Repair/Maintenance Of Security/ Street Hgih Mast Solar Light System And Other Connected Works At Nad Bheemunipatnam And Ins Karna Visakhapatnam And Repair/ Maintenace Of E/M Installation And Other Misc Allied Work At Ins Kalinga And Nad Bheemuniatnam, visakhapatnam-Andhra Pradesh

Military Engineer Services-MES has published Repair/Maintenance Of Security/ Street Hgih Mast Solar Light System And Other Connected Works At Nad Bheemunipatnam And Ins Karna Visakhapatnam And Repair/ Maintenace Of E/M Installation And Other Misc Allied Work At Ins Kalinga And Nad Bheemuniatnam. Submission Date for this Tender is 19-07-2022. Solar Light Tenders in visakhapatnam Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

32620711
Corrigendum : Repair/Maintenance Of Security/ Street Hgih Mast Solar Light System And Other Connected Works At Nad Bheemunipatnam And Ins Karna Visakhapatnam And Repair/ Maintenace Of E/M Installation And Other Misc Allied Work At Ins Kalinga And Nad Bheemuniatnam
Open Tender
Indian
Andhra Pradesh
visakhapatnam
19-07-2022

Tender Details

Repair/Maintenance Of Security/ Street Hgih Mast Solar Light System And Other Connected Works At Nad Bheemunipatnam And Ins Karna Visakhapatnam And Repair/ Maintenace Of E/M Installation And Other Misc Allied Work At Ins Kalinga And Nad Bheemuniatnam

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Jul-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 08-07-2022
2 06-Jul-2022 corrigendum in date Date 19-07-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 34000.0 /-
Tender Value
INR 17 Lakhs /-

BOQ Items

Name of Work : REPAIR/MAINTENANCE OF SECURITY/ STREET HGIH MAST SOLAR LIGHT SYSTEM AND OTHER CONNECTED WORKS AT NAD BHEEMUNIPATNAM AND INS KARNA VISAKHAPATNAM AND REPAIR/ MAINTENACE OF E/M INSTALLATION AND OTHER MISC ALLIED WORK AT INS KALINGA AND NAD BHEEMUNIATNAM UNDER GE(P) NAVY KALINGA
Sl. No. Item Description
1Taking down carefully existing aluminium conductor point wiring (light / fan / socket or power point) complete, with all fittings such as switches, socket, regulator, ceiling rose, utility light fittings and lamp holders etc and removing materials from site and making good the disturbed surfaces of walls roof and floor etc as per existing specification complete all as specified and as directed.
2Taking down carefully by unscrewing from boards / outlet boxes, fittings and fixtures such as switches, sockets, ceiling roses, lamp holders, brackets, ceiling fittings, bulk head fittings, tube light fittings and fan regulators etc. for reuse at site complete all as specified and as directed.(Note : To be measured only when found serviceable in all respects complete for reuse)
3Material and labour for point wiring for one light controlled by 1 one way switch with 1.5 Sqmm PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable 1100 Volts grade drawn carefully through existing/New concealed conduit along with 1.5 sqmm continuous PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable for earth continuity wire, connected to earth dolly and to be terminatedfor mountingswitches, sockets, fan regulators etc including testing on completion complete including making good disturbed surface all as specified and as directed.
4All as per Item no 3 here-in-before but for one fan point controlled by 1 one way switch and regulator all as specified and as directed.
5All as per Item no 3 here-in-before but for one switch socket outlet, 5 Amp on same board with other switches all as specified and as directed
6All as per Item no 3 above but for one 3 pin switch socket outlet, 5 Amp on independent board all as specified and as directed.
7All as per Item no 3 here-in-before but for one16 Amp 3 & 5 pin switch socket outlet, independent with 4 Sqmm single core multi-stranded copper conductor cable (FRLS) along with 4 sqmm continuous PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable for earth continuity wire all as specified and as directed.
