Repair/Maintenance Of Lt Elect Installations Oh Lines Lt External Electrification Ug Cables Including Allied Works And Transformers Feeder Pillar Boxes Apfc Panels Etc At Certain Locations Under Ge Shillong , shillong-Meghalaya

Military Engineer Services-MES has published Repair/Maintenance Of Lt Elect Installations Oh Lines Lt External Electrification Ug Cables Including Allied Works And Transformers Feeder Pillar Boxes Apfc Panels Etc At Certain Locations Under Ge Shillong . Submission Date for this Tender is 29-08-2022. Electrification Work Tenders in shillong Meghalaya. Bidders can get complete Tender details and download the document.




Tender Notice

33198267
Corrigendum : Repair/Maintenance Of Lt Elect Installations Oh Lines Lt External Electrification Ug Cables Including Allied Works And Transformers Feeder Pillar Boxes Apfc Panels Etc At Certain Locations Under Ge Shillong
Open Tender
Indian
Meghalaya
shillong
29-08-2022

Tender Details

Repair/Maintenance Of Lt Elect Installations Oh Lines Lt External Electrification Ug Cables Including Allied Works And Transformers Feeder Pillar Boxes Apfc Panels Etc At Certain Locations Under Ge Shillong

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Aug-2022 BOQ Corrigendum BOQ 17-08-2022
2 01-Aug-2022 Amndt to tender Terms and Conditions 17-08-2022
3 17-Aug-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 24-08-2022
4 25-Aug-2022 Date Corrigendum Date 29-08-2022

Key Value

Document Fees
INR 1000 /-
EMD
INR 145000.0 /-
Tender Value
INR 80 Lakhs /-

BOQ Items

Name of Work: REPAR/MAINTENANCE OF LT ELECT INSTALLATIONS, OH LINES, LT EXTERNAL ELECTRIFICATION, UG CABLES INCLUDING ALLIED WORKS AND TRANSFORMERS, FEEDER PILLAR BOXES, APFC PANELS ETC AT CERTAIN LOCATIONS UNDER GE SHILLONG
Sl. No. Item Description
1Excavation in trenches n exc 1.5 mtr wide and depth n exc 1.5 mtr deep for foundation, laying GI pipes and UG cables etc n exc 10 sqmtr on plan, in hard/dense soil and getting out complete all as specified and directed.
2Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
3M & L for providing dry river sand as in sand cushioning to UG cable including punning gently complete all as specified and directed.
4Removing excavated material not exc 50 mtr and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed.
5M & L Sub class"B" old size well burnt brick laid flat in trenches as protection to LT cable complete all as specified and as directed.
6Re-laying of old serviceable bricks as protection to LT cable complete all as specified and as directed.
7Supply and fixing GI Tubing light grade80 mm bore under road, on pole floor and on wall for cable protection complete all as specified and as directed.
8Supply and fixing GI Tubing light grade 50 mm bore under road, on pole floor and on wall for cable protection complete all as specified and as directed.
9Supply, laying, testing & commissioning XLPE insulated PVC inner sheathed, armoured with galvanized steel strip or wire heavy duty underground cable withstranded aluminumconductor 1100 volt grade of size 150 Sqmm 3.5 Core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing complete all as specified and directed including taking down old unserviceable XLPE cable with brick protection andcomplete all as specified and as directed.
10All as per Item No.9 above but size of XLPE cables 120 Sqmm 3.5 Core.
11All as per Item No.9 above but size of XLPE cables 95 Sqmm 3.5 Core.
12All as per Item No.9 above but size of XLPE cables 70 Sqmm 3.5 Core.
13All as per Item No.9 above but size of XLPE cables 50 Sqmm 3.5 Core.
14All as per Item No.9 above but size of XLPE cables 25 Sqmm 4 Core.
15All as per Item No.9 above but size of XLPE cables 16 Sqmm 4 Core.
16All as per Item No.9 above but size of XLPE cables 10 Sqmm 4 Core.
17All as per Item No.9 above but size of XLPE cables 16 Sqmm 2 Core.
18Re-laying of old XLPE insulated PVC inner sheathed, armoured with galvanized steel strip or wire heavy duct underground cable with stranded alminium conductor 1100 volt grade of size 70 Sqmm to 240 sqmm 3.5 Core laid in trenches/dct passing through pipe/duct or fixed on pole and connecting and testing complete all as specified and directed[Note : (i) Excavation, returning filling and removal, sand and bricks to be measured and paid separately under relevant items and (ii) serviceable piece of old cables taken out vide item No 9 to 12 to be reused]
19All as per item No 18 above but size of XLPE cable 10 Sqmm 2/4 core to 50 sqmm 3.5 core[Note : (i) Excavation, returning filling and removal, sand and bricks to be measured and paid separately under relevant items and (ii) serviceable piece of old cables taken out vide item No 13 to 17 to be reused]
20S&F Steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screws of type 410 SP-31 ( 9 metre long) complete all as specified and directed.
21S&F LT cable joiniting kit 1100Volts grade cable for Straight through joint, cold shrink type, complete with jointing material and accessories suitble for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 120 Sqmm including taking down old unserviceable one.
22Cutting and trimming of tree branches to clear OH lines in the area of LT OH lines feeders for a span of 30m Each(including repairing and jointing of ACSR conductor if damaged during cutting of tree) and removal of the trimmed branches of trees and depositing the same in MCD waste bins inside the campus complete all as specified and directed by Engr-in-charge.
23Restringing of existing ACSR conductor on LT over head line on the poles without taking down of ACSR from over head line by disconnecting and untying from insulator and retying with new binding wire, rejoining of service connection of street light, and all other jumper connection complete all as directed by Engr-in-Charge. Note : Three runs of phase conductor one run of neutral conductor and two runs for street light ACSR conductor will be measured as one length.
24Supply & Fixing Pin type, porcelain, viterous white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height,65 mm dia for 1100 volts grade including taking out of old one
25Supply & Fixing Shackle type, porcelain, viterous white, brown or green insulator including galvanised mild steel straps with section of straps 31 X 3 mm, dia of bolts 12 mm and working pressure 1100 volts of size 75 mm height and 90 mm max dia complete all as specified and directed by Engr-in-Charge including taking out of old one
26M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending, cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including taking down old unserviceable one.
27M&L, GI strip 32 x 6 mm as eath continuity conductor or main earthing lead buried in ground or drawn through pipes or fixed to wall or poles or any other situation for loop earthing etcincluding dismantling old unserviceable strip complete all as specified and directed by Engr-in-Charge.
28M&L PCC, type C1, (1:3:6, using 20mm graded stone aggregate) as in coping of poles including formwork complete all as specified and as directed including demolition of old damaged concrete from pole.
29M&L PCC, type D2, (1:4:8, using 40mm graded stone aggregate) as in PCC/Road cutting /installation area and foundation of pole etccomplete all as specified and as directed by Engr-in-Charge.
30S&F in repair Indicator lamp (AC/DC), LED, type for as per existing fitting
31S&F in repair 3 Phase LED AmmeterCat Part No WL131020OOO Make - L&T or equivalent
32S&F in repair, 3 phase LED Voltmeter Cat Part No WL132020OOOO Make:- L& T or equivalent
33Supply and fix as in repairMCCB four pole , 415 Volt, 63 Amps,16 KA , fixed thermal &magnetic setting complete all as specified and directed .
34Supply and fix as in repairMCCB four pole , 415 Volt, 100 Amps,16 KA , fixed thermal &magnetic setting complete all as specified and directed .
35Supply and fix as in repair MCCB four pole , 415 Volt, 125 Amps,16 KA , fixed thermal &magnetic setting complete all as specified and directed .
36S&F MCCB, 160 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
37S&F MCCB, 200 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
38S&F MCCB, 250 Amps, 4P, 25 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
39S&F MCCB, 400 Amps, 4P, 36 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
40S&F MCCB, 630 Amps, 4P, 36 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
41S&F MCCB, 800 Amps, 4P, 36 kA, 415 Volts, with adjstable thermal release & adjustable magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed.
42M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.00 mm buried directly in ground connected to galvanized earth lead strip of size 32 mm x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including 40mm bore medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC type C1 (1:3:6, using 20mm graded stone aggregates) 50mm thick precast RCC type B1, (1:2:4, using 20mm graded stone aggregate) pit cover reinforced with 8mm dia deformed bar and suitablehandle made of 10mm dia round bar including galvanised strip of size 32mm x 6mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance n.exc 50m and necessary connection and testing complete all as shown in electrical plate No 3 of SSR Part-I, 2009 and all as specified and directed including taking down old unserviceable earth pit. [Note : GI Strip upto 7.5m length shall be deemed to include in the cost of above item.Quantity required over and above shall be measured and paid seperately ubder relevant item of this schedule]
43M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.00 mm buried directly in ground connected to galvanized earth lead wire of 4.0 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including 40mm bore medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm bore, charcoal or coke and common salt in alternative layer of 15 cm compacted thickness all around the electrode with concrete earth pit of PCC type C1 (1:3:6, using 20mm graded crushed stone aggregates) 50mm thick precast RCC type B1, (1:2:4, using 20mm graded crushed stone aggregate) pit cover reinforced with 8mm dia deformed bar and suitablehandle made of 10mm dia round bar including galvanised strip of size 32mm x 6mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance n.exc 50m and necessary connection and testing complete all as shown in electrical plate No 3 of SSR Part-I, 2009 and all as specified and directed including taking down old unserviceable earth pit. [Note : GI wire upto 7.5m length shall be deemed to include in the cost of above item. Quantity required over and above shall be measured and paid seperately ubder relevant item of this schedule]
44M & L painting LT Panel/feeder pillar by one coat of synthetic enamel paint after preparation of surfaces complete all as specified and as directed.
45Servicing of LT Panel after shut downand removing all dust particles and proper layout of LT panel wlth gland packing including 2.5 sqmm copper single core copper cable including repairing/replacing door hinges/door lock etc for necessary connections complete all as specified and directed
46M&L Preparation of old painted (outer exposed surface) of electric steel tubler polesover all diminsion 8.5/9.0 metres long, painting starts from ground level with black bituminious paint up to one metre andthereafterapplying one coat of aluminium paint including MS channel / angle iron andclamps with bolts, nutsof street light fittingandwriting pole No with black colur synthetic enamel paint of existing size letters complete all as specified and as directed.
47Filtration and dehydration of transformer oil and removing sludge by continuous circulation through centrifuging filtration plant with strip heater and improvement of dielectric strength to minimum 60 KV at 2.5 mm gap of electrode as per IS: 6792 (latest) for different capacities of transformer complete all as directed by Engineer-in-Charge.
48M&L Topping up / replacement of transformer oil with new transformer oil suitable for working voltage 11000 volts grade, including necessary dehydration to achieve dielectric strength min 40 KV at 4mm gap transformer for various capacities of transformercomplete all as directed. Make of transformer oil : GULF/Castrol/HP/IOC/BP. Notes :for Ser Item No 1 & 2 (a) New transformeroil to be bought by the contractor in sealed (ISI marked) container with original test certificate. (b) Filtration/dehydration of transformer oil shall be carried out at the location where transformer is installed and necessary instruments shall be brought at site by the contractor. (c)During the process of filtration, transformer will be on load condition. (d)The old unserviceable oil shall be offered under schedule of credit. (e) Filtration and topping up transformer shall be done by authorised agent / dealer of manufacturer of transformer.
49Supply and replacement of silica gel grains in the breather assembly of transformers of various capacities complete all as directed by Engineer-in-Charge.
50Supply and replacement of breather assembly of size 50mm dia, min 250mm long for transformer of various capacities complete all as directed by Engineer-in-Charge.
51Supply and replacement of transformer temperature gauge, dial type, having temperature range 0 to 120°C complete all as directed by Engineer-in-Charge.
52Opening of top cover by unscrewing all nuts, bolts and washers forreplacement of transformer HT/LT bushing, lifting of core assembly, cleaning and refixing the complete unit with new cork sheet, gasket, existing/wherever required with new nuts, bolts and washers for transformer capacity 63 KVA to 500 KVA indoor/outdoor type complete all as directed by Engineer-in-Charge. Note: - (i) HT/ LT bushing shall be measured and paid separately under relevant items of these schedule as "supply only" items and labour element involved for replacing the same shall deemed to be included in the rate quoted by the tenderer in this item. (ii) Works to be carried out by standard agencies in the field only approved by Engr-in-Charge
53Opening of top cover by unscrewing all nuts, bolts and washers forreplacement of transformer HT/LT bushing, lifting of core assembly, cleaning and refixing the complete unit with new cork sheet, gasket, existing/wherever required with new nuts, bolts and washers for transformer capacity 3.15MVA indoor/outdoor type complete all as directed by Engineer-in-Charge. Note: - (i) HT/ LT bushing shall be measured and paid separately under relevant items of these schedule as "supply only" items and labour element involved for replacing the same shall deemed to be included in the rate quoted by the tenderer in this item. (ii) Works to be carried out by standard agencies in the field only approved by Engr-in-Charge
54Supply only HT porcelain bushing suitable for 11 KV grade complete with brass rod & rubber bush for 63 to 500 KVA capacities of transformer complete.
55Supply only HT porcelain bushing suitable for 33 KV grade complete with brass rod & rubber bush for 3.15 MVA capacities of transformer complete.
56Supply only HT porcelain bushing suitable for 11 KV grade complete with brass rod & rubber bush for 3.15 MVA capacities of transformer complete.
57Supply only LT porcelain bushing suitable for 1100 volt grade complete with brass rod & rubber bush for 63/100 KVA capacities of transformer complete.
58Supply only LT porcelain bushing suitable for 1100 volt grade complete with brass rod & rubber bush for 160/250 kVA capacities of transformer complete.
59Supply only LT porcelain bushing suitable for 1100 volt grade complete with brass rod & rubber bush for 315/500 kVA capacities of transformer complete.
60Shifting of transformer carefully of capacity of 63 - 500 KVA from its position upto road n.exc 50 m high by manually or chain pulley arrangement and carrying it to other installation by vehicle (Recovery Van) within Cantonment area n.exe 2 KM and install it to new places including commissioning and testing complete all as directed by Engineer-in-Charge.
61M & L for attending fault of defective transformer step down 11 KV / 0.433 upto 500 KVA transformer any make, plinth/ floor/ pole mounted, indoor/ outdoor type, inspecting the transformer,meggering, step opening, removing the top cover of transformer, detecting the fault, rectfying the defect at site except major fault of burnt winding or other. and reassemble the same incl minor repairs i.e. tightening all loose connections at HV/LV bushings, any portion, spare parts of the transfomer and replace the gasket, cleaning outer surface by using cotton waste, panting complete all as directed by Engr-in-charge. (a) Step opening of the transformer and taking out the transformer oil from transformer into seperate container barrel and shall be included in quoted rates. (b)Replacement cost of the rubber gasket set for top cover, spindles, HT/LT bushing, insulators, breather, temp gauge, silica or any other item etc. as required shall be measured and paid separetely under relevant items of BOQ. (c)The cost of Cotton waste shall be included in quoted rates. (d)Dehydration/Filteration & heating of trf oil, suspended dust particles ect. shall be measured paid separetely under relevant items of BOQ).(e) The cost of nuts&bolts incl washers deemed to be included in the quotedrate. (f)Entire job shall be measured and paid after testing and entire satisfaction of Engr-in-Charge. (g) Replacement of LV / HV bushing /brass spindles / rewinding of HV / LV coils / tap changer,painting etc, shall be measured and paid for separately under relevant items of BOQ. (h) Transformer oil (if required) for topping up will measured and paid for separately under relevant item of BOQ.
62M & L for removing from site by disconnecting all connections of defective step down 11 KV / 0.433 any capacity upto 500 KVA transformer any make, plinth/ floor/ pole mounted, indoor/ outdoor type, transporting/ lifting with required T&P, hydra machine etc. to local/ authorised work shop for carrying out major repair of the transformer, detecting the fault, step opening of the transformer, including spray painting. A factory test should be carried out after repair and before dispatch of the transformer.including transporting carefully, refixing back to original position complete all as directed and entire satisfaction of Engr-in-charge.Note: (a) Dismantling/ reassembling, at work shop shall be included in quoted rates (b) lifting, transportation from site to work shop and refixing back to original posittion shall inculded in quoted rates (c) Dehydration/filteration & trf oil shall be mesured and paid separetely under relevant item of BOQ (d) Spray painting, nuts, bolts and washer deemed to be included in the quoted rate.(e) The cost of silica jel, rubber gasket, temperature gauge, breather assembly, gate valves shall be measured and paid separetely under relevant items of BOQ(f) Rewinding part or entire windings, replacement of LV / HV bushing/ spindles/ copper wire wt. for rewinding of HV / LV coils / tap changer etc will be measured and paid for separately under relevant items of BOQ. (g) Topping up of transformer oil (if required) shall be mesured and paid separetely under relevant item of BOQ (h)Dismantling the transformer limb, drainingout transformer oil and lifting the core coil assembly, cleaning the core coil assembly by oil complete and remove the dirt, sludge in the coil and core gently without making damage of insulation complete all as directed by Engineer-in-Charge (j) Cleaning inside the chamber of transformer, scrapping complete all sludge and iron particle. (k) M & L Two coats of oil resistance paint on inside surfaces of transformer over a coat of red oxide metal primer. (l) Works to be carried out by standard agencies in the field only approved by Engr-in-Charge (m) The contractor shall produce the test certificate issued by factory/ work shop. (n) The neccesary T&P,hydra machine shall be provided by the contractor and the same shall be included in quoted rates) (o) The contractor shall give guarantee for a period of 01 year for all works and for repaired transformer.
63Servicing and repair to 33KV/11KV Transformer of capacity 3.15 MVA including the following works :- (a)Transport the transformer to workshop and return back after servicing including installation and commissioning and testing complete all as directed by Engineer-in-Charge. (b)Dismantling the transformer limb, drainingout transformer oil and lifting the core coil assembly, cleaning the core coil assembly by oil complete and remove the dirt, sludge in the coil and core gently without making damage of insulation complete all as directed by Engineer-in-Charge. (c) Cleaning inside the chamber of transformer, scrapping complete all sludge and iron particle. (d) M & L Two coats of oil resistance paint on inside surfaces of transformer over a coat of red oxide metal primer. (e) Re-assembling all dismantled parts including provision of new gaskets, spacers, nut, bolt refilling with new transformer oil. [Note :-(i) Works to be carried out by standard agencies in the field only approved by Engr-in-Charge (ii) Oil filtration, supply of new oil and major spares will be measured and paid separately. (iii) All petty parts including nut, bolts, gaskets, minor welding deemed to be included in the quoted rate. (iv) All defective spare parts shall be approved by Engineer-in-Charge for replacement.
64M & L Rewinding of HT coils suitable for 11000 volts grade with new super enamelled copper wire having Class - F insulation as per existing size and turns for capacity of transformer 63- 500 KVA complete all as directed by Engineer-in-Charge.
65M & L Rewinding of LT coils suitable for 1100 volt grade with new DPC copper wire having Class F insulation as per existing size and turns for capacity of transformer 63 to 500 KVA complete all as directed by Engineer-in-Charge.
66M & L Painting of transformer outer surface with one coat of synthetic enamel paint for transformer capacity 63KVA/100KVAafter preparation of old painted surface by spray painting complete all as directed by Engineer-in-Charge.
67M & L Painting of transformer outer surface with one coat of synthetic enamel paint for transformer capacity 160KVA/250KVAafter preparation of old painted surface by spray painting complete all as directed by Engineer-in-Charge.
68M & L Painting of transformer outer surface with one coat of synthetic enamel paint for transformer capacity 315 KVA/500KVAafter preparation of old painted surface by spray painting complete all as directed by Engineer-in-Charge.
69M & L Painting of transformer outer surface with one coat of synthetic enamel paint for transformer capacity 3.15 MVAafter preparation of old painted surface by spray painting complete all as directed by Engineer-in-Charge.
70Supply and replace HT/LT side terminal box made out of mild steel SA 40405 angle iron and 2mm thick MS sheet including removalble cover with required holes onflnge to fix at body of transformer and removable cover and fixing with new cork sheet gasket with nuts, bolts and washers inclding one coat of synthetic enamel paint as under coat and one as finishing coat to both side of box for 63 KVA/ 100 KVA Transformer capacities complete all as directed by Engr-in-Charge.
71Supply and replace HT/LT side terminal box made out of mild steel SA 40405 angle iron and 2mm thick MS sheet including removalble cover with required holes onflnge to fix at body of transformer and removable cover and fixing with new cork sheet gasket with nuts, bolts and washers inclding one coat of synthetic enamel paint as under coat and one as finishing coat to both side of box for 160 KVA/ 250 KVA Transformer capacities complete all as directed by Engr-in-Charge.
72Supply and replace HT/LT side terminal box made out of mild steel SA 40405 angle iron and 2mm thick MS sheet including removalble cover with required holes onflnge to fix at body of transformer and removable cover and fixing with new cork sheet gasket with nuts, bolts and washers inclding one coat of synthetic enamel paint as under coat and one as finishing coat to both side of box for 315 KVA/ 500 KVA Transformer capacities complete all as directed by Engr-in-Charge.
73S&F in repair Gun metal gate valve (ISI marked) Class-I, 25mm bore with iron wheel head screwed both ends for iron pipe sitable for following bore of pipe including taking down old nserviceable one complete all as specified and as directed.
74S&F XLPE Cable jointing kit 11000 volts grade, outdoor termination, heat shrinkable type with jointing materials and accessories suitable for HT XLPE armoured aluminium condctor cable of size 95 Sqmm 3 core complete inclding taking down old unserviceable jointing kit complete all as specified and as directed.
75S&F XLPE Cable jointing kit 11000 volts grade, indoor termination, heat shrinkable type with jointing materials and accessories suitable for HT XLPE armoured aluminium condctor cable of size 95 Sqmm 3 core complete inclding taking down old unserviceable jointing kit complete all as specified and as directed.
76S&F XLPE Cable jointing kit 11000 volts grade, outdoor termination, heat shrinkable type with jointing materials and accessories suitable for HT XLPE armoured aluminium condctor cable of size 120 to 185 Sqmm 3 core complete inclding taking down old unserviceable jointing kit complete all as specified and as directed.
77S&F XLPE Cable jointing kit 11000 volts grade, indoor termination, heat shrinkable type with jointing materials and accessories suitable for HT XLPE armoured aluminium condctor cable of size 120 to 185 Sqmm 3 core complete inclding taking down old unserviceable jointing kit complete all as specified and as directed.
78S&F XLPE Cable jointing kit 33000 volts grade, indoor termination, heat shrinkable type with jointing materials and accessories suitable for HT XLPE armoured aluminium condctor cable of size 240 sqmm single core complete inclding taking down old unserviceable jointing kit complete all as specified and as directed.
79S&F XLPE Cable jointing kit 11000 volts grade, indoor termination, heat shrinkable type with jointing materials and accessories suitable for HT XLPE armoured aluminium condctor cable of size 240 sqmm three core complete inclding taking down old unserviceable jointing kit complete all as specified and as directed.