Repair Replacement And Maintenance Of Lt Acb Ats Apfc Panel And Servo Stabilizers At Ins Valsura Jamnagar, jamnagar-Gujarat

Military Engineer Services-MES has published Repair Replacement And Maintenance Of Lt Acb Ats Apfc Panel And Servo Stabilizers At Ins Valsura Jamnagar. Submission Date for this Tender is 20-07-2022. Air Circuit Breaker Tenders in jamnagar Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

33015867
Repair Replacement And Maintenance Of Lt Acb Ats Apfc Panel And Servo Stabilizers At Ins Valsura Jamnagar
Open Tender
Indian
Gujarat
jamnagar
20-07-2022

Tender Details

Repair Replacement And Maintenance Of Lt Acb Ats Apfc Panel And Servo Stabilizers At Ins Valsura Jamnagar

Key Value

Document Fees
INR 500 /-
EMD
INR 58000.0 /-
Tender Value
INR 29 Lakhs /-

BOQ Items

Name of Work:REPAIR/ REPLACEMENT AND MAINTENANCE OF LT ACB, ATS, APFC PANEL AND SERVO STABILIZERS AT INS VALSURA, JAMNAGAR
Sl. No. Item Description
1M&L for Maintenance of Automatic transfer switch of rating up to 630 Amp of Make Havell"s/ Legrand/ L&Tat Valsura complete by taking the shut down with prior intimation and disconnecting incoming and out going connections, refixing the same after complete maintenance, replacement of fuses, tripping mechanism, tripping coils, pole assembly, control unit, auxillary switch, incoming and outgoing connections, replacement and M&L of overheated/ faulty portion of control circuit wiring as per above mentioned make as and when as directed by Engineer-in-Charge Note: (i) Spares required for repairing/ servicing of ATS will be measured and paid separately under relvant item of this BoQ. (ii) Fixing rate of the spares including testing is deemed tobe inclusive in quoted rate of thisitem.
2Supply only Closing Coil for ATS up to 630 Amp 4 pole suitable for automatic transfer switch. Make: Havells/ L&T
3Supply only Control unit up to 630Amp 4 pole suitable for automatic transfer switch. Make: Havells/ L&T
4Supply only Trip coil of assy ATS of rating upto 630 Amp suitable for automatic transfer switch. Make: Havells/ L&T
5Supply only Auxiliary switch of ATS of rating up to 630 Amp suitable for automatic transfer switch.Make: Havells/ L&T
6Supply only Pole assemblyfor ATS up to 200 Amp suitable for automatic transfer switch.Make: Havells/ L&T
7Supply only Pole assemblyfor ATS of rating 315 Amp suitable for automatic transfer switch.Make: Havells/ L&T
8Supply only pole assembly for 400 Amp ATS suitable for automatic transfer switch.Make: Havells/ L&T
9Supply only pole assembly for 630 Amp ATS suitable for automatic transfer switch.Make: Havells/ L&T
10M&L for servicing and repair to HT oil switchofsize up to 630 Amp complete by taking the shut down with prior intimation and opening the Oil chamber of HT switch gear and cleaning the contacts put the fuse in position and testing complete all as specified and as directed by EIC.
11M&L for replacement of HT HRC type fuse rating40/63 Amp of HT Oil switch complete by taking the shut down with prior intimation and opening the Oil chamber of HT switch gear and cleaning the contacts put the fuse in position and testing complete all as specified and as directed by EIC. Make: L&T/ Bussmann/ CG Lucy
12M&L for servicing of LT ACB of rating up to 630 Amp 415 Volt 50 Hz of any make at Valsura complete by taking the shut down with prior intimation and cleaning the ACB by using air blower tightening of connection of control circuit and complete checking of all fuses and control circuit for smooth functioning by employing one skilled tradesman as and when required including consisting of followings:- a) Checking the control circuit wiring and rectifying the same with newrewiring with proper size and color code if found required at site. b) Checking andfor replacing the components such as Shunt release, UV release,ammeter, voltmeter etc c) Resetting and testing.of relay setting for proper functioning
13S&F in repair copper bus bar of rating as per required at site, with supporting insulator duly fitted in PVC insulated sleeve in existing panel with requisite in shape and size required at site for fixing the bus bar at existing panel complete all as specified and directed by EIC.
14S&F in repair 1100 Volt flexible single core cables with tinned copper stranded conductor PVC insulated and sheathed including copper lugs at both sides of the ends and all accessories required as per the site requirement for cross-sectional area 240 Sqmm including testing on competion complete all as directed.
