| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell pointwith 1.5 sq.mm FRLS PVC insulated copper conductor single corecable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable etcas required.a) Group C |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required. a) Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | c) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | Supplying & Fixing GI Box alongwith modular base, cover plate, 2 no. 16A modular switch & 2 nos 6 pin 15/16 amps socket in recessed etc as reqd |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 8 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. A)2 Module |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.a) RJ 45 Computer Socket Cat-6 |
| 10 | b) Telephone Socket outlet |
| 11 | Supplying and drawing UTP 4 Pair Cat 6 LAN Cable In the Existing Surface/recessed Steel/PVC Conduit as Required |
| 12 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 13 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/recessed steel/ PVC Conduit as reqd. a) 4 Pairs |
| 14 | Supplying, installation, testing & commissioning of 18/20/22watt 6000K (4 ft.) energy saving LED wall mounted light fitting, extruded aluminum heat sink provided for efficient heat dissipation & integrated electronic driver, suitable to work 230 volt AC supply complete with connection etc. with 1.5 sq.mm PVC insulated copper conductor wire as reqd. |
| 15 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. lades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 16 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. a) 8 way (4 + 24), Double door |
| 17 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. A) single Pole |
| 18 | Providing and fixing following rating and breaking capacity and pole MCCB in existing TPN DB including, making connections, etc. as required. a) 100 Amp, 16 KA,TPMCCB |
| 19 | Supplying and layingof one number PVC insulated and Al. Conductor armored power cable of 1.1 KV grade of following size direct on cable tray as required. a) 4 X 25 Sq.mm |
| 20 | Supplying, installation, testing & commissioning of 2.0 Ton Split type Air-Conditioner (5 Star only) suitable for operation on 230 Volt, 50Hz single phase capable of performing Cooling, Dehumidifying, Air Circulating & Filtering complete connection with refrigerant copper pipe heavy gauge 2\"/8\" / 3\"/8\" & 5/8\" covered with minimum 10mm thick insulation i/c 3 x 2.5 sq.mm flexible copper conductor wire wrapped in flexible pipe irrespective of length and also providing 25mm dia PVC drain connection i/c accessories, fixing on surface with clamp to the nearest drain connection pipe complete with repairing of wall with minor civil work at site. |
| 21 | Supplying, installation, testing & commissioning of following capacity Window type Air-Conditioner unit suitable for operation on 230 Volts, 50Hz, single phase capable of performing Cooling, Dehumidifying, Air Circulating & Filtering complete connection including accessories, fixing on window including wooden work (fixing plywood of appropriate size) repairing of wall/window with minor civil work at site etc as required.a) 2 TR capacity |
| 22 | Supplying and fixing of following capacity automatic voltage stabilizer suitable for above said units complete as reqd.(a) 5 KVA [Input-165 - 280 V] [ Output- 195-245 V] |
| 23 | Providing and fixing of hard drawn threaded wired PVC drain pipe line of 25mm dia for drain out condensed water etc as required. |
| 24 | Providing and fixing of M.S. outdoor, floor/ wall mounting powder coated stand suitable for 2.0 Ton capacity split type A.C. outdoor unit complete as reqd. |
| 25 | Providing & Laying of refrigerant copper piping of size (5/8” & 1/4” dia) from indoor unit to outdoor unit of split type AC duly insulated along with necessary support etc complete as required. |
| 26 | SITC of exhaust fan of 300 mm sweep, 900 rpm speed with shutter & louvers in the existing opening i/c making the hole to suit the size of the above fan, making good the damages, connection, testing & commissioning etc. as required. |
| 27 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.a) 5/6 amps switch |
| 28 | Supplying, installation, testing & commissioning of stains steel panel pedestal type with G.I. cabinet storage type Water Cooler 150/150 Ltr. Capacity, fully Stainless Steel suitable for operation on 230V + 10% 50 Hz single phase AC supply includingmaking water line & electrical connection etc. as reqd. |
| 29 | Supplying, installation, testing & commissioning of energy efficient recessed mounted type 34W to 38W full window glare free opal diffuser LED panel luminaries of size 595mm x 595mm (nominal size)suitable for both Armstrong/POP/Geypsum Board or grid false ceiling fabricated with MS powder coated white CRCA housing including mounting with thehelp of chain/other suitable method, hanging from the ceiling including connections with 3 x 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required including dismantling alongwith credit for worn out luminaries under buy back arrangement.The Total system Lumen of 34W to 38W LED should be 3600 with minimum system efficacy of 100 lumen /watt colour temperature 5500K to 6500K, power factor>0.95, CRI (Ra)>75, THD <10%, with APFC driver having driver efficiency >85%, operating voltage 150-270 volts with minimum 2.5KV surge protection. |
| 30 | SITC of 10 KVA capacity (1 Phase Input and 1 Phase output) high performance IGBT / PWM based True-On-Line, Double Conversion Microprocessor controlled UPS system alongwith 20 nos.batteries of capacity 12 Volts, 42 AH batteries to provide 30 minutes backup on connected loads along with battery rack (powder coated) & accessories including connection, interconnection etc., as per technical specification attached and as per direction of Engineer-in-charge etc.as reqd. |
| 31 | Supplying, installation, testing & commissioning of Reverse Osmosis Purifier 50LPH basic on line complete i/c plumbing worki/c suitable stand made out of angle iron of 25 x 25 x 5 mm i/c painting complete etc. as reqd. as per following specification. .(a) Dimension (WXDXH) : 460X250X790(b) Input Power rating : 230V AC,50Hz(c) Production Capacity : 50LPH(d) RO Membrane : 80GPD X 4Nos(e) Power Consumption : 120W(f) Weight in KG : 45(g) % of Rejection in TDS : 90% |
| 32 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.a) 6 Module (200mm X 75mm) |
| 33 | b) 8 Module (125mm X 125mm) |
| 34 | Credit for old dismantled materials under buy back arrangement etc. complete as required.a) STAC with indoor and outdoor unit |
| 35 | b) WTAC unit |
| 36 | c) Assorted SPN DB |
| 37 | d) Assorted mirror optic fittings |
| 38 | e) Assorted Ceiling Fans |
| 39 | f) Assorted UPS System with battery banks. |
| 40 | g) Assorted switch/sockets |
| 41 | h) Water cooler and RO aqua guard |