Electrical Work In Construction Of Building Govt. College, Bassi District Jaipur
Tender Value
47.35 Lakhs
Estimated cost
Bid Submission
08 Jun 2022
0 days left
EMD
94700
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
bassi → Rajasthan
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Electrical Work In Construction Of Building Govt. College, Bassi District Jaipur
BOQ
| Sl. No. | Item Description |
| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point as per PWD specification for electrical Works with ISI marked 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade (IS:694)and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit & it\"s all accessories( J.B. , Bends etc.) , round tiles,18 SWG Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / lamp Holder/ 3 pin connector , screws etc, making connections,all as per pre approved by Engineer in charge, testing etc. complete as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessoriesrefer Chapter E - 04, E - 05 & E - 07 . For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 2 | Short point (up to 3 mtr.) |
| 3 | Medium point (up to 6 mtr.) |
| 4 | Long point(up to 10 mtr..) |
| 5 | Wiring of 3/5 pin 6 amp. Light plug point as per PWD specification for electrical Works with ISI marked 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV grade (IS:694)and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit & it\"s all accessories( J.B. , Bends etc.) , round tiles, 18 SWG Hot Dipped Galvanized Modular Box with earth terminal, 6 A modularswitch, 3/ 5 pin 6 A modular socket, Modular face plate with grid plate, screws etc,all as per pre approved by Engineer in charge,making connections, testing etc. complete as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessoriesrefer Chapter E - 04, E - 05 & E - 07.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 6 | On board |
| 7 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) vergin material PVC conduit as per PWD specification for electrical Works along with its accessories (IS: 3419 ) as requiredinrecess includingcutting the wall, covering conduit and making good the same as required. All relative and latest acceptance tests reports by any NABL accredited lab for the conduit shall be submitted before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 8 | MMS ( IS:9537 P - III ) PVC conduit |
| 9 | 20 mm |
| 10 | 25 mm |
| 11 | 32 mm |
| 12 | Wiring of twin control light point as per PWD specification for electrical Works with ISI marked 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor1.1 kV grade (IS:694)and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit & it\"s all accessories( J.B. , Bends etc.) , round tiles,2 nos. 18 SWG Hot Dipped Galvanized Modular Box with earth terminal ,2 Nos 6 A two way Modular switch, 3 pin ceiling rose / lamp holder/ 3 pin connector ,Modular face plate with grid plate,screws etc,all as per pre approved by Engineer in charge,making connections, testing etc. complete as required.For specification of copperConductor,Phenolic Laminated sheet\"s & Electrical/ Wiring accessoriesrefer Chapter E - 04, E - 05 & E - 07.For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 13 | Medium point (up to 6 mtr.) |
| 14 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 18 SWG with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 3/5 pin 16 amp. socket outlet (IS:1293) [ as per detailed in respective item in BSR] , making connection , testing , etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 15 | Providing & Fixing of modular type Step Fan regulator duly ISI marked (IS :11037) as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , minimum width of 1 module switch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 16 | 5 step fan regulator 100 watt 2 Module |
| 17 | Providing & Fixing of ISO Certified company made BEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanas per PWD specification for electrical Works, conforming to IS:374-2019, & IS:1885 -P-V- 1981. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required.Appropriate OEM test certificate shall be submitted by contractor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 18 | 1200 mm Sweep BEE 2 Star rated (service value >=4.5 to < 5 ) |
| 19 | P & F 18 swgM.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm,12 mm dia rod fan hook with 100 mmlength extended on each side . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 20 | Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. OEM shall be an ISO certified company.Appropriate OEM test certificate shall be submitted by contractor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 21 | 300 mm sweep |
| 22 | Providing & Fixing of Heavy duty capacitor start, copper woindDouble ball bearing900/1400 RPM single phaseExhaustfan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. OEM shall be an ISO certified company. Appropriate OEM test certificate shall be submitted by contractor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 23 | 300 mm sweep(900/1400 RPM) |
| 24 | P & F of Gravity Louver shutter of superior quality made out of frame of18 swg M.S. sheet & Louvers made from 24 swg MS Sheetwith enamel paint including cost of nuts, bolts, etc as reqd.Appropriate OEM test certificate shall be submitted by contractor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 25 | Up to 380 mm size |
| 26 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.99% purity copper, class 5 stranding in acc. to IEC 60228 forlower watt loss , oxygen free ( <10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4,, in existingsurface or recessed PVC/ MS conduit/casing capping includingall as per pre approved by Engineer in charge,making connections, etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 27 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 28 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 29 | 1 x 6.0 sq.mm |
| 30 | 4 x 10.0 sq.mm |
| 31 | 1 x 1.5 sq.mm |
| 32 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured / Armouredaluminiumcable of 1.1 KV grade as per PWD specification for electrical Worksin existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench, on existing cable trays or on surface etc.including making necessary connection, testing etc. as required of size andas per points (a), (b), (c), mentioned below:- |
| 33 | (a) Material :- H4- Gradealuminium conductor of purity >99.6 %& as perIS:1554 P-I / IS :7098 P - I |
| 34 | (b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999for armouring of cables in armoured cable items , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures . |
| 35 | (c)OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities forcables . Appropriate type test certificate / OEM test report shall be submitted .All above as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 36 | Armoured Cable |
| 37 | 6.0 Sq. mm |
| 38 | 2 core |
| 39 | 4 core |
| 40 | 10.0 Sq. mm |
| 41 | 4 core |
| 42 | 25.0 Sq. mm |
| 43 | 3.5 core |
| 44 | 150.0 Sq. mm |
| 45 | 3.5 core |
| 46 | Providing & Fixing of IK09 recessed/surface mounting heavy duty horizontal type sheet steel of 1.6 mm thickDistribution board as per PWD specificationfor electrical Works ISI marked conforming to IS-13032 & IS-8623 / conforming to IEC 61439-3. Phosphatised/ powder painted complete with suitable rating insulated copper bus bar, shorting link , neutral link, earth link , connecting wire of suitable rating and din bar,masking sheet, including making internal DBterminations with copper lugs and with detachable gland plate, including making connections, testing etc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab test reportsbefore execution & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 47 | IP-43 Double door (Three phase) |
| 48 | 6 Way ( 18 O/G + 8 I/C ) |
| 49 | Providing & Fixing of 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C tripping characteristic as per type of load andsite requirement) 4KV impulse withstand voltage,as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductorline load reversibility, label holding facility , IP 20 contact protection and fitted withexisting distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A ratingincluding making connections, testing etc. as required.. OEM shall have submitNABL / CPRI / ERDA accrediated lab test reportsbefore execution & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 50 | Single pole MCB |
| 51 | 6 A to 32 A rating |
| 52 | Four pole MCB |
| 53 | 50-63 A rating |
| 54 | SITC of wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as per PWD specification for electrical Works, made out of CRCA sheet . Other parameters requiredas per point (a) ,(b), (c),(d) below:- |
| 55 | (a)Thickness of sheet shallnot be less than 1.6 mm up to 600 mm length / widthof any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall beof 2.0 mmthick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors with / withoutdetachable extension type structure |
| 56 | (b)panel shall beduly treated for derusting in 7 tank process with dephosphating and with powder coating of minimum 70 microns on both side of panel in desired shadeThe panel having PU/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware, separate detachable gland plate M.S. base channel (min75mm) , hinged door with locking arrangement for equipment/switchgear |
| 57 | [c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 125 amp ) and by solid bus bar(>125 amp ) . All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. |
| 58 | (d) only outer area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator. All as per drawing pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 59 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar as per PWD specification for electrical Works, by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 60 | Electrolytic grade Aluminium bus bar 6010 grade |
| 61 | Providing & Fixing of ISO certified company made UL listed , IP 65 110/220 V, unibody LED Indicatinglamp IEC 60947 , CSA 22.2 with integral circuit, IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 62 | Red/yellow/Green colour |
| 63 | Blue / white Colour |
| 64 | Providing & Fixing of IP 51 ( upto 500) V range Volt meter on existing panel as per PWD specification for electrical Works, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. Meter shall give true RMS measurments, acc. CI 1.0 or better , with field programmable primary & sec. values PT(VT) primary upto 2000 KV. Field-programmable high and low threshold values, meter shall compliance of IS 13875 & IEC 61236. as required. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDAlab test reportsbefore execution &All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 65 | Digital type |
| 66 | Providing & Fixing ofCT operated direct reading type IP- 51Ampere meter on existing panel as per PWD specification for electrical Works, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. Ampere meter shall give true RMS measurement, Acc. Cl 1.0 or better , Measuring current range 50 mA to 6 A, with Field-programmable primary and secondary values CT primary up to 15000 A, Field-programmable high and low threshold values as required. compliant to IS 13875, & IEC 61326. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDAlab test reportsbefore execution &. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 67 | Digital type Confirming to IEC 62053-21 |
| 68 | Below 500 A |
| 69 | Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Resin Cast Wound Primary / Ring Type Tape Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 70 | C T Class 1, Ratio upto 150/5, Burden 5 VA |
| 71 | Providing & Fixing of ISO certified company made selector switch of 10 A for voltmeter (4 position ) using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc.as required . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 72 | Providing & Fixing of ISO certified company madeCT linked selector switch of 10 AforAmpere meter (4 position )using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour , including making connection etc.as required . Allas per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 73 | Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 74 | 11 KV,2.5 mm thick with proof voltage 22 KV / 3 min. and Break Down Voltage45 KV |
| 75 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) as per PWD specification for electrical Works, ISI marked IS:13340-41 / conforming to IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz and total wattage loss less than 0.35 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 250 times of rated current,including making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 76 | Heavy dutyThree phase 480 V, 50 Hzcylindrical capacitor (Bank) |
| 77 | Providing & Fixing of440 Volt 3 pole capacitor(AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 78 | up to 6 kVar |
| 79 | 10 kVar |
| 80 | 15.0 kVar |
| 81 | Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 82 | One day & week reserve (mechanical type ) |
| 83 | Providing & Fixing ofISO certified company madeCam operated rotary (Auto/manual) switches on existing panel with 2 way and off position using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc.as required . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 84 | 10 AMP |
| 85 | 32 AMP |
| 86 | Providing & Fixing of IP54 on front microprocessor based three phase sensingpower factor correction relay , IEC / EN 61000-6-(2&4)having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485,indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, VTHD, ITHD,metering facility as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab test reports.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 87 | 6 to 8 stage |
| 88 | SITC of IP 40quick make and quick break4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings as per PWD specification for electrical Works, conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 800 V, provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections with lugs & spreaders,etc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 89 | With Thermal Magnetic release |
| 90 | up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 91 | 160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 92 | 250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 93 | 400 Amp ,50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu |
| 94 | Providing & Fixing in position frame made out of M.S. angle (riveted or welded) as per IS: 2062-2011 finished with two coats of red oxide and two coats of enamel paint including cutting, welding, holes etc. of following sizes as required. All drawing as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 95 | 50mm x 50mm x 6mm |
| 96 | Supplying and making one end termination with heavy duty brass compression gland (as per IS 12943- 1990) SIBG type, heavy duty aluminium lugs (as per IS 8309 -1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tapeas per PWD specification for electrical Works etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required of size. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 97 | 2 x 6.0 sq.mm |
| 98 | 3.5 x 150.0 sq.mm |
| 99 | 4 x 10.0 sq.mm |
| 100 | 3.5 x 25.0 sq.mm |
| 101 | 4 x 6.0 sq.mm |
| 102 | Plate Earthing as per PWD specification for electrical Works as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 103 | Plate Earthing as per PWD specification for electrical Works as per IS:3043 withcopper Earth plate of size 600mm x 600mm x 3.0mm by embodying3 to 4 mtr. below the ground level with 20mm dia. G.I. \"B\" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 104 | Supply & Laying following size earth stripin horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 105 | 30mm x 5 mm copper strip |
| 106 | 32mm x6mm G.I. ( Hot Dipped) Strip |
| 107 | Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from polycarbonate /extruded aluminium powder coatedhousing with in built driver, Power Consumption of18W/20W ,system lumen efficacy = 120 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% ,p.f.=0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. |
| 108 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 109 | 4\" LED Tube shape fixture 18/20 W (Polycarbonate Base) |
| 110 | Providing & Fixing of IP40 LED Recessed / Surface Mounted, Round / Sqaure Non-Dimmable Back lit SMD Mid Power LED Downlight with die-cast aluminum housing & Heat Sink for heat dissipation with UV Stabilized non yellowish Diffuser with internal/ external BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% and in compliance to IEC standards. System Lumen efficacy of = 120 lm / watt, THD < 10 % ,p.f.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. |
| 111 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 112 | LED Downlight 18/20W |
| 113 | Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of = 120 lm/Watt ,THD < 10 % , p.f.=0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. |
| 114 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 115 | Suspended Mounting/Surface Moutning |
| 116 | 36W LED light fixture 2\"x2\" with acrylic / prismatic front cover. |
| 117 | Providing & Fixing ofIK07 IP-66 protected high power LED flood light system with Pressure diecast aluminium housing LM6/ ADC12 material , toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED lamps . Integrated driver must be potted & has a unique BIS R number shall be high efficiency having efficiency more than 85 % and in compliance to BIS certified and T.C. certificate. The System level Luminaire efficacy >=120 lm/ wtwith High Power LEDs is to be used . LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety . Input Frequency 50Hz±3%, Power Factor >0.95 ,driverEfficiency >85% , THD(I) <10%, driver current <1000mA shown in LM79 report. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector Must be provided, Surge Protection Min >=4KV internal and 10KV external, System life of 30000 Burning hours with 70% of Initial Lumens maintained, color Rendering Index >70 and CCT 5700K±355K.Driver current <1000mA shown in LM79 report. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced. |
| 118 | OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 119 | High Power LED Flood Light 100W |
| 120 | Supply and erection of M.S. Galvanized Octagonal pole ( as per BSEN 40-3-3:2003 /BSEN 10025/IS 2062 IS:875 Part-1 – 2015/ for MS plate for baseflange )of following length and dimension as per table P-01 with base plate on the cement concrete foundation of M-20 grade (1:1.5:3) as perIS 456/IS 2911. with the help of anchor bolts of grade 6.8 (IS: 1367 P III ).The pole shall have a weatherproof flush door and locking arrangements. complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 121 | Octagonal MS Polesmade of S-355JO grade steel sheet , folded lengthwise to obtained Octagonal shape, having single longitudinal seam weld and hot dipped galvanised internally & externally in accordance with IS 2629. (See Table P -01 for specs.) |
| 122 | 7 Mtr. |
| 123 | Supply, Erection and Fixing of hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 124 | Single arm overhang |
| 125 | Double arm overhang |
| 126 | Providing & Fixing of IK07 IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum LM6/ ADC12 material with heat dissipation fins on housing with UV stabilized PC/Toughened Glass cover (UV stablzation report submitted for UV cover ) and secondary lens on each LED & should be SMD type . The System level Luminaire efficacy >=120 lm/ wtwith High Power LEDs is to be usedand potted driver must be potted & has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety ,Input Frequency 50Hz±3% Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <1000mA shown in LM79 report. The luminaireshall be BIS certified and T.C. certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened ,color Rendering Index >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced. |
| 127 | OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 128 | LED Street Light fixture 90 Watt |
| 129 | Providing & Fixing of ISO certified company made IK10IP65 protected Top/Bottom mounted LED Post top Light system. Fixture made of powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy =90 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N)and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz. System life of 30000 Burning hours with 70% of Initial Lumens maintainedLight output in Cool white or Warm White Colour as per engineers choice. driver current <1000mA shown in LM79 report.Fixture must be in compliance with BIS Standards and T.C . Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 130 | 25W LED Post Top Fixture |
| 131 | Providing & Fixing of Street light bracket made out from following size of \" B \" class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 132 | 32 mm Dia. |
| 133 | Providing & Fixing of energy efficient /energy saving IP 20 LED direct retrofit Bulbin existing holder or fixture as required with system lumen efficacy =100 lm/Watt output ,pf 0.95 , CRI >70,minimum life time of minimum25000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. |
| 134 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . foe additional technical parameters of product/ work, refer Annexure \"A\" attacheded with this BSR. |
| 135 | 15 Watt |
| 136 | Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , minimum width of 1 module switch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 137 | RJ-11 telephone jack single two line |
| 138 | Blanking plate |
| 139 | 25 Amp. 2 Module Motor Starter with on / off Push button |
| 140 | Providing & Fixing offollowing size mounting grid plates with cover plates as per PWD specification for electrical Works, made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 141 | 1/2 Module |
| 142 | Providing & Fixing offollowing size hot dip galvanized M.S. box of 18 SWG as per PWD specification for electrical Works, with earthing terminal in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 143 | 1-2 Module |
| 144 | Supplying and fixing of ISO Certified company made Krone module with base frameas per PWD specification for electrical Works, in the recess / surface made out of 16 SWG sheet steel box, front openable, having locking arrangements duly powder painted., including dressing, ferrulingandpunchingof telephone cable with krone tool etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 145 | 10 Pairs |
| 146 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected byPVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack &ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 147 | Supply and Installation of unsheilded/ sheilded Information outlets made of high impact plastic body with ABS, FR Grade with provision for protection against dust in jack/ FP, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact punch termination on reliable copper tin plated Insulation displacement contact, Itcomplied with ANSI/TIA/EIA 568standard. In existing modular/MS Boxes along with necessory connections as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR. |
| 148 | Cat 6, Un-sheilded Information Outlet |
| 149 | Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture ,material should bePC+ABS body, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 150 | Single Aperture |
| 151 | Supply, Installation, & Testing of 19\" 1U Rack Mounted/ surface mounted aluminum/ CRCA 1.2mm powder coated, Singlemode glass Fiber Optic Cable Patch panel/LIU loaded with flangless/screwable duplex adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs, screws, nuts to install the panel for rack/wallmount applications as per requirment complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR. |
| 152 | 24 Ports |
| 153 | Supplying and drawing PVC/ Polythene insulated and PVC sheathed unarmoured telephone cable with 0.5 mm dia. Tinned /annealed copper conductor taped & confirming tolatest TEC specification , GR / WIR/06-03 March 2002 offollowing pair in existingsurface or recessed PVC/MS conduit/casing capping including all as per pre approved by Engineer in charge, making connections, as required.For additional technical parameters of products/ work, referAnnexure \"A\" attached with this BSR . |
| 154 | 2 pair |
| 155 | 10 pair |
| 156 | Supply , Installation, Testing and Comissioning of 11 KV, 630 A, 20kA / 3 sec, Out door,Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, earthing switch, mechanical ON / OFF /Earth indication, Voltage presence indicator, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, Shunt trip coil, Anti reflex operating handle, right angle boots etc. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDAlab typetest reportsbefore execution as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 157 | S I T C of star ratedAluminium wound distribution Transformerof following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star level- 2 & BIS approved as per IS 2026- 1977 & lossesas defined as per IS 1180 part I 2014. including standardaccessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint,including carrying of pre-commission Testing & Charging of Transformer complete in all respect .NABL accredeated/ CPRI/ ERDA lab testing reports with OEM certificate must submitted to engineer in charge .Transformer must be tested from CTL test lab of discom (if reqd.) before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, CTL testing charges & Inspection charges shall be reimbursed by the department to the contractor as per actual expenditure. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 158 | 250 KVA with Off -LTC (+5% to - 10% @ 2.5%) |
| 159 | Providing & Laying XLPE insulated as per IS:7098/II/85H.T.cable as per PWD specification for electrical Works for working voltage 11 K.V.(E) in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench, on existing cable trays or on surface etc.including making necessary connection, testing etc. as required of size as per points (a), (b), (c) mentioned below:- |
| 160 | (a) Material :- H4- Gradealuminium conductor of purity >99.6 %& as perIS:1554 P-I / IS :7098 P - I |
| 161 | (b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999for armouring of cables , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures |
| 162 | (c)OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities forcables .All above as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 163 | 3 core 185.0 Sq.mm |
| 164 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit as per PWD specification for electrical Works suitable for11 KV / 33 KV cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. OEM test lab should be as per ISO 9001:2015 & 14001 : 2015 & reports submitted to engineer in charge includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 165 | 11 KV End Termination Kit Indoor type |
| 166 | 3 core 120/150/185 Sq.mm |
| 167 | Providing & laying of Double wall corrugated pipe confirming to IS : 14930 P - 1 & 2with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required( Excavation of Earth to be paid Extra as required. )of following Outer Dia. / Inner dia as per IS:4984:1995. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 168 | 110 / 95 mm |
| 169 | Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: |
| 170 | Cement Mortar 1:6 ( 1-Cement : 6-Sand). |
| 171 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. |
| 172 | M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stoneaggregate 20mm nominal size). |
| 173 | Plaster on new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish : |
| 174 | 25 mm thick |
| 175 | Supply , Installation, Testing and Comissioning of ISO certified company made Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and50 hz ,1 phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. Min 5 year OEM warranty both compressor and PCB. |
| 176 | NABL accredeated as per IS/ISO/IEC 17025 standards / CPRI/ ERDA lab testing reports as per IS 1391(Part-2) 2018 with OEM certificate must submitted to engineer in charge. All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 177 | Invertor Type |
| 178 | 1.8/2.0 TR with 5 star rating of BEE (ISEER not less then 4.7 ) |
| 179 | Supply & fixing of external thermal closed cell elastomeric nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified \"Class O\" in Fire Propagationas per BS 476 Part 6 in form of tubular insulation between each set of indoor & outdoor units as per specificationsnitrile including cost of adhesive complete as per specification and as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 180 | 6mm thick insulation |
| 181 | 6mm thick insulation and 6 mm internal Dia |
| 182 | 6mm thick insulation and 13 mm internal Dia |
| 183 | Providing & Fixing of ISI marked (IS : 15778 - 2007) Rigid CPVC drain water piping 6 kg/ cm2 withfittings like elbow, soket, Tee etc & support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 184 | 25 mm dia |
| 185 | Supply , Installation, Testing and Comissioning of Interconnecting refrigerantcopper pipe forsplitof DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. Material TestCertificaterequired with each supplied material.Piping between each set of indoor & outdoor units of different sizesas per OEM requirement & specifications including chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 186 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp plug top making connection etc complete in all respect.NABL accredeated/ CPRI/ ERDA lab testing reports with OEM certificate must submitted to engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 187 | 5 kVA |
| 188 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 189 | 100 mm dia per running inch length |
| 190 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 191 | Supply , Installation, Testing and Comissioning of ISO certified company made self contained drinking water coolar with BEE Rated energy efficient hermetic sealed type compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz ac supply,Full stainless steel (S304)body and tank , stainless steel water tray,minimum two nos faucets and suitable drainage system complete in all respect with 300mm height MS fabricated and painted plateform. complete in all respect of the following capacity.NABL accredeated/ CPRI/ ERDA lab testing reportswith OEM certificate must submitted to engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 192 | cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs |
| 193 | Providing & Fixing of ISI marked (IS:1258)6 ampbatten/angle lampholder as per PWD specification for electrical Works,made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 194 | Providing & Fixing ofISI marked (IS:371) 6 amp surface type 3 pin ceiling roses as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 195 | Supply & Fixing of current and valid BIS certification IS: 15683:2018 approvedPortable fire Extinguisher, Carbon-dioxidetype flat base including valve, dischargehose of not less than 10 mm dia. min. 600 mm long& completeinall respectsincluding initial fill with C02 gas confirming to IS:307-1966 filled to a filling ratio ofnot morethan0.667 andwallsuspension bracket . bidder must have valid PESO license to refill and store compressed gas cylinders as per Gas Cylinder rules 2004 , vessel should be PESO Approved. carbon dioxide gas shall conform to IS 15222 with latest amendment. Co2 Cylinder shall be conform to all the requirement given in IS 7285:2004. Serial no. and date of manufacturing should be embossed or printedon the body of the fire extinguisher. The firm should submit the product certificate from an EN notified body & product performance test report from NABL accredited Lab as per IS 15683. . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 196 | Capacity 4.5 Kg. |
| 197 | Supply & Fixing of ABC Type (MAP 50)type powder Fire Extinguisher (Stored Pressure type) of following capacity duly current and valid BIS certification conforming to IS: 15683:2006, withDry chemical powder used as extinguishing agent should be Mono Ammonium Phosphate 50% concentration conforming to IS 14609:1999. OEM will produce supplier certificate complete with squeeze grip release valve, locking arrangement, pressure gauge and bracket includinginitial fill and wall suspension complete in all respect. Serial no. and date of manufacturing should be embossed or printedon the body of the fire extinguisher. The firm should submit the product certificate from an EN notified body & product performance test report from NABL accredited Lab as per IS 15683. . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 198 | 6 kg |
AI Tender Summary
Tender Timeline
May 28, 2022
11:30 IST
Tender Published
Tender notice published.
CompletedJun 08, 2022
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedJun 09, 2022
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender