Special Repairs And Replacement Of Conventional Type Water Level Indicator With Digital Level Indicator, Data Collecting And Tansmitting System Under Ge Belgaum, belgaum-Karnataka

Military Engineer Services-MES has published Special Repairs And Replacement Of Conventional Type Water Level Indicator With Digital Level Indicator, Data Collecting And Tansmitting System Under Ge Belgaum. Submission Date for this Tender is 02-09-2022. Liquid Level Controls Tenders in belgaum Karnataka. Bidders can get complete Tender details and download the document.




Tender Notice

33409456
Corrigendum : Special Repairs And Replacement Of Conventional Type Water Level Indicator With Digital Level Indicator, Data Collecting And Tansmitting System Under Ge Belgaum
Open Tender
Indian
Karnataka
belgaum
02-09-2022

Tender Details

Special Repairs And Replacement Of Conventional Type Water Level Indicator With Digital Level Indicator, Data Collecting And Tansmitting System Under Ge Belgaum

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 16-Aug-2022 Certain Changes in PS Other 26-08-2022
2 26-Aug-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 02-09-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 46000.0 /-
Tender Value
INR 23 Lakhs /-

BOQ Items

Name of Work: SPECIAL REPAIRS AND REPLACEMENT OF CONVENTIONAL TYPE WATER LEVEL INDICATOR WITH DIGITAL LEVEL INDICATOR ,DATA COLLECTING AND TANSMITTING SYSTEMUNDER GE BELGAUM.
Sl. No. Item Description
1NOTE : THE ITEMS MENTIONED BELOW SHALL BE OF SPECIALIZED IN NATURE AND EXECUTED UNDER THE SUPERVISION AND GUILD LINES FROM OEM . THE ENTIRE WORK ONCE COMPLETED WILL BE INSPECTED AND CERTIFIED BY REP OF OEM FOR FUNCTIONAL ASPECTS OF ITEMS INSTALLED AT SITE. COMPLETION CERTIFICATE WILL BE ISSUED BY THE ACCEPTING OFFICER ONLY AFTER RECEIPT OF ABOVE CERTIFICATE FROM OEM . THE RATE QUOTED BY THE CONTRACTOR FOR THE FOLLOWING ITEMS SHALL BE DEEMED TO INCLUDE THE ABOVE PROVISIONS.
2Supply, install, test and commisioning of PLC basedWater Level Control Panel Outdoor Type floor mounted free standing weather , dust and vermin proofIP-55 protection suitable for monitoring ultrasonic level Sensor (01 No for each OHT) Non Contact type to monitor the water level forover head tankwith a percentage from 0% to 100% . The Panel should have the provision for 02 Nos of motorized valve operation for the future PLC based Panel andconsist of 4" HMI for Local monitoring of the Level. withan including digital display unit for over head reservoir showsthe water level indication on seven segment display 2inch size 3 digit display.
3The PLC should have the following features : Inputs: (i) 32 Nos, Outputs: 32 Nos Analog Input: 02 Nos. (ii) Panel Box fabricated from 2.0 mm thick CRCA sheet andPowder coated (Minimum 50 Micron ) to operate the water supply system. (iii)The Panelshall also be equipped with GPRS communication Modem along with suitable external antenna of required gain, patch chord and mounting accessories .Note : The rate quoted by the contractor for this itemshall be deemed to include the cost of communication for a period of 12 months from the date of completion of work. Locations of OHT as below: (a). Kambale OHT (b). B & R OHT (c). Military Hosoital OHT (d). Naagzira Pump House OHT (e). MLIRC OHT Make of PLC Panel : SCHNEIDER /SIEMENS / ABB/ MITUBISHI
4Supply, install, test and commisioning of PLC basedWater Level Control Panel outdoor type floor mounted free standing weather , dust and vermin proofIP-55 protection suitable for monitoring ultrasonic level Sensor in Laxmi Tek Pump House two UG Sump and one OHT (Reservoir Sump, Black Stone Sump and Bottle type Over Head Tank) non Contact type to monitor the water level forOHT and UG sump with a percentage from 0% to 100% . The Panel should have the provision for05 Nosof motorized valve operation for the future. PLC based Panel andconsist of 4" HMI for Local monitoring of the Levelwithan including digital display unit for over head reservoirs and UG sumpsshowsthe water level indication on seven segment display 2inch size 3 digit display.
5.The PLC should have the following feature: Inputs :(i) 32 Nos Outputs: 32 Nos Analog Input: 02 Nos. (ii)Panel Box fabricated from 2.0 mm thick CRCA sheet andpowder coated(Minimum 50 Micron ) to operate the water supply system. (iii) The Panel shall also be equipped with GPRS communication Modem along with suitable external antenna of required gain, patch chord and mounting accessories . Note :The rate quoted by the contractor for this itemshall be deemed to the cost of communication for a period of 12 months from the date of completion of work. Make of PLC Panel : SCHNEIDER /SIEMENS / ABB/ MITUBISHI
6Supply, install, test and commisioning of PLC basedWater Level Monitoring Panel Indoor Type IP 42 protection suitable for monitoring ultrasonic sensor (08 Nos) Non Contact type to monitor the water level for 04 Nos of OHT and04 Nos of Under Ground Sump in Parade Road Pump House with a percentage from 0% to 100% PLC based Panel should consist of 4" HMI for Local monitoring of the Levelwithan including digital display unit for over head reservoirs and UG sumpsshowsthe water level indication on seven segment display 2inch size 3 digit display.
7The PLC should have the following feature: Inputs:(i) 32 Nos, Outputs: 32 Nos Analog Input: 10 Nos . (ii)The Panel Box shall befabricated from 2.0mm thick CRCA sheet andPowder Coated(Minimum 50 Micron ) to operate the water supply system.(iii)The Panel shall be equipped with GPRS communication Modem along with suitable external antenna of required gain, patch chord and mounting accessories . Note : The rate quoted by the contractor for this itemshall be deemed to the cost of communication for a period of 12 months from the date of completion of work. Make of PLC Panel : SCHNEIDER /SIEMENS / ABB/ MITUBISHI
8Supply Install, Test andCommissioning of Indoor type Programmable Logic Controller based Valve Automation and communication Panel IP 42 protection suitable for control and monitoring of 05 Nos of Pumps ,05 Nos of Pressure Transmitter, 06 Nos of Priming Motorised Valve, 05 Nos of Air release Solenoid Valves, 13 Nos of motorized valves ( Plus 03NosSpare) and 02 Nos of Magnetic Level sensor for Priming of Tank ,05 Number of energy meters for Pump"s and 02 Nos of Ultrasonic level sensor ( 1 No for Sump and 1 No for MAP OHT). The panel should be of suitable size fabricated from 2.0 mm thick CRCA sheet andpowder coated (Minimum 50 Micron ) The Panel should consists of the following items:- (a) Water Level Sensor and Display (b) Pump On/Off (c) Auto priming (d) Operation of Motor Actuated Butterfly Valves (e) Automatic Toggling of Pumps (f) Auto Change Over in case of Pump Failure
9(g) Single Phasing Prevention . (h) Manual Mode Operation System : (all connected sub systems including all valves (in pump houses and overhead tanks) and pumps from the PLC based Control Panel. (I) 7"" HMI The PLC based Panel shall consist of the follwing sub systems:- (a) 01 No.PLC with follwing specifications; (b) Suitable Digital inputs/ outputs (c)4 serial ports supporting open communication protocol, 01 No. Ethernet port. (d)Programming software based on IEC to facilitate building of custom built function blocks. (e) Expandable upto 192 DI / DOs. (f)01 No SMPS of 5 A rating (Make: SCHNEIDER / Siemen/ABB/MITUBISHI)
10(g)Suitable No of interposing relays 24 V D.C. coil rating, 4 pole and 2 A contact rating. (Make: OEN / ALLEN BRADLEY/IDEC ) (h)MCB of rating 10A (i)Selector Switches / Push Buttons / Indicators / Hooter as per requirement Make :L&T/SIEMEN/Control and Switch Gear Lacation : Laxmi Tech Pump House Make ofIndoor type Programmable Logic Controller based Valve Automation and communication Panel : SCHNEIDER /SIEMENS / ABB/ MITUBISHI
11Supply, install, test and commissioning of SCADA software with the following technical Specifications:- (a) Minimum No of process tags- Unlimited (b) Minimum graphic screens- Unlimited (c) No of variables per screen - Unlimited (d) Store text - 30000 (e) Recipes- 1000 (f) Maximum visual basic scripts- Unlimited (g) Communication with controller- Ethernet, MODBUS, MODNET
12(h) Maximum connections to controller system- more than 10 connections (j) Maximum No of archives - 100 (k) Achievable data - Process data, Messages. (l) Maximum No of entries per archiving - CSV, RDB (m) No of messages-4000 ( bit triggered)/500 Analog (n) Message text( No of character)-80 (o) Password protectionRequirment. (q) Alarm and Trend View - Alarm view in the form of trends( Process analyst). (r) Statistical process control - SPC module for Cp and Ck charts to be embedded. (s) Clustering - The package should support clustering architectures which can a global client concept for the services.
13(t) Redundancy - Redundancy configuration should be inbuilt without any coding. Make -Hardware Requirement: i3 processor, 8 RAM, 1 TB HDD, keyboard, Microsoft mouse, Ethernet card, 42" Flat screen monitor, Windows XP latest version Static IP: in the name of AGE/GE Location : SCADA Room Make of SCADA Software : SCHNEIDER / SIEMENS/ABB/MITUBISHI
14Supply, Install,Test and Commissioning of Ultrasonic Level Transmitter fixing onOHT and UG sump including all fixing arrangement with IP 67 protection complete all as sopecified and as directed.Note : The Ultrasonic Level Transmitter shall consists of rhe following technical specifications : (i)Range : 0-6 metres (ii)Accuracy : 0.5 % minimum (iii)Supply Voltage : 24V dc (iv)Output : 4-20 mA Make ofUltrasonic Level Transmitter: SCHNEIDER / SIEMENS /BANNER Location : All OHT & SUMP
15Supply and fix FRLSPVC insulated unsheathedarmoured copper conductorcable of size 4 core x 1.5 sqmm for connecting power supply to digital box complete all as specified andas directed .Note :Make of FRLSPVC copper cable : Finolex/Polycab/Asian
16Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for foundation, laying pipe etc. or for shafts, wells, cesspits, manholes, pier holes, etc. and getting outin any type of soil complete all as specified and as directed.
17Returning filling in soft/loose soil including spreading levelling watering and well ramming in layers n.exc 25 cm thick complete all as specified and directed.
18Returning filling in soft/loose soil including spreading levelling watering and well ramming in layers n.exc 25 cm thick complete all as specified and directed.