8Supply and fixing switch piano flush button single poleone way 5 amps all as specified and as directed
9Fixing only switch flush button single pole one way 5 amp all as specified and as directed. (Note : Material obtained from item No 2 here in before shall be re-used)
10Supply and fixingsocketcombination 2 in 1 3 pin 5 amp flush type universalall as specified and as directed.
11Fixing only switch socket outlet 5 amp flush typeall as specified and as directed. (Note : Material obtained from item No 2 here in before shall be re-used)
12Supply and fixingsocketcombination 2 in 1 3 pin 5 and 15 amp flush type universalall as specified and as directed.
13Supply and fixing ceiling rose surface bakelite three terminals all as specified and as directed.
14Fixing only ceiling rose surface bakelite three terminals all as specified and as directed. (Note : Material obtained from item No 2 here in before shall be re-used)
15Supply and fixing fan regulator electronic deluxe rotary step type all as specified and as directed.
16Fixing only fan regulator any type all as specified and as directed. Note : Material obtained from item No 2 here in before shall be re-used
17Supply and fixing indoor luminare decorative batten for wall/ceiling mountingenergy efficient saving LED BATTEN LIGHT 18 /20 W 4" (feet) with inclLED Tube T8 Type long incl twin twisted copper conductor flexible wire from ceiling rose to connector with taking down old unserviceable one complete all as specified and as directed.
18M & L forLED Tube 18 /20 watt Fixing in existing unserviceable tube light Fitting with taking down old unserviceable tube complete all as specified and as directed
19M & L forLED Tube 10 watt Fixing in existing unserviceable tube light Fitting with taking down old unserviceable tube complete all as specified and as directed
20S&F on wall security light luminaire for 1x25 w LEDwith deep drawn housing complete with and including cable for connection from ceiling rose with 1.5 Sqmm PVC insulated stranded copper conductor complete all as specified and as directed.
21Supply and fixing LED Strip Light 10Watt with Suitable Driver of same makeFixing in False ceiling Grooves at Required Siteand installed By Expert Electrician and Connect From existing incoming wire, incl taking down old u/scomplete all as specified and as directed .
22Supply and fixing LED Flood Light 120 W, IP65 suitable for at Existing falseCeiling/ Pole/ wall/ Tower/ Ground with suitable size necessary fitting and fixture(hook/suspended rod of reqired size) existing electric incoming cable including taking down old unservicebale one complete all as specifiedand as directed.
23Supply and fixing LED highbay Light 150 W, IP66 suitable for at Existing false Ceiling /shedwith suitable size necessary fitting and fixture (hook/suspended rod of reqired size) existing electric incoming cable, including taking down old unservicebale one complete all as specifiedand as directed.
24Supply and fixing LED lamp 40 Watt in repairs of existing lamp fitting any type and size,incl taking down old u/s, all as specified and as directed .
25Supply and fixing lamp holder insulated body suitable for Retrofitlampincl taking down old u/s, all as specified and as directed.
26Supply and fixing sheet metal enclosure for two pin and earth plug and socket complete with one 20 ampsMCB, incl taking down old u/s all as specified and as directed .
27Supply and fixing sheet metal enclosure for MCB, DBs, phosphatised, Powder coated , Triple Pole and Neutral (TPN), suitable for 4 way, Double door 415 Volts all asincl taking down old u/s specified and as directed .
28Supply and fixing sheet metal enclosure for MCB, DBs, phosphatised, Powder coated , single pole and neutral (SPN) 240 Volt , double door, suitable for 8 way with dim rail earth and neutral bar all asincl taking down old u/s specified and as directed.
29Supply and fixing sheet metal enclosure for MCB, DBs, phosphatised, Powder coated , single pole and neutral (SPN) 240 Volt , double door, suitable for 4 way with dim rail earth and neutral bar all asincl taking down old u/s specified and as directed.
30Supply and fixing MCB FourPole (FP) C curve 10kA breaking capacity of63 amps, 415 Volts in proper position incl taking down old u/sall as specified and as directed.
31S&F in proper position MCB Double Pole of capacity up to 40 amps, 240 Volts c-series with 10kA breaking capacityall as specified and as directed.
32Supply and fixing MCB Single Pole (SP) C curve 10kA breaking capacity of6 to 32 amps, 240 Volts in proper positionincl taking down old u/sall as specified and as directed.
33Material and labour for sub main wiring with two single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 6 sqmm and one single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 6 sqmm as in continuous earth wire drawn into andExisting/ New , concealed/surfacePVC conduit medium grade 25mm dia ISI marked complete with fittings and fixings accessories complete with taking down old unserviceable submain wiring and including cutting chases pinning and making good disturbed surface complete all as specified and as directed.
34Material and labour for sub main wiring with two single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 4.0 sqmm and one single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 4.0 sqmm as in continuous earth wire drawn into andExisting/ New , concealed/surfacePVC conduit medium grade 25mm dia ISI marked complete with fittings and fixings accessories complete with taking down old unserviceable submain wiring and including cutting chases pinning and making good disturbed surface complete all as specified and as directed.
35Material and labour for sub main wiring with two single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 2.5 sqmm and one single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 2.5 sqmm as in continuous earth wire drawn into andExisting/ New , concealed/surfacePVC conduit medium grade 25mm dia ISI marked complete with fittings and fixings accessories complete with taking down old unserviceable submain wiring and including cutting chases pinning and making good disturbed surface complete all as specified and as directed.
36Material & Labour for taking down theunserviceablecontactor & burned out copper wire, lugs and supply and fixing new powercontactor 3 pole AC control capacity 25 Amp,220-240 coil volt, including the copper wire &copper lugs and testing complete all as directed. (Make : GE Cat no:- CL01A310T orequivalent as approved by GE.)
37Material & Labour for taking down theunserviceablecontactor & burned out copper wire,lugs and supply and fixing New power contactor 3 pole AC control capacity 25 Amp, 220-240 coil volt, including the copper wire& copper lugs and testing complete all as directed. Make : GE cat no:-CL25A300T orequivalent as approved by GE.
38Material & Labour for taking down theunserviceablecontactor & burned out copper wire,lugs and supply and fixing New power contactor 3 pole AC control capacity 32 Amp mounting type Din rail , 220-240 coil voltincluding the copper wire& copper lugs and testing complete allas specified and as directed. Make : ABB cat no: A30-30-10 orequivalent as approved by GE.
39Material & Labour for taking down theunserviceablecontactor & burned out copper wire,lugs and supply and fixing power contactor 3 pole AC control capacity 25 Amp mounting type Din rail 220-240 coil voltincluding the copper wire& copper lugsall as specified and as directed, Make :C&S Model No : TC1D2510 orequivalent as approved by GE.
40Material & Labour for taking down theunserviceablecontactor & burned out copper wire lugs and supply and fixing power contactor 3 pole AC control capacity 30 Amp,MNX12 TYPE, mounting type Din rail all as specified and as directed, Make :L&T MODEL no: CS94108 orequivalent as approved by GE.
41Material & Labour for taking down theunserviceablecontactor & burned out copper wire,lugs and supply and fixing power contactor 3 pole AC control capacity 32 Amp, MNX32 TYPE, mounting type Din rail all as specified and as directed.
42Material & Labour for taking down theunserviceablecontactor & burned out copper wire, lugs and supply and fixingauxiliary contract block single phase DCvoltage 600 V power contactor 3 pole AC control capacity 25 Amp all as specified and as directed. Make : GE cat no:-BCLP10 orequivalent as approved by GE.
43Material & Labour for taking down theunserviceableCONTACT BLOCK and supply and fixingauxiliary contract block single phase DCvoltage 600 V power contactor 3 pole AC control capacity 25 Amp. Make : C&S Modelno:-TA1-DN 22 orequivalent as approved by GE.
44Material & Labour for taking down theunserviceableCONTACT BLOCK and supply and fixingauxiliary contract block single phase DCvoltage 600 Vpower contactor 3 pole AC control capacity 25 Amp Make :L&T MODEL no:-MNX-A2 orequivalent as approved by GE.
