Construction Of 2 X 630Kva, 11 / 0.4Kv Sub-Stations A / W 3Phase Lt Lines & Ht Metering Equipment At Bajahar On Partial Turnkey Basis Under Esd Hpsebl, Sujanpur ( Ed Hamirpur ) ( Deposit Scheme ) - 630, Kva, 11 / 0.4Kv Distribution Tran, sujanpur-Himachal Pradesh

Himachal Pradesh State Electricity Board-HPSEB has published Construction Of 2 X 630Kva, 11 / 0.4Kv Sub-Stations A / W 3Phase Lt Lines & Ht Metering Equipment At Bajahar On Partial Turnkey Basis Under Esd Hpsebl, Sujanpur ( Ed Hamirpur ) ( Deposit Scheme ) - 630, Kva, 11 / 0.4Kv Distribution Tran. Submission Date for this Tender is 02-08-2022. Coats and Jackets Tenders in sujanpur Himachal Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

33266296
Corrigendum : Construction Of 2 X 630Kva, 11 / 0.4Kv Sub-Stations A / W 3Phase Lt Lines & Ht Metering Equipment At Bajahar On Partial Turnkey Basis Under Esd Hpsebl, Sujanpur ( Ed Hamirpur ) ( Deposit Scheme ) - 630, Kva, 11 / 0.4Kv Distribution Tran
Open Tender
Indian
Himachal Pradesh
sujanpur
02-08-2022

Tender Details

Construction Of 2 X 630Kva, 11 / 0.4Kv Sub-Stations A / W 3Phase Lt Lines & Ht Metering Equipment At Bajahar On Partial Turnkey Basis Under Esd Hpsebl, Sujanpur ( Ed Hamirpur ) ( Deposit Scheme ) - 630, Kva, 11 / 0.4Kv Distribution Transformer ( Outdoor Type ) Conforming To Isi & Bee Specifications. 2 Pole 11 Mtr. Longisi Marked Swaged Steel Tubular Pole As Per Is 2713 / 1980 ( Part I-Ii ) As Ammended From Time To Time With Cap Welded On Top &Cast Iron Base Plate Of Designation 410-Sp-56. 3 Rcc Muff 2000Mm Long Withconcrete Filling Material 4 Ms Channelironcross Arm: [ Size ( 100X50x6 ) Mm, Length : 2800 Mm ] X 2 Nos / Strfor Top Channel For Incomer Line. 5 Ms Angle Iron ( 50X50x6 Mm ) , Length: 2800 Mm X ( 1 Nos For LaS ) . 6 Ms Channelironcross Arm: : [ Size ( 75X40x6 ) Mm, Length : 2800 Mm X 4 Nos ] Supporting Do Fuse Unit & Go Switch / Isolator. 7 Ms Channelironcross Arm: [ Size ( 100X50x6 Mm ) , Length: 2800Mm×2 Nos. For Transformer Bed. 8 Ms Channelironcross Arm: [ Size ( 100X50x6 Mm ) , Length: 460 Mm×2 Nos. For Supporting Main Channel Of Transformer. 9 Ms Angle Iron ( 50X50x6 Mm ) , Length: 950 Mm X2 Nos. For Bed Knee Bracing. 10 Ms Angle Iron ( 35X35x6 Mm ) , Length: 460 Mm X 2 Nos. 11 Ms Angle Iron ( 50X50x6 Mm ) , Length ( 2800 Mm ) × 2 Nos.Lt Box & Go 12 Ms Angle Iron ( 50X50x6 Mm ) , Length ( 450 Mm ) :× 1 Nos. 13 Isolator 11Kv, 800A, 25Ka With Earth Switch, Tripple Pole Gang Operated Outdoor Horizontal Double Break Isolator. 14 D.O Fuse Unit 15 Surge Arrester, 9 Kv Station Class ( Porcelain Type ) 16 Discs Insulator Sets ( Comprising 1 No. Disc: ^^ ( Polymer Composit Disc Insulator, Bs, 12 Kv, 90 Kn ) Including Dead End Clamps, Ball Cleave & Bend Stapple Etc. ) . 17 H.T. Stay Set Complete I / C Guy Assembly With Hellically Fitting. 18 Stay Wire ( 7 / 3.15 Mm ) ( 9.0 Kg Per Stay Set ) 19 Stay Clamp / Full Clamp ( M.S. Flat 50X6 Mm ) 20 Pipe Earthing Set 21 Lt Distribution Panel Box Suitable For 630Kva, 11 / 04Kv ( Outdoor Type ) Sub-Station Comprising Of 01No. Acb ( 1000A, 50 Ka, 4P, ) On Incomer And 2Nos., 3Pole Mccb Of 630Amps, 50Ka & 1No., 3Pole Mccb Of 400Amps, 50Kacapacitycomplete In All Respect As Per Hpsebl / Rec Specifications As Given In Tender Document 22 Half Clamp ( M.S. Flat 50X6 Mm ) 23 Full Clamps ( M.S. Flat 50X6 Mm ) 24 Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16 Mm F Or More ( With Flat And Spring Washers ) ] 25 Aluminium Thimble 26 Aluminium Thimble Cable Size 27 Danger Plate 28 Barbed Wire 29 Lt Cable 500 Mm², Pvc ( 1.1Kv, 3½ Core, Al, Unarmoured ) ( X 2Nos. Incommer Cables ) 30 Lt Cable 70 Mm², Pvc ( 1.1Kv, 3½ Core, Al, Unarmoured ) ( X 6Nos. Outgoing Cables ) 31 Energy Meter, 3-Phase, 4-Wire, Lt Ct Operated Static Trivector Meter With Box ( Ct- 1000 / 5Amps, Dlms Compliant ) Suitable For 630Kva Transformer 32 Red Oxide 33 Aluminium Paint. 34 Gi Earth Wire ( Gi, 8 Swg ) { Additional 1% ( Sag And Wastages ) } @0.102 Kg / M 35 Automation And Digitisation Equipments For 11Kv Line System I.E.One Hp / Dell All-In-One Personal Computer Having Operating System Windows 11, 11Th Generation Intel® Core™ I3 Processor, 8 Gb Ddr4 Ram, 512 Gb Pcie® Nvme™ M.2 Ssd, 60.5 Cm ( 23.8 ) Diagonal Ips Desplay With One Nos. Laser Jet Printer ( Hp Model Hp1136mfp Or Mfp M126a ) And One No.Ups 1Kva Libert Iton Cx 1000Va Or Luminous Lb1000pro. 36 Ht Metering : Ct Pt Combined Unit ( Outdoor Type ) 11Kv / 110V, 200 / 5Amps, Accuracy Class 0.5S Isi Markconforming Bee Specification. 37 Ht Energy Meter Suitable Ct Pt Combined Unit 11Kv / 110V, 200 / 5Amps Accuracy Class 0.5S Isi Markconforming Bee Specification, Dlms Complaint With Rs 232 & Rs485port.. 38 Metal Meter Box For Housing The Ht Energy Meter With Locking & Sealing Mechanism Complete Water Proof Duly Painted A / W Mounting Nuts & Bolts / Anchor Fastners . 39 Control Cable ( 1.1Kv, 12Core, 2.5Mm, Hr Frls, Copper, Unscreened Cable ) . 40 Magger / Analog Insulation Tester 5000Mega Ohms / Hand Operated, 2500Volt Isi Mark ( Model Waco 1005 Or Equivalent ) 41 Aluminium Wall Supportladder 6.09Meter ( 20Steps ) Meter Long 42 Lt Line : Aaac 7 / 3.15Mm ( 50Mm² ) Conductor { Includes 4 Conductor Lengths For 3F And Additional 1% ( Sag, Jumpering And Wastage } 43 9 Mtr. Long Isi Marked, Swaged Steel Tubular Poles As Per Is:2713 / 1980 ( Part-I-Iii ) As Amended From Time To Time, Along With Cap Welded On Top & Cast Iron Base Plate Of Designation 410Sp-32. 44 Rcc Muff 2000 Mm Long With Concrete Filling Material 45 Shackle Insulator ( 16 Kn ) 46 D-Iron ( U- Clamps ) Made Of Ms Flat 50X6mm. 47 Lt Stay Set Complete I / C Guy Assembly And Helicallyfittings ) 48 Stay Wire 7 / 3.15 Mm ( 6.00 Kg. Per Stay Set ) 49 Stay Clamp / Full Clamp Made Of M.S. Flat Of Size ( 50 X 6Mm ) . 50 Half Clamp Made Of Ms Flat 50X6mm 51 Msci Arm ( 75X40x6 ) Mm Length 0.750Mtr 52 Lt Earthing Set Complete In All Respect. 53 Earth Wire ( Gi, 8 Swg ) { Additional 1% ( Sag And Wastage ) } @ 0.102Kg / M Andguarding Iacross The Road Including Cross Lacings. 