Supply Installation Testing And Commissioning Of Energy Efficient Vrv Air Conditioning Unit For Security Units Cabin At Top Floor Of Lock Up Building , Saket Court Complex , New Delhi, delhi-Delhi

Public Works Department-PWD has published Supply Installation Testing And Commissioning Of Energy Efficient Vrv Air Conditioning Unit For Security Units Cabin At Top Floor Of Lock Up Building , Saket Court Complex , New Delhi. Submission Date for this Tender is 30-07-2022. Air Conditioner Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

33225589
Supply Installation Testing And Commissioning Of Energy Efficient Vrv Air Conditioning Unit For Security Units Cabin At Top Floor Of Lock Up Building , Saket Court Complex , New Delhi
Open Tender
Indian
Delhi
delhi
30-07-2022

Tender Details

Supply Installation Testing And Commissioning Of Energy Efficient Vrv Air Conditioning Unit For Security Units Cabin At Top Floor Of Lock Up Building , Saket Court Complex , New Delhi

Key Value

Document Fees
Refer document
EMD
INR 32566.0 /-
Tender Value
INR 16.28 Lakhs /-

BOQ Items

Name of Work: SITC of Energy Efficient VRV Air Conditioning Unit for Security Units Cabin at Top floor of Lock Up Building , Saket Court Complex , New Delhi.
Sl. No. Item Description
1SITC of Air Cooled VRV / VRF units with Inverter Scroll Compressor capable of modulating capacity i.e. it should be able to vary speed of the compressor as per the varying load conditions and works on R410A with heating & cooling both. The outdoor unit shall be factory assembled unit housed in a sturdy weather proof casing constructed from rust-proofed mild steel panels coated with powder coated finish. The outdoor unit shall have multiple scroll compressors. Each unit shall be equipped, with an oil separator to ensure stable operation with long refrigerant piping.Variable refrigerant flow modular type air-conditioning system suitable for Cooling/Heating by inverter driven capacity control compressor Outdoor unit having minimum COP at 100% Load must be 3.2 & 50% Load it must be 4.5 at 35 deg. Outside ambient conditions.(ARI Condition). All the units shall be provided with built-in microprocessor control panel, for automatic operation and capacity control. All compressor shall have inverter technology i.e. outdoor units shall have all inverter based compressor. Each ODU weather used individually or used to make module should have multiple compresors. All Bidders has to submit the test certificates along with the delivery of VRF/VRV units at site agency to provide shop drawing of complete HVAC system along with calculations along with technical submittal and submit for approval before execution complete etc as required at site.
2ODU - Heating and cooling.
3Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
44.0 TR
5Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for VRV / VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing / brazing including accessories, insulated with XPLE Class-O tubular insulation / with Class- O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquidlines, all accessories as per specifications etc. as required
634.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
731.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
828.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
925.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
1022.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
1119 mm dia (OD) (Softdrawn) with tube thickness 1.2 mm with 19 mm thick insulation
1215.86 mm dia (OD) (Softdrawn) with tube thickness 1.2 mm with 19 mm thick insulation
13Supply,laying testing and commissioning of following sizes of XLPE insulated PVC sheathed round wire armouredconductor cable of 1.1 KV grade on existing cable tray / surface including clamps, ties etc. as required. (Make: Havells , Polycab, Finolex)
143.5 C x 35 Sqmm Aluminium armoured
153 C x 2.5 Sqmm copper armoured
16Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
17150 mm width X 50 mm depth X 1.6 mm thickness
18300 mm width X 50 mm depth X 1.6 mm thickness
19Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required.
20Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in electrical panel baord including connection complete etc as required at site.
21100 A 16 KA TPMCCB
22Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required
23Single pole
24Supplying and fixing of following ways surface/recess mounting, vertical type, 415V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200A tinned copper bus bar, common neutral link, earth bar din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
258 Way(4 + 24), Double door
26Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
27Providing & fixing of Refrigerent pipingCopper Y joints or Refnets as required to connect the outdoor & indoor units. (Make: Same as VRV System)
28Supply and fixing of following CPVC pipe 15 kg/ cm sq working pressure along with 6 mm thick nitrile rubber insulation with accessories on surface/recess i/c cutiing the cutting wall and making for condensate water. (Make: Prince/ Astral/ Supreme)
2932 mm (1.25 inch)
3025 mm (1 inch)
31Supplying, laying,fixing, testing and commissioning of 6mm thickness closed cell elastrometric nitrile rubber of class ‘O’ applied by suiatable adhesive, as per specifications and as required complete in all respect.(Make: Supreme/ ALP/ Visiaro)
32Annual Comprehensive maintenance of above complete item VRV System
33For 1st year (Defect liability period)
34For2nd year
35For3rd year
36For4th year
37For5th year