45Material & Labour for taking down theunserviceable Timer and supply and fixing Timermounting din rail rated voltage 230 V ,IP 50all as specified and as directed. MAKE:-SELEC CAT N0-800 SD-2-230 ororequivalent as approved by GE.
46Material & Labour for taking down theunserviceable relay and supply and fixingrelaysRT series wide range of AC AND DC COIL VOLTAGE high switching current capability and reliable,long operational , all as specified and as directed
47Material & Labour for taking down relays and supply and fixingrelays ,range 14 to 23 amps , MN series type MN2 high switching current capability and reliable,long operational , all as specified and as directed.
48Material & Labour for taking down relyas and supply and fixingrelays ,range 09 to 15 ampsMN series type MN2 , high switching current capability and reliable,long operational , all as specified and as directed.
49S&F Digital Ammeter, 3 phase, 5 Amps, class 1, AC supply as fixed in repairs , incl taking down old u/s ,complete all as directed.
50S&F Digital Voltmeter,3 phase,5 Amps,class 1,AC supply as fixed in repairs complete all as directed.
51S&F MPD Power supplier of capacity 5-30 Amps auxilary supply,15 V,AC 230V,50Hz,AC supply as fixed in repairs ,incl taking down oldu/s complete all as directed.
52Material & Labour for taking down the defective unserviceablesolenoid valve coil and supply & fixing of new coil suitable to work in single phase, AC 220 V,50 Hz complete all as directed.
53Taking down unserviceable single phase preventer and S&F new single phase preventer,6 wires,230 V complete all as directed.
54Supply and fixing modular plate switch flush type, single pole one way 16 Amps 250 voltswith taking down old unserviceable oneall as specified and as directed.
55Supply and fixing modular socket 6 Amps 5 pin. with taking down old unserviceable oneall as specified and as directed.all as specified and as directed.
56Supply and fixing modular socket 6-16 amps 2/3 pin combined shuttered with taking down old unserviceable oneall as specified and as directed.
57Supply and fixing modular step fan speed regulator 120 w ,2 modulewith taking down old unserviceable oneall as specified and as directed.
58Supply and fixing modular plates white colour suitable for flush metal boxes for mounting modular switches or sockets etc for 8 modules.
59All as per item No. 58 here-in-before but for 6 modules all as specified and as directed.
60All as per item No. 58 here-in-before but for 3 modules all as specified and as directed.
61All as per item No. 58 here-in-before but for 2 modules all as specified and as directed.
62Comprehensive repair/maintenance electric operating system with gear and 3 phase 415 V for rooling shutter motor Dismantling the electrical connection from systemand removing outthe Induction Motor and Gear Box forReconditioning /OverhaulingCompletely Transporting the Induction Motor capacity1 HPto civil workshop and strip opening the motor and removing out the burntout winding and cleaning of the stator core and rewinding with suitable size super enameled copper wire with necessary insulations and varnishing becking and replacement of unserviceableball bearing and assembling back the motor andre -fixing with gear Box and necessary electrical connections and testing and commissioning the rolling shutter all as specified and as directed.
63M&L for Earthing complete with 2.5m CI pipe 80 mm dia with flanged ends, centifugally cast, class A, in any length, joints with suitable stainless steel nuts and bolts and sufficient slote up to 2 mtrs length buried directly and preferably vertically in ground with top flanged ended 2 mtrs below ground lebel welded/connected with GIstrip 25X4mm dia Galvanised iron or steel wire, connected toEarth electrodeto DB for earthing including filling the pit with charcol common salt surrounding the earth pipe includingdrilling 400 mm dia bore in any strata of soil to lower the CI pipe complete
64M&L for taking down high pressure SV/MV/MH/FTL/LED street light fittings and flood Light fittings of any wattage/ any height of pole/walls/ any location for repairs or replacement of burnt out the accessories and rectifying the fault etc. complete all as specified and as directed by the Engineer-in-Charge. Note: LED drivers, surge protection and cable etc. shall be measured separately under relevant items of this schedule.