54 Nuts And Bolts Of Various Sizes ( Galvanised / Coated ) [ Preferably 16Mm² Or More ( With Flat And Spring Washers ) ] 55 Aluminium Paint 56 Earth Knob For Lt Line 57 Construction Of Concrete Cement Plateform ( 1:3:6 ) Of Size ( 1.2X1.5X1.5 ) Mtr For Installation Of 630Kv, 11 / 0.4Kv Transformer Including Providing Of Material I.E. I ) 0.54Cum Concrete 1:3:6, Ii ) 2.16 Cum Concrete 1:1.5:3 Iii ) Ms / Tor Steel Reinforcement 175Kg. Iv ) Msci 21.42Kg & Cement Plaster 15Mm Thick Includingexcavation & Form Work Etc. Complete In All Respect As Per Technical Specifications And Drawings 58 Providing And Fixing Of Wire Mesh ( G.I.Wire Of Size 3 Mm ) Fencing 4X4=16 Sq Meter With 2 Mtr. Height ( - ) 1X2 Mtr.=2 Sq Mtr.For Gate =14 Sq Mtr.Net Qty For Wiremesh Fencing Including Providing Of Material I.E. I ) 1.08Cum Concrete 1:6:12, Ii ) 2.16 Cum Concrete 1:2:4 Iii ) 4.26 Cum Concrete 13:6 Iv ) 120.06Kg Ms Ai 65X65x6 Mm V ) 32Sqm Wire Mesh And Welding Work, Painting & Erection Etc Complete In All Respect. 59 Providing And Fixing Of Steel Gate Of Size 1Mtr In Width And 2 Mtr. In Height I.E. 2 Sq Mtr.= 2 Sq. Mtrs. Including Providing Of 28Kg Ms Angle Iron 45X45x6 Mm Long, Ii ) 19.20Kg Ms Flat 50X6mm Iii ) Locking Mechanism & Hinges Etc Welding , Painting & Erection Etc Complete In All Respect. 60 Erection Part :Erection Of11 / 0.4Kv, 630Kva Sub-Station Structure Using Steel Tubular Poles A / W Rcc Muff & Its Concrete Filling As Per Latest Standard Practices / Specification Of Rec / Hpsebl Including Digging Of Pits, Erection Of Poles & Muffs, Filling Muffs With Pcc Mixture, Re-Filling Of Pit & Ramming, Drilling Of Holes In Cross X Arms, Preparation Of Plateform Structure Members Ms Channel X Arms And Knee Bracing Sets, Erection Of Plateform, Fixing Of M.S. Cross Arms S / Stn Fitting, Go Switch, Do Fuse Units, Lightening Arrestors, Disc Insulators, Pin Insulators, Lt Ditribution Panel, Energy Meter. Erection Of S / Stn. Pipe Earthing Set ( 3Nos. ) Complete In All Repect Including Providing Char Coal, Salt Etc., Erection Of Transformer, Providing Earthing Connection To Go Switch, Transformer Lighteneing Arrestor Etc. Erection Of Stay Sets ( 2 Nos. ) , Erection Of Lt Cable And Fixing Of Jumpers. Testing And Commissioning Of Transformer And Allied Equipments Complete In All Respect. 61 Erection Of Ct-Pt Unit & Energy Meter A / W Allied Material At Tapping Point And Making Connections As Per Latest Standard Practices / Specification Of Rec / Hpsebl ( Per Job ) . 62 Erection Of Earthing Ofht Structure Including Digging Of Pit Of Size 1.80X 1.2 X1.2 Mtrs, Fixing Of Ht Earth Set, Refilling The Same Andprov. Earthing Connectioncompletein All Respect. 63 Erection Of Lt Pole Structure With Steel Tubular Pole 11Mtr. Long : ( Including Digging Of Pit For Pole, Muffing Of Pole, Erection Of Poles, Refilling Of Pit & Ramming , Drilling Of Holes In Pole And X-Arm, Fixing Of X-Arm, Shackle Insulators And Painting Of Structure With Redoxide Primer & Aluminium Paintetc.Complete In All Respect As Per The Standard Practices / Specifications Of The Rec / Hpsebl. 64 Erection Of Stay Set ( Lt ) :- Digging Of Pit ( Size0.9*1.20*1.33 ) , Fixing Of Stay Rod, Filling And Ramming Of Pit, Nozzelling And Tightening Etc. Complete In All Respect. 65 Erection Of Earthing Oflt Including Digging Of Pit Fixing Of Ht Earth Set, Refilling The Same Andprov. Earthing Connectioncompletein All Respect. 66 Laying Of Conductor, Stringing, Sagging Ofacsr 50Mm² / 7 / 3.15Mm² And Binding With Insulators ( 3 Wires ) And Fixing Of Jumper. 67 Laying Ofearth Wire With Gi Wire 8Swg , Stringing, Sagging Ofand Binding With Insulators. 68 Erection Charges Of Fixing Of Jumpers Of 11Kv Line As Per Latest Standard Practices / Specification Of Rec / Hpsebl ( Per Set ) . 69 Local Transportation, Loading / Unloading / Stacking Charges For The Carriage Material Of2 X 630Kva, 11 / 0.4Kv Sub-Station, Ht & Lt Lines And Ht Metering Equipments By Road & Mannual Carriage Etc. 70 Testing Fees & Commissioning Charges Etc. For 2Nos 630Kv11 / 0.4Kv Sub-Stations And Allied Ht / Lt Lines & Metering Equipments For Comlete Job. ( As Per Schedule Of General & Service Charges & Hp Govt. Notification ) 71 Labour Cess For The Design, Supply, Erection, Testing Commissioning Of 4Nos. 11 / 0.4Kv Sub-Stations, Ht / Lt Lines & Metering Equipments For Comlete Job.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 28-Jul-2022 Corrigendum.. Fee 02-08-2022

Key Value

Document Fees
Refer document
EMD
INR 42000.0 /-
Tender Value
INR 41.82 Lakhs /-

BOQ Items

Name of Work: Construction of 2 x 630KVA, 11/0.4KV Sub-Stations a/w 3Phase LT Lines & HT metering equipment at Bajahar on partial turnkey basis under ESD HPSEBL, Sujanpur (ED Hamirpur) (Deposit Scheme)
Sl. No. Item Description
1630,KVA,11/0.4KV Distribution Transformer (Outdoor Type)conforming to ISI & BEE Specifications.
2Pole 11 Mtr. LongISI marked Swaged Steel Tubular Pole as per IS 2713/1980 (Part I-II) as ammended from time to time with cap welded on top &Cast Iron Base Plate of designation 410-SP-56.
3RCC Muff 2000mm Long withconcrete filling material
4MS ChannelIronCross Arm:[Size (100x50x6)mm, Length : 2800 mm] x 2 Nos/Strfor Top Channel for incomer line.
5MS Angle Iron (50X50x6 mm), Length: 2800 mm x (1 Nos for LA"s ).
6MS ChannelIronCross Arm: :[Size (75x40x6)mm, Length : 2800 mm x 4 Nos] supporting DO fuse unit & GO switch/ Isolator.
7MS ChannelIronCross Arm: [Size (100x50x6 mm),Length: 2800mm×2 Nos. For Transformer bed.
8MS ChannelIronCross Arm:[Size (100x50x6 mm),Length: 460 mm×2 Nos. For supporting main channel of Transformer.
9MS Angle Iron (50X50x6 mm), Length: 950 mm x2 Nos. for bed knee bracing.
10MS Angle Iron (35X35x6 mm), Length: 460 mm x 2 Nos.
11MS Angle Iron (50X50x6 mm), Length (2800 mm) × 2 Nos.LT Box & Go
12MS Angle Iron (50X50x6 mm), Length (450 mm) :× 1 Nos.
13Isolator 11KV, 800A, 25KA with Earth Switch, Tripple Pole Gang operated Outdoor Horizontal Double break Isolator.
14D.O Fuse Unit
15Surge Arrester, 9 kV Station Class(Porcelain Type)
16Discs insulator sets (comprising 1 No. Disc: ^^(Polymer Composit Disc Insulator, BS, 12 kV, 90 kN) including Dead End Clamps, Ball Cleave & Bend Stapple etc.).
17H.T. Stay Set complete i/c Guy assembly with hellically fitting.
18Stay Wire (7/3.15 mm) (9.0 kg Per Stay Set)
19Stay Clamp / Full Clamp (M.S. Flat 50X6 mm)
20Pipe Earthing Set
21LT Distribution Panel Box suitable for 630KVA, 11/04KV (Outdoor type) Sub-Station comprising of 01No. ACB (1000A, 50 kA, 4P,)on incomer and 2Nos.,3Pole MCCB of 630Amps, 50KA & 1No.,3Pole MCCB of 400Amps, 50KACapacitycomplete in all respect as per HPSEBL/REC specifications as given in tender document
22Half Clamp (M.S. Flat 50X6 mm)
23Full Clamps (M.S. Flat 50X6 mm)
24Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm F or more(with flat and spring washers)]
25Aluminium Thimble
26Aluminium Thimble Cable Size
27Danger Plate
28Barbed Wire
29LT Cable 500 mm², PVC (1.1kV, 3½ Core, Al, Unarmoured) (x 2Nos. Incommer cables)
30LT Cable 70 mm², PVC (1.1kV, 3½ Core, Al, Unarmoured)(x 6Nos. Outgoing Cables)
31Energy Meter, 3-Phase, 4-Wire, LT CT operated Static Trivector Meter with Box (CT- 1000/5Amps, DLMS compliant) suitable for 630KVA Transformer
32Red Oxide
33Aluminium Paint.
34GI Earth wire (GI, 8 SWG) {Additional 1%(Sag and wastages)} @0.102 kg/m
35Automation and digitisation equipments for 11KV Line System i.e.one HP/Dell All-in-One Personal Computer having Operating System Windows 11, 11th Generation Intel® Core™ i3 processor, 8 GB DDR4 RAM, 512 GB PCIe® NVMe™ M.2 SSD, 60.5 cm (23.8") diagonal IPS desplay with One Nos. Laser Jet Printer (HP Model HP1136MFP or MFP M126a) and One No.UPS 1KVA Libert ITON CX 1000VA or Luminous LB1000Pro.
36HT METERING : CT PT Combined Unit (outdoor type) 11KV/110V, 200/5Amps, accuracy Class 0.5s ISI Markconforming BEE specification.
37HT Energy meter suitable CT PT Combined Unit 11KV/110V, 200/5Amps Accuracy Class 0.5S ISI Markconforming BEE specification, DLMS Complaint with RS 232 & RS485Port..
38Metal Meter Box for housing the HT Energy meter with locking & sealing mechanism complete water proof duly painted a/w mounting nuts & bolts / anchor fastners .
39Control Cable (1.1kV, 12Core, 2.5mm, HR FRLS, Copper,unscreened cable).
40Magger / Analog Insulation tester 5000Mega Ohms/ Hand Operated, 2500Volt ISI Mark(Model Waco 1005 or Equivalent)
41Aluminium Wall SupportLadder 6.09Meter (20Steps)Meter long
42LT LINE : AAAC 7/3.15mm (50mm²) conductor{Includes 4 conductor lengths for 3F and additional 1% (Sag, Jumpering and wastage}
439 Mtr. Long ISI marked, Swaged Steel Tubular poles as per IS:2713/1980 (Part-I-III) as amended from time to time, along with Cap Welded on top & Cast iron Base plate of designation 410SP-32.
44RCC Muff 2000 mm long with concrete filling material
45Shackle Insulator (16 kN)
46D-Iron (U- Clamps)made of MS Flat 50x6mm.
47LT Stay Set Complete i/c Guy Assembly and Helicallyfittings)
48Stay wire 7/3.15 mm (6.00 kg. per stay set)
49Stay Clamp / Full Clamp made of M.S. Flat of size (50 x 6mm).
50Half Clamp made of MS Flat 50x6mm
51MSCI Arm (75x40x6)mm Length 0.750Mtr
52LT Earthing Set complete in all respect.
53Earth wire (GI, 8 SWG) {Additional 1% (Sag and wastage)} @ 0.102kg/m andGuarding iacross the road including cross lacings.