15All as per item No. 14 here in above, but cross-sectional area 185 Sqmm.
16All as per item No. 14 here in above, but cross-sectional area 16 Sqmm.
17All as per item No. 14 here in above, but cross-sectional area 10 Sqmm.
18All as per item No. 14 here in above, but cross-sectional area 2.5 Sqmm.
19Supply, laying, jointing, testing 3½ core, cross-sectional area 120Sq.mmXLPE,insulated outersheathed and innersheathed, galvanised steel armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, conforming to IS: 7098 (Part-I) of 1988 and laid in trenches, pipe, ducts, including taking down existing damaged UG cable complete all as specified.
20All as per item No. 19 here in above, but for 3½ core, cross-sectional area 50 Sq.mm
21Excavation in trenches not exceeding1.5 m wide and not exceeding 1.5 m in depth for foundation, laying of cables/ pipes etc and getting out in soft/ loose soil complete all as specified and directed.
22Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick with soils.
23Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point
24M&L river sand cushioning for cable protection in trenches 8 cm before laying cable and 15 cm deep over the cable. (Note: Thickness after punning shall be measured for payment)
25Taking down old existing PCC Cable Cover complete all as specified.
26Supply and laying un-reinforced precast concrete cable cover , class LV type flat size 250 mmx150mmx40 mm for protection of underground cable in trenches complete all as specified.
27Laying only oldPCC Cable Cover for protection of underground cable in trenches,obtained from taking down.
28Cutting of existing road for removing / laying UG Cables/ pipe line,depth of cutting not exceeding 60 cm and width 45 cm and filling the trench of road i.e. excluding top 15cms with existingaggregateobtained from cutting , watered and properlyrammed to satisfaction of EIC and finally provide150 mm thick PCC 1:3:6 type C1 using 20 mm graded crushed stone aggregate to entire width of trench & finally match the top surface to road & disposal of debris to a distance not exceeding 50 Mts and depositing where directed complete all as directed. (Note: Quoted rate is deemed to be inclusive of 150 m thick PCC 1:3:6, cutting any type of road and removal of debris).
29S&F 100 mm bore GI tubing light grade with necessary fittings such as bends, tees, elbows, etc in trenches, fixed on wall complete all as specified.
30M&L for CT"s of required ratio from 200/5 to 800/5 in replacement in existing feeder pillar box and connectterminals to APFC panel and testing on completion complete all as directed.
31S&F in repair Capacitor duty contactors, 3 pole, 230/415 V, 50 Hz of type MO C5 with auxiliary contacts for upto 5 kVAR rating complete all as directed. Make: C&S/ L&T
32All as per item No. 31 here in above, but upto 12.5 kVAR, MO C12.5.
33All as per item No. 31 here in above, but upto 15 kVAR, MO C15.
34All as per item No. 31 here in above, but upto 25 kVAR, MO C25.
35S&F in repair 6-stage APFC relay with built in P.F Meter. Make: C&S/ HPL/ L&T
36S&F in repair 8-stage APFC relay with built in P.F Meter. Make: C&S/ HPL/ L&T
37S&F in repair 3-position selector switch centre off for auto Manual operation. Make: C&S
38S&F in repair MCB SP 6 to 32 Amp, C curve.Make: Legrand/ ABB/ Havells
39S&F in repair MCB TP 20 to 32 Amp, 240 V, 50 Hz, AC Supply. Make: Legrand/ ABB/ Havells
40S&F in repair MCB TP 40 to 63Amp, 240 V, 50 Hz, AC Supply. Make: Legrand/ ABB/ Havells
41S&F in repair Power factor improvement Capacitor banks, Cylindrical type, 3 phase, 440 V,Heavy duty ofas per required at sitefrom 5 to 25 kVAR LTCCR super heavy duty type capacitor. Make: L&T or equivalent in EPCOS/ C&S
42S&F in repair R/Y/B phase Indicator lamps LED type. Make: Neptune/ L&T/ Vaisnavo
43S&F in repair power contactor ML 3 including necessary connections for incoming and outgoing connections. Make: L&T SS90721 or equivalent in C&S
44Disconnecting/ Taking out the existing Servo stabilizers transformer from site for repairing and transporting to workshop for servicing and repairing including loading unloading and handling to carry out the following repairs and refixing the same after repairing, installation, testing and commissioning at its original/ newlocation as ordered, decanting the transformer oil and checking of all parts for repair/ replacement of parts of cap from 100 to 300 kVA capacity of servo controlled stabilizers 440 V, 3 Phase, AC 50 Hz complete all as directed by Engineer-in-Charge. Note: (i) Spares required for replacement is measured and paid separately under respective items of BOQ (ii) Fixing rate of the spares including testing is deemed to be inclusive in quoted rate of this item.
45Disconnecting/ Taking out the existing Servo stabilizers transformer from site for repairing and transporting to workshop for servicing and repairing including loading unloading and handling to carry out the following repairs and refixing the same after repairing, installation, testing and commissioning at its original/ newlocation as ordered, decanting the transformer oil and checking of all parts for repair/ replacement of parts of cap from 15 to 30 kVA capacity of servo controlled stabilizers 440 V, 3 Phase, AC 50 Hz complete all as directed by Engineer-in-Charge. Note: (i) Spares required for replacement is measured and paid separately under respective items of BOQ (ii) Fixing rate of the spares including testing is deemed to be inclusive in quoted rate of this item.
46Supply only spares for BOQ item Nos. 45 & 46 as under:- (a) Control push buttons/ switches/ fuse carriers/ knobs etc
47(b) Rewinding of coils all as per its original specifications by copper conductor and with necessary insulation materials.
48(c) LT bushing with brass terminal, neoprene rubber gasket and washers etc complete.
49(d) Transformer oil up to standard level marking with new oil as per IS 335 having dielectric strength not less than 40 KV at 2.5 mm gap.
50(e) Servo control motor as per existing model for controlling the voltage.
51(f) Cork/ Neoprene rubber Gasket set complete.
52(g) PCB for Servo controlled voltage stabilizers as per existing model and make or equivalent model and make as approved.
53(g) Painting of Stabilizer body complete with two coat of Siemens gray paint with spray paint complete all as directed.
54(h) Filtration of transformer oil of the transformer at site by providing filtration machine at site.
55M&L for Earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead 32x6 mm GI strip means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected or indicated including testing on completion including necessary excavation, earth work, pcc pit, RCC cover, funnel with watering pipe 20mm bore medium grade, GI protection pipe 40 mm bore light grade and complete all as specified and as directed.
56S&F in repair MCCB thermal magnetic protection unit rating 630 Amp, 4 pole, 36 kA type DPX3 in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items andtaking down old item complete all as specified. Make:Legrand Cat Part No. 4220 09 or equivalent in ABB / Siemens.
57S&F in repair MCCB thermal magnetic protection unit rating 400 Amp, 4 pole, 36 kA type DPX3 in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items andtaking down old item complete all as specified. Make:Legrand Cat Part No. 4220 07 or equivalent in ABB / Siemens.
58S&F in repair MCCB thermal magnetic protection unit rating 160 Amp, 4 pole, 36 kA type DPX3 in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items andtaking down old item complete all as specified. Make:Legrand Cat Part No. 4200 97 or equivalent in ABB / Siemens.
59S&F in repair MCCB thermal magnetic protection unit rating 250 Amp, 4 pole, 36 kA type DPX3 in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make:Legrand Cat Part No. 4202 49 or equivalent in ABB / Siemens. Note for Sl item No. 56 to 59: Rate quoted deemed to included for taking down the existing MCCB from panel board and incoming / outgoing cable and fix the new MCCB / incoming / outgoing cable connections of any size/ rating in position at panel board.
60S&F AC, 3 Phase, LT/CT Multifunction DLMS compliance energy meter of accuracy class 0.5s, 3 x 240V, 50Hz with optical & RS232 Port, Backlit LCD Display, Measures & displays trivector energy, Load survey, TOD, Tamper detection & logging, Power On/Off events, instantaneous parameters of rating -/5A with display in absence of Power. Make: HPL Item code: TLPB2921131000OC00
61S&F AC 3 Phase static energy meter of accuracy class 1.0, 3 x 240V, 50Hz with Backlit LCD Display, of rating 10-60 Amp (Measures & Display kWh, V,I,Kw, PF, Hz, Last month history of kWh & MD in kW) with special features like TOD, Tamper logging, Optical communication port & Display in absence of Power, with Transparent Hinge Type Box. Make: HPL item code: TPPB1521130002ME01
62S&F in repair ATS 630 Amp cap, 4 pole complete all as specified and directed. Make: Havells IHYFCDO630 or equivalent in L&T/ ABB
63S&F in repair ATS 400 Amp cap, 4 pole complete all as specified and directed. Make: Havells IHYFCDO400 or equivalent in L&T/ ABB
64S&F in repair ATS 200 Amp cap, 4 pole complete all as specified and directed. Make: Havells IHYFCDO200 or equivalent in L&T/ ABB
65M&L in replacement for Multifunction meter of 96x96 mm size complete with digital display, LED showing Voltage, current, PF, Frequency model WL411010OOOO of make L&Telectrical parameters in replacement of existing meters. Make: L&T Model: Nova or equivalent in MECHO/ Rushabh
66M&L for air termination, single pointed aluminium rod 12mm dia and 450mm long
67M&L for aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground including taking down existing strip complete.
68M&L for galvanised iron strip 32 x 6mm buried in ground/ wall including taking down existing strip complete.
69S&F in repair Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex. head screw complete.
70M&L for precast PCC 1:3:6, type C1 (using 20mm graded granite stone aggregate) as in block masonry with solid blocks, exceeding 10cm in width and setting in CM 1:4 complete all as specified.
71M&L for porcelain insulator with two Nos of screws of size 40mm long fixed in PCC solid block for running the roof/ down conductor.
72S&F 32mm bore GI tubing light grade with necessary fitting and fixed to walls and ceilings or laid in floors complete all as specified.
73S&F in repair ACB 630 Amp, 4 pole, 50kA single frame drawout, mannual and Electrical Versions, including advanced self powered electronic protection units (Legrand Cat No. 0281 67) and shunt coil, close coil working on 220-250 V AC, Neutral Overload protecton OFF-50%-100% inbuilt temperature protection, Real terminals- vertical or horizontal connection with bars (Legrand Cat No. 0288 97), fast operation type DMX SP 2500 in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and ncluding necessary addition/ alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified and as directed. Make: Legrand Cat No 6695 42 or equivalent in L&T/ ABB/ Havells/ Siemens/ schnider
74Disconnecting electric connection for taking down existing High mast lighting system with light fittings for replacement with LED flood light fittings including electric motor for re-winding purposes, servicing & replacement of existing steel wire rop of suitable diameter and type complete. After repairing work, the High Mast system at the top of pole. Testing system for smooth functioning all as directed by Engineer-in-charge. NOTE: (i) Spares required for replacement is measured and paid separately under respective items of BOQ
75M&L for taking out burn out copper wire by cleaning the slots properly and Re-winding of coils all as per its original specifications by copper conductor and with necessary insulation materials ie varnishing, cotton tape, insulating paper,sleeves drying the winding with required temperature re-assembling the rotor complete all as directed by Engr-in-charge.
76S&F steel wire rope 8mm.
77Taking out existing Cable and S&F 3 core, 2.5 sqmm PVC insulated sheathed multistranded flexible copper conductor cable drawn through existing conduit pipe from junction box to fitting complete all as directed. Make: Havells / Finolex / Polycab
78S&F Astro digital time switch and suitable power contactor,mounting in existing High Mast pole, suitable for switching ON/ OFF light and other electric devices according to the rising/ setting of the sun with combination function for creating switching programs in which devices are switched according to astronomical time and/ or fixed preset times and also suitable for daily astronomical calculation of the sunrise/ sunset time based on the entered location or location coordinate complete all as directed. Make: Legrand Cat No. 4126 54 or equivalent in L&T / Siemens / Schneider / C&S
79S&F in repair 200 W LED flood lighting fittings with high pressure die cast housing with lens IP 65 protection, powder coated CCT(k) 6000, asymmetric fixing to existing bracket including nut bolts of suitable size and electrically connected to the existing system complete all as directed. Make: Jaquar LFLDSLM200XC or equivalent in Havells / Bajaj / Philips
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail