| 1 | FIRE ALARM |
| 2 | SITC of Addressable analogue multicriteriatype smoke detectors with dual chamber, solid state design, indicating LED, mounting base etc. as per detailed specification. The rate shall inclusive of necessary base box, connecting glad for above detectors etc. as required. |
| 3 | SITC of Fault isolation module to electrically isolate different sections of detector loops. |
| 4 | SITC of Rate of Rise Heat Detectors (Thermal Detectors):GRADE-I Addressable analogue type Heat Detectors with solid state design with sensing element combination of fixed type and rate of rise of temperature indicating LED, mounting base etc. as required. |
| 5 | SITC of Addressable type manual fire alarm boxes (MCP/Pull Station ) shall, on command from the control panel, send data to the panel representing the state of the manual switch and the addressable communication module status. Manual fire alarm boxes shall be constructed of Lexan with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches (44 mm) or larger. etc. as required. |
| 6 | SITC of Response Indicator for addressable type detectors as required |
| 7 | SITC of Hooter suitable for addressable type fire alarm system withstorb light with minimum 85 db audiableetc. as required. |
| 8 | Supply , installation testing and commisioning of folowing modules suitable for Addressable fire Alarm Control panel taken |
| 9 | Monitor module for monitoring of flow switches of hydrent / sprinklers |
| 10 | Controlrelay modules for tripping of AHU / pressurise fans and ventilators |
| 11 | Control modules for floor wise activation of hooters |
| 12 | SITC of microprocessor basedloop (each loop accessing 127 addressable detectors and 127 devices ) UL/ EN54AddressableFire Alarm Control Panel as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The Panel shall have built in buzzer, SMF batteries for min. 24 Hrs.back up, battery charger, rectifier. Loop interface cards, communication module,LCD unit to indicate Fire / Fault Signal of individual unit, option for external printer,to log all incoming data etc complete in all respect. |
| 13 | 2 - Loop |
| 14 | Supply , installation testing and commisioning of Digital Voice Command Center withFACP, it shall contain all equipment required for all audio control, emergency telephone system control, signaling and supervisory functions. This shall include speaker zone indication and control, telephone circuit indication and control, digital voice units, microphone and main telephone handset. etc. as required. |
| 15 | SITC of6 W Wall Mounted Speakers suitable for addressable type fire alarm system with line matching transformers & selecteable tap setting as required. |
| 16 | SITC of6 W ceiling mounted Speakers suitable for addressable type fire alarm system with line matching transformers & selecteable tap setting as required. |
| 17 | SITCof Repeater Panel for Fire Alarm System with piezo sounder, LCD alpha numeric character display with accept / reset buttons for alarm address of any sensor / fielddevice.The Repeater Panel shall only provide fielddevice address with room number.Analogue Output is not required. The Panel shall be connected to the Fire Alarm Panel. |
| 18 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existingsurface or recessed conduit/casing capping including making connections etc. as required. |
| 19 | 2 x 1.5 sq.mm |
| 20 | Supply , Drawing and Testing of 4 pair, 24 AWG UTP Cat 6 Cable as per latest ammendments of TIA /EIA 568 B.2-1 Specifications in existing MS/PVC Conduits including making connections to Information outlets and Patch Panels with ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing required |
| 21 | S&F following sizes (dia.) of ISI marked ( IS:9537 P - II ) rigid steel conduit along with accessories in surface / recessed using saddles, clamps, fastener pvc bushes, check nuts, as required includingcutting the wall and making good the same as required. |
| 22 | 20 mm |
| 23 | 25 mm |
| 24 | Central PA System |
| 25 | S&F following sizes (dia.) of ISI marked medium duty PVC conduit along with accessories in surface / recessed using saddles, clamps, fastener as required includingcutting the wall and making good the same as required. |
| 26 | 25 mm |
| 27 | Supply, Installation, Testing & Commissioning of Main EN-54 Certified EVAC controller, with 14x 4 Audio matrix with full DSP functionality. 8 audio inputs, 4 audio outputs, 4 channel output matrix. Shall supportsingle line switching or redundant group A/B switching,amplifier redundany, 4 x 100V audio inputs and12 speaker line outputs. 8000 fault, warning and event conditions log.Built in message manager for 100 emergency/business calls up to 85 minutes. 10 control inputs and 13 control outputs. Should be able to send 2 different pre-recorded messages simultaneously. Impedance measurement and Pilot Tone supervision for speaker line monitoring. Shall be able to handle up to 2000Watt load,20 routers,16 call stations,492 speaker zones.Frequency response (ref.1 kHz) 20 Hz to 20 kHz (-0.5 dB)Signal-to-noise ratio(A-weighted): Line in to line out: 106 dB typical EN54 Certified EVAC Router for 24 zones to route4 channels into 8 100V audio inputs to 24 loudspeaker line outputs (Approved makes : Bosch, Toa, DIS) |
| 28 | Supply, Installation, Testing & Commissioning of EN-54 certified Call Station with extension keypad to with programmable keys forZone selection, source selection, level control, emergency on/off, message on/off, failure acknowledge/reset,Switching output trigger on/off or 0 to 10V, select scheduled events, scheduled event on/off. Multilanguage LC display(122 ? 32) pixel ,Five menu/function keys, gooseneck microphone with supervised electret microphone, pop shield and permanent monitoring, integrated loudspeaker for system sounds.The call station should havve the provision to be configured as a numeric keypad(Approved makes : Bosch, Toa, DIS) |
| 29 | Supply, Installation, Testing & Commissioning of 480 Watt Power Amplifier to be connected with digital PA controller in a 19” rack mounted housing, 70 V / 100 V and 8/4 ohm outputs, Dual inputs with priority switching, 100 V input for slave operation on 100 V speaker line, acoustic noise level of fan: <48 db SPL at 1 m (max output), color: Charcol.EN 60065 certified(Approved makes : Bosch, Toa, DIS) |
| 30 | Supply, Installation, Testing & Commissioning of 8 inch 24 Watt Ceiling Speaker with power tapping option as required. (Makes: Bosch/ Bose/ JBL / Honeywell) |
| 31 | Supply, Installation, Testing & Commissioning of30 Watt Wall Mounted Cabinet Speaker with power tapping option as required. (Makes: Bosch/ Bose/ JBL / Honeywell) |
| 32 | SITC of COUNTER COMMUNICATION SYSTEMUnique design, pleasing aesthetics & rugged construction.Duplex communication technology, ideal for ticket counters, enquiry counters, two way communication is required across a glass barrier.Separate switches for switching the Host Unit mic, or the External Unit mic, ON or OFF. Separate volume controls on the Host Unit for adjusting the audio output level of the Host Unit and the External Unit. Host Unit mic has automatic voice priority over the External Unit mic.3.5mm phone jack is provided on the rear panel of the Host Unit for Line Input. Host Unit is a table top unit which operates on 12V DC, through an AC adapter supplied alongwith Make: ahuja/Bosch/Sure |
| 33 | Supply, Drawing and Testing of ISI marked 2 core 1.S sq mm P.V.C. insulated & PVC sheathed cable confirming to IS:694 with flexible copper conductor inctuding making connection etc. as required for Cameras in existing MS /PVC Conduits / HDPE pipe as approved by engineer in charge.make:RR,Polycab,Havells |
| 34 | CCTV Survilience System |
| 35 | Supply, Installation, Testing & Commissioning of ONVIF S/G Profile Compliance based Indoor 2MP PoE True IP IR Dome Camera with latest H.264 or H.265 Compression with 1/2.8\" CMOS Sensor with built in IR Illuminator 15 Mtrs having automatic varifocal lens from 2.3 to 10 mm lens with autofocus for both day/Night operation with Camera Built In Video Analytics like as Line Crossing, Enter/Leave Field, Follow Route, Loitering, Idle/Removed,object,. Camera should having intelligent stream management and Bandwidth reduction facility for storage management and better bit rate optimization facility. Camera Should have TCP/IP recording (dual acknowledgement). Camera should have Edge based recording facility for approx 3-5 minutes without attaching any additional SD memory card in case of network failure, Camera Should support ISCSI protocol for direct communication with client station in case of management / recording server failure, Camera should have minimum Color Illumination of 0.5 lux, Mono 0.08 lux and IR on @ 0 Lux. Camera should have True WDR facility 120db or more. The on-board Trusted Platform Module (TPM) and Public Key Infrastructure (PKI) support, guarantee superior protection from malicious attacks. The 802.1x network authentication with EAP/TLS, supports TLS 1.2 with updated cipher suites including AES 256 encryption. Camera should have UL, CE, FCC certification with IP 66 and IK10 impact protection. The camera, software, storage should be of the same make for seamless integration with each other of Approved Makes: Bosch / Axis/ Avigilon |
| 36 | Supply, Installation, Testing & Commissioning of ONVIF S/G Profile Compliance based Outdoor 5MP PoE True IP IR Bullet Camera with latest H.264 or H.265 Compression with 1/2.9\" CMOS Sensor with built in IR Illuminator 30 Mtrs having automatic varifocal lens from 3.2 to 10 mm lens with autofocus for both day/Night operation with Camera Built In Video Analytics like as Line Crossing, Enter/Leave Field, Follow Route, Loitering, Idle/Removed,object,. Camera should having intelligent stream management and Bandwidth reduction facility for storage management and better bit rate optimization facility. Camera Should have TCP/IP recording (dual acknowledgement). Camera should have Edge based recording facility for approx 3-5 minutes without attaching any additional SD memory card in case of network failure, Camera Should support ISCSI protocol for direct communication with client station in case of management / recording server failure, Camera should have minimum Color Illumination of 0.37 lux, Mono 0.04 lux and IR on @ 0 Lux. Camera should have True WDR facility 120db or more. The on-board Trusted Platform Module (TPM) and Public Key Infrastructure (PKI) support, guarantee superior protection from malicious attacks. The 802.1x network authentication with EAP/TLS, supports TLS 1.2 with updated cipher suites including AES 256 encryption. Camera should have UL, CE, FCC certification with IP 66 and IK10 impact protection. The camera, software, storage should be of the same make for seamless integration with each other of Approved Makes: Bosch / Axis/ Avigilon |
| 37 | Supply, Installation, Testing & Commissioning of 30X 2MP IP IR ONVIF S/G Integrated Pan,Tilt, Zoom Camera:30X IP IR Integrated Pan,Tilt, Zoom Camera with latest H.265 Video Compression with intelligent stream management capability for Bit rate optimization and storage management with 1/2.8\" Progessive Scan CMOS sensor having lens of 4.5mm to 135mm (F1.6-F4.4) with optical zoom field of view from 2.4°-60.9°. 4 Number of LED\"s having wave length of 850nm having IR distance of 180 Mtrs, 1920 x 1080 sensor pixels or more. Camera should have on-board storage facility up to 2TB. Make:-Bosch/Axis/Avigilon |
| 38 | Supply Installation Testing & Commissioning of VMS & Storage device, The device shall beRAID-6 protected, Recording, viewing and management solution for network surveillance system with 128 channels pre-licenced including mobile viewing license. It shall be designed for high speed, high capacity digital video storage and high performance play back applications. The storage array shall be a full featured RAID 6 configuration.The digital video storage array shall have inbuilt 128 TB HDD Storage, 7200 rpm, SATA, HDD, withtwo (2) redundant power supplies. The system shall have minimum 8 GB DDR3 RAM, and per channel min 3 - 4 M bits per seconds band width. The storage array shall provide an audible alarm to notify the user in the event of a failure. The system should be such that the video recording from camera should be done directly on storage array without the use of Network manager so if network manager server fails than also recording should not be effected as required in the tender and directions of Engineer-in-charge. ONVIF Profiles S & G, CE, UL Certified. The camera, software, storage should be of the same make for seamless integration with each other MAF: Tender Specific OEM authorisation is mandatory for bid consideration of Approved Makes: Bosch / Axis/ Avigilon |
| 39 | SITC of Workstation latest Intel® i5 processor, Intel Chipset motherboard, 08 GB RAM, 1 TB SATA HDD at 7200 rpm, with 4GB GPU type higher end Graphic card for H.265 compression technique with dual display ports/DVI/ HDMI port, Giga LAN Card, wireless Keyboard, wireless optical Mouse with original license Windows software of Approved Makes: Lenovo, HP, Dell. |
| 40 | SITC of 17\"\" Screen for viewing for Storage of approved Makes: Lenovo, HP, Dell. |
| 41 | SITC of 55\"\" Flat Smart Screen HD Profesional LED with remote control and wall mount unit / floor stand complete with making connections etc of approved Makes: LG, Samsung, Panasonic. |
| 42 | SITC of 5/6 KVA 1 Phase Input, 1 Phase Output advance DSP controlled UPS with IGBT based rectifier, LCD display, double conversion / Digital Signal Processing UPS,with isolationtransformer,with 26Ahx x 16 nos SMF Batteries for back up, with required cabling for incoming & outgoing connection of approved Makes: Numeric, Eaton, Emerson, APC. |
| 43 | Supply ,Installation of 40 mm PN 6 grade HDPE pipe as per IS:4984 with nylon rope for fiber / LAN cable / telephone / power cable laying inclusive of digging with the help of bogi & sand finishing, making the surface in good condition as approved by engineer in charge etc |
| 44 | LAN SYSTEM |
| 45 | Supply , Drawing and Testing of 4 pair, 24 AWG UTP Cat 6 Cable as per latest ammendments of TIA /EIA 568 B.2-1 Specifications in existing MS/PVC Conduits including making connections to Information outlets and Patch Panels with ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing required .Gp-I |
| 46 | Supply & fixing of Faceplate for Flush / SurfaceMount Information Outlets Single Aperture with screw hole covers & Icon Tree Size 86mmX86mm. Gp-I |
| 47 | Single Aperture |
| 48 | Supply and Installation of Information outlets made of high impact plastic body ABS FR Grade with spring loaded collapsible shutters in jack Recess, suitable for Cat 6 application complying to latest ammendments EIA/ TIA 568 B.2-1 Specifications in existing modular /MS Boxes along with necessory connections as required.Gp-I |
| 49 | Supply , Installation, Testing and Comissioning of Rack mounted 19\", Cat 6 UTP,1.5-1.6 MM CRS chasis , powder coated Modular Patch Panels with collapsible shutters on jacks to support latest ammendments of TIA / EIA Cat 6 Specifications in Existing Communication Rack along with necessary connections of Cat 6 UTP Cables, With Rear Cable management trays and clamps.Gp-I |
| 50 | 24 Ports |
| 51 | Supply , Installation and Testing of 4 pair , 100 Ohm, 24 AWG , Cat 6 UTP, flexible , Double ended Patch Cords along with 2 No of RJ 45 connectors with strain relief transparent boots as per TIA /EIA 568 B.2-1 Specifications.Gp-I |
| 52 | 1 Mtr/3 ft |
| 53 | 2 Mtr / 7 ft |
| 54 | 3 Mtr / 10 ft. |
| 55 | Supply ,Installation and Testing of 19 \" Rack mounted/ surface mounted aluminium / CRS powder coated multimode glass Fiber Optic Cable Patch panel / LIUalong with cable manager, adapters for ST II/ SC/LC/MT-RJ/PC Gp-I |
| 56 | 12 Ports |
| 57 | Supply , Drawing and Testing of outdoor singlemode [ 9 micron ] glass Fiber Optic cable as per latest ammendments of TIA /EIA 568B.3 , GR 409 CORE / UL listed NEC 770 Standards in existing MS/PVC Conduits/ slotted channels with ferruling at both ends for identification Gp-I. |
| 58 | 6 fiber |
| 59 | Supply , Installation, OTDR Testing & Fusion Splicing of Fiber singlemode Pigtail [ 9 micron ] glass Fiber Optic Cable as per latest ammendments of TIA /EIA 568B.3 , GR 20 CORE / UEC 794-1/ EN 187000 Standard Specifications including ST II / SC/LC/MT-RJ/PC connector as per requirements Gp-I. |
| 60 | Supply ,Installation and Testing of indoor 1 pair singlemode [ 9 micron ] glass Fiber Optic Patch Cords of three mtr length as per latest ammendments of TIA /EIA 568B.3 and IEC 794 Standard Specifications including ST II / SC/LC/MT-RJ/PC connectors at both ends as per requirements Gp-I. |
| 61 | Supply ,Installation and Testing of 19 \" Rack mounted/ surface mounted aluminium / CRS powder coated singlemode glass Fiber Optic Cable Patch panel / LIU along with adapters for ST II/ SC/LC/MT-RJ/PCGp-I |
| 62 | 6 Ports |
| 63 | S&F following sizes (dia.) of ISI marked medium duty PVC conduit along with accessories in surface / recessed using saddles, clamps, fastener as required includingcutting the wall, covering conduit and making good the same as required.Gp-I |
| 64 | 20 mm |
| 65 | 25 mm |
| 66 | S & F of PVC trunking system for cable management including finishing accessories like corners, tee, adjustable angles, junction etc. as required . The trunking system shall haveadaptable system for modular type RJ 45 data socket/ wiring accessories/ power sockets and shall be covered with peal off plastic cover.Gp-I |
| 67 | 32mm X 20mm |
| 68 | 100/105mm x 50mm |
| 69 | Supply , Installation, Testing and Comissioning of Wall mounted Communication rack with glass doors, handles ,lock , Top and Bottom Cable entries, Supports for mounting rack on wall , Cable managers, one Fan, Equipment mounting hardware, power supply box for supplying power to switches, fans etc along with earth continuity kit, Mcb, indicator, moulded power supply cable |
| 70 | 15 U(44 mm ) wall mounted |
| 71 | Supply , Installation, Testing and Comissioning of Floor Standing Server / Communication rack with width 800 MM, Depth 1000 MM, front glass door, rear MS door, side openable panels, min 10 socket Vertical Cable manager -02 no, two nos Vertical Cable managers, 05 nos Horizontal Cable managers, Keyboard tray-01, 720 mm heavy duty shelf-03 (for mounting servers & components), swing handles, lock on both doors, Top and Bottom Cable entries with gland plates, Coastor with brakes, 1 no Fan tray with 2 x 230 Volt fans, Equipment mounting hardware. |
| 72 | 42 U Floor Standing Rack |
| 73 | Supply, Installation, Testing & Commissioning of Managed Layer-3 Intelligent Ethernet Switch providing with min 24 SFP Giga unpopulated Ports (provision for Fiber Giga connectivity) with provision of retundent power supply with related IP Base Software,all switches & related Fiber modules should be of same make & category for seamless integration with each other of Approved Makes: Cisco Catalyst Series or Equivalent inAvaya, Juniper ) |
| 74 | Supply, Installation, Testing & Commissioning of Managed Layer-2 Intelligent Ethernet POE Switches providing 24 x 10/100/1000 Fast Ethernet POE ports- 370W or better and 4 dual purpose uplink ports (provision for Copper / Fiber Giga connectivity)all switches & related Fiber modules should be of same make & category for seamless integration with each other of Approved Makes: Cisco Catalyst Series or Equivalent inAvaya, Juniper ) |
| 75 | Supply, Installation, Testing & Commissioning of Managed Layer-2 Intelligent Ethernet Switches providing 24 x 10/100/1000 Fast Ethernet ports and 4 dual purpose uplink ports (provision for Copper / Fiber Giga connectivity)all switches & related Fiber modules should be of same make & category for seamless integration with each other of Appproved Makes: Cisco Catalyst Series or Equivalent inAvaya, Juniper ) |
| 76 | Supply Installation Testing & Commissioning of 1000 Base-SX, SFP, Hi, MMF 220 & 550 meters, LC connector, Industrial Temp Multimode Fiber Giga module, all switches & related Fiber modules should be of same make & category for seamless integration with each other of Approved Makes: Cisco Catalyst Series or Equivalent inAvaya, Juniper ) |
| 77 | AIR CURTAIN SYSTEM |
| 78 | SITC of Air Curtain (6 Feet / Air Throw 21 M/S) power coted body Make:Euronics/Dolphy/Cornax |
| 79 | Body Material :- MS Powder Coated |
| 80 | Width Size :- 6 Feet |
| 81 | Voltage :- 220V/50Hz |
| 82 | Power (W) :- 820 |
| 83 | Phase :- Single |
| 84 | No. of Motors :- 3 |
| 85 | Maximum Air Velocity at Nozzle Discharge :- 21 m/s |
| 86 | Noise level (5ft from Floor) :- 50-55db |
| 87 | CFM :- 1490 |
| 88 | Effective Height :- 7-9 Feet |
| 89 | No. of Blower :- 6 Blower |
| 90 | Blower Material :- ABS |
| 91 | Dimensions (H x D x W) :- 1800x230x212 |
| 92 | Weight Kgs. :- 32 |
| 93 | SITC of Air Curtain (5 Feet / Air Throw 21M/S) power coted body Make:Euronics/Dolphy/Cornax |
| 94 | Body Material :- MS Powder Coated |
| 95 | Width Size :- 5 Feet |
| 96 | Voltage :- 220V/50Hz |
| 97 | Power (W) :- 700 |
| 98 | Phase :- Single |
| 99 | No. of Motors :- 3 |
| 100 | Maximum Air Velocity at Nozzle Discharge :- 21 m/s |
| 101 | Noise level (5ft from Floor) :- 50-55db |
| 102 | CFM :- 1380 |
| 103 | Effective Height :- 7-9 Feet |
| 104 | No. of Blower :- 5 Blower |
| 105 | Blower Material :- ABS |
| 106 | Dimensions (H x D x W) :- 1500x230x212 |
| 107 | Weight Kgs. :- 26 |
| 108 | SITC of Sensor for air curtain 2 door with siemens contractor Make:Euronics/Dolphy/Cornax |