Construction Of Surveillance Cum Op Shelter G Plus 2 In Between Bp No 1905 40 S To 1906 M In Aor Of Bop Morechera Of 105 Bn Bsf Under Shq Bsf Panisagar Sh Ie And Fans
Tender Value
8.69 Lakhs
Estimated cost
Bid Submission
03 Aug 2022
0 days left
EMD
17394
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
North Tripura → Tripura
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Construction Of Surveillance Cum Op Shelter G Plus 2 In Between Bp No 1905 40 S To 1906 M In Aor Of Bop Morechera Of 105 Bn Bsf Under Shq Bsf Panisagar Sh Ie And Fans
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Group-A) |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface /recessed medium class PVC conduit, 2 way modular switch,modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Wiring for circuit wiring along with earth wire with the following size of PVC insulated copper conductor single core cable in the surface / recesed medium class PVC conduit etc as required. a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.a) 2 Pair |
| 6 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 amps switch |
| 7 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.b) 3 pin 5/6 amp socket outlet |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) Telephone socket outlet |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required for cable entry. a) 40 mm |
| 10 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \"C\"curve including connections, painting etc. as required. |
| 11 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 12 | Supplying and fixing PVC holder including connection etc. as required. |
| 13 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator)-Make L&T/Havells/Legrand. a) 8 way , Double door |
| 14 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single Pole |
| 15 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. b) Double Pole (32 A) |
| 16 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 17 | Providing and fixing of lightning conductor finial, made of 25mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 18 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 19 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 20 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 21 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 22 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 23 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 24 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 25 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 26 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 27 | Supplying, Installation, testing and commissioning of20 watt LED batten Decorative ultra slimLED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient etc. as required including making connection etc. as required directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc as required |
| 28 | Supplying, Installation, testing and commissioning of10 watt LED batten with polycarbonate housing & integrated electronic driver, box type etc. as required including making connection etc. as required of directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc as required |
| 29 | Supplying, Installation, testing & commissioning of Wall fan 400 mm sweep double ball bearing,copper winding,3 blades with speed regulator etc asrequired. |
| 30 | Providing & fixing of plastic body fresh air fan of size 250 mm sweep1 phase,240 Voltwith plastic louvers/shutters including making hole in the existing wall and making good the damage, connection, testing, commisioning etc as required. |
| 31 | Providing and fixing of 25 watt LED street light LED OF 5700 K made up of pressure die cast housing with toughned glass and individual high power LEDs of havells make with inbuilt LED light source, 32 mm dia X 1 Mtr long GI pipe brakcet for mounting on the wall including bending the pipe to the required shape, flat iron clamps with nut, bolts and washers including painting with connection, testing commissioning etc as required. |
| 32 | Supplying and Laying of one number XLPE insulated and PVC sheathed, armoured aluminium power cable of size 2 X 25 Sq. MM conf to IS: 7098 (Part-I) direct in groundincluding excavation, and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 33 | Supplying & laying of one number PVC insulated and PVC sheathedarmoured power cable of 1.1 KV grade of 2 x 25 sq.mm in the existing RCC/ HUME/ METAL pipe as required. |
| 34 | Supplying and Laying of one number XLPE insulated and PVC sheathed aluminium conductor power cable of 1.1 KV grade of size 2 X 25 sq.mm in the existing masonry/ open duct as required. |
| 35 | Supplying &Fixing of Single Phase 01 HP Monoblock Pump having head range of 12 to 30 mtr,discharge flow range 21000 Ltr /Hr - 6960 Ltr /Hr, and including motor starter for single phase motor. |
| 36 | Supplying &Fixing of2 Core 4 Sqmm size Flat Copper Cable for 01 HP Monoblock Pump |
| 37 | Supplying of Single Phase 01 HP Monoblock Pump having head range of 12 to 30 mtr,discharge flow range 21000 Ltr /Hr - 6960 Ltr /Hr, and including motor starter for single phase motor |
| 38 | SITC of2 KWP , 24Volt single phase PWM Solar power package consisting of 2 KVA capacity, 24 V rated solar conditioning unit 6 X 335 WP solar PV module having nominal voltage 24 V, 04nos LMLA C - 10 rated 12 V, 150 AH tubular solar battery with 5 years warranty including field junction box,suitable galvanized iron stand for module,interconnectionof modules and junction box through 6 sqmm cross linked polyolefin insulated, halogen free polyolefin sheathed annealed tinned copper conductor,heat resistant upto 120 degree C,UV resistant solar cable & connection between junction box,PCU & battery through PVC insulated PVC sheathed 6 sqmm twin core stranded copper conductor cable including of panel G.I Pipe earthing and all accessories includingbrick work for making foundation for solar panel legs including plastering etc as required as per site requirement.The module/panel should complaince with IEC- 61215.The solar PCU unit should consists of the following:- A) Solar charger controller:- Single phase solar charge controller based on PWM technology,max input PV current 40 A, protection against overcurrent,battery overcharge,PV/battery reverse polarity,reverse current & high temperature B) Inverter :- Solar hybrid inverter with inbuilt charge controller 2KW, 24 V DC input and 220 V pure sine wave output at rated load 2 KVA @ 0.8 PF,efficiency >85%having 2 years warranty. |
| 39 | ADD COST INDEX @ 35.59% ON DSR 2018 SR NO. 1 TO 26 RS. 148772 |
AI Tender Summary
Tender Timeline
Jul 26, 2022
11:30 IST
Tender Published
Tender notice published.
CompletedAug 03, 2022
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedAug 04, 2022
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender