| Sl. No. | Item Description |
| 1 | od250799/2020_2021 : Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile above 100 tonne and upto 150 tonne Safe capacity<br>Initial test (Test Load 2.5 times the Safe capacity)<br><br> |
| 2 | od250802/2020_2021 : Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile above 150 tonne and upto 200 tonne Safe capacity<br>Initial test (Test Load 2.5 times the Safe capacity)<br><br> |
| 3 | od250804/2020_2021 : Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile above 100 tonne and upto 150 tonne Safe capacity<br>Routine test (Test Load 1.5 times the Safe capacity)<br><br> |
| 4 | od250807/2020_2021 : Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile above 150 tonne and upto 200 tonne Safe capacity<br>Routine test (Test Load 1.5 times the Safe capacity)<br><br> |
| 5 | od174480/2021_2022 : SPT test-Conducting Standard penetration test at various depths inside the pile bore along with report all complete as per the insturction of Engineer in charge. |
| 6 | 5.9.1 : Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete |
| 7 | 5.9.2 : Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 8 | 5.9.3 : Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform |
| 9 | 5.9.5 : Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers |
| 10 | 5.9.6 : Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 11 | 5.9.7 : Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases) |
| 12 | 5.9.9 : Centering and shuttering including strutting, etc. and removal of form for:Arches, domes, vaults up to 6m span |
| 13 | 5.9.16.1 : Centering and shuttering including strutting, etc. and removal of form for:Edges of slabs and breaks in floors and wallsUnder 20 cm wide |
| 14 | 5.9.16.2 : Centering and shuttering including strutting, etc. and removal of form for:Edges of slabs and breaks in floors and wallsAbove 20 cm wide |
| 15 | 5.9.19 : Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges |
| 16 | 4.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size) |
| 17 | od250958/2020_2021 : Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete,improve workability without impairing strength and durability as per direction of the Engineer - in -charge. Note:- Minimum Cement content considered in this item is @330kg/cum. <br>All wiork upto plinth level |
| 18 | od250974/2020_2021 : Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete,improve workability without impairing strength and durability as per direction of the Engineer - in -charge. Note:- Minimum Cement content considered in this item is @330kg/cum. <br>All work above plinth level upto floor V level |
| 19 | 5.38 : Extra for R.C.C. /B.M.C/R.M.C. work above floor V level for each four floors or part thereof. |
| 20 | od252027/2020_2021 : Extra for providing richer mixes at all floor levels.<br>Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Minimum Cement content considered in M-30 is @ 340 kg/cum). |
| 21 | od268392/2020_2021 : Steel reinforcement (corrosion resistance steel) for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth level<br>Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 22 | od268411/2020_2021 : Steel reinforcement (corrosion resistance steel) for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 23 | od251209/2020_2021 : "Providing and injecting chemical emulsion for PRE-CONSTRUCTIONAL Anti termite treatment and creating a chemical barrier on top surface of plinth filling, junctions of inside walls and floors, soil along external perimetre using the chemical lmidacloprid emulsifiable (IS 6313 (part2:2013) SC mixed with water in 1:499 ratio. The emulsion is spread at 5litre/sqm on top surface of plinth filling,at 1 litre/linear metre along the junction of wall and floor and at 2.25litres/linear metre of the plinth wall as per the specifications and directions. (Note: plinth area only shall be measured for payment) <br>"<br> |
| 24 | 2.25 : Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 25 | 50.2.25.1 : Filling with contractor\"s own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge |
| 26 | 4.2.5 : Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc. up to floor five level, excluding the cost of centering, shuttering and finishing:1:3:6 ( 1 cement : 3 coarse sand :6 graded stone aggregate 20 mm nominal size) |
| 27 | 4.17 : Making plinth protection 50 mm thick of cement concrete 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)over 75 mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and groutedwith fine sand, including finishing the top smooth. |
| 28 | od267180/2020_2021 : Providing & Laying Cinder Filling in Sunk slab including compacting manually with rammer<br>and finishing true line & level at all floor level etc. complete as directed by E.I.C.<br> |
| 29 | 22.4.1 : Providing and Placing in position suitable PVC water stops conforming to IS : 12200 for construction / expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete:Serrated with central bulb ( 225 mm wide, 8-11 mm thick) |
| 30 | 5.25 : Providing and fixing in position copper plate as per design for expansion joints. |
| 31 | od254096/2020_2021 : Providing and filling in position, blow bitumen in expansion joints. |
| 32 | 5.28 : Providing and fixing in position 12 mm thick bitumen impregnated fibre board conforming to IS: 1838, including cost of primer, sealing compound in expansion joints. |
| 33 | 5.29.2.1 : Providing and fixing sheet covering over expansion joints with iron screws as per design.Aluminium fluted strips 3.15 mm thick150 mm wide |
| 34 | 50.6.2.1 : Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15 cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 15cm in: CM 1:6 ( 1 cement :6 coarse sand) etc complete |
| 35 | 50.6.1.2 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete. |
| 36 | 50.6.1.3 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure above floor two level up to floor V level thickness 20cm and above in: CM 1:6 ( 1 cement :6 coarse sand) etc complete |
| 37 | od268629/2020_2021 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure above floor V level thickness 20cm and above in: CM 1:6 ( 1 cement :6 coarse sand) etc complete<br> |
| 38 | 6.5 : Extra for brick work/ AAC block masonry/Tile brick masonry in super structure above floor V level, for each four floors or part thereof by mechanical means. |
| 39 | 50.6.3.2 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x10 cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level for 10 cm thick wall in: CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding complete |
| 40 | od267552/2020_2021 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x10cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor V level for 10cm thick wall in: CM 1:6 ( 1 cement: 6 coarse sand) including cost of scaffolding complete. |
| 41 | od268635/2020_2021 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x10cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor V level for 10cm thick wall in: CM 1:6 ( 1 cement: 6 coarse sand) including cost of scaffolding complete.<br> |
| 42 | 6.47 : Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm thick AAC blocks in super structure above plinth level up to floor Vlevel with RCC band at sill level and lintel level with approved block laying polymermodified adhesive mortar all complete as per direction of Engineer-in-Charge. (Thepayment of RCC band and reinforcement shall be made for seperately). |
| 43 | od251268/2020_2021 : Providing and fixing GI hexagonal chicken wire mesh of 22 gauge at the junction of dissimilar surfaces of brick/AAC/block masonry wall and RCC column, beams and the like including overlaps wherever required and necessary nails for fixing etc. complete all as per specification and direction of engineer-in-charge for all floors at all heights. (Measurement shall be in running metres of 30 cm width)<br> |
| 44 | 13.2.1 : 15 mm cement plaster on the rough side of single or halfbrick wall of mix:1:4 (1 cement :4 fine sand) |
| 45 | 13.4.1 : 12 mm cement plaster of mix:1:4 ( 1 cement : 4 coarse sand) |
| 46 | 13.22 : Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof. |
| 47 | od251288/2020_2021 : Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.<br>13 to 16m<br> |
| 48 | od251312/2020_2021 : Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.<br>16 to 19m<br> |
| 49 | od251314/2020_2021 : Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.<br>19 to 22m<br> |
| 50 | 13.16.1 : 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand) |
| 51 | 5.30 : Add for plaster drip course / groove in plastered surface or moulding to R.C.C. projections. |
| 52 | 22.5 : Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 53 | 7.38.1.1 : Stone tile work for wall lining upto 10 m height with special adhesive over 12mm thick bed of cement mortar 1:3 (1 cement :3 coarse sand), including pointing in white cement with an admixture of pigment to match the stone shade.8 mm thick (mirror polished and machine cut edge)Granite stone of any colour and shade |
| 54 | 8.2.2.2 : Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm |
| 55 | 8.3.2 : Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer -in-Charge.Granite work |
| 56 | 8.5 : Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc.including moulding, rubbing and polishing of cut edges etc. complete. |
| 57 | 11.56.1 : Providing and laying Polished Granite stone flooring in required design andpatterns, in linear as well as curvilinear portions of the building all complete asper the architectural drawings with 18 mm thick stone slab over 20 mm (average)thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed withcement slurry and pointing with white cement slurry admixed with pigment ofmatching shade including rubbing , curing and polishing etc. all complete asspecified and as directed by the Engineer-in-Charge.Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. |
| 58 | 11.3.1 : Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate)finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete.40 mm thick with 20 mm nominal size stone aggregate |
| 59 | 8.31 : Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622(thickness to be specified by the manufacturer), of approved make, in all colours,shades except burgundy, bottle green, black of any size as approved by Engineerin-Charge,in skirting, risers of steps and dados, over 12 mm thick bed of cementmortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @3.3kg per sqm, including pointing in white cement mixed with pigment of matchingshade complete. |
| 60 | 11.40 : Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer) of Ist quality conforming to IS: 15622 of approved make in all colours, shades, except white, Ivory, Grey Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigments etc., complete. |
| 61 | 11.41.2 : Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm. |
| 62 | od251859/2020_2021 : Providing and laying Matt finished vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.<br>Size of Tile 600 x 600 mm. |
| 63 | 11.46.2 : Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, ofapproved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm |
| 64 | 9.1.1 : Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately).Second class teak wood |
| 65 | 13.114 : Melamine polishing on wood work (one or more coat). |
| 66 | 9.21.2 : Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non- decorative Type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 67 | 13.62.1 : Painting with synthetic enamel paint of approved brand and manufacture of required colour to givean even shade:Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture . |
| 68 | 9.53 : Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 69 | 21.17 : Providing and fixing anodised aluminium grill ( anodised transparent or dyed to required shade according to IS : 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P brass/stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge.(Only weight of grill to be measured for payment ). |
| 70 | 9.88 : Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete. |
| 71 | 9.97.2 : Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:250x10 mm |
| 72 | 9.100.1 : Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm |
| 73 | 9.101.2 : Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper |
| 74 | 9.117.1 : Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1 mm), with wall thickness 2.0mm (±0.2 mm), corners of the door frame to be jointed with galvanized brackets and stainless steel screws, joints mitred and plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size19 x 19 mm and 1 mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer\"s specification and direction of Engineer-in-chargeExtruded section profile size 48x40 mm |
| 75 | 9.118.2 : Providing and fixing to existing door frames30 mm thick factory made Polyvinyl Chloride (PVC) door shutter made of styles and rails of a uPVC hollow section of size 60x30 mm and wall thickness 2 mm (± 0.2 mm), with inbuilt decorative moulding edging on one side.The styles and rails mitred and joint at the corners by means of M.S. galvanised/plastic brackets of size 75x220 mm having wall thickness 1.0 mm and stainless steel screws.The styles of the shutter reinforced by inserting galvanised M.S. tube of size 25x20 mm and 1 mm (± 0.1 mm) wall thickness. The lock rail made up of \"H\" section, a uPVC hollow section of size 100x30 mm and 2 mm (± 0.2 mm) wall thickness fixed to the shutter styles by means of plastic/galvanised M.S. \"U\" cleats. The shutter frame filled with a uPVC multi-chambered single panel of size not less than 620 mm, having over all thickness of 20 mm and 1 mm (± 0.1 mm) wall thickness. The panels filled vertically and tie bar at two places by inserting horizontally 6 mm galvanised M.S. rod and fastened with nuts and washers, complete as per manufacturer\"s specification and direction of Engineer-in-charge. |
| 76 | 9.147A.1 : Providing and fixing factory made uPVC white colour casement/casement cumfixedglazedwindowscomprisingofuPVCmulti-chamberedframe,sashandmullion(whereeverrequired)extrudedprofilesdulyreinforcedwith1.60+/-0.2mm thick galvanized mild steel section made from roll forming process of requiredlength (shape & size according to uPVC profile), uPVC extruded glazing beads ofappropriatedimension,EPDMgasket,stainlesssteel(SS304grade)frictionhinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8mmsizeforfixingframetofinishedwall,plasticpackers,plasticcapsandnecessary stainless steel screws etc. Profile of frame & sash shall be mitred cutand fusion welded at all corners, mullion (if required) shall be also fusion weldedincluding drilling of holes for fixing hardware\"s and drainage of water etc. Afterfixing frame the gap between frame and adjacent finished wall shall be filled withweather proof silicon sealant over backer rod of required size and of approvedquality, all complete as per approved drawing & direction of Engineer-in-Charge.(Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profilesminus 5% tolerancein dimension i.e. in depth & width of profile shall be acceptable.Casement window single panel with S.S. friction hinges (300 x 19 x 1.9 mm), made of(small series) frame 47 x 50 mm & sash 47 x 68 mm both having wall thickness of1.9 +/- 0.2 mm andsingle glass pane glazing beadof appropriate dimension. (Area ofwindow upto 0.75 sqm.) |
| 77 | 9.147A.3 : Providing and fixing factory made uPVC white colour casement/casement cumfixedglazedwindowscomprisingofuPVCmulti-chamberedframe,sashandmullion(whereeverrequired)extrudedprofilesdulyreinforcedwith1.60+/-0.2mm thick galvanized mild steel section made from roll forming process of requiredlength (shape & size according to uPVC profile), uPVC extruded glazing beads ofappropriatedimension,EPDMgasket,stainlesssteel(SS304grade)frictionhinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8mmsizeforfixingframetofinishedwall,plasticpackers,plasticcapsandnecessary stainless steel screws etc. Profile of frame & sash shall be mitred cutand fusion welded at all corners, mullion (if required) shall be also fusion weldedincluding drilling of holes for fixing hardware\"s and drainage of water etc. Afterfixing frame the gap between frame and adjacent finished wall shall be filled withweather proof silicon sealant over backer rod of required size and of approvedquality, all complete as per approved drawing & direction of Engineer-in-Charge.(Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profilesminus 5% tolerancein dimension i.e. in depth & width of profile shall be acceptable.Casement window double panels with top fixed with S.S. friction hinges (350 x19x1.9mm)madeof(smallseries)frame47x50mm,sash47x68mm&mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazingbead of appropriate dimension. ( Area of window upto 2.50 sqm). |
| 78 | 9.147D.5 : Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware\"s and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately)Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Three track three panels sliding window made of (big series) frame 116 x 45 mm& sash 46 x 62 mm both having wall thickness of 2.3 +/- 0.2 mm and singleglazing bead / double glazing bead of appropriate dimension. (Area of windowabove 1.75 sqm) |
| 79 | od200291/2020_2021 : Providing and fixing of Metal Fire door fromISO 9001:2015 certified Manufacturer . The door must have been manufactured with galvanised - GI sheet of GPSP Grade as per IS 277. All Fire doors must satisfy the requirement of latest Fire & Life Safety guidelines for 120 minutes Fire Rating with its Stability & Integrity for 120 minutes. The door must also suffice the critrian of 20 minutes insulation as per NBC 2016 guidelines. The Prototype sample of the door must carry a prior test evidence as per IS 3614 part-2 / BS 476 Part 20 & 22 .The manufacturer must submit the copy of test evidence prior to start of production .The offered test certificate should either carries it's Validity or certificate must not be older than 5 years from CBRI / NABL Accreditated Lab i.e Spectro / International Lab i.e Exova / TBW etc . Recommended fire door must also be certified by a third party evaluation program from approved International agency like IFC and must carry a lable on all doors . All doors should be finished with Powder coating in desired regular RAL Shades.Door frame shall be Single rebate profile of section 100 x 57 mm made out of 1.20mm thick galvanised steel sheet with a factory pre-punched groove so as to accomodate Fire & smoke seal size 10x4mm . Frames should be butt jointed andfield assembled with bolting system for proper strength .Frames should be provided with back plate for anchor fasteners (payable extra ) for installation on a finished plastered wall opening. Door leaf should be minimum 46mm thick fully flush double skin door. Door leaf must be manufactured from 0.8mm (22 guage) thick galvanised steel sheet.Thedoor should be provided with reinforcement pads to receiving appropriate Hardwares of Becker Fire Solutions or Equivalent make. The Shutter shall be filled with proprietary infill material . For Double leaf doors; astragal has to be provided on meeting stile for both active and inactive leaf. Vision panels wherever required should be of 120 minutes fire rating and should be of non-wired type. Supply and fixing of Interlayered FR Glass of minimum 11 mm thickinterlayred , 120 minutes fireRated (EW120, EI 20 minutes )Non Wired, ToughenedInterlayered Glass of approved makeand is to be fixed in between the glass beading by using ceramic fiberof size 300 mm x 600mm (Clear vision ) and the manufacturer should have tested the similar glass of similar size or bigger size . The Location of the Fr Glass will be as per the directions of Engineer-in-charge. Rate should include Supply & fixing of necessary hardwares- SS Ball Bearing Hinges of size 100 x 75 x 3mm ( 4 Nos per panel ), anchor fastners, door closers, Panic Bar single / doubleleaf panic exit devices, Panic Trim, Mortise Dead Lock, SS D Type Offset Pull Handle of size 300x22mm, Stainless Steel 304 grade 300mm Long Concealed Flush Bolt of aproved make.<br>Hollow Metal fire doors 2 hrs Rated - 1300x2200 Double Leaf (Firestair door)<br><br><br> |
| 80 | 21.1.1.2 : Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 81 | 21.1.2.2 : For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 82 | 21.2.2 : Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides |
| 83 | 21.3.2 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness |
| 84 | 21.3.3 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 8 mm thickness |
| 85 | od181199/2021_2022 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):<br>With toughened glass panes of 6 mm thickness |
| 86 | od181308/2021_2022 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):<br>With toughened glass panes of 8 mm thickness |
| 87 | 21.4.2 : Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With brass cover plate minimum 1.25 mm thickness |
| 88 | od251658/2020_2021 : Filling the gap in between aluminium frame/UPVC & adjacent RCC/ Brick/ Stonework by providing weather silicon sealant over backer rod of approved qualityas per architectural drawings and direction of Engineer-in-charge complete.<br> |
| 89 | 21.13 : Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete |
| 90 | 10.16.1 : Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes |
| 91 | 10.18 : Providing and fixing circular / hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners.Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing . |
| 92 | 10.28 : Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) |
| 93 | 12.52.3 : Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main \"T\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross \"T\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \"T\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \"T\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \"T\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.12.5 mm thick square edge PVC Laminated Gypsum Tile size 595x595 mm made of Gypsum plasterboard , manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16 mm thick fire retardant PVC film on the face side and 12 micron metalized polyster on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyster film so as to make the tile a completely sealed unit. |
| 94 | 13.80 : Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 95 | 13.43.1 : Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer |
| 96 | 13.60.1 : Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 97 | 13.46.1 : Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 98 | 13.61.1 : Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 99 | 5.12 : Providing, hoisting and fixing up to floor level precast reinforced cement concrete work in string courses, bands, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but excluding cost of reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone - III) : 3 graded stone aggregate 20 mm nominal size) |
| 100 | od109906/2019_2020 : Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement.12 mm cement plaster including providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers. |
| 101 | od109912/2019_2020 : Providing and fixing C.I. M.H.cover with frame 500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg<br> |
| 102 | od268663/2020_2021 : Providing and fixing C.I. M.H.cover with frame (Heavy duty) 560 mm diameter,total weight of cover and frame to be not less than 208 kg (weight of cover 108 kg and weight of frame 100 kg). <br> |
| 103 | 19.16 : Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steeel barconforming to IS:1786, having minimum cross section as 23 mm x 25 mm and over allminimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufactures permanent identification mark to be visible even after fixing including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1cement: 3 coarse sand: 6 graded stone aggregate 20 mm nominal size)Complete as per design |
| 104 | 22.14.1 : Grading roof for water proofing treatment with:Cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 105 | 22.23.2 : Providing and applying integral crystalline slurry of hydrophilic in nature forwaterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 partsintegral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 partsintegral crystalline slurry : 1 part water) for horizontal surfaces and applying thesame from negative (internal) side with the help of synthetic fiber brush. The materialshall meet the requirements as specified in ACI-212-3R-2010 i.e by reducingpermeability of concrete by more than 90% compared with control concrete as perDIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystallineslurry shall be capable of self-healing of cracks up to a width of 0.50mm. The workshall be carried out all complete as per specification and the direction of the engineerin-charge. The product performance shall carry guarantee for 10 years against anyleakage.For horizontal surface one coat @1.10 kg per sqm. |
| 106 | 22.22 : Providing and mixing integral crystalline admixture for waterproofing treatment toRCC structures like basement raft, retaining walls, reservior, sewage & watertreatment plant, tunnels / subway and bridge deck etc.. at the time of transportingof concrete into the drum of the ready-mix truck , using integral crystalline [email protected]% (minimum) to the weight of cement content per cubic meter of concrete)or higher as recommended by the manufacturer\"s specification in reinforced cementconcrete at site of work. The material shall meet the requirements as specified inACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90%,compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostaticpressure. The crystalline admixture shall be capable of self-healing of cracks up toa width of 0.50mm. The work shall be carried out all complete as per specificationand the direction of the Engineer-in-charge. The product performance shall carryguarantee for 10 years against any leakage. |
| 107 | SUB TOTAL PART 1- MAIN BUILDING |
| 108 | EXTERNAL DEVELOPMENT |
| 109 | 2.31 : Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared |
| 110 | 2.6.1 : Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil |
| 111 | 2.26.1 : Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil |
| 112 | 2.8.1 : Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil |
| 113 | 2.25 : Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 114 | 50.2.26.1 : Filling with contractor own earth (excluding rock) in open areas in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge. |
| 115 | od110086/2019_2020 : Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete,improve workability without impairing strength and durability as per direction of the Engineer - in -charge. (Note:Minimum Cement content considered in this item is @ 330 kg/cum.)<br>All work upto plinth level |
| 116 | od110087/2019_2020 : Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete,improve workability without impairing strength and durability as per direction of the Engineer - in -charge. (Note: Minimum Cement content considered in this item is @ 330 kg/cum).<br>All work above plinth level upto floor V level |
| 117 | 4.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size) |
| 118 | 4.2.3 : Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc. up to floor five level, excluding the cost of centering, shuttering and finishing:1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 119 | 5.12 : Providing, hoisting and fixing up to floor level precast reinforced cement concrete work in string courses, bands, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but excluding cost of reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone - III) : 3 graded stone aggregate 20 mm nominal size) |
| 120 | 5.9.1 : Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete |
| 121 | 5.9.2 : Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 122 | 5.9.6 : Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 123 | 5.22.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more |
| 124 | 50.6.1.2 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete. |
| 125 | 7.1.1 : Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 126 | 13.2.1 : 15 mm cement plaster on the rough side of single or halfbrick wall of mix:1:4 (1 cement :4 fine sand) |
| 127 | 13.45.1 : Finishing walls with textured exterior pint of required shade:New work (Two or more coats applied @ 3.28 ltr/ 10 sqm ) over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm |
| 128 | 13.46.1 : Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 129 | 10.16.1 : Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes |
| 130 | 13.61.1 : Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 131 | 16.1 : Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc.and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres. |
| 132 | 16.78.1 : Construction of granular sub- base by Providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, Carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in- Charge.With Material conforming to Grade - I ( size range 75 mm to 0.075 mm) having CBR Value- 30 |
| 133 | 16.91.2 : Providing and laying factory made chamfered edge Cement Concrete paver blocksin footpath, parks, lawns, drive ways or light traffic parking etc, of required strength,thickness & size/ shape, made by table vibratory method using PU mould, laid inrequired colour & pattern over 50mm thick compacted bed of sand, compacting andproper embedding/laying of inter locking paver blocks into the sand bedding layerthrough vibratory compaction by using plate vibrator, filling the joints with sand andcutting of paver blocks as per required size and pattern, finishing and sweepingextra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern. |
| 134 | 16.69 : Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature jointed with cement mortar 1:3 ( 1 cement : 3 coarse sand) , including making joints with or without grooves ( thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge ( length of finished kerb edging shall be measured for payment ).( Precast C.C. kerb stone shall be approved by Engineer-in-Charge) |
| 135 | od207337/2020_2021 : "Supply & installation of vitrified external tile of size 24 x7.5 cm with thickness of 6 to 10mm laid with<br>proper adhesive leaving 3mm wide joints using spacers between individual tiles and filling the gaps with epoxy of suitable colur as per the direction of engineer in charge"<br> |
| 136 | 15.9.2 : Demolishing stone rubble masonry manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer -in- Charges:In cement mortar |
| 137 | od268934/2020_2021 : Demolishing brick work /block work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.<br>In cement mortar |
| 138 | SUB TOTAL PART 2- EXTERNAL DEVELOPMENT |
| 139 | PLUMBING WORKS |
| 140 | 17.3.1 : Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid |
| 141 | 17.7.2 : Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630 x 450 mm with a single 15 mm C.P. brass pillar tap |
| 142 | 17.10.2.1 : Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required:Kitchen sink without drain board610x510 mm bowl depth 200 mm |
| 143 | 18.21.2.1 : Providing and fixing uplasticised PVC connectionpipe with brass unions:45 cm length15 mmnominal bore |
| 144 | 17.69.2 : Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.Waste coupling 38 mm dia of 83 mm length and 77 mm breadth, weighing not less than 60 gms |
| 145 | 17.28.2.2 : Flexible pipe40 mm dia |
| 146 | 17.28.2.1 : Flexible pipe32 mm dia |
| 147 | 18.53.1 : Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore |
| 148 | od116558/2019_2020 : "Supply and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931.:<br>20 mm nominal bore. (Lowest retail price of concealed part 20mm not less than Rs 860/each and exposed part not less than Rs 560/each.)<br>Make: Cera , Jaquar, Parryware"<br> |
| 149 | 18.51.1 : Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore |
| 150 | od116568/2019_2020 : "Supply and fixing 15mm CP douche tap (Health faucetABS bodywith Wall hook and one metre chrome plated pvc hose pipe and CP brass angle valve) in position.(Lowest retail price of health faucet with wall hook and 1m chrome plated pvc hose pipe not less than Rs 745/each)<br>Make: Cera , Jaquar, Parryware"<br> |
| 151 | od116570/2019_2020 : "Supply and fixing sink cock with long swivel spout (table mounted) in position.(Lowest retail price ofsink cock not less than Rs 2000/each.)<br>Make: Cera , Jaquar, Parryware"<br> |
| 152 | od116571/2019_2020 : "Supplying and fixing C.P wall mounted shower arm and over head showerin position.(Lowest retail price of shower arm not less than Rs 575/each and shower not less than Rs 580/each.)<br>Make: Cera, Jaquar, Parryware"<br> |
| 153 | 18.8.1 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge.Concealed work, including cutting chases and making good the wall etc.15 mm nominal outer dia pipes |
| 154 | 18.8.2 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge.Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes |
| 155 | 18.8.3 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge.Concealed work, including cutting chases and making good the wall etc.25 mm nominal outer dia pipes |
| 156 | 18.7.1 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall15 mm nominal outer dia pipes |
| 157 | 18.7.2 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall20 mm nominal outer dia pipes |
| 158 | 18.7.3 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall25 mm nominal outer dia pipes |
| 159 | 18.7.4 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall32 mm nominal outer dia pipes |
| 160 | 18.7.5 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall40 mm nominal outer dia pipes |
| 161 | 18.7.6 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall50 mm nominal outer dia pipes |
| 162 | od116585/2019_2020 : "Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work/external work- Exposed on wall <br> Make: Supreme, Finolex, Astral"<br>65 mm nominal dia.Pipes (SCH 40 do - do) <br> |
| 163 | od116586/2019_2020 : "Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work/external work- Exposed on wall <br> Make: Supreme, Finolex, Astral"<br>80 mm nominal dia .Pipes (SCH 40 do - do)<br> |
| 164 | od116588/2019_2020 : "Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work/external work- Exposed on wall <br> Make: Supreme, Finolex, Astral"<br>100 mm nominal dia .Pipes (SCH 40 do - do)<br> |
| 165 | 18.9.3 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings.This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge.External work25 mm nominal outer dia pipes |
| 166 | 18.17.1A : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :20 mm nominal bore |
| 167 | 18.17.1 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore |
| 168 | 18.17.2 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :32 mm nominal bore |
| 169 | 18.17.3 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :40 mm nominal bore |
| 170 | 18.17.4 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :50 mm nominal bore |
| 171 | 18.17.5 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :65 mm nominal bore |
| 172 | 18.17.6 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :80 mm nominal bore |
| 173 | od116623/2019_2020 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :<br>100 mm nominal bore<br> |
| 174 | 18.19.5.2 : Providing and fixing gun metal non-return valve of approved quality (screwed end):65 mm nominal boreVertical |
| 175 | 18.32.1 : Constructing masonry chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for stop cock, with C.I. surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:With common burnt clay F.P.S (non modular) bricks of class designation 7.5 |
| 176 | 18.37.1 : Constructing masonry chamber 60x45x50 cm inside, in brick work in cement mortar 1:4 ( 1 cement : 4 coarse sand) for water meter complete with C.I double flap surface box 400x200x200 mm ( inside ) with locking arrangement and RCC top slab 1:2:4 mix ( 1 cement : 2 coarse sand : 4 grades stone aggregate 20 nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5fine sand : 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 ( 1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:With common burnt clay F.P.S. ( non modular ) bricks of class designation 7.5 |
| 177 | od116628/2019_2020 : "Supplying and fixing PVC Floor Trap 100mmx75mm size without Jali including cutting open, boring through RCC slabs and making good the damages.(Lowest retail price oftrap without jali not less than Rs 290/each)<br>Make: Supreme, finolex"<br> |
| 178 | od116637/2019_2020 : "Supplying and fixing SS grating of approved quality:Rectangular type with openable circular lid.150 mm nominal size square 100 mm diameter of the inner hinged round grating(Lowest retail price of grating not less than 230/each.)<br>Make: Viking"<br> |
| 179 | 18.76.1 : Cutting holes up to 30x30 cm in walls including making good the same:With common burnt clay F.P.S. ( non modular ) brick |
| 180 | 18.77 : Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof. |
| 181 | od116651/2019_2020 : "Supply and fixingSWR Type B sanitary concealed pipes and specials , jointing with solvent cement and fixing them on slabs, floors etc. in position for connecting various fixtures (including fixing of pipes in sleeves/ drilled holes before water proofing) and specials with brick or CC supports wherever necessary includingcutting and chasing brick walls as required, making good the same with brick in CM 1:6 and plastering with CM 1:4, 12mm thick one coat, sealing joints between pipe and concrete, complete.<br>Make: Supreme, Finolex"<br>110 mm diameter<br> |
| 182 | od116653/2019_2020 : "Supply and fixingSWR Type B sanitary concealed pipes and specials , jointing with solvent cement and fixing them on slabs, floors etc. in position for connecting various fixtures (including fixing of pipes in sleeves/ drilled holes before water proofing) and specials with brick or CC supports wherever necessary includingcutting and chasing brick walls as required, making good the same with brick in CM 1:6 and plastering with CM 1:4, 12mm thick one coat, sealing joints between pipe and concrete, complete.<br>Make: Supreme, Finolex"<br>75 mm diameter <br> |
| 183 | od116654/2019_2020 : "Supply and fixingSWR Type B sanitary concealed pipes and specials , jointing with solvent cement and fixing them on slabs, floors etc. in position for connecting various fixtures (including fixing of pipes in sleeves/ drilled holes before water proofing) and specials with brick or CC supports wherever necessary includingcutting and chasing brick walls as required, making good the same with brick in CM 1:6 and plastering with CM 1:4, 12mm thick one coat, sealing joints between pipe and concrete, complete.<br>Make: Supreme, Finolex"<br>50 mm diameter uPVC 10kgf -do -do<br> |
| 184 | od116658/2019_2020 : "Supply , jointing and fixingSWR type B Sanitary exposed pipes andspecials with good quality solvent cement and teflon tapeand fixing the same to line, plumb and level on the sides of ducts, walls, suspended to slabs as the case may be by using slotted rails , U clamps, 8mm threaded rods and other required materials including drilling holes,making good the walls, cleaning etc. and finishing complete.<br>Make: Supreme, Finolex"<br>110 mm diameter <br> |
| 185 | od116660/2019_2020 : "Supply , jointing and fixingSWR type B Sanitary exposed pipes andspecials with good quality solvent cement and teflon tapeand fixing the same to line, plumb and level on the sides of ducts, walls, suspended to slabs as the case may be by using slotted rails , U clamps, 8mm threaded rods and other required materials including drilling holes,making good the walls, cleaning etc. and finishing complete.<br>Make: Supreme, Finolex"<br>75 mm diameter<br> |
| 186 | od116662/2019_2020 : "Supply , jointing and fixingSWR type B Sanitary exposed pipes andspecials with good quality solvent cement and teflon tapeand fixing the same to line, plumb and level on the sides of ducts, walls, suspended to slabs as the case may be by using slotted rails , U clamps, 8mm threaded rods and other required materials including drilling holes,making good the walls, cleaning etc. and finishing complete.<br>Make: Supreme, Finolex"<br>50 mm diameter uPVC 10kgf - do - do<br> |
| 187 | od116666/2019_2020 : "Supply , jointing and fixingSWR type Aexposed pipes andspecials for vent with good quality solvent cement and teflon tapeand fixing the same to line, plumb and level on the sides of ducts, walls, suspended to slabs as the case may be by using slotted rails , U clamps, 8mm threaded rods and other required materials including drilling holes,making good the walls, cleaning etc. and finishing complete. (Antisyphonage pipes)<br>Make: Supreme, Finolex"<br>75 mm diameter<br> |
| 188 | od116673/2019_2020 : "Supply and Fixing PVC Ventilation Cowl with wired meshin position.<br>Make: Supreme, Finolex"<br>100 mm diameter(Lowest retail price of vent cowl not less than Rs 78/each.)<br> |
| 189 | od116675/2019_2020 : "Supply and Fixing PVC Ventilation Cowl with wired meshin position.<br>Make: Supreme, Finolex"<br>75 mm diameter(Lowest retail price of vent cowl not less than Rs 43/each.)<br> |
| 190 | od116678/2019_2020 : "Supply , jointing and fixingSWR type Aexposed pipes andspecials for Rain water with good quality solvent cement and teflon tapeand fixing the same to line, plumb and level on the sides of ducts, walls, suspended to slabs as the case may be by using slotted rails , U clamps, 8mm threaded rods and other required materials including drilling holes,making good the walls, cleaning etc. and finishing complete.<br>Make: Supreme, Finolex"<br>110 mm diameter<br> |
| 191 | od116682/2019_2020 : "Supply , jointing and fixingSWR type Aexposed pipes andspecials for Rain water with good quality solvent cement and teflon tapeand fixing the same to line, plumb and level on the sides of ducts, walls, suspended to slabs as the case may be by using slotted rails , U clamps, 8mm threaded rods and other required materials including drilling holes,making good the walls, cleaning etc. and finishing complete.<br>Make: Supreme, Finolex"<br>75mm diameter |
| 192 | 12.44 : Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 193 | od116686/2019_2020 : Constructing masonry shoe to the bottom of the rain water pipes with brick in cement mortar 1:6 over CC 1:4:8 using 40mm metal concrete, plastering the exposed surfaces using CM 1:5 one coat, forming the circular spout outlet, finishing etc. complete.<br> |
| 194 | od116687/2019_2020 : "Supply and fixing inline rain water filter with ss304 screen with 110mm inlet and 90mm drain outlet(Lowest retail price of rain water filter not less than Rs 5200/each)<br>Make: Rainy, Supreme"<br> |
| 195 | 19.4.1.1 : Providing and fixing square-mouth S.W. gully trap class SP -1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:100x100 mm size P typeWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 196 | 19.4.2.1 : 150x100 mm size P typeWithcommon burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 197 | od116747/2019_2020 : "Supply and Laying SWR Type B pipes, lowering into trenches, placing in position, aligning to line and levels and jointing with solvent cement including earth work excavation in all classes of soil, refilling the trenches and transporting excess soil as recommended by the site engineer, complete. (For sewer lines).<br>Make:- Supreme, Finolex"<br>110 mm diameter <br> |
| 198 | od116748/2019_2020 : "Supply and Laying SWR Type B pipes, lowering into trenches, placing in position, aligning to line and levels and jointing with solvent cement including earth work excavation in all classes of soil, refilling the trenches and transporting excess soil as recommended by the site engineer, complete. (For sewer lines).<br>Make:- Supreme, Finolex"<br>160 mm diameter <br> |
| 199 | od116756/2019_2020 : "Supply and Laying SWR Type B pipes, lowering into trenches, placing in position, aligning to line and levels and jointing with solvent cement including earth work excavation in all classes of soil, refilling the trenches and transporting excess soil as recommended by the site engineer, complete. (For sewer lines).<br>Make:- Supreme, Finolex"<br>200 mm diameter uPVC 4kgf <br> |
| 200 | od116761/2019_2020 : "Supply and Laying SWR Type B pipes, lowering into trenches, placing in position, aligning to line and levels and jointing with solvent cement including earth work excavation in all classes of soil, refilling the trenches and transporting excess soil as recommended by the site engineer, complete. (For sewer lines).<br>Make:- Supreme, Finolex"<br>250 mm diameter uPVC 4kgf <br> |
| 201 | 19.7.1.1 : Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size,) inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) finished with a floating coat of neat cement complete as per standard design:Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weigh of cover 23 kg and weight of frame 15 kg):With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 202 | 19.7.2.1 : Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size,) inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) finished with a floating coat of neat cement complete as per standard design:Inside size 120x90 cm and 90 cm deep including C.I. cover with frame ( medium duty ) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg ( weight of cover 58 kg and weight of frame 58 kg):With common burnt clay F.P.S ( non modular) bricks of class designation 7.5 |
| 203 | 19.8.1.1 : Extra for depth for manholesSize 90x80 cmWith common burnt clay F.P.S. ( non modular ) bricks of class designation 7.5 |
| 204 | 19.8.2.1 : Extra for depth for manholesSize 120x90 cmWith common burnt clay F.P.S. ( non modular ) bricks of class designation 7.5 |
| 205 | 19.16 : Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steeel barconforming to IS:1786, having minimum cross section as 23 mm x 25 mm and over allminimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufactures permanent identification mark to be visible even after fixing including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1cement: 3 coarse sand: 6 graded stone aggregate 20 mm nominal size)Complete as per design |
| 206 | od116774/2019_2020 : "Supply,Erection, Testing and Commissioning of open well submersible pump (Transfer pump) set capable of lifting 110 lpm of water against a total head of 37m with accessories such as non return valve, full way wheel valve, starter, MCB, voltmeter and ammeter, Indicating lamps, panel board forworking of pumps and dry run preventer etc.(approximately 2HP, filling time 1hour) (1 working and other standby for each block) (for Domestic water)(Lowest retail price of pump not less than Rs 18000/each and panel not less than 2500/each.)<br>Make:- Lubi, Kirloskar, Groundfos<br>"<br> |
| 207 | od116778/2019_2020 : "Supply,Erection, Testing and Commissioning of open well submersible pump (Transfer pump) set capable of lifting 80 lpm of water against a total head of 35m with accessories such as non return valve, full way wheel valve, starter, MCB, voltmeter and ammeter, Indicating lamps, panel boardforworking of pumps and dry run preventer etc.(approximately 1.5HP, filling time 45min) (1 workingfor each block) (for Rain water )(Lowest retail price of pump not less than Rs 15000/each and panel not less than 2500/each.)<br>Make:- Lubi, Kirloskar, Groundfos<br>"<br> |
| 208 | od116779/2019_2020 : "Supply,Erection, Testing and Commissioning of open well submersible pump (Transfer pump) set capable of lifting 80 lpm of water against a total head of 35m with accessories such as non return valve, full way wheel valve, starter, MCB, voltmeter and ammeter, Indicating lamps, panel boardforworking of pumps and dry run preventer etc.(approximately 1.5HP, filling time 45min) (1 working and other standby for each block) (for STP treated water )(Lowest retail price of pump not less than Rs 15000/each and panel not less than 2500/each.)<br>Make:- Lubi, Kirloskar, Groundfos<br>"<br> |
| 209 | od116780/2019_2020 : "Supply,Erection, Testing and Commissioning of open well submersible pump (Transfer pump) set capable of lifting 80 lpm of water against a total head of 35m with accessories such as non return valve, full way wheel valve, starter, MCB, voltmeter and ammeter, Indicating lamps, panel boardforworking of pumps and dry run preventer etc.(approximately 1.5HP, filling time 45min) (1 working and other standby for each block) (for Flushing water)(Lowest retail price of pump not less than Rs 15000/each and panel not less than 2500/each.)<br>Make:- Lubi, Kirloskar, Groundfos<br>"<br> |
| 210 | 18.9.6 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings.This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge.External work50 mm nominal outer dia pipes |
| 211 | 18.18.2 : Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:20 mm nominal bore |
| 212 | 19.32.1 : Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design.With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 213 | SUB TOTAL PART 3 - PLUMBING WORKS |
| 214 | ELECTRICAL WORKS |
| 215 | 1.10.3 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 216 | 1.11 : Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 217 | 1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 218 | 1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 219 | 1.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 220 | 1.14.4 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire |
| 221 | 1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 222 | 1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 223 | 1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm |
| 224 | 1.22.11 : Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.200 mm X 150 mm X 100 mm deep |
| 225 | 1.22.16 : Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.250 mm X 300 mm X 100 mm deep |
| 226 | 1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 227 | 1.26 : Supplying and fixing modular blanking plate on the existing modular plate & switch box excludingmodular plate as required. |
| 228 | 1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 229 | 1.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or inrecess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 ampsmodular switch, connection etc. as required. (For light plugs to be used in non residentialbuildings). |
| 230 | od215541/2021_2022 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.<br> |
| 231 | 1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden blockincluding connection etc as required. |
| 232 | 1.44 : Installation, testing and commissioning of ceiling fan, including wiring the down rods of standardlength (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc.as required. |
| 233 | 1.50.1 : Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 234 | 1.55.3 : Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 235 | 90.5.1.3 : Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell |
| 236 | 1.58 : Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 237 | 2.2.1 : Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required100 Amp, 16 KA, TPMCCB |
| 238 | 2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door |
| 239 | 2.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door |
| 240 | 2.4.4 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (4+12), Double door |
| 241 | 2.4.5 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)6 way (4+18), Double door |
| 242 | 2.4.6 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way (4+24), Double door |
| 243 | 2.5.4 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB\"s (butwithout MCB\"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (4+12), Double door |
| 244 | 2.5.5 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB\"s (butwithout MCB\"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 way (4 + 24), Double door |
| 245 | 2.5.6 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB\"s (butwithout MCB\"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 way (4 + 24), Double door |
| 246 | 2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 247 | 2.10.3 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole |
| 248 | 2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole |
| 249 | 2.10.5 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole and neutral |
| 250 | 2.11 : Supplying and fixing single pole blanking plate inthe existing MCB DB complete etc. as required. |
| 251 | 2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 252 | 2.12.2 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 253 | 2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 254 | 2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 255 | 2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 256 | 2.14.2 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 257 | 2.15.1 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 258 | 2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 259 | 2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 260 | 2.16 : Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 261 | 2.17 : Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32amps 415volts \"C\" curve TP MCB complete withconnections, testing and commissioning etc. as required. |
| 262 | 2.18 : Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top alongwith 20 amps \"C\" curve, SP, MCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 263 | 4.6.8 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 264 | 4.6.10 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450 mm width X 62.5 mm depth X 2.0 mm thicknessICDDescriptionUnit |
| 265 | 4.6.11 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 266 | 5.2 : Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providingmasonry enclosure with cover plate having locking arrangement and watering pipe etc. withcharcoal/ coke and salt as required |
| 267 | 5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 268 | 5.6 : Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 269 | 5.7 : Supplying and laying 6 SWG G.I. wire at 0.50metre below ground level for conductor earthelectrode, including connection/ termination with GI thimble etc. as required. |
| 270 | 5.8 : Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 271 | 5.9 : Supplying and laying 25 mm X 5 mm G.Istrip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 272 | 5.14 : Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 273 | 5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 274 | 5.18 : Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 275 | 5.19 : Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 276 | 5.20 : Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 277 | 7.1.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering andrefilling the trench etc as required.Upto 35 sq. mm |
| 278 | 7.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering andrefilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm |
| 279 | 7.1.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering andrefilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mm |
| 280 | 7.1.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering andrefilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm |
| 281 | 7.2.1 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size direct in ground in the same trench in one tier horizontal formationincluding excavation, sand cushioning, protective covering and refilling the trench etc asrequired.Upto 35 sq. mm |
| 282 | 7.2.2 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size direct in ground in the same trench in one tier horizontal formationincluding excavation, sand cushioning, protective covering and refilling the trench etc asrequired.Above 35 sq. mm and upto 95 sq. mm |
| 283 | 7.2.3 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size direct in ground in the same trench in one tier horizontal formationincluding excavation, sand cushioning, protective covering and refilling the trench etc asrequired.Above 95 sq. mm and upto 185 sq. mm |
| 284 | 7.2.4 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size direct in ground in the same trench in one tier horizontal formationincluding excavation, sand cushioning, protective covering and refilling the trench etc asrequired.Above 185 sq. mm and upto 400 sq. mm |
| 285 | 7.5.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm |
| 286 | 7.5.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Above 35 sq. mm and upto 95 sq. mm |
| 287 | 7.5.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Above 95 sq. mm and upto 185 sq. mm |
| 288 | 7.5.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Above 185 sq. mm and upto 400 sq. mm |
| 289 | 7.7.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 290 | 7.7.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 291 | 7.7.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 292 | 7.7.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 293 | 7.8.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 294 | 7.8.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 295 | 7.8.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on cable tray as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 296 | 7.8.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on cable tray as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 297 | 7.9 : Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand :4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X50 cm at the top with a thickness of 10cm including inscription duly engraved asrequired. |
| 298 | 8.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm |
| 299 | 8.3.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm |
| 300 | 8.4.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade offollowing size in the existing masonry open duct as required.Above 120 sq. mm and upto 400 sq. mm |
| 301 | 9.1.20 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm) |
| 302 | 9.1.21 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 303 | 9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 304 | 9.1.23 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm) |
| 305 | 9.1.25 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm) |
| 306 | 9.1.26 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm) |
| 307 | 9.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm) |
| 308 | 9.1.29 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm) |
| 309 | 9.1.31 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm) |
| 310 | 9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 311 | od274736/2019_2020 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.<br>4C x 6 sqmm <br> |
| 312 | 9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 313 | od275036/2019_2020 : Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :<br>150 sq. mm<br> |
| 314 | 14.13.1 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia |
| 315 | 14.13.3 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required100 mm dia |
| 316 | 14.13.4 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required150 mm dia |
| 317 | 14.14.1 : Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete withRCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.100 mm dia |
| 318 | 14.14.2 : Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete withRCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.150 mm dia |
| 319 | 14.14.4 : Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete withRCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.300 mm dia |
| 320 | od274877/2019_2020 : Supply and installing of structural steel work for exhaust pipe of DG set, support for cable tray, panels etc using structural steel (riveted, bolted or welded) in built up sections, including angle, channel, I section, necessary nut and bolt and all required accessories including cutting, hoisting, fixing in position and applying 2 coats of primer and 2 coats of enamel paint of approved quality etc as required. The design of the structural members shall be got approved before fabrication. <br> |
| 321 | 15.4.3 : Supplying, installation, testing and commissioning of Astronomical time switch capable of following output in feeder pillars/ Lighting DBs for automatic switching On &OFF of street lights at sun set & sun ruse or twilight override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete ad required3 output (1output per phase) and suitable for three phase supply |
| 322 | od273994/2019_2020 : Supply, erection, testing and commissioning of 630 kVA outdoor type unitised substation (USS),11 kV / 433 V, 3 phase, Vector DYn-11, Copper wound, resin cast transformer with off circuit tap changer from +5% to -10 % in steps of 2.5 %. The HV side shall be connected to HTSFU and LV cable box with 1000A, FP, 50kA, MCCB with Isolation duty, thermal magnetic release with OL, SC protection and suitable for connecting 4 runs 3.5C x 400sqmm XLPE Aluminium cable. The transformer shall be provided with O/C and E/F protection on HV side, winding temperature indicator and all other standard fittings and accessories conforming to IS 11171/85 and IS 2026 / 1975. The low set earth fault relay with neutral CT 200/5A, class 5P10, 10VA shall be provided.<br>All the equipments shall be mounted on a common galvanised GI base with fabricated enclosure painted with outdoor type rust proof paint / powder coated. The wall of the enclosure shall be detachable type with louvers for natural cooling The busbars inside the cubicle shall be sleeved using heat shrinkable sleeves. <br>The USS shall be provided with 11kV CT/PT unit with CT rating suitable as perKSEB, class 0.2S, 15VA CT, 11kV/110V, class 0.2, 100VA PT & TOD meter to be mounted in the USS. The metering chamber shall have locking arrangement, glass view panel, all accessories & control wiring as per the requirement of KSEB. <br>The HV side of the USS shall be provided with 11kV, 26.2kA, 630A, load break switch with earth switch. The HT HRC fuse, seal off bushing, 230V shunt trip coil, space heater with thermostat, Copper busbar with support insulator shall be provided. <br> |
| 323 | od273996/2019_2020 : HT CABLE<br>Supply of following 11kV (E) grade XLPE insulated PVC sheathed compact circular armoured aluminium conductor HT power cable, insulation screened with extruded semi conducting compound in combination with copper tape suitable for 11kV earthed system confirming to relavent standard. <br>3C x 150 sq.mm <br> |
| 324 | od274001/2019_2020 : DG SET<br>Supply, Installation, Testing and Commissioning of prime power rated 160 KVA, silent type, water cooled, radiator type, four stroke, electric start D.G Set with acoustic enclosure and standard control panel for housing necessary engine controls.. The engine shall be capable of taking 10% overload for one hour after 12 hours of continuous operation. The DG shall be suitable for AMF operation. The synchronous alternator shall be brushless, self excited, self regulated,SPDP enclosure, class F/H insulation, suitable for continuous duty operation at 1500 rpm, generating 415 V +/- 5% at 0.8 p.f, 50Hz, 0.85 load factor, 3 phase, 4 wire system generally conforming to BS: 2613 & IS: 4722. The DG set shall comply with latest norms for emmission & noise level. The low set earth fault relay with neutral CT 50/5A, class 5P10, 10VA shall be provided in the standard control panel. <br>The control panel shall be provided with all engine protection equipments, indications etc The DG set shall be suitable for AMF operation and include all necesaary control cabling from DG set to Control panel and Main LT panel for AMFoperation.The DG set shall have in-built diesel day tank with all necessary fuel piping, fittings etc.<br>Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as antiviberation pad, lead acid batteries (as specified by engine manufacturer) and engine driven battery charger along with leads, battery stand, fuel piping from fuel tank to Engine, electronic governor, Residential silencer, suitable size termination box for cables, external battery charger with float & boost charger etc as required. Rate shall be inclusive of all lift, lead charges. The work should be as per Electrical Inspectorate / Pollution control board norms. |
| 325 | od274003/2019_2020 : Supply & installation of exhaust gas piping of suitable diameter as per manufactures standard, welded black MS, B class pipe confirming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti- vibration mountings, insulation ofexhaust system with mineral wool / Rockwool, 50mm thick wire mesh & aluminum cladding etc. <br> |
| 326 | od274005/2019_2020 : Supply, Installation, Testing & Commissioning of DG panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. <br>Incomer<br>1 No. 250A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. <br>Busbar<br>1 Set of 250 A TPN busbars of high conductivity electrolytic quality aluminium conductor and suitable size earthing conductor through out the panel for its earthing. <br>Instruments<br>2A, C curve SP MCB - 1 set<br>RYB indication lamp, LED type - 1 set<br>On, Off, Trip indication lamp, LED type - 1 set <br>1 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWh, Acc class 1 and with necessary accessories.<br>250/5A 10VA class 1 resin cast CT - 1 set<br>Outgoing.<br>200A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL, protection - 1 no. <br>63A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL, protection - 5 nos. <br> |
| 327 | od274006/2019_2020 : Supply, Installation, Testing & Commissioning of Essential panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. <br>Incomer<br>200A, FP, 25kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 2 set. <br>200A, FP, AC3 duty Power Contactor with all required control accessories and electrical interlock - 2 set<br>Busbar<br>1 Set of 200 A TPN busbars of high conductivity electrolytic quality aluminium conductor and suitable size earthing conductor through out the panel for its earthing. <br>Instruments<br>2A, C curve SP MCB - 2 set<br>RYB indication lamp, LED type - 2 set<br>On, Off, Trip indication lamp, LED type - 2 set <br>2 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWh, Acc class 1 and with necessary accessories.<br>250/5A 10VA class 1 resin cast CT - 2 set<br>Microprocessor based AMF logic with EB sensing, protection for under / over voltage, reverse power, under/over frequency, unbalance, programmable start/stop timings, DG battery supervision, integral push button for DG stat/stop, DG breaker close/open, Auto/Manual/Off and Annunciator accept / reset. Programmable mainsrestoration, re-cooling timings, Micro-processor based Protection relays, 16 window LCD Annunciator for DG faults.shall be provided.<br>This item shall be including all neccesary control cables between LT panel, DG sets etc, including all necessary instruments, relays and accessories for the auto / manual, AMF logic for DG set. The panel shall be provided with 1 set 16 window solid state alarm annunciator with test, acknowledge, rest push buttom with hooter for indicating trip / alarm / fault status of Transformer & DG set.<br>Integrated microprocessor based AMF and auto load sharing relay shall be provided with outputs for voltage increase/decrease, Frequency increase / decrease, and programmable breaker closing time with load sharing. <br>Necessary control wiring shall be provided for isolating the capacitor panel with suitable time delay circuit during the starting of DG set and putting the capacitor panel back into operation after the stabilisation of load in DG set.<br>Outgoing.<br>125A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL, protection - 1 no. <br>100A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL, protection - 1 no. <br>63A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL, protection - 4 nos. <br> |
