Technical Proposal For Augmentation Water Supply Scheme Bhattu Kalan Tehsil & Distt. Fatehabad. Const. Of Rcc Pipe Inlet Channel, Suction Well For Raw Water & Clear Water, 1 No. Pump Chamber, Repair & Raising Of 3 Nos. S / S Tank, 2 No. Clear Water T, kalan-Haryana

Public Health Engineering Department-PHED has published Technical Proposal For Augmentation Water Supply Scheme Bhattu Kalan Tehsil & Distt. Fatehabad. Const. Of Rcc Pipe Inlet Channel, Suction Well For Raw Water & Clear Water, 1 No. Pump Chamber, Repair & Raising Of 3 Nos. S / S Tank, 2 No. Clear Water T. Submission Date for this Tender is 06-07-2022. Concrete Pipe Tenders in kalan Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

32589538
Technical Proposal For Augmentation Water Supply Scheme Bhattu Kalan Tehsil & Distt. Fatehabad. Const. Of Rcc Pipe Inlet Channel, Suction Well For Raw Water & Clear Water, 1 No. Pump Chamber, Repair & Raising Of 3 Nos. S / S Tank, 2 No. Clear Water T
Open Tender
Indian
Haryana
kalan
06-07-2022

Tender Details

Technical Proposal For Augmentation Water Supply Scheme Bhattu Kalan Tehsil & Distt. Fatehabad. Const. Of Rcc Pipe Inlet Channel, Suction Well For Raw Water & Clear Water, 1 No. Pump Chamber, Repair & Raising Of 3 Nos. S / S Tank, 2 No. Clear Water Tank, Rcc Column Based Boundary Wall, Road & Path, Laying Of Pipe Line At Head Works, Pumping Machinery For Raw Water & Clear Water At Old Water Works, Shifting Of Rcc Pipe Channel, Suction Well For Clear Water, Construction Of 1 No. S / S Tank, 1 No. Clear Water Tank, 1 No. Pump Chamber, Road And Path, Laying Of Pipe Line At Head Works, Pumping Machinery For Clear Water At 2Nd Water Works, Construction Of Rcc Clear Water Tank At 4 Nos. Boosting Station, Installation Of Pumping Machinery, Distribution System, High Light Masts, Const. Of 3.00 Mld Cap. Wtp At Old Water Works And 2.00 Mld Cap. Wtp At 2Nd Water Works, O & M For 6 Yearincluding One Year Defect Liability Period After 3 Months Trial Run Period And All Other Works Contingent Thereto

Key Value

Document Fees
INR 20000 /-
EMD
INR 2170220.0 /-
Tender Value
Refer document

BOQ Items

BHATTU KALAN:-Technical Proposal for Augmentation water supply Scheme Bhattu Kalan Tehsil & Distt. Fatehabad. "Const. of RCC Pipe Inlet channel, Suction Well for Raw water & Clear water, 1 No. Pump Chamber, Repair & Raising of 3 Nos. S/S Tank, 2 No. Clear Water Tank, RCC Column based Boundary wall, Road & Path, Laying of Pipe line at head works, Pumping machinery for raw water & Clear water at Old Water works, Shifting of RCC Pipe Channel, Suction Well for Clear Water, construction of 1 No. S/S Tank, 1 No. Clear Water Tank, 1 No. Pump Chamber, Road and Path, Laying of Pipe line at Head works, Pumping machinery for Clear water at 2nd Water works, Construction of RCC Clear Water Tank at 4 Nos. Boosting Station, Installation of Pumping machinery, Distribution System, High Light masts, Const. of 3.00 MLD Cap. WTP at Old Water Works and 2.00 MLD Cap. WTP at 2nd Water Works, O & M for 6 yearincluding one year defect liability period after 3 Months Trial run period and all other works contingent thereto"
Sl. No. Item Description
1N.S. Item
2Desinging , Testing , Commissioning ofwater purification plant of 3.00 MLD capacity SCADA based at Old Water Works,all other installation etc. comprising of DI pipe from existing raw water main/pump, inlet box of WTP and to CWT to C.W. suction well, inlet channel, Alum dozing, Flash mixing, Clari floculator, filter box, over head Reservoir for back wash including pump sets and electric control panel, waste water tank including pump sets and electric control panel, DI pipes, DI specials, manhole covers, air scour equipment, chemical house including chlorination equipment and arrangement of floe measurement and sand bed with automation complete in all respects as per NIT (Sluice valve of make IVC/ VAG ) (At Old Water Works)
3Desinging , Testing , Commissioning ofwater purification plant of 2.00 MLD capacity SCADA based at 2nd Water Works,all other installation etc. comprising of DI pipe from existing raw water main/pump, inlet box of WTP and to CWT to C.W. suction well, inlet channel, Alum dozing, Flash mixing, Clari floculator, filter box, over head Reservoir for back wash including pump sets and electric control panel, waste water tank including pump sets and electric control panel, DI pipes, DI specials, manhole covers, air scour equipment, chemical house including chlorination equipment and arrangement of floe measurement and sand bed with automation complete in all respects as per NIT (Sluice valve of make IVC/ VAG )(At 2nd Water works)
4Supply & erection of Horizontal spindle split casing type puming sets minimum Four (4) Star rating duties coupled to AC squrrel cage induction type motor with 1440 RPM, 3 phase 50 Hz and accessories as described in Schedule No.II complete in all respect with priming arrangement with complete base frame. A) Raw water pump set Raw Water Pump set 3800 LPM 12 Mtrs Head (At Old W/W)
5B) Clear water pump set Clear Water Pump set 4000 LPM 35 Mtrs Head (At Old W/W for filling of B/Stn)
6Clear Water Pump set 3000 LPM 40 Mtrs Head (At Old W/W for direct Supply)
7Clear Water Pump set 2700 LPM 35 Mtrs Head (At 2nd W/W for filling of B/Stn)
8Clear Water Pump set 2700 LPM 40 Mtrs Head (At B/Stn BD& PO office)
9(A) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm having following items. ( At Old water works) (A) For Clear Water Pump set 3800 LPM 12 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 3800 LPM 12 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
10(B) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm and 400 mm deep having following items. (At Old W/W for Filling of B/Stn) (A) For Clear Water Pump set 4000 LPM 35 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 4000 LPM 35 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
11(C) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm and 400 mm deep having following items. (At old Water Works Direct Supply) (A) For Clear Water Pump set 3000 LPM 40 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 3000 LPM 40 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
12(D) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm and 400 mm deep having following items. (At 2nd Water Works for filling of B/stsn) (A) For Clear Water Pump set 2700 LPM 35 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 2700 LPM 35 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
13(E) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm and 400 mm deep having following items. (At Boosting Station BD & PO office) (A) For Clear Water Pump set 2700 LPM 40 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 2700 LPM 40 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
14(F) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm and 400 mm deep having following items. (At Boosting Station DHBVNL) (A) For Clear Water Pump set 1100 LPM 40 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 1100 LPM 40 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
15(G) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm and 400 mm deep having following items. (At Boosting Station PHC) (A) For Clear Water Pump set 1000 LPM 40 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 1000 LPM 40 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
16(H) Supply, erection, testing and commissioning of wall mounted electrical panel board, fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200x900 mm and 400 mm deep having following items. (At Boosting Station Govt. collage) (A) For Clear Water Pump set 1000 LPM 40 Mtrs Head 2 Nos. a) Main switch as required2 No.(L&T Siemens, ABB) b) Volt meter 100x100 mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) C) Amp meter 100X100mm range 0 to 100 Amp 2 Nos. (AE/KAPPA/L&T) D) CT 100/ 3 Nos. (AE/KAPPA/L&T) E) VSS 1 No.& ASS 2 No. each of approved make F) SPP 2 No. of approved make g) Motor starter, Star delta 2 No.for 1000 LPM 40 MtrH) Capacity KVAR as per site requirement 2 No. I) Indicating Lamp - One Set J) Change Over switch as required = 1 No.
17Supplying erection, testing of ISI marked copper wire for 16 Nos. motors with under ground system in PVC and flexible pipes copper wire size 6 sq. mm complete in all respects with accessories like thimble etc. complete in respects.
18Supplying erection, testing of ISI marked copper wire for 16 Nos. motors with under ground system in PVC and flexible pipes copper wire size 10 sq. mm complete in all respects with accessories like thimble etc. complete in respects.
19Supplying erection, testing of ISI marked copper wire for 16 Nos. motors with under ground system in PVC and flexible pipes copper wire size 16 sq. mm complete in all respects with accessories like thimble etc. complete in respects.
20Supply ereetion, testing of light fittings including wire in the Pump Chamber with material upto 10 points including switch, button, plug, PVC conduit pipe & copper wire etc. as per approved specifications
21Operation and maintenance for the complete scope of work mention in the DNIT (Disinfection material supplied by the PHED) as per schedule IV for a period of 5 years after 12 months during defect liability period 3 months trial run (Will be charged to the A/Mtc. estimate. Operation and Maintenance of during defect liability (Operation Only) Operation and Maintenance of during the 1st yeardefect liability period
22Operation and Maintenance of during the 2nd year
23Operation and Maintenance of during the 3rd year
24Operation and Maintenance of during the 4th year
25Operation and Maintenance of during the 5th year
26Operation and Maintenance of during the 6th year
27Less Credit for old materil Pumping machinary Raw Water - 1100LPM x 12 Mtr.
28Less Credit for old materil Pumping machinary Clear Water - 3000LPM x 40 Mtr.
29Less Credit for old materil Pumping machinary Clear Water - 800LPM x 35 Mtr.
30Less Credit for old materil Pumping machinary Clear Water - 1500LPM x 35 Mtr.
31Less Credit for old materil RCC Pipe 600 mm dia
32Less Credit for old materilBricks = 122+64= 186 cum x 60/100 x 480
33Less Credit for old materil Bricks bats = 186 cum x 40/100