Repair To Internal Elecrtrification,Mcbs And Dbs And Other Fittings And Fixtures In Technical Area At Main Campus Of Ge (Af) Chandigarh , chandigarh-Chandigarh

Military Engineer Services-MES has published Repair To Internal Elecrtrification,Mcbs And Dbs And Other Fittings And Fixtures In Technical Area At Main Campus Of Ge (Af) Chandigarh . Submission Date for this Tender is 29-07-2022. Electrical Maintenance Tenders in chandigarh Chandigarh. Bidders can get complete Tender details and download the document.




Tender Notice

32819602
Corrigendum : Repair To Internal Elecrtrification,Mcbs And Dbs And Other Fittings And Fixtures In Technical Area At Main Campus Of Ge (Af) Chandigarh
Open Tender
Indian
Chandigarh
chandigarh
29-07-2022

Tender Details

Repair To Internal Elecrtrification,Mcbs And Dbs And Other Fittings And Fixtures In Technical Area At Main Campus Of Ge (Af) Chandigarh

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Jul-2022 Date Corrigendum Date 22-07-2022
2 08-Jul-2022 BOQ Corrigendum BOQ 22-07-2022
3 22-Jul-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 29-07-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 40000.0 /-
Tender Value
INR 20 Lakhs /-

BOQ Items

Name of Work: REPAIR TO INTERNAL ELECRTRIFICATION,MCB"s and DB"s AND OTHER FITTINGS AND FIXTURES IN TECHNICAL AREA AT MAIN CAMPUS OF GE (AF) CHANDIGARH
Sl. No. Item Description
1Taking down copper/aluminium point wiring (light, fan, socket or power) complete, removing materials to store for keeping in safe custody or for taking credit (credit for mentioned items shall be made as per conditions separately) and making good disturbed surface of walls, floors, etc. complete all as specified and directed.
2M&L for point wiring complete with single core multi stranded Copper conductor cable of size 1.5 sqmm PVC insulated unsheathed 1100 volt grade in and including PVC conduit of size 20 mm dia including Tee, junction, bends etc concealed in wall/fixed on ceiling and including M.S modular boxes of suitable size for housing modular switches, sockets etc including 1.5 sqmm green PVC insulated wire for earth continuity complete all as specified and directed.
3One light/fan point controlled by one way switch
4One three pin 5 amp socket outlet multipurpose on independent board
5One three pin 5 Amp switch socket cum on same board
6All as per item No 2 above but with 2.5 sqmm cable insulated for 3 pin 15 amp multipurpose outlet including 1.5 sqmm PVC insulated copper wire for earth continuity on independent board complete all as specified and directed.
7S&F in replacement of switch piano type, flush type, single pole, one way, 5 Amps complete all as specified and directed.
8S&F in replacement of socket outlet flush type 2/3 pins,6 Amps multipurpose, complete all as specified and directed.
9S&F in replacement of switch piano type, flush type, single pole, one way, 16 Amps, complete all as specified and directed.
10S&F in replacement of socket outlet, flush type, multi purpose 3 pin, 6 Amps & 16 Amps, 230 volts, complete all as specified and directed.
11S&F in replacement of switch bell push, flush type, 05 Amps (230 volts) ,complete all as specified and directed.
12S&F in replacement ceiling rose, surface bakelite, 65 x 50 mm, two to three terminals, complete all as specified and directed.
13S&F in replacement ceiling fan regulators, step type, electronic for 1200/1400 mm sweepcomplete all as specified and directed.
14S&F in replacement of wiring for circuit/Sub main wiring along with earth wire with two runs single core 2x 4 Sqmm (nominal area) PVC insulated and unsheathed cables with stranded copper FRLS conductor in and including PVC concealed conduit 20mm dia ISI markedincluding one run of continuous PVC insulated FRLSmultistranded copper cable of size 1x4 Sqmm earth wirefor earth continuity conductorcomplete all as specified and directed. Note: Two runs of 4 sqmm single core and one run of 4 sqmm single core with PVC Conduit complete will be measured as one unit.
15S&F in replacement of wiring for circuit/Sub main wiring along with earth wire with two runs single core 2x 6 Sqmm (nominal area) PVC insulated and unsheathed cables with stranded copper FRLS conductor in and including PVC concealed conduit 20mm dia ISI markedincluding one run of continuous PVC insulated FRLSmultistranded copper cable of size 1x6 Sqmm earth wirefor earth continuity conductorcomplete all as specified and directed, Note: Two runs of 6 sqmm single core and one run of 6 sqmm single core with PVC Conduit complete will be measured as one unit.
16S&F in replacement sheet metal enclosure for IncomingMCCB and outgoing MCBs factory made double door, VTPN 415Volts 4ways with 200 Amp bus bar with IP43 protection complete in all aspects all as specified and directed.
17Supply, fix, connecting and testing MCCB four pole, 100 Amps, 415 volts, 16kA breaking capacity with fixed thermal and magnetic conforms to IS/IEC:60497-2 including taking down the existing one complete all as specified and directed.
18Supply, fix, connecting and testing MCCB four pole, 125 Amps, 415 volts, 16kA breaking capacity with fixed thermal and magnetic conforms to IS/IEC:60497-2 including taking down the existing one complete all as specified and directed.
19S&F in replacement sheet metal enclosure single pole and neutral with a two pin & earth plug and socket complete including one Double pole MCB 20 Amps, "C" series 240 volts 10 KAcomplete all as specified and directed.
20S&F in replacement MCB SP 240 Volts, 6 Amps to 32 Amps, 10 KA, "B" seriescomplete all as specified and directed.
21S&F in replacement MCB SP 240 Volts, 63 Amps,10 KA, "B" seriescomplete all as specified and directed.
22S&F in replacement MCB, SPN, 240V, 63 Amps AC, 10 KA, "B" seriescomplete all as specified and directed.
23S&F in replacement MCB, SPN, 240V, 40 Amps AC, 10 KA, "B" series complete all as specified and directed.
24S&F in replacement DB sheet metal enclosure, double door for MCBs, company made, SPN 240 Volts, 8 ways with IP 42 protection complete all as specified and directed.
25S&F in replacement DB sheet metal enclosure, double door for MCBs, company made, SPN 240 Volts,4 ways with IP 42 protection complete all as specified and directed.
26S&F in replacement LED light fitting mirror type with high output diffuser, 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed
27S&F in replacement ofround slim surface mounted LED panel6 Watt6500 K with PDC aluminium housing and high transparent frosted plastic diffuserto ensure glare free & even light distributionComplete all as specified and directed.
28S&F in replacement ofLED lights fittingcompact commercial batten type suitable for single T8 LED tube 1x20 Watt ,includingLED tube light 20 watt connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
29S&F in replacement ofLED luminaries 600 mm x 600 mm, 36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cable of suitable size complete all as specified and directed.
30S&F in replacement of louvers suitable for exhaustfan steel body of size 300 mm sweep complete all as specified and directed.
31S&F in replacement of louvers suitable for exhaustfan steel body of size 450 mm sweep complete all as specified and directed.
32S&F in replacement of LED flood light luminaries 200 Wattmade up of pressure die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP-66 protection, system efficacy not less than 110 lumens per wattwith 10KV built-in surge protection device with electrical connections complete all as specified and directed.
33S&F in replacement energy saving, environment friendly & robust highbay LED 150 watt with PDC housing suitable for industrial application for ceiling (surface/suspended) made up of pressure die cast aluminium housing with toughened glass and high power LEDswith IP-66 protection, system efficacy not less than 110 lumens per wattwith 10KV built-in surge protection device with electrical connections complete all as specified and directed.
34S&F in replacement indoor elegant suspendedLED light fittings 36 watt4 feet lighting solution 75 mm width and 85 mm height, cleanluminance levelwith mounting arrangements , efficacy not less than 100lumens per wattwith electrical connections including joining kit and mains cable complete all as specified and directed.
35M&L disconnecting and taking down the complete exhaust fan flame proofof 300 mm sweep 240/415 V from the existing locationand carry out rewinding by dismantling from frame with and includingsuper enameled copper wire of suitable gaugeincluding replacement of insulating materials such as laminated lethroid paper, sleeves, necessary varnishing with golden colour varnish, greasing, lubricating, replacement of missing / worn out nuts, bolts & washers, split pins etc. and testing, complete all as specified and directed.
36S&F in replacement of LED drivers suitable for 35/36 watts2x 2 panel fittings complete all as specified and directed.