| 328 | od274035/2019_2020 : Supply, Installation, Testing & Commissioning of Main LT panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. <br>Incomer<br>1000A, FP, 50kA, thermal magnetic based ACB, manually drawout, electrically operated, motorised, with overload, short circuit and ground fault protection with shunt trip coil, U/V release etc - 1 no.<br>Busbar<br>1 Set of 1000 A TPN busbars of high conductivity electrolytic quality copper conductor and suitable size earthing conductor through out the panel for its earthing. <br>Instruments<br>2A, C curve SP MCB - 1 set<br>RYB indication lamp, LED type - 1 set<br>On, Off, Trip indication lamp, LED type - 1 set <br>(0-500)V voltmeter, Digital type - 1 set<br>(0-1000)A ammeter, Digital type - 3 nos<br>1 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWh, Acc class 1 and with necessary accessories.<br>1000/5A 10VA class 1 resin cast CT - 1 set<br>1000/5A 10VA class 1 resin cast CT for connection to APFC panel - 1 set<br>Outgoing.<br>500A, TP+NL, 35kA, MCCB with thermal magnetic release for adjustable OL, SC protection - 3 nos. <br>250A, TP+NL, 35kA, MCCB with thermal magnetic release for adjustable OL, SC protection - 2 nos. <br>200A, TP+NL, 35kA, MCCB with thermal magnetic release for adjustable OL, SC protection - 1 no. <br> |
| 329 | od274036/2019_2020 : Supply, Installation, Testing & Commissioning of 200kVAR APFC panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. Required nos of louvers and panel mounted cooling fan with auto/manual switch shall be provided. <br>Incomer<br>1 No. 500A, TP+NL, 35kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. <br>Busbar<br>1 Set of 500 Amp TPN busbars of high conductivity electrolytic quality Aluminium alloy and suitable size earthing conductor through out the panel for its earthing. <br>Instruments<br>1 No 3 phase Digital Multi function meter to read V, A, F, PF with Acc class 1.<br>1 Set of phase indicating lamps, LED type, RYB. <br>1 Set of 2A 10kA C curve SP control MCB <br>1 Set of 500/5A, Class 1.0, 10VA, Cast Resin CT for metering. <br>1 no. 8 stage APFC relay <br>6 set On, Off push button<br>7 set On, Off, Trip indication lamp, LED type<br>1 set Auto / manual selector switch.<br>Suitable type Timer circuit shall be provided for disconnecting the APFCpanel during the starting of DG set. The APFC panel shall be put into operation once the DG set load is stabilised. <br>Outgoing.<br>2 Nos 100A, FP, 16kA, MCCB with thermal magnetic release for adjustable OL protection.<br>3 Nos 63A, FP, 16kA, MCCB with thermal magnetic release for adjustable OL protection.<br>2 Nos 40A, FP, 16kA, MCCB with thermal magnetic release for adjustable OL protection.<br>2 Nos. 50 kVAR MPP heavy duty capacitor with capacitor duty contactor & 7% detuned harmonic filter copper wound.<br>3 Nos. 25 kVAR MPP heavy duty capacitor with capacitor duty contactor & 7% detuned harmonic filter copper wound.<br>1 No. 12.5 kVAR MPP heavy duty capacitor with capacitor duty contactor & 7% detuned harmonic filter copper wound. <br>1 No. 12.5 kVAR MPP heavy duty capacitor with 7% detuned harmonic filter copper wound directly connected.<br> |
| 330 | od274037/2019_2020 : Supply, Installation, Testing & Commissioning of LT panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. <br>Incomer<br>1 No. 500A, TP+NL, 35kA, MCCB with thermal magnetic release for adjustable OL & SC protection - 1 no. <br>Busbar<br>1 Set of 500 A TPN busbars of high conductivity electrolytic quality aluminium conductor and suitable size earthing conductor through out the panel for its earthing. <br>Instruments<br>2A, C curve SP MCB - 1 set<br>RYB indication lamp, LED type - 1 set<br>On, Off, Trip indication lamp, LED type - 1 set <br>1 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWh, Acc class 1 and with necessary accessories.<br>500/5A 10VA class 1 resin cast CT - 1 set<br>Outgoing.<br>100A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL protection - 8 nos. <br>63A, TP+NL, 25kA, MCCB with thermal magnetic release for adjustable OL protection - 1 no. <br> |
| 331 | od274038/2019_2020 : Supply, Installation, Testing & Commissioning of Lift panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. <br>Incomer<br>1 No. 100A, TP+NL, 16kA, MCCB with thermal magnetic release for adjustable OL protection - 1 no. <br>Busbar<br>1 Set of 100 A TPN busbars of high conductivity electrolytic quality aluminium conductor and suitable size earthing conductor through out the panel for its earthing. <br>Instruments<br>2A, C curve SP MCB - 1 set<br>RYB indication lamp, LED type - 1 set<br>On, Off, Trip indication lamp, LED type - 1 set <br>1 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWh, Acc class 1 and with necessary accessories.<br>100/5A 10VA class 1 resin cast CT - 1 set<br>Outgoing.<br>40A, TP+NL, 16kA, MCCB with thermal magnetic release for adjustable OL protection - 4 nos. <br> |
| 332 | od274039/2019_2020 : Supply, Installation, Testing & Commissioning of Common panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. <br>Incomer<br>1 No. 125A, TP+NL, 16kA, MCCB with thermal magnetic release for adjustable OL protection - 1 no. <br>Busbar<br>1 Set of 150 A TPN busbars of high conductivity electrolytic quality aluminium conductor and suitable size earthing conductor through out the panel for its earthing. <br>Instruments<br>2A, C curve SP MCB - 1 set<br>RYB indication lamp, LED type - 1 set<br>On, Off, Trip indication lamp, LED type - 1 set <br>1 set 3 phase Digital Multi function meter to read V, A, F, kW, PF, kWh, Acc class 1 and with necessary accessories.<br>125/5A 15VA class 1 resin cast CT - 1 set<br>Outgoing.<br>40A, TP+NL, 16kA, MCCB with thermal magnetic release for adjustable OL protection - 8 nos. <br> |
| 333 | od274040/2019_2020 : Supply, installing, testing and commissioing of following capacity circuit breaker in sheet steel enclosure for use on 3 phase 4 wire 415 volts, 50Hz AC complete with all necessary accessories including fixing connectors, spreaders, extended rotory handle, steel fasteners, connecting to earthing system etc. as required. <br>100A, TP+NL, 16kA, MCCB with thermal magnetic release for adjustable OLprotection.<br> |
| 334 | od274041/2019_2020 : 63A, TP+NL, 16kA, MCCB with thermal magnetic release for adjustable OLprotection.<br> |
| 335 | od274090/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 400 sq.mm<br> |
| 336 | od274091/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 240 sq.mm<br> |
| 337 | od274092/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 185 sq.mm<br> |
| 338 | od274093/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 150 sq.mm<br> |
| 339 | od274094/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 120 sq.mm<br> |
| 340 | od274095/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 70 sq.mm <br> |
| 341 | od274096/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 50 sq.mm <br> |
| 342 | od274097/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 35 sq.mm <br> |
| 343 | od274098/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>3.5C x 25 sq.mm <br> |
| 344 | od274099/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>4C x 16 sqmm<br> |
| 345 | od274100/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>4C x 10 sqmm<br> |
| 346 | od274101/2019_2020 : Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. <br>4C x 6 sqmm <br> |
| 347 | od78723/2021_2022 : Supply & installation of surface mounted, extruded aluminium housing, high efficiencytranslucence diffuser,20-24 W LED light fixture (4 feet), p.f ≥ 0.9, THD < 20%, 2kV surge protection, CCT ≥ 5700K, Efficacy ≥ 90 Lm/W, CRI ≥ 70 etc with all required accessories. (Wipro LL20-221-XXX-65NE3 / Crompton LCCLB24-CDL / Bajaj BCLSBAL 20W CW ).<br> |
| 348 | od274125/2019_2020 : Supply & installation of recess mounted downlight fixture, die cast aluminium body, PMMA / PC diffuser,15 W LED light fixture, p.f ≥ 0.9, THD < 20%, 2kV surge protection, CCT≥ 5700K, Efficacy ≥ 90 Lm/W, CRI ≥ 70 etc with all required accessories. (Wipro LD80-131-XXX-60-XX / Crompton LCDN-15-CDL/TL/WW / Bajaj BPSLR 15W NW). |
| 349 | od78726/2021_2022 : Supply & installation of surface mounted downlight fixture, die cast aluminium housing, PMMA / PC diffuser, 15-18W LED light fixture, p.f ≥ 0.9, THD < 20%, 2kV surge protection, CCT≥ 5700K, Efficacy ≥ 75 Lm/W, CRI ≥ 70 etc with all required accessories. (Wipro LD80-131-XXX-60-SM / Crompton LCDSPLN-R-18W-CDL / Bajaj BGSLO SLEEK SURFACE 15 WH RD).<br> |
| 350 | od78727/2021_2022 : Supply & installation of surface mounted, die cast aluminium housing, frosted PMMA / PC diffuser,6 W LED round light fixture, 2kV surge protection, CCT ≥ 5700K, Efficacy ≥ 60 Lm/W, CRI ≥ 70 etc with all required accessories. (Wipro LD80-350-XXX-60-SM / Crompton LCDSPLN-R-06-CDL / Bajaj BGSLO SLEEK SURFACE 6 WH RD ).<br> |
| 351 | od78728/2021_2022 : Supply & installation of surface mounted, engineering plastic housing, PMMA / PC diffuser,9-10W LED light fixture (2 feet), p.f ≥ 0.9, THD < 20%, 2kV surge protection, CCT≥ 5700K, Efficacy ≥ 90 Lm/W, CRI ≥ 70 etc with all required accessories. (Wipro LL20-111-XXX-65-NE3 / Crompton LCTL-9-CDL / Bajaj BCLSB 10 NW).<br> |
| 352 | od78729/2021_2022 : Supply & installation of surface mounted, die cast aluminium with powder coated housing, uniform light distribution, outdoor application, 30-50 W LED flood light fixture with glass, p.f ≥ 0.9, THD <10%, 5kV surge protection, CCT ≥ 5000K, Efficacy ≥ 90 Lm/W, CRI ≥ 70 etc with all required accessories including mounting accessories. (Wipro LF19-471-060-57-XX / Crompton LFLE-50-CDL / Bajaj BJFL 30W LED).<br> |
| 353 | od78730/2021_2022 : Supply & fixing 7W LED lamp in the existing PVC batten / angle holder.<br> |
| 354 | od274131/2019_2020 : Supply, Installation, testing & commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) motor, class of insulation B, 3 nos blades, 30 cm long down rod, 2 nos canopies, shackle kit, safety rope, copper winding, power factor not less than 0.9, service value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 rpm (tolerance as per IS:374-2019) THD less than 10%, compactable with electronic regulator unit for speed control, temperature rise max 75 deg. C, insulation resistance more than 2 mega ohm, suitable for 230V, 50Hz, single phase AC supply, including all accessories complete as required. |
| 355 | od78743/2021_2022 : <br>Supply & installation of wall fan 400 mm sweep, 230V, 1Ph, plastic body and blades, pull cord for speed regulation, complete with all accessories as required. (Crompton High Flo LG / Khaitan Dezire / Orient Wall 43). <br> |
| 356 | od78744/2021_2022 : Supply & installation of 250 mm sweep, 1250-1280 rpm, rust proof body & blade, made with light weight PP material, automatic shutter, exhaust fan complete with all required accessories including mounting accessories. (Crompton Brisk Air / Khaitan vento / Orient Ventilator DX).<br> |
| 357 | od274134/2019_2020 : Supply of 300 mm sweep, 1325 - 1400 rpm, metal blade & bird guard, Epoxy powder coated, exhaust fan complete with all required accessories including mounting accessories. (Crompton Trans Air 300 / Khaitan Euro metal / Orient Air flow).<br> |
| 358 | od78786/2021_2022 : Supply & installation of Hot dipped Galvanised (internally and externally), seamless, octagonal pole of overall length 6M with single arm bracket of 1.0m length 48mm dia x 3.25mm thick with standard arm cap. The pole shall have inbuilt cable loop in loop out with flush door and locking facility. The bottom dia of the pole shall be 135mm and top 70mm with 3mm sheet thickness. The pole shall be with base plate of 225x225x16mm and 4nos required size of foundation bolt. The pole shall be mounted on suitable size foundation (design to be got approved) with baseplate arrangement and provided with 4A SP C curve MCB, loop in loop out terminals block, required dia GI / PVC pipe shall be provided in the foundation for taking cable in & out from the pole, 3Cx1.5sqmm unarmounred PVC insulated round copper cable from loop in loop out to light fixture etc with all required accessories.The cost of the civil foundation is not considered in this item.<br> |
| 359 | od78787/2021_2022 : Supply & installation of36-45 W LED street ligh luminaire, die cast aluminium with powder coated housing, outdoor application, uniform light distribution, p.f ≥ 0.95, THD <15%, 5kV surge protection, CCT 5700 K, Efficacy ≥ 100 Lm/W, CRI ≥ 70, integral electronic driver, stainless steel toggle etc as required. The light fitting shall be suitabily installed with all required accessories to the street light poles. (Crompton LSTP-45-CDL / Wipro LR02-501-XXX-57-XX / Bajaj BRTFG 45W LED WW)<br> |
| 360 | od78259/2021_2022 : "Providing and fixing Fully Solid Vertical Air terminals, Semi-hard (E-AlMgSiO5) with complete mounting accessories for the installation of 4 meter aluminium air terminal (16mm tapered to 10mm, with Interception tip at the top of air terminal)suitable for high wind load /wind stability as per IS/IEC -62305 part-3. <br>System consist of Fang Fix with base and clamp, Air terminal Joining Clip / fang fix clamp made of Stainless Steel SS 304, lightning tested for 100 kA 10/350 micro sec waveform, Stainless Steel Wall Clamp (rod holder), holder clamp and 16 kg stone of 365 mm diameter base support etc in accordance with IEC 62561. The no. of stones/wall clamps depending on wind load. Govt. Approved labs test certificate required for material approval.. "<br> |
| 361 | od78260/2021_2022 : "Providing & fixing of 8mm solid aluminium round conductor with complete accessories, necessary holders @ required interval as specified below:Meets the requirement of (IS / IEC 62305) : Semi-hard (E-AlMgSiO5) with minimum 50 sq.mm cross sectional area.The item shall also include Providing and fixing of Cross Universal Connector / T Connector / Folding Clamp / Clamping Shoe / Expansion Piece @every 20m for horizontal air termination / Connector : To route vertical down conductor / mesh formation made of Aluminium Ferrule using screw free joints. Folding Clamp / Clamping Shoe made of stainless steel SS 304/316 grade. All the connectors should conforms to the requirements accordingto (IS/IEC 62305). <br>"<br>Connectiion components to be lightning tested for 100kA 10/350 micro sec waveform / in accordance with IEC 62561. Joints should be crimp joints / minimum four bolt joint for cross & T joints only accepted. Govt. Approved labs test certificate required for material approval.<br>Conductor with Parapet Holder made of weather resistant plastic (nylon) / polyamide conductor holder @ every 0.5 meters. Weather and temperature resistant from -35 to +90 degree celsius tested (or tested for the temperature range on the extreme climatic condition of the region of installation). <br> |
| 362 | od78261/2021_2022 : Conductor with Down Conductor Holder made of weather resistant plastic (nylon) / polyamide conductor holder @ every 0.75 meters. Weather and temperature resistant from -35 to +90 degree celsius tested (or tested for the temperature range on the extreme climatic condition of the region of installation). <br> |
| 363 | od78262/2021_2022 : Conductor with Terrace Conductor Fibre Reinforce Concrete holder / polyamide roof cable holder for flat roof @ every 0.75 meters. The holder shall be closed form with bottom, filling weight 1kg (frost-resistant concrete), sleeve from polyethylene. <br> |
| 364 | od78263/2021_2022 : Providing and fixing of Stainless Steel Test Joint (high grade SS) with suitable outdoor enclosure (IP65/66): For 8mm dia solid round aluminium conductor & 10mm dia copper coated solid steel round conductor having 100 microns of copper bonding . Conforms to the requirements accordingto (IS/IEC 62305).The enclosure should be outdoor glass-fibre reinforced polycarbonate opaque having minimum inner dimension of 75mm x 75 mm x 50 mm. The test link has to be straight and needs minimum 4 mounting screws for strong joints. Inspection of bimetallic corrosion at site required. Seperation of 8mm Aluminium & 10mm Copper bonded steel is required for future inspection and contractor has to make sure both conductors should not touch eachg other to avoid bimetallic corrosion. Test joint to be lightning tested for 100kA 10/350 micro sec waveform in accordance with IEC 62561. Joint should be crimp joint / four bolt-screw joint only accepted. Govt. Approved labs test certificate required for material approval.<br> |
| 365 | od78264/2021_2022 : "Providing and laying copper coated steel solid round conductor 10mm diameter from earth electrode directly in ground (including excavation & refilling) as required. Copper coated steel, high corrosion resistant. Meets the requirement of (IS/IEC 62305) copper coating thickness of min. 100microns Should be tested and use exclusively for lightning protection earthing system and ring equipotential bonding. After test link needs to be routed inside Heavy duty conduit to avoid touch potential till ground level. Connection components to be in accordance with IS/IEC 62561 tested, connectors made of SS/ exothermic weld joints etc. All connection joints to be wrapped with petrolatum-coated chemical fibre (fabric having 1.1mm thick and 50mm width) or equivalent arrangement for better corrossion resistance. If using SS connectors minimum four bolt joint for cross & T joints only accepted. Govt. Approved labs test certificate required for material approval.<br>"<br> |
| 366 | od78265/2021_2022 : Providing and fixing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of min 3000mm length (10 feet), having a diameter of 20mm with copper bonding thickness of 250 microns as per UL 467.The Rod has to be either continuous or with self-coupling peg & bore arrangement with fault current withstand capability of 30 kA rms value for 1 second and I peak of 76 kA. The rod must be having corrosion test, peel off test for uniform coating, 180 degree bend test with out peeloff of copper bonding. Universal stainless steel with four bolt joint clamp or Exothermic welded clamp as per NBC 2016. For self coupling peg & bore arrangement rod needs Impact point on the bottom rod for easy insertion. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 Ωm. It should be free from hazardous substances. (TCLP certificate required).<br>The mineral / earth conductivity enhancing compound shall be required to have minimum 17.5 Kg / pit of the total composite, tested as per IEC-62561. The compound should be chemically inert and needs to submit approved labs test certificate. Concrete / FRP Heavy duty Earth electrode inspection chamber with heavy duty cover to ensure safety of earthing system. The dimension shall be min. 320mmx 320mmx 190mm. Govt. Approved labs test certificate required for material approval.<br> |
| 367 | od274289/2019_2020 : MISCELLANEOUS<br>Earthing with GI earth plate 1200 mm X 1200 mm X 12 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke as required.<br> |
| 368 | od274290/2019_2020 : Supply and laying 50 mm x 6 mm GI strip at 0.5m below ground as strip earth electrode, including connection / terminating with nut, bolt, spring, washer etc as required (Jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced 50mm). |
| 369 | od274291/2019_2020 : Providing and fixing 50 mm X 6 mm GI strip on surface or in recess for connections etc. as required.<br> |
| 370 | od274292/2019_2020 : Supplying and fixing FP sheet steel enclosure on surface/ recess along with 40 / 63 amps 415 volts "C" curve FP MCB complete with connections, testing and commissioning etc. as required.<br> |
| 371 | od274293/2019_2020 : Supplying and fixing 40A / 63A, TP / TPN / FP MCB, 415 Volts, "C" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc as required.<br> |
| 372 | od78840/2021_2022 : Supplying and fixing FP poly-carbonate enclosure (outdoor type), IP65, on surface/ recess along with 16/25/32amps 415 volts "C" curve FP MCB complete with connections, testing and commissioning etc. as required.<br> |
| 373 | od78841/2021_2022 : Supplying and fixing FP poly-carbonate enclosure (outdoor type), IP65, on surface/ recess along with 40/63amps 415 volts "C" curve FP MCB complete with connections, testing and commissioning etc. as required.<br> |
| 374 | od78842/2021_2022 : Supplying and fixing following ways surface / recess mounting vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder coated / painted. Inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar, provision for mounting MCCBs with 100 / 125 amps TP 16kA MCCB as incomer interconnection between incomer MCCB and busbar (but without MCBs/MCCB) as required. (Note vertical type MCB TPDB is normally used where 3 phase outlets are required). <br>4 way <br> |
| 375 | od78843/2021_2022 : 6 way <br> |
| 376 | od274298/2019_2020 : Supply, installation, testing & commissioing of SPN (1ph/1ph), 230V, Automatic source change over with current limiter (ACCL) with Mains 30A, Gen 1.5A, LEDs for indication of different operations in existing DB / enclosure on surface / recess mounted including connections, all accessories etc as required. |
| 377 | od274299/2019_2020 : Supply, installation, testing & commissioing of Single phase (5-40)A energymeter, class 1, installed in existing DB / enclosure on surface / recess mounted including connections, all accessories etc as required.<br> |
| 378 | od78850/2021_2022 : Supply and fixing extra down rod of GI pipe, 15 mm dia, heavy gauge including painting etc as required. <br> |
| 379 | od78851/2021_2022 : Supply and providing 2.5 mm thick & 1 m wideelectrical grade insulating mat to withstand 11 KV dielectric strength conforming to IS 15652/ 2006.<br> |
| 380 | od78852/2021_2022 : Supply and providing 2 mm thick & 1 m wideelectrical grade insulating mat to withstand 3.3 KV dielectric strength conforming to IS 15652/ 2006.<br> |
| 381 | od78853/2021_2022 : Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.<br> |
| 382 | od78854/2021_2022 : Supply and providing Electrical Main Single line Diagram (A1 size - colour print) duly framed, laminated and placed in a conspicuous location in the Electrical substation for clear vision.<br> |
| 383 | SUB TOTAL PART 4 - ELECTRICAL |
| 384 | CCTV SURVEILLANCE SYSTEM - IP TYPE |
| 385 | Supplying and fixing of 25 mm Medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 386 | Supply and drawing of UTP 4 pair Cat 6 LAN cable in the existing surface/recessed PVC conduit as required. |
| 387 | one run |
| 388 | Supplying and installing following size of perforated GI cable trays(galvanisation thickness not less than50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including bolts & nuts, required bends, tees, reducesetc as required. |
| 389 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 390 | NON DSR ITEMS |
| 391 | Supply, installation, testing and commissioning ofIP based IRVarifocal dome Camera, 1/3\" CMOS, 3 MP, 2.7–12 mm MFZ, night vision compatible,IR range of 40 mtrs PoE, inbuilt micro SD card,Ethernet port, H.264, IP 66, ONVIF, UL, FCC & CE certified. All mounting accessories shall be included |
| 392 | Supply, installation, testing and commissioning ofIP based IRbullet Camera, 1/3\" CMOS,3 MP,night vision compatible,IR range of 40 mtrs PoE,inbuilt micro SD card,Ethernet port, H.264, IP 66, ONVIF, UL, FCC & CE certified. All mounting accessories shall be included |
| 393 | Supply,installation, testing and commissioning of IP Network Video Recorders 16 channel with 16 ports, 2 SATA, audio 1 input 1 output, video 1 HDMI 1 VGA, recording resolution 5MP/3MP/1080P, 720P/ D1 @ 30 fps, network throughput 200 Mbps from IPC and 128 Mbps to Client, Smart search supported, Remote access by DDNS & P2P, 4 channel alarm input and 2 channel relay output, 2 USB ports, ONVIF, UL & CE certified. |
| 394 | Supply, installation, testing and commissioning ofL2 Management Switch - Core Switch |
| 395 | Supply, installation, testing and commissioning of 24 port- Edge PoE switch |
| 396 | Supply, installation, testing and commissioning of Patch Panel UTP Keystone- 24 Port- Fully loaded (Cat 5e,Cat 6 & Cat 6 A ) |
| 397 | Supply and installation of Cat 6 UTP patch cord, 1 mtr |
| 398 | Supply, installation, testing and commissioning of Server PC, Intel i7 processor, 24 inch LED monitor, Gigabit LAN port, USB port, 8GB DDR3 RAM,1TB HDD,1GB dual graphic card, 100/1000 LAN ports, optical mouse, Keyboard, DVD Writer. Genuine Win 8.1 Pro - Down grade to Win 7 professional, 24 inch LED monitor |
| 399 | Supply, installation, testing and commissioning of Surveillance/ ESATA compatible Hard Disk of 4TB capacity to achieve the total storage for the NVR server |
| 400 | Supply, Installation, Testing & Commissioning of 42 inch full HD LED monitor with resolution 1920X1080 pixel including wall mounting accessories (location: security room & central control room).Material shall be UL/CE listed |
| 401 | Supply and installation of wallmounted 9U rackincluding cable manager, power supply units etc.to accommodate ehternet switch and fiber patch panel at each floor |
| 402 | Supply and installation of wall mounted 22U rackincluding cable manager, power supply units etc.to accommodate NVR, ethernet switch patch panel etc in control rooom |
| 403 | SUB TOTAL PART 5 - CCTV SYSTEM |
| 404 | Fire Fighting System |
| 405 | od108161/2019_2020 : Supply, installation, testing and commissioning of terrace pump rated for 900lpm at 35 M head high efficiency volute type with cast iron casing coupled to a squirrel cage induction motor, totally enclosed fan cooled with supply condition 415 V, 3 phase, 50 HZ, foot mounted type rated for suitable12.5 HP at 2900 rpm with suitable starter (DOL/ Star Delta) and control panel for automatic and manual operation |
| 406 | od108198/2019_2020 : Providing and fixingin position the industrial type pressure gauges with gun metal/brass valve complete as required |
| 407 | od108199/2019_2020 : Supplying and applying thick readymade wrapping & coating 4mm thickmaterial over one coat of coal tar primer for underground pipes (100 mm dia) |
| 408 | od108222/2019_2020 : Providing and fixing forged brassball valve with forged brass ball suitable for operating pressure ofnot less than 16 kg / sq.cm of thefollowingsize.<br>50 mm dia |
| 409 | od108223/2019_2020 : Supplying, fixing, testing and commissioning of following BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specified.<br>100 mm dia |
| 410 | od108224/2019_2020 : Supplying, fixing, testing and commissioning of following NON - RETURN VALVE with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN16 pressure rating as specified.<br>100 mm dia |
| 411 | od108225/2019_2020 : ProvidingandfixingY Strainersuitable for operating pressure of 16 Kg / sqcm with SS 304perforatedsheetbasket includingrubber gasket, flanges, nuts, bolts and washers, complete as required.<br>100 mm dia |
| 412 | od108226/2019_2020 : Providing and fixing of spring loaded relief valve suitable for pressure of 16 Kg / sqcm including flanges nuts bolt and washer etc. complete as required.<br>25 mm |
| 413 | od108227/2019_2020 : Providing & fixing SS fire hydrant single landing valve with 80 mm NB. flanged inlet, brass spindle controlled 63 mm dia femaleinstantaneous outlet type. SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS standards with ISI mark. Includingfixing with anchor fastner and flanged tappingfromwet riser. |
| 414 | od108228/2019_2020 : Providing & fixing swinging type First Aid hose reel in red colour drum with 30 mts. long and 19 mm dia heavy duty thermoplastic water hose, globe valve stop cock, terminating with SS coupling & nozzle of 6mm outlet with shut off valve confirming to IS:12585 complete with MS socket for tap-off, drum and brackets (including painting) for fixing on wall with anchor fastner, bolts & nuts conforming to IS:884-1969 complete as required. |
| 415 | od108229/2019_2020 : Providing & fixing non-perlocating, rubber reinforced lined fire hose pipe (as per IS : 636, Type A) of 63 mm dia and length as described below. The hose shall be rated for brust pressure of 35.7 Kg/sqcm. Hose shall be complete with ISI marked brass male & female coupling (IS:903) bound & rivetted to hose pipe with copper rivets & 1.5 mm copper wire.<br>15 m length |
| 416 | od108230/2019_2020 : Providing and Fixing SS 63 mm dia instantaneous pattern branch short pipe, 20 mm dia nozzle conforming to IS standard, suitable for inter connection to hose pipe coupling complete as required. |
| 417 | od108231/2019_2020 : Supply, installation, testing and commissioning of weather proof hose cabinet having the size of 750x600x250mm made of 16gaugeMS Sheet with full front front glass door and locking arrangements suitable to accommodate 2 nos 15m long hose pipes and 1 No. branch pipe.The cabinet shall be painted to scarlet red color outside and white inside. |
| 418 | od108273/2019_2020 : Providing & fixing SS fire brigade connectionconsisting of 4 No. 63 mm dia instantaneous type male couplings with built-in check valves, 1 No. 100 mm dia sluice valve, (1 No. 100 mm dia non-return valve) and100 mm dia flanged outlet complete with bolts, nuts and rubber packings as required and as per IS standards |
| 419 | od108278/2019_2020 : Providing, laying, jointing and testing of following sizes of MS 'C' class pipes, heavy grade, conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia MS fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting / fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and then supply of the same shall also be included for rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted. Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow.<br>25 mm dia |
| 420 | od108279/2019_2020 : Providing, laying, jointing and testing of following sizes of MS 'C' class pipes, heavy grade, conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia MS fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting / fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and then supply of the same shall also be included for rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted. Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow.<br>32 mm dia |
| 421 | od108280/2019_2020 : Providing, laying, jointing and testing of following sizes of MS 'C' class pipes, heavy grade, conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia MS fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting / fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and then supply of the same shall also be included for rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted. Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow.<br>40 mm dia |
| 422 | od108281/2019_2020 : Providing, laying, jointing and testing of following sizes of MS 'C' class pipes, heavy grade, conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia MS fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting / fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and then supply of the same shall also be included for rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted. Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow.<br>50 mm dia |
| 423 | od108282/2019_2020 : Providing, laying, jointing and testing of following sizes of MS 'C' class pipes, heavy grade, conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia MS fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting / fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and then supply of the same shall also be included for rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted. Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow.<br>65 mm dia |
| 424 | od108283/2019_2020 : Providing, laying, jointing and testing of following sizes of MS 'C' class pipes, heavy grade, conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia MS fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting / fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and then supply of the same shall also be included for rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted. Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow.<br>80 mm dia |
| 425 | od108284/2019_2020 : Providing, laying, jointing and testing of following sizes of MS 'C' class pipes, heavy grade, conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia MS fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting / fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and then supply of the same shall also be included for rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted. Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow.<br>100 mm dia |
| 426 | od108331/2019_2020 : Supply, installation, testing and commissioning of electrically operated water flow switches (Vane type) including tamper switch and accessories, complete with tap off socket arrangement as required, withpotentialfreecontactwith 2 Nos. NONC. |
| 427 | od108332/2019_2020 : Providing & fixing brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows :<br>Supply, installation, testing and commissioning of approved make 15mm dia brass Sprinkler heads, quick response, designed to operate at 68 deg.Celsius etc. with necessery fittings etc of Pendant type |
| 428 | 2.10.1.2 : Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within alead of 50 m:Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia |
| 429 | Fire Extinguisher |
| 430 | od108337/2019_2020 : Supply, installation, testing and commissioning of following types of extinguisher with provision of wall bracket (fixed with anchor fastner) or floor mounted. ISI marked (IS:2878) Fire Extinguisher, Carbon-di-oxide type capacity 4.5 Kg. Flat base including valve, discharge hose of not less than 10 mm dia, 1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 filled to a filling rate of not more than 0.667 and wall suspension bracket. |
| 431 | od108338/2019_2020 : Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters “FIRE” in black and gold. Cost shall be inclusive of providing MS stand for 2 nos of fire buckes, or , duly painted over a coat of primer. |
| 432 | od108339/2019_2020 : Supply, installation, testing and commissioning of following types of extinguisher with provision of wall bracket (fixed with anchor fastner) or floor mounted. ABC (Powder Type) Fire Extinguisher. In HP Mild Steel Cylinders ISI markedfitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and confoming to IS:1349-1993. 4 kg |
| 433 | Fire Alarm |
| 434 | od108341/2019_2020 : Supply, installation, testing and commissioning of conventional Control Panel of 4 Zone complete with charger, rectifier, alarm display with all other necessary attachments with12 V 7 Ah battery |
| 435 | od108342/2019_2020 : Supply, installation, testing and commissioning of conventional manual call points, break glass type |
| 436 | od108343/2019_2020 : Supply, installation, testing and commissioning of conventional audio alarm hooters. |
| 437 | od108344/2019_2020 : Supply ,Installation, testing and commissioning of 2*1.5sqmm coper armoured FRLScable |
| 438 | Fire Signages |
| 439 | od108353/2019_2020 : Providing and installing in position the following type of sign boards made out of 3mm thick rigid PVC board with computer cut with texts written to recommended height in photolumiscentmaterialcompletevidetechnical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification. Providing and installing in position the Fire safety Plan to a recommended scale and at suggested locations. |
| 440 | od108354/2019_2020 : Providing and installing in position the following type of sign boards made out of 3mm thick rigid PVC board with computer cut with texts written to recommended height in photolumiscentmaterialcompletevidetechnical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification. Providing and fixing in position the signage's " FIRE ORDER"r on 3mm thick "Opaque" PVC foam board of computerized cut, PVC non-reflective self adhesive vinyl painted foam board of 750mm x 450mm. |
| 441 | od108355/2019_2020 : Providing and installing in position the following type of sign boards made out of 3mm thick rigid PVC board with computer cut with texts written to recommended height in photolumiscentmaterialcompletevidetechnical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification. Assembly point12"x12". |
| 442 | od108356/2019_2020 : Providing and installing in position the following type of sign boards made out of 3mm thick rigid PVC board with computer cut with texts written to recommended height in photolumiscentmaterialcompletevidetechnical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification. Life safety related signage's (EXIT, DIRECTION ARROWs i.e., left ,right ,straight ,down up, Both way, MCP etc )as per site condition. The size of the board shall be 10cm x 30 cm |
| 443 | od108360/2019_2020 : Providing and installing in position the following type of sign boards made out of 3mm thick rigid PVC board with computer cut with texts written to recommended height in photolumiscentmaterialcompletevidetechnical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification. Signage with printed"IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white back ground.The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished floor near Manual call points.Auto Glo |
| 444 | SUB TOTAL PART 6 - FIRE FIGHTING SYSTEM |
| 445 | Lift |
| 446 | od209274/2020_2021 : Supply, installation, testing & commissioning of electric traction type elevator of following capacities and type suitable for operation on 415 V, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency type traction control, machine room less, speed of 1.00 Mtr/sec, electromagnetic brake system, simple operations, operating control panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to EPABX, infrared ray sensing door protection for full height, reverse phase relayon controller, fireman’s switch at ground floor, <br>digital car positions indicator in car and at all positions indicator in car and at all floors with Up/DOWN direction, all signal fixtures in stainless stell faceplates, light fixtures, ventilation fan, etc complete with all accessories includingautomatic rescue device in the event of power failure etc., Complete with necessary scaffolding, electrical panel, logic control panel and shaft lighting etc required for the erection of the elevators as required.<br>Machine Room Less Type with the traction motor placed on top of the hoistway and elevator shall be of gearless type(suitable for lift well size 3000mm (D)X 1900m(W))complete as per technical specification, simplex full collective operation with/without attendant. Car/Hoistway Entrance, protected by stainless steel hairline doors and clear center /side opening min 800mm wide X 2000mm height. 15passengers (Minimum) hospital lift of capacity (minimum 1020 Kgs) Bed Lift , car size of 1000mm wide x2400mm deep x 2200mm Height Inside dimensions and entrance at front side on all the serving floors, provided with matt finish stainless steelpanel on all four sideand ceiling, stretcher protection on three sides complete as per specifications. <br>7stops &7openings ,Total travel height is approximately 24M<br> |
| 447 | od209290/2020_2021 : Supply, installation, testing & commissioning of electric traction type elevator of following capacities and type suitable for operation on 415 V, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency type traction control, machine room less, speed of 1.00 Mtr/sec, electromagnetic brake system, simple operations, operating control panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to EPABX, infrared ray sensing door protection for full height, reverse phase relayon controller, fireman’s switch at ground floor, <br>digital car positions indicator in car and at all positions indicator in car and at all floors with Up/DOWN direction, all signal fixtures in stainless stell faceplates, light fixtures, ventilation fan, etc complete with all accessories includingautomatic rescue device in the event of power failure etc., Complete with necessary scaffolding, electrical panel, logic control panel and shaft lighting etc required for the erection of the elevators as required.<br>Machine Room Less Type with the traction motor placed on top of the hoistway and elevator shall be of gearless type(suitable for lift well size 1900mm (D)X 1900m(W))complete as per technical specification, simplex full collective operation with/without attendant. Car/Hoistway Entrance, protected by stainless steel hairline doors and clear center /side opening min 700mm wide X 2000mm height. 8 passengers (Minimum) capacity (minimum 544Kgs) Passenger Lift , car size of 1300mm wide x1100mm deep x 2200mm Height Inside dimensions and entrance at front side on all the serving floors, provided with matt finish stainless steelpanel on all four sideand ceiling complete as per specifications. <br>7stops &7openings ,Total travel height is approximately 24M<br><br> |
| 448 | SUB TOTAL PART 7- LIFT |
| 449 | TOTAL AMOUNT |