Urban Local Bodies has published Redevelopment Of Adarsh Nagar Faridabad Redevelopment Of Adarsh Nagar , Faridabad With Defect Liability Period Of Two Years And Including Maintenance For 5 Years Under Smart City Mission. Submission Date for this Tender is 28-07-2022. Civil Work Tenders in faridabad Haryana. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 21-Jul-2022 | Corrigendum | Date | 28-07-2022 |
Sl. No. | Item Description |
1 | PART-A--Dismantling work |
2 | Diversion of water flow and desilting and taking out of debris/silt rubbish etc. from Open Drain by Poklain and disposal of silt / malba at suitable place complete in all respect to the entire satisfaction of Engineer -in -charge. The cleaning / desilting shall be supported by date proof photographs at each location on daily basis inclusive of all material, labour, T&P including provision of safety equipment as per guideline laid in (IS-972*1987) International standard, traffic control arrangements and proper lighting at night, barricading, display of sign board, insurance of workers and cleaning of site by removal from all hindrances/obstructions, unforeseen items permission from other Deptt. Shall be arranged with assistance of FSCL. The rates are inclusive thecollection, removal, transportation and disposal of silt / malba to hazard free dumping ground complete in allrespect to the entire satisfaction of Engineer -in -ChargeCleaning of open drain of given below sized drains andaverage silt thickness 0.75 Mtr and aboveincluding thediversion of water flow with velocity @ 0.10 m/sec &discharge 0.06 m3/sec of open drains along the followingroads. |
3 | PART-B--Civil work |
4 | Providing and fixing of reinforced Ferro-Cement drain coversdesigned for "A" class loading duly marked on cover with adequatesteel reinforcement having thickness 75mm to 150mm anti corrosive bitumen painted M.S. plate , Rim and M.S. lifting hooks, Admixtureslike plasticizer, bond improving compound, shrinkage, resistancecompound, abrasion resistant complete as per approved design etc.Standard Size 1500x600mm (125mm thick) for span 701 to 1200mm |
5 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc |
6 | 25 mm dia. nominal bore |
7 | 50 mm dia. nominal bore |
8 | 3x4 feet Non- Magrnetic Double Sided whiteboard- chalkboard (Black Board) |
9 | Part- C LIGHTING PANEL |
10 | MAIN CUBICAL PANEL / STREET LIGHT CONTROL PANEL P/F testing & commissioning of kiosk type weather proof out door main cubical panel size 750 mm X 1250 mm X 500 mm (app.) made out of 14 gauge MS sheet front and back both side openable duly hinged door with locking arrangement by providing both side held draft and all required hard wares. The cubical should be dust and vermin proof followed by coat of zimpholite primer and finally two coats of enamal gray paint. The cubical should be mounted with hard ware on angle iron frame size 50 X 50 X 6 mm and 1500 legs duly painted framed be grouted 750 mm below ground level with cement concrete 1:3:6 in 1000 X 500 X 600 mm and providing brick masonary along angle iron frame above G.L. They shall be in two section comprising as follows: (i) Providing & Fixing 415 V ,TPMCCB 100 Amp. rating for incoming supply. (ii) Providing fixing timer switch TSQ 100 series 240 Volts, and full running service standred mounting with base of L & T or equivalent make including the cost of contactor 63 amp. 50 Hz. 440/400 volt. (iii) P/F open busbars 25mmX3mm of required length duly covered by heat shrinkable sleeves with busbar supporters (iv) Provision for residual current operated 63 Amp. 1 Pole ELCB of 30MA to 300 MA sensitively as required including making connections etc.(EE/Load stop make) (v) P/F 2 Nos. 415 Volts TPN MCCB,63 Amp. Rating for outgoing cable and making connection etc. also to have a provision for two nos. above switchs. (vi) P/F of 3 nos. RYB phase indicator resitance type complete with lamp P/F of HT danger plate of size 200 X 150 mm made of aluminium sheet 20 gauge. (vii) P/F cable glands double compression type and Al. lugs duly crimped for incoming cable and out going Cables. (viii) Providing 2 Nos. earth terminals including lugs and H/W duly inter connected with 8 SWG copper wire . (ix)Inter connection of main busbar to each out going switch and cable terminal shall be with 4 sqmm PVC copper conductor duly crimped with AL lugs. (x) Cable termination shall be fixed at backside of the panel with H/W and spring washers (xi) Light control switch with photo senser complete unit as required |
11 | Part D- LIGHT and Poles |
12 | P/ F IP-65/ IP-66 protected street light luminaries on existing bracket. Fixture made from powder coated single piece pressure die cast aluminum housing with heat dissipation fins on housing with high power LEDs . Diffuser / glass cover for ensuring IP-65 protection for lamp and control gear compartment, system lumen output of 100 lum/watt high power LED. Integrated driver shall be high efficiency having efficiency more than 85 % and in compliance to IEC standards. System life of 50000 burning hours with 70 % of initial lumens maintained. Fixture shall be in CE compliance, of suitable wattage to achieve desired lux |
13 | Supply, Erection and Fixing of hot dipped galvanised Overhang (60 X 3.25 mm) with cap (250 x 137.9 x 4.05 mm) over the existing poles Single arm overhang |
14 | Part E - EARTHING |
15 | Supplying and installation of maintenance free Earthing with all alied materials |
16 | GI strip 25*6 mtr 9 mtr for earthing wt 10.80kg (TATA/SAIL make) |
17 | Earth boaring |
18 | Erection of GI strip 25 X 6 mm, 9 Meter For earthing |
19 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
20 | Part F- CABLE AND OTHER ACCESSORIES |
21 | Supply ofLT XLPE Armoured 4 core, 16 sqmm AL cable |
22 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.-4 X 16 sq. mm (28mm) |
23 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL/HDPE pipe as required. Upto 35 sq. mm |
24 | Supply and erection of 3 core PVC copper insulated and sheathed circular flexible cable size 1.5sqmm |
25 | Supply and erection of copper lugs/thimble 1.5sqmm, including crimping etc upto the entire satisfaction of engineer in charge |
26 | P & F of M.S. J- hook of standard design made out of 16 mm dia. M.S. round bar and fixed with cement concrete mortar with required support as required. |
27 | Civil and Electrical work maintenance cost for 1 years |
28 | Civil and Electrical work maintenance cost for 2 years |
29 | Civil and Electrical work maintenance cost for 3 years |
30 | Civil and Electrical work maintenance cost for 4 years |
31 | Civil and Electrical work maintenance cost for 5 years |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy