panel Cooling Fan & Filters 2nos, Panel Light with Door Switch 1no, Power Socket 2nos , Control & Power wiring, Fuse TBs, suitable for monitoring of Motors & Valves status, Flow, Level, Pressure data, 11KV Switchyard & Transformers Data, Energy Data, Post Chlorination & diffusion system dataect. The all Pump House Data shall be communicated with MCC Bagri SCADA system. |
| 1875 | HIM Display, Colour, 15\" having Ethernet Port, USB Port ect. |
| 1876 | Operator & Engg. StationPC includes,Corei5processor,8GB DDR-3RAM,2TBSSD,DVDRWDrive,RS-232/485Ports,1ParallelPort,4nos.USBPort,2x EthernetCards,Keyboard,opticalmouse,32\"\"LED monitor, Latest Original window, MS Office, Anti Virus ect.Make - HP/DELL/ LENOVA |
| 1877 | Quad-bandGSM/GPRSmodemwithEthernetbridge/ router/ serial server (RS232/485) interface. |
| 1878 | Providing,installation,testingandcommissioningof UPS, 3Phase 415 V, 50 Hzwith 60 min back up Ni+Cd battery bank. |
| 1879 | 2KVA |
| 1880 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup togetheroverallpolyestertapedAl(innersheetedGI Steel wire Mylar/Drain wire) along with ATC drain wire , round/steelArmouredoverallPVCsheathed(ST-1) overallscreenedCoreArmouredinstrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1881 | 1 SQMM, 24 Core |
| 1882 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair Armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. |
| 1883 | 1 SQMM, 1 Pair |
| 1884 | ProvidingandlayingXLPE/PVCinsulated&PVC sheathed Armoured control cables of 1.1KV gradewith copper conductor as per IS 1255 including excavation of 30CmX75Cmsizetrench25Cmthickunderlayerof sandandsecondclassbrickscovering,backfilling& compaction. |
| 1885 | 4C x 2.5 sq.mm |
| 1886 | 4C x 1.5 sq.mm |
| 1887 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1888 | 0-5M |
| 1889 | Providing,Installation,TestingandCommissioningofPRESSURE TRANSMITTERforWaterApplication:Range:0-10Bar/Power Supply:24VDC/Output:4-20mAwithHART/Diaphragm: SS316L/ProcessConnection:1/2\"NPT(M)/Accuracy:0.15%Protection: IP67 |
| 1890 | 1/2\" M (NPT) |
| 1891 | PROVISION OF AUTOMATION & PLC - SCADA WORK FOR ESR @ 39 NOS |
| 1892 | PRE-WIRED RTU Panel Compact RTU for variable power supply using batteries, rechargeable batteries, solar or 10.8 V DC to 28.8 V DC with integrated UMTS modem; connection to control center via Tele Control Basic, DNP3, IEC60870-5-104 and required communication protocols, on-board I/O (8 DI, 4 DQ, 4 AI), configuration and diagnostics per web interface, RJ45 port, mobile communications antenna (GSM/UMTS), Mini SIM card, with adapter Micro SIM card, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3, Open VPN-Client. |
| 1893 | Application , Programming and Troubleshooting software for Compact RTUs |
| 1894 | 12Ah, 12V DC Power safe Dry Battery for RTUs, ABS Container & Lid, Sealed Maintenance free, Better conductivity, Free from corrosion, Over Partition Welding, Free from inter-cell weld failure.Thicker Separator, More acid volume, Better capacity retention, Improved electrical performance, mall and medium sized sealed lead acid battery performance characteristics conforming to JIS C8702, 0 to 40 deg C, Operating Relative Humidity: 0-95%,Storage Relative Humidity: 0-95%, 47-63 Hz, Brass Terminal with Lead Coating,Low Self-Discharge, |
| 1895 | Providing, Installation, Testing and Commissioning of ULTRASONIC LEVELTRANSMITTER for WaterApplication : Principle :Timeof Flight/ Sensor MOC PP / Process Connection1 1/2 inchBSP or 2 inchBSPThreadedtype/PowerSupply:24VDC/Output:4- 20mA/Display:IntegraldisplayforprogrammingandDisplay Reading/ IP 66 |
| 1896 | 0-5M |
| 1897 | Earthing Schedule Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. \"B\" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 1898 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required.25mm x 3mm GI strip |
| 1899 | ProvidingandlayingStranded/FlexibleAnnealedBare copperconductor,XLPE/PVCinsulatedsuitablylaidup together overall polyester taped Al (Mylar tape wrapped) along with ATC Drain wireoverall PVC sheathed (ST-1) overall screenedPair armoured instrumentation Cables generally confirming to PAS 5308- Part-2-2009. (1 Pair * 0.75SQMM) |
| 1900 | PROVISION OF AUTOMATION & PLC - SCADA WORK FORVTC @138 NOS |
| 1901 | Supply of GSM based data transmitter Bulk Flowmeter (woltman pulse output ), SIM 2G/3G,Battery power -7.4V battery life 3 yr (data once a day) , Input Pulse , 4-20ma From pressure RS485 Display-16*2 LCD Encloser-165*120*65 mm ABS Protection-IP65 Operating tempreature -055 C |
| 1902 | For the 1st yearof O&M after DLP |
| 1903 | For the 2nd yearof O&M after DLP |
| 1904 | For the 3rd yearof O&M after DLP |
| 1905 | For the 4th yearof O&M after DLP |
| 1906 | For the 5th yearof O&M after DLP |
| 1907 | For the 6th yearof O&M after DLP |
| 1908 | For the 7th yearof O&M after DLP |
| 1909 | For the 8th yearof O&M after DLP |
| 1910 | For the 9th yearof O&M after DLP |
| 1911 | For the 10th yearof O&M after DLP |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-4 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents