| 1 | Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depthfor foundation of pole,laying of cables etc in Hard and dense soiland getting out complete all as specified and directed. |
| 2 | Excavating in trenches not exceeding 1.5m wide and exceeding 1.5 m but not exceeding 3.00m in depth for foundation of pole, laying of cables etc in hard/dense soil and getting out complete all as specified and directed. |
| 3 | Returning fillingin including spreading, leveling, watering and well ramming in layer not exc 25 cm complete all as specified and directed. |
| 4 | Removing excavated material not exc 50 mtr and depositing where directed at a level not exc. 1.5 m above the starting point complete all as specified and directed. |
| 5 | M&L for providing dry river sand as in sand cushioning to UG cable including punning gently all as directed. Note : Depth after punning shall be measured and paid. |
| 6 | M&L for plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundtion of PCC poles/struts all as specified and directed. |
| 7 | M&L for plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundtion of pole/stay assembly etc including necessary form work, all as specified and directed. |
| 8 | M&L for plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate for padestal/coping around poles, including necessary form work, finishing even and smooth without using extra cement, all as specified and directed. |
| 9 | Taking outsub class burnt bricks from the trenches and stacking at site serviceable /unserviceable bricks for reuse. |
| 10 | Supply and laying sub classold \"B\" burnt bricks laid as cable protection covercomplete all as specified and directed. |
| 11 | Laying only sub class brunt bricks as cable protection cover all as directed. |
| 12 | Dismantling old unserviceable Steel poles/struts, any size complete all as specified and directed. |
| 13 | M&L for steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws, type 410 SP-31 (09 Mtr long) including two coats of bituminous paint internally and externally for the portion embedded in concrete and two coats of aluminium paint over one coat of red oxide primer to external/exposed surfaces complete all as specified and directed . Note:- Excavation/PCC will be measured and paid separately under relevant items |
| 14 | Dismantling cross-arms of M.S channel or angle sections etc. complete all as specified and directed. |
| 15 | Taking out the existing PVC/XLPE, 1100 volts grade,LT UG electric cable with glands, cable protection pipes etc., complete from the trenches/fixed on wallremoving the unserviceable fault cable andcarefully stacking the serviceable cable for reusing all as specified and directed by the Engr-in- charge for the following sizes of cable. Note:- Excavation and Earth work shall be measured and paid separately under appropriate items all as per existing make |
| 16 | (a)6 Sqmm 2 core |
| 17 | (b) 10 Sqmm 2 core |
| 18 | (c) 16 Sqmm 2/4 core |
| 19 | (d) 35 sqmm 3.5 core |
| 20 | (e) 50 sqmm 3.5 core |
| 21 | (f)70 sqmm 3.5 core |
| 22 | (g) 95 sqmm 3.5 core |
| 23 | Re-Laying only in trenches/fixed on wall (or) passing through pipes/in floors, connecting up testing and commissioning of Serviceable PVC/XLPE , 1100 volts grade, LT UG electric cable obtained vide item No 7 above all as per existing make complete all as sepcified and directed for the following sizes of cable :- |
| 24 | (a) 35sqmm 3.5 core |
| 25 | (b) 50sqmm 3.5 core |
| 26 | (c) 70sqmm 3.5 core |
| 27 | (d) 95sqmm 3.5 core |
| 28 | Supplying & laying, XLPE insulated PVC inner sheathed, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor, 1100 volt grade, laid in trenches/duct, passing through pipe/duct or fixed on pole and connecting and testing complete all as specified and directed for following size of cable :- |
| 29 | (a)6 sqmm 2 core |
| 30 | (b) 10 sqmm 2 core . |
| 31 | (c) 10 sqmm 4 core . |
| 32 | (d) 16 sqmm 4 core . |
| 33 | (e) 35 sqmm 3.5 core |
| 34 | (f)50 sqmm 3.5 core |
| 35 | (g) 70 sqmm 3.5 core |
| 36 | (h) 95 sqmm 3.5 core |
| 37 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for cable of following sizes :- |
| 38 | (a) 25 sqmm 3.5 core . |
| 39 | (b) 35 sqmm 3.5 core . |
| 40 | (c) 50 sqmm 3.5 core |
| 41 | (d) 95 sqmm 3.5 core |
| 42 | S&F, in repair, GI pipe 80mm bore, light grade, laid below road / fixed along thepoles / walls with necessary clamping, etc complete all as per specified and directed. |
| 43 | S&F, in repair, GI pipe, 40mm bore, light grade, laid below road/fixed along thepoles / walls with necessary clamping, etc complete all as per specified and directed. |
| 44 | Dismantling of old un-serviceable ACSR conductor of any size and make from LT over head line complete all as specified and directed. |
| 45 | M&L for ACSR squeral type conductor of any size drawn for over head line fixed to insulator with binding wire complete all as specified and as directed. |
| 46 | Supply and fix LT junction box for street light, FRP type with hinged type door and locking arrangement, off white colour, of size 300 x 200 x 105mm(internal)comprising of suitable size Aluminium busbar 3 rows with terminals,1 No bakelite base neutral link and 01 No earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs all as specified and as directed. |
| 47 | S&F, in repair, FRP insulated and PVC sheathed copper conductor cable of size 1.5 Sqmm, 3 core, 1100 volts grade, multistranded, passing throuth existing pipe, fixed on pole/wall from juntion box to street light fitting complete all as specified and directed. |
| 48 | S&F, in repairs, bracket made out of light grade, Galvanised steel tube, 35mm bore, 1.2 Mtr length, bent to 120 degree for fixing street light fitting at the top, fixed to pole with necessary clamps made out of FI 40mm x 4mm with nuts & bolts including preparation of steel surfaces & apply two coat of synthetic enamel paint over red oxide prime rincluding taking dowo oldcomplete all as specified and directed. |
| 49 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure diecast aluminum hosing and heat resistant including taking dowo old complete with driver, lamp bracket with impactand corrosion resistant including thermalmanagement in multiple optics complete withIP 66 protection complete |
| 50 | M&L for stay assembly complete with accessories as shown in electrical plate No. 1, complete with galvanised stay strand of size 7/3.5mm with vitreous porcelain looptype insulator,white, brown or green with over all dimension 65x90 mm, clearance of hole16 mm, stay clamps made out of FI 50mmx 6 mm complete with nut, bolts and washer of galvanised ironincluding excavation & earthwork in any type of soil and concretework in PCC (1:3:6) type C-2 using 40mm graded stone aggregate (Pit size 800x600x1200mm) complete all as specified and directed and including taking down old stay assembly. |
| 51 | M&L, in repair, Pin type porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volt grade including taking down unservicebale insulator complete all as specified and directed. |
| 52 | M&L, in repair,shackle type insulator, porcelain vitreous, white, brown or green, 75 mm height, 90 mm dia for working pressure 1100 volt grade including galvanized mild steel straps, 31 x 3 mm washers, insulator GI bolts of 12 mm diaincluding taking down unservicebale insulator complete all as specified and directed. |
| 53 | Suplying, fabricating & fixingstructural mild steelchannel, angle, iron, flat iron and brackets etc for fabrications of cross arms, bracings, supports, D-clamps, stiffeners,eye hooks, bolts,pole clamps and back platesincluding nuts, bolts and washers, welding banding cold , or hot drilling holes for insulators bolts in any shape or sizeas indicated or directed and inclusive of one red oxide primer coat, one under coat and one finishing coat of aluminium paint complete. |
| 54 | M&L for horinzontal borring under the road in soft/loose strata for insertion of GI tube up to 80mm bore all as directed. |
| 55 | M&L, in repairs, earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth strip of 32x6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SSR Part I connected to earth test point using as earth lead all as specified and testing on completion includingprovisionof earth lead protected by 40 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work in any type of soil, PCC pit with RCC cover, char coal, salt, funnel etc complete. Note : Rate quoted by tenderers shall be deemed to include for following provisions;-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 M.[ii]. PCC 1:3:6 type C1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B1 cover 50x50 cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore [ISI marked] medium grade & copper lugs, charcoal & salt as reqd.[v]. GI protection pipe of size 40 mm bore light grade 7.5m. |
| 56 | Disconnecting the existing Unserviceable MCCB, taking out from the panel board and replace by S&F new MCCB, thermal & adjustable magnetic setting, fixed in existing panel and connecting with existing cable, including nuts bolts and washer etc complete all as specified and directed for the following capacity of MCCB :- |
| 57 | (a) MCCB of rating 250 Amp, 35/36 KA breaking capacity, 4 pole. |
| 58 | (b) MCCB of rating 200 Amp, 36 KA breaking capacity, 4 pole. |
| 59 | (c) MCCB of rating 160 Amp, 36 KA breaking capacity, 4 pole. |
| 60 | (d) MCCB of rating 125 Amp, 36 KA breaking capacity, 4 pole. |
| 61 | (e) MCCB of rating 100 Amp, 25 KA breaking capacity, 4 pole. |
| 62 | (f)MCCB of rating 63 Amp, 16 KA breaking capacity, 4 pole. |
| 63 | Disconnecting the existing Unserviceable MCCB, taking out from the panel board and replace by S&F new MCCB, thermal & adjustable magnetic setting, fixed in existing panel and connecting with existing cable, including nuts bolts and washer etc complete all as specified and directed. Make : STANDRAD / HAVELLS / ABB/C&S/ L&T |
| 64 | (a)MCCB, 200 Amps, 35/36 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 pole |
| 65 | (b)MCCB of rating 160 Amp, 36 KA breaking capacity, 3 pole |
| 66 | (c)MCCB of rating 125 Amp, 25 KA breaking capacity, 3 pole |
| 67 | Supply, installation, commissoning and testing, in repair, feeder pillar board,Kiosktype, LT(415 Volts, 50 Hz , 3-phase, 4 wire supply) plinth mounted, factory made, outdoor type,weather and vermin proof (Protection Class IP-54) made out of 50m x 50mm x 5mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet powder coated with front & back hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enemell gray paint (First Quality) over a coat of red oxide primer, grouting panel through angle iron 0.45 mtr in ground and 0.3 mtr over the ground including excavation & earth work in any type of soil and PCC (1:3:6) type C-2 using 40mm graded stone aggregate complete comprising of the followings:- (a) Incoming supply:- (i) Aluminium bus bar chamber 350 amps rating of 04 strip - 01 No (ii) MCCB, thermal and meganitic setting, 4 pole AC 415volts, 200 Amp rating, 35 KA rupturing capacity - 01 No (iii) Digital type voltmenter 0-500 V with selector switches - 01No (iv) Digital type Amp meter 0-300A with selecter switch with CT ratio 300/5- 01 No (v) Indicatiing lamp Neon type for R-Y-B - 3 Nos (b)Outgoing supply:- (i) MCCB, thermal and meganitic setting, 4 pole AC 415volts, 160 Amp rating, 36 KA rupturing capacity - 02 No (ii) MCCB, thermal and meganitic setting, 4 pole AC 415volts, 125 Amp rating, 25 KA rupturing capacity - 02 No. (iii) MCCB, thermal and meganitic setting, 4 pole AC 415volts, 63 Amp rating, 16 KA rupturing capacity - 02 No. (iv) MCB SPN, C-curve, 32 Amps, AC 230 Volt - 03 No including internalconnections |
| 68 | Supply, installation, commissioning and testing, feeder piller board,Kiosktype , LT (415 Volts, 50 Hz , 3-phase, 4 wire supply), plinth mounted, factory made, outdoor type,weather and vermin proof made out of angle iron frame and 3.00 mm thick MS Sheet CRCA sheet powder coated with front & back hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint (First Quality) over a coat of red oxide primer, grouting panel through angle iron, 0.2 mtr in ground and 0.30 mtr over the ground including excavation & earth work in any type of soil and PCC complete comprising of the followings:- (a) Incoming supply:- (i) Aluminium bus bar 100 amps rating of 04 strip having suitable whole with nuts and bolts (ii) MCCB 63 Amps, 04 pole415 Volt-01 No, (iii) MCB 40 Amp, 04 pole, 415 Volts-04 Nos (iV) MCB 40 Amp, 02 pole, 230 Volts-02 Nos(v) Digital type multifunctional meter showing A, V, Hz etc with suitable CT ratio -1No (vi) Indicating lamp Neon type for R-Y-B - 3 Nos. |
| 69 | M&L for fault finding of LT cable by using cable fault dectector machine and other necessary T&P, finding out the spot of cable fault and marking on ground complete for any size and length of cable all as specified and directed. (Note : Fault dectector and other necessary T&P shall be arranged by the contractor without pay any extra cost by the Dept.) |
| 70 | Supply and erecting of CI Cable path indicators made out of MS sheet duly marked with LT cable 415 volts and with MS angle embeded in PCC 1:4:8 with 60 cm below ground level and 30cm above groundwithsheetpaintedby \" Blue colour” complete all as specified and directed by Engr-in-charge. |
| 71 | M&L for painting of indoor/outdoor LT panel of any size with two coats of synthetic enamel grey colour paint after throughly scrapping/cleaning the rushed portion and fixing the LT panel door properly do the welding work if necessary and miscelleneous items complete all as specified and directed by Engr-in-Charge |