54Nuts and Bolts of various sizes (Galvanised / Coated) [Preferably 16mm² or more (with flat and spring washers)]
55Aluminium Paint
56Earth Knob for LT Line
57Construction of Concrete Cement Plateform (1:3:6)of Size (1.2x1.5x1.5) Mtr for installation of 630KV, 11/0.4KV Transformer including providing of material i.e. i) 0.54Cum Concrete 1:3:6, ii)2.16 Cum Concrete 1:1.5:3 iii) MS/Tor Steel reinforcement 175Kg. iv) MSCI 21.42Kg & cement Plaster 15mm Thick includingExcavation & Form work etc. complete in all respect as per technical specifications and drawings
58Providing and fixing of wire mesh (G.I.Wire of size 3 mm) fencing 4x4=16 sq meter with 2 mtr. Height(-) 1x2 mtr.=2 sq Mtr.for gate =14 sq mtr.net qty for wiremesh fencing including providing of material i.e. i) 1.08Cum Concrete 1:6:12, ii)2.16 Cum Concrete 1:2:4 iii)4.26 Cum Concrete 13:6 iv) 120.06Kg MS AI 65x65x6 mm v) 32Sqm Wire mesh and welding work, Painting & erection etc complete in all respect.
59Providing and fixing of Steel gate of size 1mtr in width and 2 mtr. In height i.e. 2 sq Mtr.= 2 Sq. mtrs. Including providing of 28Kg MS Angle Iron 45x45x6 mm long, ii) 19.20Kg MS Flat 50x6mm iii) Locking Mechanism & Hinges etc welding , Painting & erection etc complete in all respect.
60ERECTION PART :Erection of11/0.4KV, 630KVA Sub-Station Structure using Steel Tubular Poles a/w RCC Muff & its concrete filling as per latest standard practices /specification of REC / HPSEBL including digging of pits, erection of Poles & Muffs, Filling muffs with PCC mixture, re-filling of pit & ramming, drilling of holes in Cross X Arms, Preparation of Plateform Structure Members MS Channel X Arms and Knee Bracing Sets, Erection of Plateform, fixing of M.S. Cross Arms S/Stn fitting, GO Switch, DO fuse units, Lightening Arrestors, Disc Insulators, Pin Insulators, LT Ditribution Panel, Energy Meter. Erection of S/Stn. Pipe Earthing Set (3Nos.) complete in all repect including providing Char Coal, Salt etc.,Erection of Transformer, Providing Earthing Connection to GO Switch, Transformer Lighteneing Arrestor etc. Erection of Stay Sets (2 Nos.), Erection of LT Cable and fixing of jumpers. Testing and commissioning of Transformer and allied equipments complete in all respect.
61Erection of CT-PT Unit & Energy Meter a/w allied material at tapping point and making connections as per latest standard practices /specification of REC / HPSEBL (Per Job).
62Erection of Earthing ofHT Structure including digging of pit of size 1.80x 1.2 x1.2 Mtrs, fixing of HT Earth Set, refilling the same andprov. earthing connectioncompletein all respect.
63Erection of LT Pole structure with Steel Tubular Pole 11mtr. Long : (including Digging of pit for pole, muffing of pole, erection of poles, refilling of pit & ramming , drilling of holes in pole and X-arm, fixing of X-arm, Shackle Insulators and painting of structure with Redoxide Primer & Aluminium Paintetc.Complete in all respect as per the standard practices / specifications of the REC /HPSEBL.
64Erection of Stay Set (LT):- Digging of pit (size0.9*1.20*1.33),fixing of Stay Rod, filling and ramming of pit, nozzelling and tightening etc. complete in all respect.
65Erection of Earthing ofLT including digging of pit fixing of HT Earth Set, refilling the same andprov. earthing connectioncompletein all respect.
66Laying of Conductor, Stringing, Sagging ofACSR 50mm²/7/3.15mm² and binding with Insulators (3 wires) and fixing of jumper.
67Laying ofEarth wire with GI Wire 8SWG , Stringing, Sagging ofand binding with Insulators.
68Erection Charges of fixing of Jumpers of 11Kv line as per latest standard practices /specification of REC / HPSEBL (Per Set).
69Local Transportation, loading / unloading / stacking Charges for the carriage material of2 x 630KVA, 11/0.4KV Sub-Station, HT & LT Lines and HT Metering equipments by road & mannual carriage etc.
70Testing fees & Commissioning Charges etc. for 2Nos 630KV11/0.4KV Sub-Stations and allied HT /LT Lines & Metering Equipments for comlete Job.(as per Schedule of General & Service Charges & HP Govt. Notification)
71Labour Cess for the design, supply, erection, testing Commissioning of 4Nos. 11/0.4KV Sub-Stations, HT /LT Lines & Metering Equipments for comlete job.
Disclaimer :