65S&Fin repair LED street light fitting pressure die cast aluminium housing with heat resistant toughened glass & IP 65 protection luminaries of capacity 45 Watt complete with driver, lamp bracket with mpact and corrosion resistanat including thermal management in multiple opticsall as specified and as directed by the Engineer-in-Charge. Make: Crompton Cat. Part No. LSTS-40-CDL-M or equivalent as approved by GE
66S&F in repairs, LED street light fitting pressure die cast aluminium housing with heat resistant toughened glass & IP 65 protection luminaries of capacity 60 Watt complete with driver, lamp bracket with mpact and corrosion resistanat including thermal management in multiple optics all as specified and as directed by the Engineer-in-Charge. Make: Crompton Cat. Part No.LSTP-60-CDL-M or equivalent as approved by GE
67S&F in repair LED Flood light fitting pressure die cast aluminium housing with heat resistant toughened glass & IP 66 protection luminaries of capacity 120 Watt complete all as specified and as directed by the Engineer-in-Charge. Make: Crompton Cat. Part No. LFLN-120-CDL/60-M or equivalent as approved by GE
68S&F in repair LED Flood light fitting pressure die cast aluminium housing with heat resistant toughened glass & IP 65 protection luminaries of capacity 200Watt complete all as specified and as directed by the Engineer-in-Charge. Make: Crompton Cat. Part No. LFLN-200-CDL/60-M or equivalent as approved by GE
69S&F LED flood light 250 W, 230 Volts luminaire with pressure die-cast aluminium housing IP 66 protection, any height and any location including internal prewired with all materials complete all as specified and as directed by the Engineer-in-Charge. Make: Crompton Cat. Part No. LFLPI-250-CDL/60-M or equivalent as approved by GE
70Supply only drivers for LED street lights 25W/35W, 230 Volts, 50 Hz complete all as specified and as directed by the Engineer-in-Charge.
71Supply only drivers for LED street lights 45W/60W, 230 Volts, 50 Hz complete all as specified and as directed by the Engineer-in-Charge.
72Supply only drivers for LED flood lights 100W/120W, 230 Volts, 50 Hz complete all as specified and as directed by the Engineer-in-Charge.
73Supply only drivers for LED flood lights150W/200W, 230 Volts, 50 Hz complete all as specified and as directed by the Engineer-in-Charge.
74Supply, laying and testing 3 core round flexible cable 1.5 Sq.mm. PVC insulated, 1100 Volts grade, PVC sheathed with two runs of single core multistranded FLRS copper conductor along with one run of necessary earth continuity conductor of 1.5 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
75S&Fdigital time switches with battery back up 1100 hours with current capacity 16 A programmable every 1min with 1 changeover and total 28 programs complete all as specified and as directed by the Engineer-in-Charge. Make: Indoasian Cat. Part No. TDA43110 or equivalent as approved by GE
76S&F in repairs contactor ML-2 of capacity of 32 Amps AC 3 phase heavy duty including taking down old unserviceable contactor complete all as specified and as directed by the Engineer-in-Charge.
77S&F in repairs contactor ML-3 of capacity of 40 Amps AC 3 phase heavy duty including taking down old unserviceable contactor complete all as specified and as directed by the Engineer-in-Charge.
78S&F in repair timelite distribution board 32 Amps, 3 pole, 230 volts digital time switch complete all as specified and directed by Engineer-in-Charge. Make: Indoasian cat No. TL032DB0 or equivalent as approved by GE
79M&L for cleaning the swaged steel tubular street light poles of 9/11 meters height including GI pipe of street light fitting and preparation of surfaces by cleaning including scrapping up old corroded paint/dirt/dust/rust carefully and applying two coats of aluminium paint over one coat of metal primer and marking of zebra crossings up to a height of 1.0m above the coping with black and yellow strips of synthetic enamel paint including writing of pole numbers and two coats of colour washing on PCC coping surfaces complete all as specified and as directed by the Engineer-in-Charge.
80M&L for cleaning the pre-stressed cement concrete street light poles of 9/11 meters height, preparing old plastered or unplastered surfaces and applying two coats of cement based paint over one coat of primer including writing of pole numbers and two coats of colour washing on PCC coping surfaces complete all as specified and as directed by the Engineer-in-Charge.
81S&F GI bracket suitable for street light fitting made out of 40mm dia. GI tubing of light grade bent to shape of 1.5m length complete including taking out old one complete all as specified and as directed by the Engineer-in-Charge.
82Supply and laying LT underground cable XLPE insulated and sheathed armoured cable 1100 Volts grade of size 4 core 16 Sq.mm. aluminium conductor in trenches/poles and connecting with all accessories including taking out the old unserviceable cable complete all as specified and as directed by the Engineer-in-Charge.
83Excavation in trenches n. exc. 1.5m wide and n. exc. 1.5m depth and getting out soft/loose soil for laying of under ground cable complete all as specified and as directed by the Engineer-in-Charge.
84Excavation in trenches n. exc. 1.5m wide and n. exc. 1.5m depth and getting out soft/loose soil for laying of under ground cable complete all as specified and as directed by the Engineer-in-Charge.
85Returning/filling including spreading, levelling and well ramming in layers n. exc. 25cm in thick complete all as specified and as directed by the Engineer-in-Charge.
86Removal of surplus soil to a distance n. exc. 50m away and depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified and as directed by the Engineer-in-Charge.
87Supply and spread sand in cable trenches and providing cushioning for the cable complete all as specified and as directed by the Engineer-in-Charge. Note: Only punned thickness of 18cm will be measured for the purpose of payment.
88Supply and lay unreinforced precast concrete cable cover class LV, type 1, flat, size 250mmX150mmX40mm for protection of cable, laying in trenches complete all as specified and directed by the Engr-in-Charge
89Supply and lay GI pipe 40mm dia. light grade for cable protection as per site requirement and sealing the pipe both ends with sealing compound complete including taking down old one complete all as specified and as directed by the Engineer-in-Charge.
90S&F HOT moulded (FRP) jucntion box for street light pole with locking arrangementt with IP-65 protection of size 250x250x150mm with 32 Amp 4 way heavy duty terminal block with 10 Amps MCB SP and two steel bracket to fix with pole complete all as specified and as directed by the Engineer-in-Charge. Make: Hansel/Sintex
91S&F in repairs, MS clamps suitable for 40mm GI pipe made out of 25x4mm flat iron complete with necessary nuts and bolts complete all as specified and as directed by the Engineer-in-Charge.
92S&F rigid non metallic PVC conduit 20mm dia. including all the fittings like Tees, bends, elbows, reducers etc. and fixtures such as couplers, lock nuts, saddles, pipe hooks etc. complete including taking down old one complete all as specified and as directed by the Engineer-in-Charge.
93M&L for repairs and maintenance of LED solar lights with charging and topping up distilled water in solar light batteries to maintain necessary specific gravity with replacement of damaged battery lead clamps andworn out leads including taking down and fixing of batteries to its position complete all as specified and as directed by the Engineer-in-Charge.
94Taking down high mast light of size 12/15/16 mtr from its base with help ofcrane, cleaning, greasing, and overhauling of all moveable parts like pullies,steel wire,chain,winches etc,replace unserviceable light if required and refix the mast on its original position complete all as specified and as directed by the Engineer-in-Charge.
95S&F in repairs of Aviation lightcomprising aluminium housing and polycarbonated enclosure at any height and location complete all as specified and as directed by the Engineer-in-Charge. Make:-Bajaj/Havells/Crompton/C&S
96S&F in repairs 12 Volt, DC, 75Ah/100Ah, maintenance free valve regulated Lead acid(VRLA) solarGEL Battery complete all as specified and as directed by the Engineer-in-Charge.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail