Replacement Of Defective Light, Repair And Maint Of Lt Panel Board Metering Equipment, Switch Gears, Day To Day Maint Of 11 Kv Distribution Cables, Attending Complaint And Replacement Of Unsv Ug Cable Gallery Earthing, Earthing Strips All Allied Work, visakhapatnam-Andhra Pradesh

Military Engineer Services-MES has published Replacement Of Defective Light, Repair And Maint Of Lt Panel Board Metering Equipment, Switch Gears, Day To Day Maint Of 11 Kv Distribution Cables, Attending Complaint And Replacement Of Unsv Ug Cable Gallery Earthing, Earthing Strips All Allied Work. Submission Date for this Tender is 08-09-2022. Coats and Jackets Tenders in visakhapatnam Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

32965241
Corrigendum : Replacement Of Defective Light, Repair And Maint Of Lt Panel Board Metering Equipment, Switch Gears, Day To Day Maint Of 11 Kv Distribution Cables, Attending Complaint And Replacement Of Unsv Ug Cable Gallery Earthing, Earthing Strips All Allied Work
Open Tender
Indian
Andhra Pradesh
visakhapatnam
08-09-2022

Tender Details

Replacement Of Defective Light, Repair And Maint Of Lt Panel Board Metering Equipment, Switch Gears, Day To Day Maint Of 11 Kv Distribution Cables, Attending Complaint And Replacement Of Unsv Ug Cable Gallery Earthing, Earthing Strips All Allied Work Replacement Of Defective Light, Repair And Maint Of Lt Panel Board Metering Equipment, Switch Gears, Day To Day Maint Of 11 Kv Distribution Cables, Attending Complaint And Replacement Of Unsv Ug Cable Gallery Earthing, Earthing Strips All Allied Work-Servicing / Maintinance Ofmultiple Section Oflt Panel Board In One Substation Comprising Minimum Up To 05 Nos Acbs / Mccbs / Sdfs , Busbar Chamber, Swich Gear Chamber, Metering Chamber Cable Termination / Tray Chamber After Opening Front / Top / Side / Back Cover By Using Forced Air Pressure Andbrushes, Cleaning Of All Dust / Durt, Complete Cleaning Of Out Side Surface Of Panel Board Using Suitable Cleaning Agents, Tighting Of All Nuts & Bolts Of Busbar / Switchgear / Cable Terminals, Repair / Replacement To Defective Metering Wiring From Acb / Mccb / Ct To Meter And Replacement Of Defective Meters, Cts, Indicator Lamp, Metering Terminal Blocks, Mcb, Replacement Of Defective Aluminum Cable Lugs, Nuts-Bolts-Washers, Replacement Of Defective Panel Knob / Door Knob And Hinges Complete All As Specified And As Directednote:- ( I ) Panel Meter, Indicator Lamp, Mcb, Busbarand Ct Will Be Measured And Paid Seperately As Supply Only. ( Ii ) Required Aluminium Cable Lugs, Metering Cables And Nuts-Bolts-Washers Shall Be Inclusive Of Quoted Rate. ( Iii ) Servicing / Maintinance Of Acbs Measured Seperatelly. 2 All As Per Item No 1.00 Above But Comprisingacbs / Mccbs / Sdfs Up To Total 10 Nos 3 All As Per Item No 1.00 Above But Comprisingacbs / Mccbs / Sdfs Up To Total 15 Nos 4 All As Per Item No 1.00 Above But Comprisingacbs / Mccbs / Sdfs Up To Total 23 Nos 5 All As Per Item No 1.00 Above But Comprisingacbs / Mccbs / Sdfs Up To Total 28 Nos 6 Servicing, Repair, Maintinance Of Air Circuit Breaker 630 Amps To 3200 Amps Capacity By Drawing Out Movable Unit, Forced Air Cleaning Of Movable And Fixed Unit, Decarbonize Breaker Contracts And Checking For Any Defects Due To Any Flush / Loose Contact, Cleaning Of All Fixed And Moving Contact Point, Terminal Connection Points With Ctc, Replacement Of Defective Parts And Re-Fixing Acb, Cables Completes All As Specified And As Directed. Note: ( A ) Required Male / Female Acb Contacts, Trip Coils, Closing Coils, Electronic Protection Unitwill Be Measured As Supply Only. ( B ) All Cleaning Agents Are Included In The Quoted Rate. 7 Supply Only Fixed Contract Of Acb 630A To 3200Acomplete All As Specified And As Directed 8 Supply Only Moving Contract Of Acb 630A To 3200Acomplete All As Specified And As Directed 9 Supply Only Electronic Protection Unit Of Acb 630A To 3200Acomplete All As Specified And As Directed 10 Supply Only Shunt Trip Coil Of Acb 630A To 3200Acomplete All As Specified And As Directed 11 Supply Only Closing Coil Acb 630A To 3200A Complete All As Specified And As Directed 12 Supply Only Digital Electronic Ammeter ( 0-3200 Amps Range ) Withbuilt In Selector Switch Suitable For Lt 415 V Panel Flush Pattern Square Type 96 Mm X 96 Mm With Adopter Completeall As Specified And Directed. Cat Part No:- 30002385 ( Dm3110 ) Make:- Schneider Or Conserve / L&T / Hpl 13 Supply Only Digital Electronic Volt Meter ( 0-500 Volts Range ) Withbuilt In Selector Switch Suitable For Lt 415 V Panel Flush Pattern Square Type 96 Mm X 96 Mm With Adopter Completeall As Specified And Directed. Cat Part No:- 30002386 ( Dm3210 ) Make:- Schneider Or Conserve / L&T / Hpl 14 Supply Only Indication Lamps ( Led Type ) Red, Yellow And Blue In Colours Of 22.5 Mm Dia To Monitor On Lt Panel Board Suitable For 240 V Ac Supply And Taking Down Unserviceable Indication Lamps Complete All As Specified And Directed. Cat Part No:-1Sfa619402r5201 Make:-Siemens / C&S / Schneider / Abb 15 Supply Only Metering Current Transformer Of 1000 / 5 Amps Class-1, 15 Va, Completeall As Specified And Directed By Engr-In-Charge.Make:-Rishabh Or Equivelent Of Kappa / Ae 16 Supply Only Metering Current Transformer Of 1200 / 5 Amps Class-1, 15 Va, All Complete All As Specified And Directed.Make:-Rishabh Or Equivelent Of Kappa / Ae 17 Supply Only Metering Current Transformer Of 1600 / 5 Amps Class-1, 12.5 Va, Complete Allas Specified And Directed.Make:-Rishabh Or Equivelent Of Kappa / Ae 18 Supply Only Metering Current Transformer Of 2000 / 5 Amps, Class-1, 12.5Va, Complete All As Specified And Directed. Make:-Rishabh Or Equivelent Of Kappa / Ae 19 Supply Only Metering Current Transformer Of 2500 / 5 Amps, Class-1, 5Va, Complete All As Specified And Directed. Make:-Rishabh Or Equivelent Of Kappa / Ae 20 Supply Only Metering Current Transformer Of 3000 / 5 Amps, Class-1, 1.5Va, Complete All As Specified And Directed. Make:-Rishabh Or Equivelent Of Kappa / Ae 21 Supply Only Metering Current Transformer Of 800 / 5 Amps, Class-1, 2.5Va, Complete All As Specified And Directed. Make:-Rishabh Or Equivelent Of Kappa / Ae 22 Supply Only Switch Disconnector Fuse Unit , Tpn , Open Execution, Bolted Fuse Link, 415V, Conforming To Is / Iec 60947-3, Telescopic Shaft For Depth Adjustment Terminal Shrouds On Both Side, Door Interlock Facility Of Current Rating 250 Amps Including Boted Hrc Fuse-03 Nos ( Make- L&T, Cat No- Fn-250-Tpn-Sk-95682 & Hrc Fuse-St-30781 Or Equivelent Of Siemens / Abb / Havells ) 23 All As Per Item No 22.00 Above But Capacity Of 400 Amps. ( Make- L&T, Cat No- Fn-315-Tpn-Sk-95591 & Hrc Fuse-St-30784 Or Equivelent Of Siemens / Abb / Havells ) 24 Supply Only Hrc Fuse Of Capacity 400 Ampscomplete All As Specified And As Directed ( Make L&T Cat No Sf94335 And Equivalent To Standard / Ge / Schneider ) 25 Supply Only Hrc Fuse Of Capacity 250 Ampscomplete All As Specified And As Directed ( Make L&T Cat No Sf94333 And Equivalent To Standard / Ge / Schneider ) 26 Supply And Fix Mccb, 4 Pole, 400 Amp, 36 Ka Braking Capacity, Ics = 100% Icu As Per Iec 60947-2, With Micrologic 2 ( Up-Asic Based ) , Complete All As Specified And As Directedmake- Schneider Cat Part No- Lv432677 Or Equivelent Of Legrand / Abb 27 All As Item No 26.00 Above But Of Size 4 Pole, 630 Amp, 36 Ka. Make Make- Schneider Cat Part No- Lv432877 Or Equivelent Of Legrand / Abb 28 All As Item No 26.00 Above But Of Size 4 Pole, 250 Amp, 36 Ka. Make Make- Schneider Cat Part No- Lv431780 Or Equivelent Of Legrand / Abb 29 All As Item No 26.00 Above But Of Size 3 Pole, 160 Amps, 36 Ka. Make- Schneider Cat Part No- Lv430770 Or Equivelent Of Legrand / Abb 30 Supply And Fix Mccb 3 Pole, 125 Amps, 25 Ka Braking Capacity, Ics = 100% Icu As Per Iec 60947-2, With Thermal Magnetic Trip Unit. Complete All As Specified And As Directed Make- Schneider Cat Part No- Lv430311 Or Equivelent Of Legrand / Abb 31 Supplay, Fix And Connecting By Mannualchangover Switchsheet Steel Enclosure Versionconforms To Iec 60947-3 Of Capacity 630 Amps Four Pole Complete All As Specified And As Directed ( Make- L&T Cat Part No-Co46300osooor Equicalent To Havells / Indo Asian. 32 Supplay, Fix And Connecting By Mannualchangover Switchsheet Steel Enclosure Versionconforms To Iec 60947-3 Of Capacity 400 Amps Four Pole Complete All As Specified And As Directed ( Make- L&T Cat Part No-Co44000osooor Equicalent To Havells / Indo Asian. 33 Supplying And Laying Synthetic Rubber Insulated Mats 2 Mm Thick For Voltage Upto 3.3 Kv For Electrical Purpose As Per Is 15652-2006, ( Superseding Is 5424 ) Suitable For Electrical Shock Safety Of Sizes 2M X 1M.Complete All As Specified And As Directed 34 M&L For Painting Of Outer Surface Of Multiple Section Ofcomplete Lt Panel Board Size Up To 5.5 M X 3.2 In One Substation Comprising Acbs / Mccbs / Sdfs , Busbar Chamber, Swich Gear Chamber, Metering Chamber Cable Termination / Tray Using One Coat Of Synthetic Enamel Paint After Preparation Of Surface, Providing Protection Cover To All Metering Equipment, Panel Meters, Switchgears, Cleaning Of All Meters And Switch Gearscomplete All As Specified And As Directed 35 All As Per Item No 34.00 Above But Lt Panel Board Size Up To 7.5 M X 4.5 M. 36 M&L For Painting Of Both Side Surface Of Ms Cable Trench Cover Using One Coat Of Black Bituminius Paint After Preparation Of Surfacecomplete All As Specified And As Directed 37 M&L For Plate Girder Or Single Stanchions, Fe-290 Built Up Of One Beam Or Channel Section With Flange Plates, Caps Bases, Splices, Angle Brackets, Cleats And Other Connection And Taking Out Of Oldunsv Ms Cable Cover / Support Structure. 38 Dimantling, Taking Out All Earth Connection Of Strip From Panel Board To Earth Test Pit Any Size And Replace The Worn Out Earth Strip, Nut / Bolts / Washers Connect All Joint With New Nots, Bolts And Washers To In Original Positioncomplete All As Specified And As Directednote :- Earth Gi Strip Measured And Paid Separetely 39 M & L For Earth Continuity Conductor Gi Strip Of Size 32 X 6 Mmcomplete All As Specified And As Directed 40 M&L For Writing Letter And Fixing Lt Panel Boardsurface Showing Incoming And Outgoing Capacity Inamps And Feeder Name Of Letter Five Not Less Than 30 X 50 Mm Complete All As Specified And As Directed 41 Dismantlingexisting Unserviceable / Corrodedlt Pillar Box And Supply, Fabricate, Install, Testing And Commissioning Out-Door Type, Double Door Dust & Vermin Proof Lt Pillar Box Of 2.1 M Length, 1 M Width & 1.6 M Height Fabricated Vertically By Using 50X50x5 Mm Angle Iron Frame, Fixing With Nuts & Bolts On 75 X 40 Mm Ismc As Per Directions Of Engineer-In-Charge And Using 3 Mm Thick Crca Ms Sheet All Over Body Front And Back Cover With Hinges And Aldrops For Locking Arrangments, 1 Mm Thick Frp Coating All Over The External Surfaces And 3 Mm Thick Ms Sheet For Bus Bar Cover, Piller Box, Partitions And Bottom Cable Entry Covers Duly Painted With One Coat Of Redoxide And Two Coats Of Synthetic Enamel Paint Including Control Wiring Complete In Lt Piller Box With 1.5 Sq Mm Frls Copper Conductor Cable And 5A Mcb Sps 2.5 Amp For Meters, Breaker Control Supply And Indication Lamps And Provision To Accommodate The Following: ( A ) 3 Ph+1N Copper Busbar Of Equal Sizes Of Capacity 1.5 Times Of Ratedcurrent Of Incoming Switchgear. ( B ) 3 Ph+1N Copper Busbar Of Equal Sizes Of Capacity 1.5 Times Of Ratedcurrent Of Outgoing Switchgears As Down Links / Connectivity Links To Switchgear. 42 ( C ) Digital Ammeter & Voltmeter For Incoming & Digital Ammeter For Outgoing. ( D ) Led Indication Lamps For Ryb For Incoming And Outgoing Indication. ( Red, Yellow & Blue Coloured ) ( E ) Lt Acb – 1600Amps, 4P, 50Ka, Complete With Over Current And Earth Fault Tripping Device As Incomer -01No ( F ) Lt Acb - 1600 Amps, 3P, 50 Ka Complete With Over Current And Earth Fault Tripping Device As Out Going-01 No ( G ) Mccb - 630Amps, 3P, 36Ka Complete With Over Current And Earth Fault Tripping Device As Out Going-01No ( H ) Mccb - 400Amps, 3P, 36Ka Complete With Over Current And Earth Fault Tripping Device As Outgoing-01Nonote : ( I ) Unit Rate Quoted Include For Necessary Grouting / Chipping Of Concrete And Anchor Fastners And Providing Necessary Pcc ( 1:2:4 ) Type B1 Using 20 Mm Gradedcrushed Stone Agreegate For Foundation To Fix The Lt Piller Box. ( Ii ) Cost Of Digital Ammeter, Voltmeter, Led Lamps, Cts, Lt Acbs, Mccbs And Mcbs Shall Be Included In The Quoted Rate. ( Iii ) Drawing Shall Be Got Approved By Ge Before Fabrication Of The Lt Piller Box. ( Iv ) All Incoming And Outgoing Cable Connections Are To Be Made As Per Existing One And Rate Deemeded To Be Included In The Quoted Rate. ( V ) The Pillar Box Shall Be Brought To Jetty Gallery Part By Part And To Be Assembled In Site Being Limited Space Of Work / Movement And Rate Shall Deemed To Be Included In Quoted Rate. ( Vi ) Copper Busbars With Pvc Sleeves Shall Be Measured And Paid Seperately Under Respective Item In This Schedule As Supply Only 43 Supply Only Copper Bus Bar Links With Pvc Sleeves Of Raing 630 A To 2000 Acomplete All As Specified And As Directed 44 Supply And Fix Lt Acb 4 Pole4000 A, 50 Ka Breaking Capacity, 415 V, 50 Hz, Manual Drawn Out Type And Manually Charged With Micro Processor Et2l Trip Unit ( Without Display ) Release Protection System Against Over Current, Earth Fault And Short Circuit With 2 No + 2 Nc Auxiliary Switch, Safety Shutter, Cradle Guard, Operating Handles Conforming To Iec 60947-2 & 3Complete All As Specified And As Directedmake:- Cat.No. Mvs40n4mw2lofschneider / L&T / Abb / Ge / Legrand 45 All As Per Item No 44.00 Above But Of Capacity2000amps, 4Polecat.No. Mvs20n3mw2lof Schnider Equivelent Make Inl&T / Abb / Ge / Legrand 46 All As Per Item No 44.00 Above But Of Capacity1600amps, 4Polecat.No. Mvs16n3mw2l Of Schnider Equivelent Make Inl&T / Abb / Ge / Legrand 47 All As Per Item No 44.00 Above But Of Capacity1250amps, 4Polecat.No. Mvs12n3mw2l Of Schnider Equivelent Make Inl&T / Abb / Ge / Legrand 48 All As Per Item No 44.00 Above But Of Capacity1000amps, 4Polecat.No. Mvs10n3mw2lof Schnider Equivelent Make Inl&T / Abb / Ge / Legrand 49 Attending Day To Day Electrical Complaints And Call On Repair Of Control Panel Of Street Light, Security Light, Garden Light, Perimeter Light, Tower Light & High Mast Light Providedinsidedockyard, Decarbonizing All Contact Points Of Contactors , Replacement Of Wornout Aluminium Cable Lugs, Wornout Screws, Nuts, Bolts And Washers, Tightening The Loose Connections Whereever Required, Adjustment Of Timer, Cleaningand Restore The Power Supply Complete All As Specified And As Directednote :- ( I ) Replacement Of Spares Vizmcb, Mccb, Contactors, Timers, Cables, Will Be Measured And Paid For Separately As Supply Only And Labour Element For Taking Down The Replaced Spares Shall Be Deemed To Include In The Unit Rate Quoted. ( Ii ) If The Qty Of Complaints To Be Attended In A Control Panel / Lt Panel Is More Than 01 No In A Day, Altogether The Complaints Will Be Considered Only 1 ( One ) . ( Iii ) The Contractor Has To Engage Qualified Electricians And Helpers In Sufficient Nos To Attend And Rectify The Defects. ( Iv ) Job Card For Repairing Work Will Be Issued By Concern Je And The Same Shall Be Signed By Contractor / Or His Rep And Shall Be Returned To Concerned Je On Completion Of Each Job Work. 50 Material And Labour For Disconnecting The Burnt Out High Mast Tower Winch Motor 3 Phase , 415V, 50Hz, 1400 Rpm, 4 Pole, 2Hp And Rewinding With Supper Enameled Copper Wire Of Same Gauge / Size Of Wire Including Re-Fixing The Same In Its Original Position Testing And Commissioning Complete All As Specified And As Directed 51 Material And Labour For Servicing Of High Mast Tower Control Mechanism By Greasing And Varnishing Of Electric Motor 2 Hp, 3 Phase 415 Volts 50Hz Including Replacement Of Unsv Plug And Socket For Trouble Free Functioning Including Painting Of Starter Panel With One Coat Of Synthetic Enamel Paint Complete All As Specified And As Directed 52 Supply And Fixing High Mast Tower Winch Motor 3 Phase 415 V 50Hz 1400 Rpm 4 Pole 2Hp Complete All As Specified And As Directed 53 S&F Pvc Junction Box Of Outdoor Type, Weather Proof, With Provision Of Hole At Bottom For Cable Entry, Hinged Door With Locking Arrangement, Of Size Not Less Than 200Mm ( L ) X 100Mm ( B ) X 300Mm ( H ) Incl Taking Down Unserviceable One, Fixed To Pole With Ms Clamp, Nuts, Bolts And Washers Complete Including One 3Ph 4 Pole Connection Block. Complete All As Specified And As Directedmake- Syntex / Hansel 54 Supply And Fixing / Laying Through Trench.Surface Or Wall Including Required Necessary Saddle / Clamp Any Highthdpe Double Wall Pipe Corugated Pipe Of Size 40 Mm Dia For Cable Protection Laid In Trenches In Lieu Of Sand / Brick Protection Complete All As Specified And As Directed 55 Taking Out Old Unserviceable Lt Ug Cable Of Any Size Any Description Including Hdpe Pipe And Bricks For Cable Protection Where Ever Appeared And Complete All As Specified And As Directed 56 Supply And Laying In Trenches Xlpe Insulated, Armoured, Heavy Duty Electric Cable With Stranded Aluminium Conductor, 1100 Volts Grade Cross Section Area 6 Sqmm 2 Core And Connection Complete With Aluminium Cable Lugscomplete All As Specified And As Directed 57 All As Per Ser No 56.00 But Of Size 10 Sqmm, 4 Core 58 All As Per Ser No 56.00 But Of Size 16 Sqmm 4 Core 59 All As Per Ser No 56.00 But Of Size 25 Sqmm 3.5 Core 60 All As Per Ser No 56.00 But Of Size 35 Sqmm 3.5 Core 61 M&L For Dismatling And Taking Out Street Light Cable Loop Near Pole Forsize Of Cable 6Sqmm To 25 Sqmm After Dismantling Connection From Junction Box, Cutting, Removing Damaged Portion Of The Cable Ends, Providing New Aluminium Cable End Terminals, Laying Of Cable Through Protection Pipe Through Coping To Junction Box Including Necessary Connection Complete All As Specified And As Directed. ( Note: Earth Work, Pole Coping Pcc, Cable Protection, Pipe Measured Separately ) 62 M&L For Dismantling Taking Out Cables 10 Sqmm To 16 Sqmm From Trench, Including Making Straight Through Joints At Damaged Portion And Relaying To Trench Complete All As Specified And As Directed ( Note: Earth Work, Hdpe Pipe For Cable Protection Will Be Measured And Paid Separately. Heat Shrink Straight Through Cable Joints Inclusive Of Quoted Rate ) 63 M&L For Dismantling Taking Out Cables 25 Sqmm To 35 Sqmm From Trench, Making Straight Through Joints At Damaged Portion And Relaying To Trench Complete All As Specified And As Directed ( Note: Earth Work, Hdpe Pipe For Cable Protection Will Be Measured And Paid Separately. Heat Shrink Straight Through Cable Joints Inclusive Of Quoted Rate ) 64 Supply And Fixing Pvc Insulated, Pvc Round Shethed Copper Flexible Electric Cable 1.5 Sqmm 3 Core, 1100 Volts Grade And Dismantling Wornout / Defective Cables From Sl / Flood Light Fitting At Pole / Tower Top To Jb At Bottom Of Pole Through Pole / Tower Complete All As Specified And As Directedmake : Plaza / Gloster / Havells / Polycab. 65 M&L For Complete Servicing, Repair, Maintenance Of Timer Panel, By Cleaning Inside And Outside, Replacement Of Burnt Mcb, Mccb, Timer, Contactor, Wiring, Bypass Toggle Switch Complete All As Specified And As Directednote: Replacement Of Mcb, Mccb, Timer, Contactor Shall Be Measured As Supply Only 66 Supply Only Power Contactor 3 Phase, 415V, 32 Amps Cap Utilsed For Heavy Duty By Taking Down The Old Perished / Deteriorated Contactor Complete All As Specified And As Directedmake: Schneider, Model-Etvs-Lc1e3201 Or Equivelent Of Legrand / L&T / Abb 67 Supply Only Surface Mounting Analog Time Switchesheavy Duty Of 230 V 50Hz Including Dismantling Taking Down Unsv One And Complete All As Specified And As Directedmake : 6499 15 Maxi Rex 4Qt ( Daily ) Of Legrand Or Equivelent Of Abb / L&T 68 Supply Only Mcb, Sp, 10Ka, C 6-32 A Including Dismantling Taking Down Unsv Onecomplete All As Specified And As Directedmake:- Schneider Or Equivelent Of Legrand / Abb / L&T 69 Supply Only Mcb, Dp, 10Ka, C 40A-63 A Including Dismantling Taking Down Unsv One Complete All As Specified And As Directed Make:- Schneider Or Equivelent Of Legrand / Abb / L&T 70 Supply Only Mcb, 4P, 10Ka, C 40A-63 A Including Dismantling Taking Down Unsv Onecomplete All As Specified And As Directedmake:- Schneider Or Equivelent Of Legrand / Abb / L&T 71 Supply Only Mccb With Thermal Magnetic Release, 16 Ka, 3 Pole, 415V, 100 A, Complete All As Specified And As Directedmake:- Schneider , Model- Easy Compact Cvs 100 Bs, Lv510950 To 58 Or Equivelent Of Legrand / Abb / L&T 72 M&L For Dismantling Of Non - Functional Street Light / Flood Lightfrom Any Type Of Pole At Hight Upto 9 Mtr By Suitable Ladder For Repair Of The Same For Replacement Unserviceable Items Like Led Driver, Connector Block And Decarbonising Contact Points And Refixing The Same To Pole After Repair Of Any Type Securitylight .Note:- Required Led Driver Shall Be Measured And Paid Separately 73 Supply Only Led Driver Suitable For Street Light Fitting 1X 120 Watt, 230V, Make- Cg / Halvells / Bajaj / Philips / Wipro 74 Supply Only Led Driver Suitable For Street Light Fitting 1X 150 W , 230V, Make- Cg / Halvells / Bajaj / Philips / Wipro 75 Supply Only Led Driver Suitable For Flood Light Fitting 1X 200 W, 230V, Make- Cg / Halvells / Bajaj / Philips / Wipro 76 Supply Only Led Driver Suitable For Flood Light Fitting 1X 250 W, 230V, Make- Cg / Halvells / Bajaj / Philips / Wipro 77 S&F On Wall / Pole Timer Enclosure Out Door Type Complete With Timeranalog Time Switchesheavy Duty Of 230 V 50Hz, Power Contactor 3 Phase Mnx 18 , 415V, 32 Amps, Mcb, Tpn, 10Ka, C 40A-63 A With, Rotary Switch With Connector For Incoming And Outgoing Cable Entry Complete All As Specified And As Directedmake Indi Asian / Havells 78 M&L For Painting Of Steel Fabricated Light Tower Not Less Than 10 Mtr High With One Coat Of Aluminium Paint After Preparation Of Complete Surface Complete Surface Including Writing Tower Number With Synthetic Enamel Black Paint Complete All As Specified And As Directed 79 M&L For Painting Of Steel Tubular Pole Any Type / Swan Neck Pole With One Coat Of Aluminium Paint After Preparation Of Complete Surface Including Writing Pole Number With Synthetic Enamel Black Paint Complete All As Specified And As Directed 80 M&L For White Wash To Pole Coping Pcc Complete All As Specified And As Directed 81 S & F Street Light Fitting Led 150 Watt Watt Incl Dismantling Taking Down Unsv One Complete All As Specified And As Directed.Make- Cg Or Equivelent Of Halvells / Bajaj / Philips / Wipro 82 S & F Flood Light Fitting Led 210 Watt Watt Incl Dismantling Taking Down Unsv One Complete All As Specified And As Directedmake- Cg Or Equivelent Of Halvells / Bajaj / Philips / Wipro 83 S & F Flood Light Fitting Led 300 Watt Incl Dismantling Taking Down Unsv One Complete All As Specified And Directed, Make- Cg, Model- Cfs-501-300-57-60D-Sl-Gl-Ngg Or Equivelent Of Halvells / Bajaj / Philips / Wipro 84 S & F Flood Light Fitting Led 350 Watt Incl Dismantling Taking Down Unsv One Complete All As Specified And Directed, Make- Cg, Model- Cfs-501-350-57-60D-Sl-Gl-Ngg Or Equivelent Of Halvells / Bajaj / Philips / Wipro 85 Taking Down Old Unserviceable Aviation Light Fitting, And Supply & Fix New Led Aviation Light Fitting Withyellow Painted Die-Cast Aluminium Alloy Housing, Red Coloured Polycarbonate Dome And Accessories Includingclamps, Nuts, Bolts And Service Connections Up To The Junction Box Complete All As Per Make Bajaj Andcat No.Bjaol 2 Bc Gls 2 X 100W Bc Bajaj Or Eqiuvalent In Philips / Cg / Havells / Wipro. 86 Excavation In Trenches Not Exceeding 1.5M Wide And Not Exceeding 1.5M In Depth And Getting Out In Soft Loose Soil For Cable Work Or From Above Cable Duct Complete All As Specified And As Directed 87 Returning, Filling In Including Spreading, Levelling, Watering And Well Ramming In Layers Not Exceeding 25Cm Thick Complete All As Specified And As Directed. 88 Removing Of Excavated Material Not Exceeding 50M And Depositing Where Directed At A Level Not Exceeding 1.5M Above The Starting Point Complete All As Specified And As Directed. 89 M&L For Dry Sand Cushioning For Under Groundcable Provided With Layer And Sand 8 Cm Deep Before Laying The Cable And 15Cm After Laying The Cable Complete All As Specified And As Directed. 90 Supplying And Laying Un-Reinforced Precast Concrete Cable Cover, Class Hv, Type 1, Flat, Size 300Mm X 180Mm X 40Mm Complete All As Specified And As Directed 91 Surface Dressing Of Areas Of Above Cable Duct By Clearing Away All Grass, Wild Vegetation, Saplings, Shrubs, Brushwood, Undergrowth, Roots, And Trees Not Exceeding 30Cm Girth And Removing Rubbish Upto A Distance Of 50 Meters Outside The Periphery Of The Area Under Clearance Complete All As Specified And As Directed 92 M & L Making Chequrered Plates As Per Existing Sizes And Thickness Both Side Lifting Handle As Per Existing One Including Painting Of One Coat Red Oxide Primerand Two Coat Of Black Bituminius Paint, Including Necessary Pcc Wks As Per Site Requirment And Taking Out Of Old Unsv Chequered Plate Complete All As Specified And Directed. 93 Cleaning Of Cable Duct Of Size 1.2 X 1.0 By Removing Out All Mud, Soil, Waste Materials And Disposal Of Waste Materials To Nearest Gurbage Bin And Soil Mud To Low Laying Area Of Dockyard 94 S / F Of Cable Rack Made With Structural Steel Section Of Isa 75X75x8mm, ( Fe-290, Gde E 165 ) Pre-Welded, Inside Duct, On Wall , Placing In Position And Fixing To Wall With Fastener Steel Bolt Not Less Than20 Mm Dia, Including Painting With One Coat Of Red Oxide And Two Coat Of Black Bituminous Paint All As Specified And Directed. Note:- Cable Rack Drawing Shall Be Obtained From Engr-In-Charge. 95 Dismantling Taking Out Unserviceable Ms Cable Support From Wall / Surface Of Gallery Any Type By Removing Nuts & Bolts / Cutting Braces Complete All As Specified And As Directed 96 Taking Out Old Unsv Ht Ug Cable Of Any Size And Any Description Including Gi Pipe Of Any Dia And Bricks For Cable Protection Where Ever Appeared And Complete All As Specified And As Directednote:- ( 1 ) Excavation And Earth Work Shall Bemeasured And Paid Separately. ( 2 ) Serviceable Cable Obtained Shall Be Stacked Properly For Re Use. 97 M & L Xlpe Insulated, Screened, Pvc Bedded, Galvanised Steel Strip Or Wire Armoured, Electric Power Cables ( Heavyduty ) With Aluminium Conductor, 11000 Volts Earthed, Grade Cross Sectional Area 185 Sq. Mm 3 Core Complete All As Specified And As Directed 98 All As Per Item No 97.00 Above But For Cable Sizes 240 Sqmm 3 Core 99 All As Per Item No 97.00 Above But For Cable Sizes 300Sqmm 3 Core 100 All As Per Item No 97.00 Above But For Cable Sizes 400Sqmm, 3 Core 101 Supply Only Cable Jointing Kit For 11 Kv ( Earthed ) Grade Cable For Indoor Termination Heat Shrink Type Joint Complete With Jointing Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 185 Sqmm Incl Dismentling / Taking Down Unserviceable One Complete All As Specified And As Directed 102 All As Per Item No 101.00 Above ( Indoor Termination ) But For Cable Of Size 240Sqmm To 300 Sqmm Incl Dismentling / Taking Down Unserviceable One Complete All As Specified And As Directed. 103 All As Per Item No 101.00 Above ( Indoor Termination ) But For Cable Of Size 400 Sqmm Incl Dismentling / Taking Down Unserviceable One Complete All As Specified And As Directed. 104 Supply Only Cable Joining Kit For 11 Kv ( Earthed ) Grade Cable For Straight Through Heat Shrink Type Joint Complete With Joining Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 185Sqmm Incl Dismentling / Taking Down Unserviceable One. 105 All As Per Item No 104.00 Above ( Straight Through Heat Shrink Type Joint ) But For Cable Of Size 240Sqmm To 400 Sqmm Incl Dismentling / Taking Down Unserviceable One Complete All As Specified And As Directed. 106 M & L For Road Cutting / Hard Standing To A Depth Not Less Than 80 Cm And Not Less Than 60 Cm Wide For Laying Of Gi Pipe To Draw To Ugcable And Making Good The Disturbed Surface By Filling Of Pcc ( 1:3:6 ) Type C-2 Using 40 Mm Graded Stone Aggregate And Finished The Surface Even And Smooth With Out Using Extra Cement And Disposal Off The Surplus Debris And Soil To A Distance Not Exceeding 50 M Complete All As Specified And As Directed By Engr-In -Charge. 107 M & L 80 Mm Bore Gi Pipe Tubes Light Grade For Cable Protection Supporting With All Fixing Accessories ( Clamp, Nuts, Bolt And Washer Etc ) Complete All As Specified And As Directed By Engr-In -Charge. 108 Dismantling Taking Out Ht Cable From Cable Rack / Floor At Gallery Of Marine Jetty For Repair / Replacement Of Wornout Steel Cable Rack Or For Realingnment Of Cable And Refixingthe Cables With Proper Staking With Proper Alignment Of Cable On Repaired / Existing Rack And Making Feeder Wise Bundle Of Cable Using Pvc Cable Tie For Sizes Of Cable 3 Core, 185 To 240 Sqmm, 11000 Volts Grade Complete All As Specified And As Directed. Note:- Each Cable Shall Be Measured Separately.Steel Cable Rack Shall Be Measured Separately As Supply And Fix 109 All As Per Item No 108.00 Above But For Cable Sizes 300 To 400 Sqmm, 3 Core. 110 M&L For Finding Of Cable Fault Of Ug 11000 Volts Grade Cable Inside Trench ( Under Soil / Drain / Pcc / Road / Trench ) By Disconnecting Both Cable Ends, Using Insulation Tester, Cable Path / Fault Finder And Rectification Complete By Necessary Excuvation, Cutting At Fault Position, Fixing Of Straight Through Heat Shrink Joint, For Cable Sizes 185 Sqmm To 400 Sqmm, 3 Core, 11000 Volts Grade Or Replacement Of Heat Shrink Indoor Cable Joint Kit Of Size 185 Sqmm To 400 Sqmm, 3 Coreand Reconnection Of Both Cable End To Original Position After Complete Satisfactory Insulation Test, Fixing With Old Or Required New Nuts-Bolts-Washers Complete With Testing Complete All As Specified And As Directednote: ( A ) Items Required For Rectification Such As Heat Shrink Indoor Cable Joint Kit / Heat Shrink Straight Through Joints / Heat Shrink Sleeves And Earth Work Shall Be Measured Separately . ( B ) Required Aluminium Cable Lugs And Nuts-Bolts-Washers Shall Be Inclusive Of Quoted Rate. ( C ) Contractor Shall Bring Necessary Testing Equipment And Rate Shall Be Inclusive Of Quoted Rate. 111 M&L For Earthing Complete With Glvn. Gi Plate Earth Electrode 60Cmx60cmx6 Mm Thick Burried In Ground Vertically To A Depth N. Less Than 1.5 M Below Normal Gl, Connected To Gi Strip32x6 Mm Earth Lead By Means Of Nuts, Bolts, Check Nuts & Washers All As Specified And Indicated Inclu. Concrete Pit In Pcc 1:3:6 Type C-2 Rcc, Precast Pit Cover Slab 400Mmx400mmx80mm With Handle For Lifting Made Out Of 8Mm Dia Ms Rod Fixed Flush To Pit, Funnel, Wiremesh, 20Mm Dia Gi Pipe Medium Grade For Watering Charcoal And Salt In Alternate Layers Including Necessary Earth Work Excuvation & Removal Etc Complete All As Specified In Plate No 5 Of Ssr Part-I 1991 ( Zone E ) 112 M & L For Earth Continuity Conductor Gi Strip Of Size 32 X 6 Mm . 113 Painting Chequrered Plates As Per Existing Sizes And Thicknessof One Coat Red Oxide Primerand Two Coat Of Black Bituminius Paint, Complete All As Specified And As Directed 114 Supply And Fix Cable Route Indicator To Indicate Path Of Ht Cable 11000 Volte Material Usde Cast Iron With Pcc Work Complete All As Specified And As Directed

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Jul-2022 Corrigendum No 1 Date 09-08-2022
2 01-Aug-2022 Corrigendum No 2 Date 16-08-2022
3 06-Aug-2022 Corrigendum No 3 Date 23-08-2022
4 10-Aug-2022 Corrigendum No 4 Date 29-08-2022
5 20-Aug-2022 Corrigendum No 5 Date 01-09-2022
6 20-Aug-2022 Corrigendum No 6 BOQ 01-09-2022
7 01-Sep-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 08-09-2022

Key Value

Document Fees
INR 1000 /-
EMD
INR 209000.0 /-
Tender Value
INR 1.34 Crore /-

BOQ Items

Name of Work: REPLACEMENT OF DEFECTIVE LIGHTS, REPAIR AND MAINTENANCE OF LT PANEL BOARD METERING EQUIPMENT’S, SWITCH GEARS, DAY TO DAY MAINTENANCE OF 11 KV DISTRIBUTION CABLES, ATTENDING COMPLAINT AND REPLACEMENT OF UNSERVICEABLE UG CABLE GALLERY EARTHING, EARTHING STRIPS ALL ALLIED WORKS AT DRY DOCK AREA SUBSTATION AND JETTY AREA OF NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) (DM) VISAKHAPATNAM
Sl. No. Item Description
1Servicing/maintinance ofmultiple section ofLT Panel board in one substation comprising minimum up to 05 Nos ACBs/ MCCBs/SDFs ,busbar chamber, swich gear chamber, metering chamber cable termination/tray chamber after opening front/top/side/back cover by using forced air pressure andbrushes, cleaning of all dust/durt, complete cleaning of out side surface of panel board using suitable cleaning agents, tighting of all nuts & bolts of busbar/switchgear/cable terminals, repair/replacement to defective metering wiring from ACB/MCCB/CT to meter and replacement of defective meters, CTs, indicator lamp, metering terminal blocks, MCB, replacement of defective aluminum cable lugs, nuts-bolts-washers, replacement of defective Panel knob/door knob and hinges complete all as specified and as directed Note:- (i) Panel Meter, indicator lamp, MCB,busbarand CT will be measured and paid seperately as supply only. (ii) required aluminium cable lugs, metering cables and nuts-bolts-washers shall be inclusive of quoted rate. (iii) Servicing/maintinance of ACBs measured seperatelly.
2All as per item No 1.00 above but comprisingACBs /MCCBs/SDFs up to total 10 Nos
3All as per item No 1.00 above but comprisingACBs /MCCBs/SDFs up to total 15 Nos
4All as per item No 1.00 above but comprisingACBs /MCCBs/SDFs up to total 23 Nos
5All as per item No 1.00 above but comprisingACBs /MCCBs/SDFs up to total 28 Nos
6Servicing, repair, maintinance of Air Circuit Breaker 630 Amps to 3200 Amps capacity by drawing out movable unit, forced air cleaning of movable and fixed unit, decarbonize breaker contracts and checking for any defects due to any flush/loose contact, cleaning of all fixed and moving contact point, terminal connection points with CTC,replacement of defective parts and re-fixing ACB, cables completes all as specified and as directed. Note: (a) required male/female ACB contacts, trip coils, closing coils, electronic protection unitwill be measured as supply only.(b) all cleaning agents are included in the quoted rate.
7Supply only fixed contract of ACB 630A to 3200Acomplete all as specified and as directed
8Supply only Moving contract of ACB 630A to 3200Acomplete all as specified and as directed
9Supply Only Electronic protection unit of ACB 630A to 3200Acomplete all as specified and as directed
10Supply Only shunt trip coil of ACB 630A to 3200Acomplete all as specified and as directed
11Supply Only closing coil ACB 630A to 3200A complete all as specified and as directed
12Supply only digital electronic Ammeter (0-3200 amps range)withbuilt in selector switch suitable for LT 415 V panel flush pattern square type 96 mm x 96 mm with adopter completeall as specified and directed. Cat Part No:- 30002385 (DM3110)make:- Schneider or Conserve/L&T/HPL
13Supply only digital electronic Volt meter (0-500 volts range) withbuilt in selector switch suitable for LT 415 V panel flush pattern square type 96 mm x 96 mm with adopter completeall as specified and directed. Cat Part No:- 30002386 (DM3210)make:- Schneider or Conserve/L&T/HPL
14Supply only indication lamps (LED type) red, yellow and blue in colours of 22.5 mm dia to monitor on LT panel board suitable for 240 V AC supply and taking down unserviceable indication lamps complete all as specified and directed. Cat Part No:-1SFA619402R5201 Make:-Siemens/C&S/schneider/ABB
15Supply only metering current transformer of 1000/5 Amps class-1, 15 VA, completeall as specified and directed by Engr-in-charge. Make:-Rishabh or equivelent of Kappa/ AE
16Supply only metering current transformer of 1200/5 Amps class-1, 15 VA, all complete all as specified and directed. Make:-Rishabh or equivelent of Kappa/ AE
17Supply only metering current transformer of 1600/5 Amps class-1, 12.5 VA,complete allas specified and directed. Make:-Rishabh or equivelent of Kappa/ AE
18Supply only metering current transformer of 2000/5 Amps, Class-1, 12.5VA, complete all as specified and directed. Make:-Rishabh or equivelent of Kappa/ AE
19Supply only metering current transformer of 2500/5 Amps, Class-1, 5VA, complete all as specified and directed. Make:-Rishabh or equivelent of Kappa/ AE
20Supply only metering current transformer of 3000/5 Amps, Class-1, 1.5VA, complete all as specified and directed. Make:-Rishabh or equivelent of Kappa/ AE
21Supply only metering current transformer of 800/5 Amps, Class-1, 2.5VA, complete all as specified and directed. Make:-Rishabh or equivelent of Kappa/ AE
22Supply only switch disconnector fuse unit , TPN , open execution, bolted fuse link, 415V, conforming to IS/IEC 60947-3, telescopic shaft for depth adjustment terminal shrouds on both side, door interlock facility of current rating 250 amps including boted HRC fuse-03 Nos(Make- L&T, cat No- FN-250-TPN-SK-95682 & HRC fuse-ST-30781 or equivelent of Siemens/ABB/havells)
23All as per item No 22.00 above but capacity of 400 Amps.(Make- L&T, cat No- FN-315-TPN-SK-95591 & HRC fuse-ST-30784 or equivelent of Siemens/ABB/havells)
24Supply only HRC fuse of capacity 400 Ampscomplete all as specified and as directed(Make L&T Cat No SF94335 and equivalent to standard/GE/Schneider)
25Supply only HRC fuse of capacity 250 Ampscomplete all as specified and as directed (Make L&T Cat No SF94333 and equivalent to standard/GE/Schneider)
26Supply and fix MCCB, 4 pole, 400 amp, 36 KA braking capacity, Ics = 100% Icu as per IEC 60947-2, with Micrologic 2 (up-ASIC based),complete all as specified and as directedMake- Schneider cat Part No- LV432677 or equivelent of Legrand/ABB
27All as item No 26.00 above but of size 4 pole, 630 amp, 36 KA. Make Make- Schneider cat Part No- LV432877 or equivelent of Legrand/ABB
28All as item No 26.00 above but of size 4 pole, 250 amp, 36 KA. Make Make- Schneider cat Part No- LV431780 or equivelent of Legrand/ABB
29All as item No 26.00 above but of size 3 pole, 160 amps, 36 KA. Make- Schneider cat Part No- LV430770 or equivelent of Legrand/ABB
30Supply and fix MCCB 3 pole, 125 amps, 25 KA braking capacity, Ics = 100% Icu as per IEC 60947-2, with Thermal Magnetic Trip Unit. complete all as specified and as directed Make- Schneider cat Part No- LV430311 or equivelent of Legrand/ABB
31Supplay, fix and connecting by mannualchangover switchsheet steel enclosure versionconforms to IEC 60947-3 of capacity 630 amps four pole complete all as specified and as directed (Make- L&T cat PART No-CO46300OSOOor equicalent to Havells/indo asian.
32Supplay, fix and connecting by mannualchangover switchsheet steel enclosure versionconforms to IEC 60947-3 of capacity 400 amps four pole complete all as specified and as directed (Make- L&T cat PART No-CO44000OSOOor equicalent to Havells/indo asian.
33Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m.complete all as specified and as directed
34M&L for painting of outer surface of multiple section ofcomplete LT Panel board size up to 5.5 m x 3.2 in one substation comprising ACBs/MCCBs/SDFs ,busbar chamber, swich gear chamber, metering chamber cable termination/tray using one coat of synthetic enamel paint after preparation of surface, providing protection cover to all metering equipment, panel meters, switchgears, cleaning of all meters and switch gearscomplete all as specified and as directed
35All as per item No 34.00 above but LT panel board size up to 7.5 M X 4.5 M.
36M&L for painting of both side surface of MS cable trench cover using one coat of black bituminius paint after preparation of surfacecomplete all as specified and as directed
37M&L for plate girder or single stanchions, FE-290 built up of one beam or channel section with flange plates, caps bases, splices, angle brackets, cleats and other connection and taking out of oldunsv MS cable cover/support structure.
38Dimantling,taking out all earth connection of strip from panel board to earth test pit any size and replace the worn out earth strip, nut/bolts/washers connect all joint with new nots,bolts and washers to in original positioncomplete all as specified and as directed Note :- Earth GI strip measured and paid separetely
39M & L for Earth continuity conductor GI strip of size 32 X 6 mmcomplete all as specified and as directed
40M&L for writing letter and fixing LT panel boardsurface showing incoming and outgoing capacity inAmps and feeder name of letter five not less than 30 X 50 MM complete all as specified and as directed
41Dismantlingexisting unserviceable /corrodedLT Pillar Box and supply, fabricate, install, testing and commissioning out-door type, double door dust & vermin proof LT pillar box of 2.1 M length, 1 M width & 1.6 M height fabricated vertically by using 50x50x5 mm angle iron frame, fixing with nuts & bolts on 75 x 40 mm ISMC as per directions of Engineer-in-Charge and using 3 mm thick CRCA MS sheet all over body front and back cover with hinges and aldrops for locking arrangments,1 mm thick FRP coating all over the external surfaces and 3 mm thick MS sheet for bus bar cover, piller Box, partitions and bottom cable entry covers duly painted with one coat of redoxide and two coats of synthetic enamel paint including control wiring complete in LT piller box with 1.5 sq mm FRLS copper conductor cable and 5A MCB SPs 2.5 amp for meters, breaker control supply and indication lamps and provision to accommodate the following: (a) 3 ph+1N Copper busbar of equal sizes of capacity 1.5 times of ratedcurrent of incoming switchgear. (b) 3 ph+1N Copper busbar of equal sizes of capacity 1.5 times of ratedcurrent of outgoing switchgears as down links/connectivity links to switchgear.
42(c) Digital ammeter & voltmeter for incoming & Digital ammeter for outgoing. (d) LED indication lamps for RYB for incoming and outgoing indication.(Red,yellow & blue coloured) (e) LT ACB – 1600Amps, 4P, 50KA, complete with over current and earth fault tripping device as incomer -01No (f) LT ACB - 1600 Amps, 3P, 50 KA complete with over current and earth fault tripping device as out going-01 No (g)MCCB - 630Amps, 3P, 36KA complete with over current and earth fault tripping device as out going-01No (h)MCCB - 400Amps, 3P, 36KA complete with over current and earth fault tripping device as outgoing-01NoNote : (i)Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC (1:2:4) type B1 using 20 mm gradedcrushed stone agreegate for foundation to fix the LT Piller Box. (ii) Cost of digital ammeter, voltmeter, LED lamps, CTs, LT ACBs, MCCBs and MCBs shall be included in the quoted rate. (iii) Drawing shall be got approved by GE before fabrication of the LT piller Box. (iv) All incoming and outgoing cable connections are to be made as per existing one and rate deemeded to be included in the quoted rate. (v) The pillar box shall be brought to Jetty gallery part by part and to be assembled in site being limited space of work/movement and rate shall deemed to be included in quoted rate.(vi) Copper busbars with pvc sleeves shall be measured and paid seperately under respective item in this schedule as "Supply only"
43Supply only copper bus bar links with PVC sleeves of raing 630 A to 2000 Acomplete all as specified and as directed
44Supply and fix LT ACB 4 pole4000 A, 50 KA breaking capacity, 415 V, 50 Hz, manual drawn out type and manually charged with micro processor ET2L trip unit (Without display) release protection system against over current, earth fault and short circuit with 2 NO + 2 NC auxiliary switch, safety shutter, cradle guard, operating handles conforming to IEC 60947-2 & 3complete all as specified and as directed Make:- Cat.No. MVS40N4MW2Lofschneider/L&T/ ABB/ GE/ LEGRAND
45All as per item No 44.00 above but of capacity2000Amps,4pole Cat.No. MVS20N3MW2Lof schnider equivelent make inL&T/ABB/GE/lEGRAND
46All as per item No 44.00 above but of capacity1600Amps,4pole Cat.No. MVS16N3MW2L of schnider equivelent make inL&T/ABB/GE/lEGRAND
47All as per item No 44.00 above but of capacity1250Amps,4pole Cat.No. MVS12N3MW2L of schnider equivelent make inL&T/ABB/GE/lEGRAND
48All as per item No 44.00 above but of capacity1000Amps,4pole Cat.No. MVS10N3MW2Lof schnider equivelent make inL&T/ABB/GE/Legrand
49Attending day to day electrical complaints and call on repair of control panel of street light, security light, garden light, perimeter light, tower light & high mast light providedinsideDockyard, decarbonizing all contact points of contactors , replacement of wornout aluminium cable lugs, wornout screws, nuts, bolts and washers, tightening the loose connections whereever required, adjustment of timer, cleaningand restore the power supply complete all as specified and as directed Note :- (i) Replacement of spares vizMCB, MCCB, contactors, timers, cables, will be measured and paid for separately as supply only and labour element for taking down the replaced spares shall be deemed to include in the unit rate quoted. (ii) If the qty of complaints to be attended in a control panel/LT panel is more than 01 No in a day, altogether the complaints will be considered only 1 (one). (iii) The contractor has to engage qualified electricians and helpers in sufficient Nos to attend and rectify the defects. (iv) Job card for repairing work will be issued by concern JE and the same shall be signed by contractor/or his rep and shall be returned to concerned JE on completion of each job work.
50Material and labour for disconnecting the burnt out high mast tower winch motor 3 phase ,415V, 50Hz,1400 RPM, 4 pole, 2HP and rewinding with supper enameled copper wire of same gauge/size of wire including re-fixing the same in its original position testing and commissioning complete all as specified and as directed
51Material and labour for servicing of high mast tower control mechanism by greasing and varnishing of electric motor 2 HP, 3 phase 415 volts 50Hz including replacement of unsv plug and socket for trouble free functioning including painting of starter panel with one coat of synthetic enamel paint complete all as specified and as directed
52Supply and fixing high mast tower winch motor 3 phase 415 V 50Hz 1400 RPM 4 Pole 2HP complete all as specified and as directed
53S&F PVC junction box of outdoor type, weather proof, with provision of hole at bottom for cable entry, hinged door with locking arrangement, of size not less than 200mm (L) x 100mm(B)x 300mm (H) incl taking down unserviceable one, fixed to pole with MS clamp, nuts, bolts and washers complete including one 3ph 4 pole connection block. complete all as specified and as directed Make- Syntex / Hansel
54Supply and fixing/Laying through trench.surface or wall including required necessary saddle/clamp any hightHDPE double wall pipe corugated pipe of size 40 mm dia for cable protection laid in trenches in lieu of sand/brick protection complete all as specified and as directed
55Taking out old unserviceable LT UG cable of any size any description including HDPE pipe and bricks for cable protection where ever appeared and complete all as specified and as directed
56Supply and laying in trenches XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 Volts grade cross section area 6 Sqmm 2 core and connection complete with aluminium cable lugscomplete all as specified and as directed
57All as per ser No 56.00 but of size 10 sqmm, 4 core
58All as per ser No 56.00 but of Size 16 Sqmm 4 core
59All as per ser No 56.00 but of Size 25 Sqmm 3.5 core
60All as per ser No 56.00 but of Size 35 Sqmm 3.5 core
61M&L for dismatling and taking out street light cable loop near pole forsize of cable 6sqmm to 25 sqmm after dismantling connection from junction box, cutting, removing damaged portion of the cable ends, providing new aluminium cable end terminals, laying of cable through protection pipe through coping to junction box including necessary connection complete all as specified and as directed. (Note: earth work, Pole coping PCC, cable protection, pipe measured separately )
62M&L for dismantling taking out cables 10 sqmm to 16 sqmm from trench, including making straight through joints at damaged portion and relaying to trench complete all as specified and as directed (Note: Earth work, HDPE pipe for Cable protection will be measured and paid separately. Heat shrink straight through cable joints inclusive of quoted rate )
63M&L for dismantling taking out cables 25 sqmm to 35 sqmm from trench, making straight through joints at damaged portion and relaying to trench complete all as specified and as directed (Note: Earth work, HDPE pipe for Cable protection will be measured and paid separately. Heat shrink straight through cable joints inclusive of quoted rate )
64Supply and fixing PVC insulated, PVC round shethed copper flexible electric cable 1.5 sqmm 3 core, 1100 Volts grade and dismantling wornout/defective cables from SL/Flood light fitting at pole/tower top to JB at bottom of pole through pole /tower complete all as specified and as directed Make : Plaza / Gloster/Havells/Polycab.
65M&L for complete servicing, repair, maintenance of timer panel, by cleaning inside and outside, replacement of burnt MCB, MCCB, Timer, contactor, wiring, bypass toggle switch complete all as specified and as directed Note: Replacement of MCB, MCCB, Timer, Contactor shall be measured as supply only
66Supply only power contactor 3 phase, 415V, 32 amps cap utilsed for heavy duty by taking down the old perished / deteriorated contactor complete all as specified and as directedMake: Schneider, Model-ETVS-LC1E3201 or equivelent of Legrand/L&T/ABB
67Supply only surface mounting Analog time switchesheavy duty of 230 V 50Hz including dismantling taking down unsv one and complete all as specified and as directed Make : 6499 15 Maxi Rex 4QT (daily) of Legrand or equivelent of ABB/L&T
68Supply only MCB, SP, 10KA, "C" 6-32 A including dismantling taking down unsv onecomplete all as specified and as directed Make:- Schneider or equivelent of Legrand/ABB /L&T
69Supply only MCB, DP, 10KA, "C" 40A-63 A including dismantling taking down unsv one complete all as specified and as directed Make:- Schneider or equivelent of Legrand/ABB /L&T
70Supply only MCB, 4P, 10KA, "C" 40A-63 A including dismantling taking down unsv onecomplete all as specified and as directed Make:- Schneider or equivelent of Legrand/ABB/L&T
71Supply only MCCB with thermal magnetic release, 16 KA, 3 pole, 415V, 100 A, complete all as specified and as directedMake:- Schneider , Model- Easy compact CVS 100 BS, LV510950 to 58 or equivelent of Legrand/ABB/L&T
72M&L for dismantling of non - functional street light/flood lightfrom any type of pole at hight upto 9 mtr by suitable ladder for repair of the same for replacement unserviceable items like LED driver, connector block and decarbonising contact points and refixing the same to pole after repair of any type securitylight . Note:- Required LED driver shall be measured and paid separately
73Supply only LED driver suitable for street light fitting 1x 120 Watt, 230V, make- CG/halvells/Bajaj/Philips/Wipro
74Supply only LED driver suitable for street light fitting 1x 150 W , 230V, make- CG/halvells/Bajaj/Philips/Wipro
75Supply only LED driver suitable for flood light fitting 1x 200 W, 230v, make- CG/halvells/Bajaj/Philips/Wipro
76Supply only LED driver suitable for flood light fitting 1x 250 W, 230v, make- CG/halvells/Bajaj/Philips/Wipro
77S&F on wall/pole timer enclosure out door type complete with timerAnalog time switchesheavy duty of 230 V 50Hz,power contactor 3 phase MNX 18 , 415V, 32 amps, MCB, TPN, 10KA, "C" 40A-63 A with, rotary switch with connector for incoming and outgoing cable entry complete all as specified and as directed Make Indi Asian/Havells
78M&L for painting of steel fabricated light tower not less than 10 mtr high with one coat of aluminium paint after preparation of complete surface complete surface including writing tower number with synthetic enamel black paint complete all as specified and as directed
79M&L for painting of steel tubular pole any type / swan neck pole with one coat of aluminium paint after preparation of complete surface including writing pole number with synthetic enamel black paint complete all as specified and as directed
80M&L for white wash to pole coping PCC complete all as specified and as directed
81S & F Street light fitting LED 150 watt watt incl dismantling taking down unsv one complete all as specified and as directed.Make- CG or equivelent of halvells/ Bajaj/ Philips/ Wipro
82S & F Flood light fitting LED 210 watt watt incl dismantling taking down unsv one complete all as specified and as directed Make- CG or equivelent of halvells/ Bajaj/ Philips/ Wipro
83S & F Flood light fitting LED 300 watt incl dismantling taking down unsv one complete all as specified and directed, Make- CG, Model- CFS-501-300-57-60D-SL-GL-NGG or equivelent of halvells/ Bajaj/ Philips/ Wipro
84S & F Flood light fitting LED 350 watt incl dismantling taking down unsv one complete all as specified and directed, Make- CG, Model- CFS-501-350-57-60D-SL-GL-NGG or equivelent of halvells/ Bajaj/ Philips/ Wipro
85Taking down old unserviceable aviation light fitting, and supply & fix new LED aviation light fitting withyellow painted die-cast aluminium alloy housing, red coloured polycarbonate dome and accessories includingclamps, nuts, bolts and service connections up to the junction box complete all as per Make Bajaj andcat No.BJAOL 2 BC GLS 2 X 100W BC bajaj or eqiuvalent in philips/CG/havells/Wipro.
86Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft loose soil for cable work or from above cable duct complete all as specified and as directed
87Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed.
88Removing of excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
89M&L for dry sand cushioning for under groundcable provided with layer and sand 8 cm deep before laying the cable and 15cm after laying the cable complete all as specified and as directed.
90Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm complete all as specified and as directed
91Surface dressing of areas of above cable duct by Clearing away all grass, wild vegetation, saplings, shrubs, brushwood, undergrowth, roots, and trees not exceeding 30cm girth and removing rubbish upto a distance of 50 meters outside the periphery of the area under clearance complete all as specified and as directed
92M & L making chequrered plates as per existing sizes and thickness both side lifting handle as per existing one including painting of one coat red oxide primerand two coat of black bituminius paint, including necessary PCC wks as per site requirment and taking out of old UNSV chequered plate complete all as specified and directed.
93Cleaning of cable duct of size 1.2 x 1.0 by removing out all mud, soil, waste materials and disposal of waste materials to nearest gurbage bin and soil mud to low laying area of Dockyard
94S/F of cable Rack made with structural steel section of ISA 75X75X8MM,(FE-290, Gde E 165) pre-welded,inside duct, on wall , placing in position and fixing to wall with fastener steel bolt not less than20 mm dia,including painting with one coat of red oxide and two coat of black bituminous paint all as specified and directed. Note:- Cable rack drawing shall be obtained from Engr-in-Charge.
95Dismantling taking out unserviceable MS cable support from wall/ surface of gallery any type by removing nuts & bolts / cutting braces complete all as specified and as directed
96Taking out old UNSV HT UG cable of any size and any description including GI pipe of any dia and bricks for cable protection where ever appeared and complete all as specified and as directed Note:-(1) Excavation and earth work shall bemeasured and paid separately. (2) Serviceable cable obtained shall be stacked properly for re use.
97M & L XLPE insulated, screened, PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed,grade cross sectional area 185 sq. mm 3 core complete all as specified and as directed
98All as per item No 97.00 above but for cable sizes 240 sqmm 3 core
99All as per item No 97.00 above but for cable sizes 300sqmm 3 core
100All as per item No 97.00 above but for cable sizes 400sqmm, 3 core
101supply only Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm incl dismentling / taking down unserviceable one complete all as specified and as directed
102All as per item No 101.00 above (indoor termination) but for cable of size 240sqmm to 300 sqmm incl dismentling / taking down unserviceable one complete all as specified and as directed.
103All as per item No 101.00 above (indoor termination) but for cable of size 400 sqmm incl dismentling / taking down unserviceable one complete all as specified and as directed.
104supply only Cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185sqmm incl dismentling / taking down unserviceable one.
105All as per item No 104.00 above (straight through heat shrink type joint) but for cable of size 240sqmm to 400 sqmm incl dismentling / taking down unserviceable one complete all as specified and as directed.
106M & L for road cutting /hard standing to a depth not less than 80 cm and not less than 60 cm wide for laying of GI pipe to draw to UGcable and making good the disturbed surface by filling of PCC (1:3:6) type C-2 using 40 mm graded stone aggregate and finished the surface even and smooth with out using extra cement and disposal off the surplus debris and soil to a distance not exceeding 50 m complete all as specified and as directed by Engr-in -Charge.
107M & L 80 mm bore GI pipe tubes light grade for cable protection supporting with all fixing accessories (clamp, nuts, bolt and washer etc ) complete all as specified and as directed by Engr-in -Charge.
108Dismantling taking out HT Cable from cable rack/floor at gallery of marine jetty for repair/replacement of wornout steel cable rack or for realingnment of cable and refixingthe cables with proper staking with proper alignment of cable on repaired/existing rack and making feeder wise bundle of cable using PVC cable tie for sizes of cable 3 core, 185 to 240 sqmm, 11000 volts grade complete all as specified and as directed. Note:- Each cable shall be measured separately.Steel cable rack shall be measured separately as supply and fix
109All as per item No 108.00 above but for cable sizes 300 to 400 sqmm, 3 core.
110M&L for finding of cable fault of UG 11000 volts grade cable inside trench (under soil / drain/PCC/road/trench ) by disconnecting both cable ends, using insulation tester, cable path/fault finder and rectification complete by necessary excuvation, cutting at fault position, fixing of straight through heat shrink joint, for cable sizes 185 sqmm to 400 sqmm, 3 core, 11000 volts grade or replacement of heat shrink indoor cable joint kit of size 185 sqmm to 400 sqmm, 3 coreand reconnection of both cable end to original position after complete satisfactory insulation test, fixing with old or required new nuts-bolts-washers complete with testing complete all as specified and as directed Note: (a) Items required for rectification such as heat shrink indoor cable joint kit / heat shrink straight through joints / heat shrink sleeves and earth work shall be measured separately . (b) required aluminium cable lugs and nuts-bolts-washers shall be inclusive of quoted rate. (c) Contractor shall bring necessary testing equipment and rate shall be inclusive of quoted rate.
111M&L for earthing complete with glvn. GI plate earth electrode 60cmx60cmx6 mm thick burried in ground vertically to a depth n. less than 1.5 m below normal GL, connected to GI strip32x6 mm earth lead by means of nuts, bolts, check nuts & washers all as specified and indicated inclu. concrete pit in PCC 1:3:6 type C-2 RCC, precast pit cover slab 400mmx400mmx80mm with handle for lifting made out of 8mm dia MS rod fixed flush to pit, funnel, wiremesh, 20mm dia GI pipe medium grade for watering charcoal and salt in alternate layers including necessary earth work excuvation & removal etc complete all as specified in plate No 5 of SSR Part-I 1991(Zone E)
112M & L for Earth continuity conductor GI strip of size 32 X 6 mm .
113Painting chequrered plates as per existing sizes and thicknessof one coat red oxide primerand two coat of black bituminius paint, complete all as specified and as directed
114Supply and Fix cable route indicator to indicate path of HT cable 11000 Volte material usde cast iron with pcc work complete all as specified and as directed
Disclaimer :